38 TECHNCOMMERCIAL

Harmonics - A power quality problem


A growing power quality concern is harmonics distortion that is caused by the non-linearity of customer
loads. This concern has drawn much attention from utilities, manufacturers of equipment and users.
Harmonics distorts the waveform shape of voltage & current, and increases the current level, which results
in many disturbances. Read on to find out how harmonics affects the power quality and the various ways in
which it can be avoided

Haren Shah
Ride-through features

T
he ideal quality of power supply is Adjustable speed drives are the most sensitive
characterised by electric power energy with equipment to prevent voltage sags; drives are
perfect sinusoidal waveform at a constant immediately tripped off when the DC bus voltage
frequency of specified constant voltage with least drops below the tripping level. There are two
amount of interruptions. Harmonics is one of the parameters involved in ride-through features. One
major factors due to which none of the conditions is the DC bus under voltage tripping level. The
are fulfilled in practice. Harmonics is defined as other is the ride-through time. In some cases,
the content of the signal whose frequency is an certain ride-through features, by way of changing
integer multiple of the systems fundamental new parameters of the drive system, are
frequency. The presence of harmonics distorts the recommended. Some parameters are user
waveform shape of the voltage and current, programmable, whereas others need changes
increases the current level, and changes in hardware in order to ride through the voltage
power factor supply, which in turn creates sag. The ride-through features can be achieved
many disturbances. in AC drives by changing user-programmable
Voltage sags is the most important cause of parameters.
interruption of industrial processes. Power quality
problems encompass a wide range of disturbances Harmonics distortion
such as harmonics distortion, swell transients, A growing power quality concern is harmonics
interruption, etc. But, voltage sags is a major distortion that is caused by the non-linearity of
source of power quality related problems. Poor customer loads. This concern has drawn much
power quality can affect industrial processes. attention from utilities, manufacturers of
equipment, and users. Harmonics distortion is load
Power quality sensitive; devices that draw non-sinusoidal current
Power quality problem is defined as any from sinusoidal voltage sources cause it.
problem manifested in voltage, current or Harmonics current, generated by non-linear loads,
frequency deviations that result in failure or interacts with power system impedance to give rise
malfunction of customer equipment. Harmonics, to harmonics voltage distortion. If this distortion
voltage flicker, voltage regulation, unbalance, exceeds the recommended limit it can cause
voltage sag, voltage swell, and interruption, usually motor, transformer, and neutral wire heating;
characterise the quality of electric power. Some of computers may exhibit data error or loss of data,
the power quality problems created by the drives and electronic process control may operate out of
are harmonics, notching, etc, being heavily sequence. Premature failure of power factor
dependent on the supply system configuration, correction capacitor is a common problem
process equipment design, system switching, and associated with harmonics distortion.
protection practices. Due to the wide use of
adjustable AC & DC drives in all industrial Harmonics mitigation techniques
applications, analysis of power quality problems is The generation of harmonics, whenever an
very important. adjustable speed drive is used, is inevitable. The

INDUSTRY WATCH - Electrical & Electronics September-October 2005


TECHNOCOMMERCIAL 39

Power supply from power company 50 Hz load current voltage drop


regulators, etc, in both domestic as well
as the industrial sectors, also inject
harmonics substantially.
Line Line B Line C
Impedence Impedence Impedence The operation of the transformers
Electrical load
closer to the saturation region of
Voltage drop of harmonic
wave current magnetisation characteristic, non-
A
Wave form of voltage Capacitance sinusoidal air gap flux in synchronous
load
Harmonic wave machines, magnetisation current of
current source D saturated reactors are some of the
Current Harmonic wave
Wave form current source causes of harmonics generation that are
load
of voltage related to electrical equipment.
Capacitors used in transmission systems
Harmonic wave do not generate harmonics. However,
they may cause resonance near a
harmonic frequency, which in turn
Figure 1: Harmonic wave voltage caused by harmonic wave current
induces a large current and voltage. Thus,
order and magnitude of these harmonics Harmonics mitigation techniques the widespread use of shunt capacitors to
will greatly depend on the drive with PWM: Harmonics can be reduced to improve power factor and stability,
configuration and system impedance. less than one per cent of the influence harmonics levels significantly.
The various harmonic mitigation fundamental with the help of PWM; it is The major causes of generation of
techniques available are as follows: programmable to eliminate specific harmonics are related to the supply
Phase multiplication: Whether the drive harmonics. In addition to the above system converters and tractions.
is AC or DC, the common means of techniques, harmonics can be reduced
reducing harmonic generation while in by a number Effects of harmonics on equipment:
the design process is by phase of circuit techniques. There are two major categories of
multiplication or harmonic cancellation. harmonics effects on equipment:
It is effective in reducing low order Harmonics waveform a) Heating effects in power handling
harmonics as long as the load is Electricity is produced and delivered equipment such as motors,
balanced. in its fundamental form as a 50 cycles/ capacitors, and transformers that
Passive filters: Improved power factor sec (Hz) sine wave in India. Harmonics most often reduce the equipments
reduces high frequency harmonics. are multiples of the 50 Hz waves. For eg, operating life
Large tuning reactors are not used as the second harmonic is at 100 Hz, the b) Disruption of operation that includes,
instability may occur due to parallel third is at 150 Hz, etc. As harmonics are for the most part, electronically
resonance with the source impedance. superimposed on the fundamental controlled equipment
Performance depends upon source waveform, frequency of the electricity
impedance; it cannot be measured does not follow a smooth sine. Most Harmonic current amplification
accurately and can vary with system electrical equipment are designed to Application of power factor
changes. Hence, passive filters are not handle smooth frequencies. Hence, improvement capacitor in presence of
appropriate for cycloconverters. distortions created by harmonics can static power converters can result in
Active filters: With improved power cause a variety of problems. another problem, especially if the
factor, the output current can be resonant frequency is close to one of
controlled. Active filters provide stable Sources of harmonics the characteristic harmonics. Exciting
operation against AC source impedance More use of solid-state power the natural frequency of the parallel
variation, and fast response irrespective converters for industrial furnaces for combination of the capacitor and system
of the order and magnitude of mini steel and non-ferrous metal plants, inductance will result in amplified
harmonics. These filters are appropriate use of thyristors for locomotives, harmonic currents. Amplified currents
for cycloconverters. The initial and especially for railways due to the may cause overheating of equipment
running costs are usually higher than massive electrification programme, protective devices.
passive filters. The injection may flow and extensive use of single-phase Parallel resonance created with the
into other system components. electronic loads in domestic sectors are use of capacitors in the presence of
Harmonics injection: Harmonics injection causes of harmonics generation. harmonics can result in overloading or
takes care of uncharacteristic Rapid use of energy conservation devices equipment damage. This problem can be
harmonics. System impedance is not a such as electronic chokes for tube lights, avoided by shifting the resonant
part of the design criteria as it may give electronic energy controllers frequency, derating the equipment, and
rise to low order harmonics. for the motors, and electronic fan applying harmonic filters.

