Sei sulla pagina 1di 16

IEEE C37.

2-1987
(Revision of ANSIAEEE
C37.2-1979)

-- IEEE Standard Electrical Power


System Device Function Numbers

4b Published by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, NY 10017, USA
lkembsr 1 4 I987 SHI 1759

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard Electrical Power System
Device Function Numbers

1. Scope and References 2. Purpose of Device Function Numbers

1.1 Scope. This standard applies to the defmi- A device function number, with appropriate
tion and application of function numbers for prefix and suffix where necessary, is used to iden-
devices used in electrical substations and generat- t@ the function of each device in all types of
ing plants and in installations of power utilization partial automatic and automatic switchgear and
and conversion apparatus. in many types of manual switchgear. These
NOTE Although the wording of this standard is directed numbers are to be used on drawings, on elemen-
specifically to equipment comprising conventional electro- tary and connection diagrams, in instruction
mechanical devices, it also applies to equipment consisting books, in publications, and in specifications. In
totally, or in part, of electronic or solid-state devices.
addition, for automatic switchgear, the number
may be placed on, or adjacent to, each device on
1.2 References. When the American National
the assembled equipment so that the device may
h
Standards referred to in this standard are super-
be readily identified.
seded by a revision approved by the American
National Standards Institute, the revision shall NOTE: These device function designations, which have been
developed as a result of usage over many years, may define the
apply. actual function the device performs in an equipment, or they
may refer to the electrical or other quantity to which the
[ l ] ANSI Y1.l-1972 (R1984), Abbreviations for device is responsive. Hence, there may be in some instances a
Use on Drawings and in Text.' choice of the function number to be used for a given device.
The preferable choice to be made in all cases should be the one
[2] ANSI/IEEE Std 315-1975, Graphic Symbols which is recognized to have the narrowest interpretation so
for Electrical and Electronics Diagrams.2 that it most specifically identifies the device in the minds of all
individuals concerned with the design and operation of the
[3] ANSI/IEEE C37.1-1987, IEEE Standard Defi- equipment.
nition, Specification, and Analysis of Systems Used
for Supervisory Control, Data Acquisition, and
Automatic Control. 3. Standard Device Function Numbers
[4]ANSI/IEEE C37.20.1-1987, IEEE Standard 3.1 Standard Device Function Numbers.. Each
for Metal-Enclosed Low-Voltage Power Circuit number with its corresponding function name
Breaker Switchgear. and the general description of each function is
[ 5 ] ANSI/IEEE C37.20.2-1987,IEEE Standard for listed below.
Metal-Clad and Station-Type Cubicle Switchgear. NOTE: When alternate names and descriptions are included
under the function, only the name and description which
applies to each specific case should be used. In general, only
one name for each device, such as relay, contactor, circuit
'ANSI publications are available from the American breaker, switch, monitor, or other device, is included in each
National Standards Institute, Sales Department, 1430 Broad- function designation. However, when the function is not
way, New York, NY 10018. inherently restricted to any specific type of device and where
'ANSI/IEEE publications are available from The Institute the type of device itself is thus merely incidental, any one of
- of Electrical and Electronics Engineers Service Center, 445
Hoes Lane, P.O. Box 1331, Piscataway, NJ, 08855.1331, or from
The American National Standards Institute, Sales Depart-
the above listed alternative names, as applicable, may be sub-
stituted. For example, if for device function 6 a contactor is
used for the purpose in place of a circuit breaker, the function
ment, 1430 Broadway, New York, NY 10018. name should be specified as starting contactor.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2-1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

For every application of device function numbers, the origi- breaker, or pull-out fuse block, used for the pur-
nator should provide a brief definition for all device function pose of respectively connecting and disconnecting
h

