Sei sulla pagina 1di 2

INSULATION SYSTEM FOR INTERNAL CON- Materials

NECTORS IN GAS COOLED TURBINE Let us proeeed to relate our experience in the effort to provide
reliable connector insulation:
GENERATORS
Asphalt Mica
by
AGusTus LEHRKIND, Senior M ember I.E.E.E. Since conventional class B stator coil insulation for many years
AND has been asphalt bonded mica, the first selection of connector
FRANK C. PETERMANN insulation was the same. No major problems in this application
Allis-Chalmers Manufacturing Company were experienced. However, the possibility of softening of the
Milwaukee, Wisconsin asphalt in the presence of excessive amounts of oil and some
thoughts on cost reduction led to trial of other materials.
IEEE 32C3-95
Silicone Rubber
Introduetion The ease with which silicone rubber tapes could be applied to
The stator windings of turbine generators require rugged, heavy the connectors and the known high dielectric strength of the rub-
duty connections to the terminal bushings. In the larger machines ber promised important benefits in the application. Since the
these connectors are internally caoled by means of hydragen gas rubber tape was thicker than mica tape, Jess time was required
circulated through them in parallel with the generator windings. to build up the required insulation thickness. Additional silicone
A typical arrangement is shown in Figure 1. The "connectors" rubber paste was applied to eliminate voids. The tape and paste
referred to in this paper are capper pipes, one to two inches out- combination required heat curing, but the finisbed product pro-
side diameter with ! to i inch wall thickness carrying currents up virled excellent resistance to heat and moisture. Protection against
to 9000 amperes and insulated for 22000 volts line-to-line. They meehanical damage was furnished by an outer wrapping of woven
operate normally at class "B" temperatures with foreed gas cooling. glass tape.
The purpose of this paper is to show some of the reliability prob- A peculiar chain of eireurnstances revealed the real capability
lerns encountered in the practica! application of insulation matcrials of the silicone rubber insulation. This experience, which we
and our means of solving these problems. noted in listing Requirement One, occurred when oil leaking into
a generator blocked the ventHation passage at the discharge end
of a connector. The initia! alarm of abnormal operation was
Reliability Requirements sounded when electrical unbalance of the generator output was
This study might never have begun except for a startling dis- observed. Ability of the insulation to withstand the extremely
covery during investigation of a machine failure in service. A por- high temperature, even for a brief moment, permitted safe remaval
tion of the capper pipe melted when ventilation became blocked. of the machine from service.
The surrounding insulation remained in place and prevented a The field repair of the connector which failed because of loss
short circuit which might have caused major damage to the ma- of ventilation required a samewhat different insulation than the
chine. Requirement One-The insulation must withstand momen- molded silicone rubber system originally applied at the facto ry.
tarily the temperature of molten copper. Limitations of space and the great difficulty in provirling means
In spite of elaborate features designed to keep oil out of large to cure the tape under heat and pressure dictated the use of self
generators, sooner or later, it seems, oil does enter. The oil accumu- fusing triangular silicone rubber tape with an outer sheath of
lates in regions of low gas velocity and low temperatures. Some glass tape. After approximately a year's normal operation, the
of our subject connectors are likely to be in these regions. Require- new insulation showed severe cracking and bulging of the self
ment Two-The insulation must beresistant to oil. fusing tape eausing rupturing of the outer glass tape, whereas
The physical structure of the connector assembly with its sup- the original insulation showed no signs of distress.
porting clamps and brackets farms a handy ladder for anyone Laboratory investigations of selected sections revealed the fol-
elimhing into the machine for inspeetion purposes. "Prohibition" lowing. Because no thermal cure was applied, the stresses intro-
doesn't work here. Therefore, Requirement Three-The insulation dueed by the stretch of the tape during winding were retained.
must have physical strength to resist abrasion and compression. The normal heat of operation tended to overcome those stresses
All parts of an altemating current machine are subjected to and caused circumferential growth resuiting in Iocalized cracking
vibration initiated by the magnetic farces. Ciaroping pressures of the insulation.
must be adequate to prevent differential vibration between parts. The presence of lubricating oil caused an overall swell of 14o/o
Requirement Four-The insulation must have dimensional stability in volume of the self fusing silicone rubber. To accommodate
to assure continued operation. this swelling, the outer glass tape would have required an elanga-
tion of 7%. The resuiting hoop stresses ruptured the glass tape.
The destruction continued. The rubber restrained laterally by the
supporting clamps of the connectors extruded into the braken tape
areas and, aided by the swelling effect of the Iubricating oil, caused