INDUSTRY WATCH - Electrical & Electronics September-October 2005


40 TECHNCOMMERCIAL

Measuring harmonics wave current: Power supply from power company


While talking about harmonic waves
the emphasis is always on harmonics A
B C
wave voltage. The resonance is very
Measuring General load
simple, because the easiest way of Voltage
observing power quality is to observe it
Measuring Capacitance
with an oscillator. The waveform Voltage load
observed with an oscillator is the voltage Measuring
Voltage D
waveform, but very few people can see Measuring
Voltage
the waveform of current. As a result, Measuring Measuring
Voltage Voltage
many people assume harmonics wave
Harmonic
voltage to be the troublemaker causing wave current
many obstacles. In fact, the
troublemaker resulting in an unusual
change in voltage waveform is the
Figure 2: Measuring points of harmonic wave
harmonics wave current. Therefore, if
you are affected by harmonics or have wave current is delivered to the monitoring the devices regularly. The
been unable to cope with the control power system. disturbances due to power quality
standards required by power/utilities As shown by the dotted-line arrow in problems can be easily monitored using
companies, you should know the Figure 1, voltage drop due to harmonic handy and quality instruments. The
measure of the harmonics wave wave current takes place in the power clamp-on power, leakage & harmonics
contained in waveform of current or system. Voltage at point A is a voltage analyser (model 5850) manufactured by
percentage value within the power drop due to 60 Hz load current as a Meco Instruments is one such
system. Nevertheless, measuring result of voltage reduction in power instrument. Meco has also introduced an
the current is not very easy unless system. Voltage at point B is the same. analyser (model PHT 4545), which is a
detection element serials are included Voltage drop at point C is due to a 60 Hz state-of-the-art versatile instrument
in the circuit. load current and harmonics wave using micro controller technology and
current as a result voltage reduction in having various functions. It would be
Measuring harmonics wave voltage the power system. Therefore, such a ideal for an inspector to carry out
Owing to a change in the load waveform is an unusual change rather periodic visits, vigilance checks, surveys,
current value, including 60 Hz base than the 60 Hz sine wave form. The raids, and audits at the industrial and
frequency and harmonics wave current increase in voltage at point D is due to consumers end.
of each level, one should check whether an unusual voltage waveform to the The objectives of 'solution for
the voltage is normal before imposing a harmonics wave current. harmonics in power' are very good, but the
load. Customarily, the voltage waveform On observing Figure 1, one realises road ahead is very long and rough. It
determines the power quality. that each point, as shown in Figure 2, is needs full cooperation from manufacturers
required for measuring the harmonics and the users of power as well as the
Harmonics wave voltage and current wave current and voltage form. As it is central and the state governments.
As shown by the full-line arrow in based on different objectives of analysis,
Figure 2, load relates to power supply the measuring points are different. This Note: Some of the details, examples
from the power company, and a 60 Hz figure serves reference purposes only. or case studies taken from articles like
load current comes from the power In order to ensure quality IEEMA journal (a article by Prof B E
system. The load current will keep on performance of various power system Kushare, Dr A A Ghatol, A K Mathur & K
causing drops in voltage. If it is a devices it is necessary to understand the Ravikumar) as well as from journals and
general load, voltage will drop by getting problems deeply and incorporate more magazines are issued herewith for the
closer to the end of feed line, if it is a remedial measures. awareness & knowledge of readers.
capacitance load current, then voltage While providing solutions to power
rises. The waveform of current is a quality problems, cost plays a major
60 Hz sine wave; hence, the waveform of role. Hence, it is always necessary to The author works with
voltage also remains a 60 Hz sine wave. find cost effective solutions to resolve the marketing
Harmonics wave current flows out of power quality issues, and minimise department of Meco
a non-linear load and some SCR equipment downtime and loss of Industries Pvt Ltd,
non-linear loads obtain 60 Hz sine production. This objective can be Mumbai.
wave current from the power achieved by not only taking some minor E-mail: info@mecoinst.com;
supplying company, and then harmonics precautions but also by measuring and harenvshah@yahoo.com

INDUSTRY WATCH - Electrical & Electronics September-October 2005