numbers used in that application, including all combinations


of prefixes, function numbers and suffies. Typical definitions the source of control power to and from the con-
are illustrated in Fig 3a. These definitions should be included trol bus or equipment.
on the drawing where the device function number is used, or
on a separate drawing or list to which the other drawings NOTE Control power is considered to include auxiliary power
refer. All instruction books and other documents shall also which supplies such apparatus as small motors and heaters.
include the device function number definitions.
Numbers from 95 to 99 should be assigned only for those 9. reversingdevice is a device that is used for the
functions in specific cases where none of the assigned stan-
dard device function numbers are applicable. Numbers which purpose of reversing a machine field or for per-
are "reserved for future application" should not be used. forming any other reversing functions.
1. master element is the initiating device, such 10. unit sequence switch is a switch that is used
as a control switch, etc, which serves either to change the sequence in which units may be
directly or through such permissive devices as placed in and out of service in multiple-unit
protective and time-delay relays to place an equipments.
equipment in or out of operation.
11. multifunction device is a device that per-
NOTE: This number is normally used for a hand-operated forms three or more comparatively important
device, although it may also be used for an electrical or
mechanical device for which no other function number is functions which could only be designated by com-
suitable. bining several of these device function numbers.
All of the functions performed by device 11 shall
2. time-delaystarting or closing relay is a device
be defined in the drawing legend or device func-
that functions to give a desired amount of time tion definition list.
delay before or after any point of operation in a
switching sequence or protective relay system, NOTE: If only two relatively important functions are per-
except as specifically provided by device func- formed by the device, it is preferred that both function
numbers be used, as described in 3.6.
tions 48, 62, and 79.
12. overspeed device is usually a direct-con-
3. checking or interlocking relay is a relay that netted speed switch which functions on machine
-
operates in response to the position of a number
overspeed.
of other devices (or to a number of predeter-
mined conditions) in an equipment, to allow an 13. synchronous-speeddevice is a device such as
operating sequence to proceed, or to stop, or to a centrifugal-speed switch, a slip-frequency relay,
provide a check of the position of these devices or a voltage relay, an undercurrent relay, or any type
of these conditions for any purpose. of device that operates at approximately the syn-
chronous speed of a machine.
4. master contactor is a device, generally con-
trolled by device function 1 or the equivalent and 14. underspeed device is a device that functions
the required permissive and protective devices, when the speed of a machine falls below a pre-
that serves to make and break the necessary con- determined value.
trol circuits to place an equipment into operation
15. speed or frequency matching device is a
under the desired conditions and to take it out of
device that functions to match and hold the
operation under abnormal conditions.
speed or frequency of a machine or of a system
5. stopping device is a control device used pri- equal to, or approximately equal to, that of
marily to shut down an equipment and hold it out another machine, source or system.
of operation. (This device may be manually or
16. Reserved for future application.
electrically actuated, but excludes the function of
electrical lockout (see device function 86) on 17. shunting or discharge switch is a switch that
abnormal conditions.) serves to open or to close a shunting circuit
around any piece of apparatus (except a resis-
6, starting circuit breaker is a device whose tor), such as a machine field, a machine arma-
principal function is to connect a machine to its ture, a capacitor, or a reactor.
source of starting voltage.
NOTE: This excludes devices that perform such shunting
7. Reserved for future application. operations as may be necessary in the process of starting a
machine by devices 6 or 42, or their equivalent, and also
-
8. control power disconnecting device is a dis- excludes device function 73 that serves for the switching of
connecting device, such as a knife switch, circuit resistors.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
~

IEEE
DEVICE FUNCTION NUMBERS C37.2-1987

18. accelerating or decelerating device is a 27. undervoltage relay is a relay which operates
---. device that is used to close or to cause the closing when its input voltage is less than a predeter-
of circuits which are used to increase or decrease mined value.
the speed of a machine.
28. flame detector is a device that monitors the
19. starting-to-runningtransition contactor is a presence of the pilot or main flame in such appa-
device that operates to initiate or cause the ratus as a gas turbine or a steam boiler.
automatic transfer of a machine from the starting
to the running power connection. 29. isolating contactor is a device that is used
expressly for disconnecting one circuit from
20. electrically operated valve is an electrically another for the purposes of emergency operation,
operated, controlled or monitored valve used in a maintenance, or test.
fluid, air, gas, or vacuum line.
30. annunciatorrelay is a nonautomatically reset
NOTE: The function of the valve may be more completely indi-
cated by the use of suffixes as discussed in 3.2. device that gives a number of separate visual
indications upon the functioning of protective
21. distance relay is a relay that functions when devices, and which may also be arranged to per-
the circuit admittance, impedance, or reactance form a lockout function.
increases or decreases beyond a predetermined
value. 31. separate excitation device is a device that
connects a circuit, such as the shunt field of a
22. equalizer circuit breaker is a breaker that synchronous converter, to a source of separate
serves to control or to make and break the equal- excitation during the starting sequence.
izer or the current-balancing connections for a
machine field, or for regulating equipment, in a 32. directional power relay is a relay which
multiple-unit installation. operates on a predetermined value of power flow
in a given direction, or upon reverse power flow
23. temperature control device is a device that such as that resulting from the motoring of a
- functions to raise or lower the temperature of a
machine or other apparatus, or of any medium,
generator upon loss of its prime mover.
when its temperature falls below, or rises above, a 33. position switch is a switch that makes or
predetermined value. breaks contact when the main device or piece of
NOTE An example is a thermostat that switches on a space apparatus which has no device function number
heater in a switchgear assembly when the temperature falls to reaches a given position.
a desired value. This should be distinguished from a device
that is used to provide automatic temperature regulation 34. master sequence device is a device such as a
between close limits and would be designated as device func- motor-operated multicontact switch, or the equiv-
tion 90T.
alent, or a programming device, such as a compu-
24. volts per hertz relay is a relay that functions ter, that establishes or determines the operating
when the ratio of voltage to frequency exceeds a sequence of the major devices in an equipment
preset value. The relay may have an instantane- during starting and stopping or during other
ous or a time characteristic. sequential switching operations.
25. synchronizing or synchronism-check device 35. brush-operatingor slip-ring short-circuiting
is a device that operates when two ac circuits are device is a device for raising, lowering, or shifting
within the desired limits of frequency, phase angle, the brushes of a machine, or for short-circuiting
and voltage, to permit or to cause the paralleling its slip rings, or for engaging or disengaging the
of these two circuits. contacts of a mechanical rectifier.
26. apparatus thermal device is a device that 36. polarity or polarizing voltage device is a
functions when the temperature of the protected device that operates, or permits the operation of,
apparatus (other than the load-carrying windings another device on a predetermined polarity only,
of machines and transformers as covered by or verifies the presence of a polarizing voltage in
device function number 49), or of a liquid or other an equipment.
medium exceeds a predetermined value; or when
-. the temperature of the protected apparatus or of 37. undercurrent or underpower relay is a relay
any medium decreases below a predetermined that functions when the current or power flow
value. decreases below a predetermined value.