further cracking of the self fusing tape. Measurements at the
cracks showed wall thicknesses in the local areas to be 45%
greater than at original application.
Epoxy Mica Tape
Except for the binder, epoxy mica tape is basically the time
proven high voltage insulation of mica splittings sandwiebed
between backing matcrials to provide meehanical strength neces-
sary for the application of the tape. Asphaltum base varnishes
were originally used as a binder for the mica and backing. Short-
comings in the thermal and meehanical properties of this asphalt
binder led to the substitution of epoxy resin binders.
Laboratory investigations of epoxy bonded mica tape showed
it to meet many of the requirements demanded for connector
insulation. A section of connector was insulated for 22,000 line-to-
line volts and cured under heat and pressure. After immersion in
lubricating oil for 738 hours at 180C, the connector insulation
samples actually had shrunk only approximately -! of a per cent.
Subjecting these samples, immediately after remaval from the
hot oil, to a damping laad of 25 pounds per inch of axial length
imposed across the diameter, caused an elastic defiection of the
insulation system of approximately 1% and an inelastic defiection
or creep of a bout 1%.
Laboratory Tests
In order to duplicate field conditions affecting the four types of
connector insulations, that is, asphaltum mica, heat-cured silicone
rubber, self-fusing silicone rubber, and epoxy mica, a number of
test bars were made. The first bar's insulation simulated the con-
nector that failed due to loss of ventilation. It was prepared from
semi cured silicone rubber tape coated with a silicone paste with
an outside armor sheath of bias glass silicone rubber tape. This
assembly was then cured under pressure for four hours at 135C.
Figure I-Internal eonneetor arrangement. After cure, the bar successfully withstood a dielectric test of
213
27,500 volts RMS 60 cycles per second for 20 minutes which dupli- The second series duplicated assembied conneetion insulation or
cates a normal field dielectric absorption test of 125% line-to-line field repair work where curing under higher temperatures and pres-
voltage. Repeated oven bakings of 24 hours at 75C and 200C sure is not practicable. The bars were insulated for 22,000 line-to-
and a final 66 hour hake at 250C each with a 27.5 kv voltage line volts, given an outer glass tape shield and painted with several
test indicated no loss of dielectric strength. However, the rubber coats of red alkyd enamel. Since normal operating temperatures of
appeared lifeJess and had completely dried out from the extreme turbo-generators are in the 100C range, the bars were baked at
temperatures of baking. this temperature for 66 hours. Complete curing of the epoxy binder
The second series of test bars simulated the field repair insula- was accomplished and this was substantiated by the fact that no
tion. Bars insulated with self fusing tape protected with an outer heating of the insulation occurred after a successful dielectric test
sheath of glass tape and several paint coats of red alkyd enamel of 27.5 kv for 20 minutes. The tests therefore confirmed that field
were heated both electrically (internally) and in an oven. Swell- repairs with epoxy-bonded mica could be made, and the cure
ing of the rubber occurred after only an hour's heating at 150C;. effected during normal operation of the unit.
after 24 hours at 290C the portion of the silicone rubber next to
the copper was deeply cracked and fissured; it had the appearance
of "a dried out river bed." Conclusions
Asphaltum base mica tape, used for many years as connector From this series of test bars. the following conclusions regarcling
and conneetion insulation, was applied to test bars and subjected phase lead insulation have been drawn:
to both thermal and dielectric tests. Baking of these bars at 100C 1. A silicone rubber insulation system comprised of the molded
showed no marked deterioration other than a slight amount of tape and paste combination exhibits good insulation prop-
bleeding of the asphaltum varnish. Subjecting the bars to 27.5 erties even when subjected to as much as twice normal operat-
kv for 20 minutes caused the insulation to become very warm, ing temperatures.
indicating corona action between the Jayers of tape. 2. A silicone rubber insulation system comprised of self fusing
Test bars made of epoxy bonded mica tape with two types of tape deteriorates under heat and bulges when contined by
application were then investigated. The first consisted of curing protective glass tape.
the tape under pressure for 8 hours at 160C~ This simulated the 3. Asphalt mica tape used as conneetion insulation indicates
normal connector insulation processed before assembly in a turbo- internal heating as demonstrated by dielectric tests.
generator. The bars were baked for 24 hours at 200, then 250, 4. Epoxy mica tape, although losing some of its binder when
and finally at 290 C. Although there was a slight amount of overheated, remains relatively unchanged under heat and
bleeding of the epoxy binder, this in no way decreased the dielectric dielectric tests. When used for field repairs of conneetion
strength of the insulation system. No heating of the insulation was insulation, it can be left to cure under normal machine
noted after applying 27.5 kv for 20 minutes. operating temperatures.