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
~

IEEE
C37.2- 1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

38. bearing protective device is a device that phase sequence or when the polyphase voltages
functions on excessivebearing temperature, or on are unbalanced or when the negative phase-
other abnormal mechanical conditions associated sequence voltage exceeds a given amount.
with the bearing, such as undue wear, which may
48. incomplete sequence relay is a relay that
eventually result in excessive bearing tempera-
generally returns the equipment to the normal, or
ture or failure.
off, position and locks it out ifthe normal starting,
39. mechanical condition monitor is a device operating, or stopping sequence is not properly
that functions upon the occurrence of an abnor- completed within a predetermined time.
mal mechanical condition (except that associated
49. machine or transformer thermal relay is a
with bearings as covered under device function
relay that functions when the temperature of a
38), such as excessive vibration, eccentricity,
machine armature winding or other load-carrying
expansion, shock, tilting, or seal failure.
winding or element of a machine or power trans-
40. field relay is a relay that functions on a given former exceeds a predetermined value.
or abnormally low value or failure of machine
50. instantaneous overcurrent or rate-of-rise
field current, or on an excessive value of the relay is a relay that functions instantaneously on
reactive component of armature current in an
an excessive value of current or on an excessive
ac machine indicating abnormally low field exci-
rate of current rise.
tation.
51. ac time overcurrent relay is a relay that
41. field circuit breaker is a device that func-
functions when the ac input current exceeds a
tions to apply or remove the field excitation of a
predetermined value, and in which the input cur-
machine.
rent and operating time are inversely related
42. running circuit breaker is a device whose through a substantial portion of the performance
principal function is to connect a machine to its range.
source of running or operating voltage. This func- 52. ac circuit breaker is a device that is used to
tion may also be used for a device, such as a con- close and interrupt an ac power circuit under
tactor, that is used in series with a circuit breaker normal conditions or to interrupt this circuit
or other fault protecting means, primarily for fre- under fault or emergency conditions.
quent opening and closing of the circuit.
53. exciter or dc generator relay is a relay that
43. manual transfer or selector device is a forces the dc machine field excitation to build
manually operated device that transfers the up during starting or which functions when the
control circuits in order to mod@ the plan of machine voltage has built up to a given value.
operation of the switching equipment or of some
of the devices. 54. turning gear engaging device is an electri-
cally operated, controlled, or monitored device
44. unit sequence starting relay is a relay that which functions to cause the turning gear to
functions to start the next available unit in a engage (or disengage) the machine shaft.
multiple-unit equipment upon the failure or non-
availability of the normally preceding unit. 55. power factor relay is a relay that operates
when the power factor in an ac circuit rises above
45. atmospheric condition monitor is a device or falls below a predetermined value.
that functions upon the occurrence of an abnor-
mal atmospheric condition, such as damaging 56. field application relay is a relay that auto-
fumes, explosive mixtures, smoke, or fire. matically controls the application of the field
excitation to an ac motor at some predetermined
46. reverse-phase or phase-balance current point in the slip cycle.
relay is a relay that functions when the polyphase
currents are of reverse-phase sequence, or when 57. short-circuiting or grounding device is a
the polyphase currents are unbalanced or con- primary circuit switching device that functions to
tain negative phase-sequence components above short circuit or to ground a circuit in response to
a given amount. automatic or manual means.
47. phase-sequence or phase-balance voltage 58. rectification failure relay is a device that
relay is a relay that functions upon a predeter- functions if a power rectifier fails to conduct or
mined value of polyphase voltage in the desired block properly.

10

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
DEVICE FUNCTION NUMBERS C37.2 - 1987

59. overvoltage relay is a relay which operates


- when its input voltage is more than a predeter-
69. permissive control device is generally a two-
position device that in one position permits the
mined value. closing of a circuit breaker, or the placing of
an equipment into operation, and in the other
60. voltage or current balance relay is a relay
position prevents t h e circuit breaker or t h e
that operates on a given difference in voltage, or
equipment from being operated.
current input or output, of two circuits.
61. density switch or sensor is a device which 70. rheostat is a variable resistance device used
operates on a given value, or a given rate of in an electric circuit, which is electrically oper-
change, of gas density. ated or has other electrical accessories, such as
auxiliary, position, or limit switches.
62. time-delay stopping or opening relay is a
time-delay relay that serves in conjunction with 71. level switch is a switch which operates on
the device that initiates the shutdown, stopping, given values, or on a given rate of change, of level.
or opening operation in an automatic sequence or 72. dc circuit breaker is a circuit breaker that is
protective relay system. used to close and interrupt a dc power circuit
63. pressure switch is a switch which operates under normal conditions or to interrupt this
on given values, or on a given rate of change, of circuit under fault or emergency conditions.
pressure. 73. load-resistor contactor is a contactor that is
64. ground detector relay is a relay that operates used to shunt or insert a step of load limiting,
on failure of machine or other apparatus insula- shifting, or indicating resistance in a power circuit,
tion to ground. or to switch a space heater in circuit, or to switch
a light or regenerative load resistor of a power
NOTE: This function is not applied to a device connected in rectifier or other machine in and out of circuit.
the secondary circuit of current transformers in a normally
grounded power system, where other device numbers with a
suffix G or N should be used, that is, 51N for an ac time over- 74. alarm relay is a relay other than an annun-
- current relay connected in the secondary neutral of the ciator, as covered under device function 30, that
current transformers. is used to operate, or to operate in connection
with, a visual or audible alarm.
65. governor is the assembly of fluid, electrical, or
mechanical control equipment used for regulat- 75. position changing mechanism is a mecha-
ing the flow of water, steam, or other medium to nism that is used for moving a main device from
the prime mover for such purposes as starting, one position to another in an equipment; as, for
holding speed or load, or stopping. example, shifting a removable circuit breaker unit
66. notching or jogging device is a device that t o and from the connected, disconnected, and
functions to allow only a specified number of test positions.
operations of a given device, or equipment, or a 76. dc overcurrent relay is a relay that functions
specified number of successive operations within when the current in a dc circuit exceeds a given
a given time of each other. It is also a device that value.
functions to energize a circuit periodically or for
fractions of specified time intervals, or that is 77. telemetering device is a transmitter used to
used to permit intermittent acceleration or jog- generate and transmit to a remote location an
ging of a machine at low speeds for mechanical electrical signal representing a measured quan-
positioning. tity, or a receiver used to receive the electrical
signal from a remote transmitter and convert the
67. ac directional overcurrent relay is a relay signal to represent the original measured quantity.
that functions on a desired value of ac over-
current flowing in a predetermined direction. 78. phase-angle measuring or out-of-step pro-
tective relay is a relay that functions at a pre-
68. blocking relay is a relay that initiates a pilot determined phase angle between two voltages or
signal for blocking of tripping on external faults in between two currents or between voltage and
a transmission line or in other apparatus under current.
predetermined conditions, or cooperates with
-_ other devices to block tripping or to block reclos- 79. ac reclosing relay is a relay that controls the
ing on an out-of-step condition or on power automatic reclosing and locking out of an ac
swings. circuit interrupter.

11

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2-1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

80. flow switch is a switch which operates on certain (generally close) limits for machines, tie
given values, or on a given rate of change, of flow. lines, or other apparatus.
81. frequency relay is a relay that responds to 91. voltage directional relay is a relay that oper-
the frequency of an electrical quantity, operating ates when the voltage across an open circuit
when the frequency or rate of change of fre- breaker or contactor exceeds a given value in a
quency exceeds or is less than a predetermined given direction.
value.
92. voltage and power directional relay is a
82. dc reclosing relay is a relay that controls the relay that permits or causes the connection of
automatic closing and reclosing of a dc circuit two circuits when the voltage difference between
interrupter, generally in response to load circuit them exceeds a given value in a predetermined
conditions. direction and causes these two circuits to be dis-
connected from each other when the power flow-
83. automatic selective control or transfer relay ing between them exceeds a given value in the
is a relay that operates to select automatically opposite direction.
between certain sources or conditions in an
equipment, or performs a transfer operation 93. field-changing contactor is a contactor that
automatically. functions to increase or decrease, in one step, the
value of field excitation on a machine.
84. operating mechanism is the complete elec-
trical mechanism or servomechanism, including 94. tripping or trip-free relay is a relay that
the operating motor, solenoids, position switches, functions to trip a circuit breaker, contactor, or
etc, for a t a p changer, induction regulator, or any equipment, or to permit immediate tripping by
similar piece of apparatus which otherwise has other devices; or to prevent immediate reclosure
no device function number. of a circuit interrupter if it should open automati-
cally even though its closing circuit is maintained
85. carrier or pilot-wire receiver relay is a relay closed.
that is operated or restrained by a signal used in
connection with carrier-current or dc pilot-wire 95-99. Used only for specific applications in
fault relaying. individual installations where none of the assigned
numbered functions from 1 to 94 are suitable.
86. lockout relay is a hand or electrically reset
auxiliary relay that is operated upon the occur-
rence of abnormal conditions to maintain asso-
ciated equipment or devices inoperative until it is 3.2 Addition of Prefixes and Suffixes. Letters
reset. and numbers may be used as prefixes or suffixes
87. differential protective relay is a protective to device function numbers to provide a more
relay that functions on a percentage or phase specific definition of the function, as discussed
angle or other quantitative difference of two below. They permit a manifold multiplication of
currents or of some other electrical quantities. available function designations for the large
number and variety of devices used in the many
88. auxiliary motor or motor generator is one types of equipment covered by this standard.
used for operating auxiliary equipment, such They may also serve to denote individual or
as pumps, blowers, exciters, rotating magnetic specific parts o r auxiliary contacts of these
amplifiers, etc. devices or certain distinguishing features, charac-
teristics, or conditions which describe the use of
89. line switch is a switch used as a disconnect-
the device or its contacts in the equipment.
ing, load-interrupter, or isolating switch in an ac
Prefixes and suffixes should, however, be used
or dc power circuit. (This device function number
only when they accomplish a useful purpose. For
is normally not necessary unless the switch is
electrically operated or has electrical accessories, example, when all of the devices in an equipment
are associated with only one kind of apparatus,
such as an auxiliary switch, magnetic lock, etc.)
such as a feeder or motor or generator, it is com-
90. regulating device is a device that functions mon practice, in order to retain maximum sim-
to regulate a quantity, or quantities, such as volt- plicity in device function identification, not to add
age, current, power, speed, frequency, tempera- the respective suffur letter F or M or G to any of
ture, and load, at a certain value or between the device function numbers.