INSULATION RELIABILITY OF WINDINGS than a dielectric harrier, and this is ve ry well fulfilled by the
FOR LARGE ROTATING MACHINES usual wire insulation for large machines, two resin-bonded Jayers
of glass servings. The meehanical strength of this insulation is
by evaluated with a scrape-resistance test, while the integrity of the
E.M. FORT ANDR. ]. HILLEN insulation as a spacer, also after forming of the coil, is assured
Westinghouse Electric Corporation by specifying continuity of the glass serving both before and
East Pittsburgh, Pennsylvania after bending of the wire.
IEEE 32C3-96 Besides the requirement that the resin should be a good dielec-
tric and be thermally stabie at operating temperatures, it is neces-
sary that it has no adverse effect on other resins used in the coil.
Introduetion
Although this can only properly be tested by the coil manufacturer,
The reliability of the winding insulation in large rotating ma- the wire resin will in general cause no troubie if it is fully cured.
chines is becoming more and more important. As the usage of And finally, in order to have a certain spacing between wires
electric power increases and the machine size with it, economic without wasting slot space, the thickness of the wire insulation
considerations dietate the necessity for long periods of continuous must be within certain Iimits. The tolerances here are mainly
operation with a minimum of shutdown time for maintenance.
In order to secure this uninterrupted service, a maximum reliability
of each coil in the winding is required. Because of the investment
of matcrials and man-hours contained in large stator coils, it is
economically advantageous to assure the reliability of each coil by
tests made as early in the manufacture as possible in addition to
the final acceptance test on the winding. The general quality level
of each separate component should therefore be assured by tests
prior to their assembly, and this should be the responsibility of
the supplier of the component. After the assembly of the coil, ii-+--WIRE
however, additional special tests are often needed. The nature of
these tests is determined by the fundion of each component in ~~:;~.IQt--1-WIRE INSULATION
the assembied coil, and the required quality levels are established
by development tests, statistica! data treatment, and past experience. +i---........._,:i----7--- TUBE

Tests Made by the Component Supplier ~~~~i=i-t--TUBE INSULATION


An inner-cooled generator coil of the type that uses separate ~i---i--SEPARATOR
cooling tubes is used for illustration (Figure 1). The insulating
components in such a coil fall in five grou ps; wire insulation, tube
insulation, separators and binders, mica tape for slot insulation, 1----1~~~--tll- Bl NDER
and resins.
.-;.--TAPE
W ire I nsulation
The voltage difference between two adjacent copper wires in a
LBINDER
one-turn generator coil is only a few volts, even for a high-voltage
coil. On the other hand, the meehanical abrasive forces between
two wires can be considerable. The function of the insulation of
the wire is therefore more that of a mechanically strong spaeer Figure 1-Typieal inner-eooled coil.

214

Potrebbero piacerti anche