12

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
DEVICE FUNCTION NUMBERS C37.2 - 1987

- 3.2.1 Defining Letter Sdfixes. In order to


prevent any possible conflict or confusion, each
C Closing relay or contactor
CL Auxiliary relay, closed (energized when
letter suffix should preferably have only one main device is in closed position)
meaning in an individual equipment. To accom- cs Control switch
plish this, short distinctive abbreviations, such as D Downposition switch relay
contained in ANSI Y1.l-1972 [lI3,or any appro- L Lowering relay
priate combination of letters, may also be used as 0 Opening relay or contactor
letter suffies, where necessary. However, each OP Auxiliary relay, open (energized when
suffix should not consist of more than three (and main device is in open position)
preferably not more than two) letters, in order to PB Push button
keep the complete function designation as short R Raising relay
and simple as possible. U UP position switch relay
The meaning of each suffix should be desig- X Auxiliary relay
nated on the drawings or in the publications with Y Auxiliary relay
which they are used, similar to: TC-trip coil, Z Auxiliary relay
V-voltage, X-auxiliary relay. NOTE: In the control of circuit breaker with a so-called X-Y
In cases where the same suffix (consisting of relay control scheme, the X relay is the device whose main
contacts are used to energize the closing coil or the device
one letter or a combination of letters) has differ- which in some other manner, such as by the release of stored
ent meanings in the same equipment, depending energy, causes the breaker to close. The contacts of the Y relay
upon the device function number with which it is provide the antipump feature of the circuit breaker.
used, then the complete device function number 3.4.2 Actuating Quantities. These letters indi-
with its suffix letter or letters and its correspond- cate the condition or electrical quantity to which
ing function definition should be listed in the the device responds, or the medium in which it is
legend in each case, as follows:63V-vacuum relay, located, such as
7OR-raising relay for device 70, 9OV-voltage A Air or amperes or alternating
regulator. C Current
- 3.3 Suggested Prefixes. A similar series of num- D Direct or discharge
bers, prefixed by the letters RE (for remote) may E Electrolyte
be used for the interposing relays performing F Frequency or flow or fault
functions that are controlled directly from the H Explosive
supervisory system. Typical examples of such J Differential
functions are RE1, RE5, and RE94. L Level or liquid
In multiple-unit installations, it may be desira- P Power or pressure
ble to use a prefix number to distinguish between PF Power factor
device functions associated with individual units. 0 oil
For example, in pipeline pump stations, the S Speed or suction or smoke
numbers 1 through 99 are applied to device func- T Temperature
tions that are associated with the overall station V Voltage or volts or vacuum
operation. A similar series of numbers, starting VAR Reactive power
with 101 instead of 1, are used for those device VB Vibration
functions that are associated with unit 1; a similar W Water or watts
series starting with 201 for device functions that 3.4.3 Main Device. These letters denote the
are associated with unit 2; and so on, for each main device to which the numbered device is
unit in these installations. applied or is related:
A Alarm or auxiliary power
3.4 Suggested Suffix Letters. Sections 3.4.1 AN Anode
through 3.4.6 describe letters which are com- B Battery or blower or bus
monly used and are recommended for use when BK Brake
required and as appropriate. BL Block (valve)
3.4.1 Auxiliary Devices. These letters denote BP Bypass
separate auxiliary devices, such as BT Bus tie
C Capacitor or condenser or compensator
3The numbers in square brackets correspond to those of or carrier current or case or compressor
the references listed in 1.2. CA Cathode

13

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2- 1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

CH Check (valve) C Close or cold


D Discharge (valve) D Decelerating or detonate or down or
DC Direct current disengaged
E Exciter E Emergency or engaged
F Feeder or field or fdament or fdter or fan F Failure or forward
G Generator or ground5 H Hot or high
H Heater or housing HR Hand reset
L Line or logic HS High speed
M Motor or metering L Left or local or low or lower or leading
MOC Mechanism operated contact4 M Manual
N Network or neutral5 0 Open
P Pump or phase comparison OFF Off
R Reactor or rectifier or room ON On
S Synchronizing or secondary or strainer P Polarizing
or sump or suction (valve) R Right or raise or reclosing or receiving or
T Transformer or thyratron remote or reverse
TH Transformer (high-voltage side) S Sending or swing
TL Transformer (low-voltage side) T Test or trip or trailing
TM Telemeter TDC Time-delay closing
Tr Transformer (tertiary-voltage side) TDO Time-delay opening
U Unit U UP
3.4.4 Main Device Parts. These letters denote 3.4.6 Use of Suffix Letters. Lower case (small)
parts of the main device, except auxiliary con- letters are used in practically all instances on
tacts, position switches, limit switches and torque electrical diagrams for the auxiliary, position, and
limit switches which are covered in Section 4. limit switches as shown in 4.1. Capital letters are
BK Brake generally used for all suffix letters in 3.4.
C Coil or condenser or capacitor The letters in 3.4.1 to 3.4.3, since they should
cc Closing coil generally form part of the device function desig-
HC Holding coil nation, are usually written directly after the
M Operating motor device function number, as, for example, 52CS,
MF Fly-ball motor 71W, or 49D. When it is necessary to use two types
ML Load-limit motor of suffix letters in connection with one function
MS Speed adjusting or synchronizing motor number, it is often desirable for clarity to separate
S Solenoid them by a slanted line or dash, as, for example,
SI Seal-in 2OD/CS or 20D-CS.
TC Trip coil The suffur letters in 3.4.4 which denote parts of
V Valve the main device, and those in 3.4.5, which cannot
or need not form part of the device function
3.4.5 Other Suffix Letters. The following let-
designation, are generally written directly below
ters cover all other distinguishing features or
the device function number on the drawings, as
characteristics o r conditions, not specifically
for example,
described in 3.4.1 to 3.4.4,which serve to describe
the use of the device in the equipment, such as 52 43
A Accelerating or automatic - or - (see Fig 3)
CC A
B Blocking or backup
3.5 Suffix Numbers. If two or more devices with
4MOC denotes a circuit breaker mechanism operated aux- the same function number and suffix letter (if
iliary switch which is mounted on the stationary housing of a used) are present in the same equipment, they
removable circuit breaker.
may be distinguished by numbered suffixes,
5Suffi N is generally used in preference to G for devices
connected in the secondary neutral of current transformers, as, for example, 4X-1, 4X-2, and 4X-3, when
or in the secondary of a current transformer whose primary necessary.
winding is located in the neutral of a machine or power trans-
former, except in the case of transmission line relaying, where
the suffix G is more commonly used for those relays that oper- 3.6 Devices Performing More Than One Func-
ate on ground faults. tion. If one device performs two relatively im-

14

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
DEVICE FUNCTION NUMBERS C37.2- 1987

portant functions in an equipment so that it is Relay7 Deenergized position


h
desirable to identlfy both of these functions, a Contactor7 Deenergized position
double function number and name, such as 50/51 Relay (latched-in type) See 4.5.3
instantaneous and time overcurrent relay, may be Contactor (latched-in Main contacts open
used. type)
Temperature relay8 Lowest temperature
Level detector8 Lowest level
4. Device Contacts Flow detector8 Lowest flow
Speed switch8 Lowest speed
4.1 Auxiliary, Position, and Limit Switch Con- Vibration detector8 Minimum vibration
tacts. The letters a and b shall be used for all Pressure switch8 Lowest pressure
auxiliary, position, and limit switch contacts for Vacuum switch8 Lowest pressure, that
such devices and equipment as circuit breakers, is, highest vacuum
contactors, valves and rheostats, and contacts of
4.1.1 Auxiliary Switches with Defined Oper-
relays:
ating Position. When it is desired to have the
a-Contact that is open when the main device auxiliary, position, or limit switch designation
is in the standard reference position, com- indicate at what point of travel the contacts
monly referred to as the nonoperated or change position, as is sometimes necessary in the
deenergized position, and that closes when case of valves and for other main devices, then an
the device assumes the opposite position additional letter (or a percentage figure, if re-
b -Contact that is closed when the main device quired) is added (as a suffix to the a or b designa-
is in the standard reference position, com- tion) for the purpose.
monly referred to as the nonoperated or For a valve, the method of designating such
deenergized position, and that opens when position switches is shown in the diagram and
the device assumes the opposite position legend in Fig 1. There are thus two points to con-
The simple designation a or b is used in all cases sider in visualizing or describing the operation of
-.. where there is no need to adjust the contacts to these position switches. The fist is whether the
change position at any particular point in the contact is an a or b as indicated by the first letter.
travel of the main device or where the part of the The second is where the contact changes position,
travel where the contacts change position is of no either at or near:
significance in the control or operating scheme.
(1) The closed position of the valve c
Hence the a and b designations usually are suffi- (2) The open position of the valve 0,or
cient for circuit breaker auxiliary switches.
(3) A specified percentage such as 25%of the
Standard reference positions of some typical full open position, as for example a25.
devices are as follows:
When applied to devices other than valves,
Standard gates, circuit breakers, and switches for which the
Device Reference Position letters o and c are used for open and closed,
Power circuit breaker Main contacts open respectively, it will be necessary to use other
Disconnecting switch Main contacts open applicable letters. For example, for such devices
Load-break switch Main contacts open as a clutch, turning gear, rheostat, electrode, and
Valve Closed position adjusting device, the letters d , e, h, 1, U , d , meaning
Gate Closed position disengaged, engaged, high, low, u p , and down,
Clutch Disengaged position respectively, are applicable. Also, other appro-
Turning gear Disengaged position priate suffix letters may be used for special a or
Power electrodes Maximum gap position b position switches, when these are considered
Rheostat Maximum resistance
position
Adjusting means6 Low or down position 7These electrically operated devices are of the non-latched-
in type, whose contact position is dependent only upon the
degree of energization of the operating or restraining or hold-
ing coil or coils which may or may not be suitable for continu-
ous energization. The deenergized position of the device is that
- 6These may be speed, voltage, current, load, or similar
with all coils deenergized.
8The energizing influence for these devices are considered
adjusting devices comprising rheostats, springs, levers, or to be, respectively, rising temperature, rising level, increasing
other components for the purpose. flow, rising speed, increasing vibration, and increasing pressure.

15

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2 -1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

VALVE POSITION
POSITION
SWITCH CLOSED OPEN

ac

a0

bc

bo

a25

a 75

b 25

b 75

LEGEND: SOLID LINE INDICATES SWITCH CONTACT CLOSED

Each of the eight valve positions can be described as a75, U contact which changes position when valve is
follows: 7 5 percent open, that is, closed only when valve is
ac, U contact which changes position at o r near the open 7 5 percent o r more
.closed position of the valve, that is, open only when b25, b contact which changes position when valve is
valve is fully closed 25 percent open, that is, closed only when valve is
ao, a contact which changes position at or near the open less than 25 percent
open position of the valve, that is, closed only when b75, b contact which changes position when valve is
valve is fully open 7 5 percent open, that is, closed only when valve is
bc, b contact which changes position at or near the open less than 7 5 percent
closed position of the valve, that is, closed only when
valve is fully closed
Example:
bo, 6 contact which changes position a t o r near the 20 BL designates an auxiliary switch, on a block valve,
open position of the valve, that is, open only when
valve is fullv oDen
-
ac which
closed
is open only when the valve is fully
_~__._
a25, a contact which changes position when whN-- ---I---
valve is-
25 percent open, closed or-
open, that is, closed only when
--I.* valve is designates an auxiliary switch, o n a discharge
open 25 percent or more a 10% valve, which is open except when the valve is
10 percent o r more open

Fig 1
Valve

more appropriate and if their meaning is clearly of the position which is 50%or more of the full
indicated. For example, in the case of an early open or on, as shown in Fig 2.
opening auxiliary switch on a power circuit 4.1.3 Auxiliary Switches for Circuit Breaker
breaker, adjusted to open when the breaker is Operating Mechanisms. For the mechanically
tripped before the main contacts part, it may be trip-free mechanism of a circuit breaker:
thus described and then designated as an ae aa Contact that is open when the operating
auxiliary switch. mechanism of the main device is in the
4.1.2 Auxiliary Switches for Devices Without nonoperated position and that closes when
A Standard Reference Position. In designating the operating mechanism assumes the oppo-
position switches for such a special device as,for site position
example, a fuel transfer device, which has no bb Contact that is closed when the operating
standard reference or nonoperated position and mechanism of the main device is in the
may be placed in either extreme or any inter- nonoperated position and that opens when
mediate position for normal operation, a and b the operating mechanism assumes the oppo-
designations are still applicable. However, a per- site position
centage figure of the full open or on position The part of the stroke at which the auxiliary
should always be used, and for the sake of consis- switch changes position should, if necessary,
tency, this percentage should always be in terms be specified in the description. LC is used to

16

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
DEVICE FUNCTION NUMBERS C37.2- 1987

VALVE POSITION
POSITION
SWITCH 100 PERCENT 100 PERCENT
LIQUID GAS
a IOOG U
0 .
0 .
b IOOG

a 75G

b 75G

a IOOL

b IOOL

a 75L

b 75L

LEGEND: SOLID LINE INDICATES SWITCH CONTACT CLOSED

Each of the eight positions can be described as fuel being supplied is gas
follows: alOOL, closed only when 1 0 0 percent of the fuel
a100G, closed only when 1 0 0 percent of the fuel being supplied is liquid
being supplied is gas blOOL, closed only when less than 1 0 0 percent of
blOOG, closed only when less than 1 0 0 percent of the fuel being supplied is liquid
the fuel being supp!ied is gas a75L, closed only when 7 5 percent o r more of the
a75G, closed only when 7 5 percent or more of the fuel being supplied is liquid
_ . fuel being supplied is gas b75L, closed only when less than 75 percent of the
b75G, cloied only when less than 7 5 percent of the fuel being supplied is liquid

Fig 2
Fuel Transfer Device

designate the latch-checking switch of such a desired torque limit at the extreme end of travel
mechanism, which is closed when the mechanism of a main device, such as a valve. It should be
linkage is relatched after an opening operation of designated as follows:
the circuit breaker. tqc Torque limit switch, opened by torque-
responsive mechanism, to stop valve closing
4.2 Limit Switches. LS designates a limit switch. tqo Torque limit switch, opened by torque-
This is a position switch that is actuated by a responsive mechanism, to stop valve open-
main device, such as a rheostat or valve, at or ing
near its extreme end of travel. Its usual function
is to open the circuit of the operating device, but it 4.4 Other Switches. If several similar auxiliary,
may also serve to give an indication that the main position, and limit switches are present on the
device has reached an extreme position of travel. same device, they should be designated with sup-
The designations ac, ao,be, and bo, given in Fig 1, plementary numerical suffixes as 1,2,3,etc, when
are actually more descriptive for valve limit necessary.
switches than such designations as LSC or LSO.
Also, in the case of a fuel transfer device as
covered in 4.1.2 designations such as alOOG, 4.5 Representation of Device Contacts on Elec-
blOOG, alOOL, and blOOL are more descriptive trical Diagrams
than LS designations. In both cases they indicate 4.5.1 Contacts with Defined Reference Posi-
whether the specific contact is an a contact or b tion. On electrical diagrams the b contacts of all
- contact. devices as described in 4.1 to 4.1.3 including those
of relays and those with suffix letters or percen-
4.3 Torque Limit Switches. This is a switch that tage figures, should be shown as closed contacts,
is used to open an operating motor circuit at a and all a contacts should be shown as open

17

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2- 1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

t
--
U

>t-
in+ u
U

W
eY
U
3 W

I-

z
a 3 - U
I:
U

a
U
x
c
c:
c
2
C

E
I&C

+- -
z-
0-
z
2
t
0
n
W

UI
-
> a -I/- it
0-
ln

18

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
DEVICE FUNCTION NUMBERS C37.2-1987

f I ::I

T-

N
n

c---+e----l I

- N W l

19

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.2- 1987 IEEE STANDARD ELECTRICAL POWER SYSTEM

contacts. The use of the single letters a and b with switches on the housing 52 TOC of a removable
the contact representation is generally super- circuit breaker unit, which are closed when the
fluous on the diagrams. However, these letters are unit is in the connected position, may be identi-
a convenient means of reference in the text of fied by
instruction books, articles, and other publications
(see Fig 3 and ANSUIEEE Std 315-1975, [2], for 52 TOC
representation of closed and open contacts on a
electrical diagrams). and those which are closed when the unit is with-
4.5.2 Contact Opening and Closing Settings. drawn from the housing may be identified by
The opening and closing settings of the contacts, 52 TOC
and auxiliary, position, and limit switches, covered
b
in 4.1 to 4.3 should, when necessary for the ready
understanding of the operation of the devices in as shown in ANWIEEE C37.20.1-1987, [4] and
the equipment, be indicated on the elementary ANSI/IEEE C37.20.2-1987, [ 5 ] .
diagram for each such contact. In the case of In the case of latched-in or hand-reset relays,
relay contacts, this indication would consist of the which operate from protective devices to perform
numerical settings; and in the case of the switches, the shutdown of an equipment and to hold it out
would consist of a chart similar to those shown in of service, the contacts should preferably be
Figs 1 and 2, respectively. shown in the normal nonlockout position. In
4.5.3 Devices Without a Standard Reference general, any devices, such as electrically operated
Position. For those devices that have no deener- latched-in relays, which have no deenergized or
gized or nonoperated position, such as manually- nonoperated position, have not been specifically
operated transfer or control switches (including covered in the above paragraphs or under 4.1,
those of the spring-return type) or auxiliary posi- should have their contacts shown in the position
tion indicating contacts on the housings or enclo- most suitable for the ready understanding of the
sures of a removable circuit breaker unit, the operation of the devices in the equipment, and
preferred method of representing these contacts sufficient description should be present, as neces-
is normally-open. Each contact should, however, sary, on the elementary diagram to indicate the
be identified on the elementary diagram as to contact operation.1
when it close^.^ For example, the contacts of the 4.5.4 Recommended Representationof Device
manual-automatic transfer switch, device 43, Functions and Contacts on Drawings. The typi-
which are closed in the automatic position, would cal elementary diagram in Fig 3 illustrates the
be identified with the letter A, and those that are recommended method of representing the con-
closed in the manual position would be identified tacts of typical devices on an elementary diagram.
with the letter M; and the auxiliary position All other representations and features, except
those specifically covered in other American
National Standards, are illustrative only and are
'This information should be included on that part of the not necessarily generally accepted practice.
elementary diagram, either with the device symbol or with the
contacts in the circuit diagram itself, where most convenient
for the ready understanding of the operation of the devices
and equipment. "See footnote 9.

20

Authorized licensed use limited to: Escuela Superior de Ingeneria Mecanica. Downloaded on March 15,2017 at 14:47:23 UTC from IEEE Xplore. Restrictions apply.

Potrebbero piacerti anche