Sei sulla pagina 1di 9

SP BER IN GIN A FIELD

PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 1 / 6

NAMA PROYEK : SP BERINGIN A FIELD PRABUMULIH

PERUSAHAAN : PT PERTAMINA EP (Persero) Tbk.

KONSULTAN : PT WIJAYA KARYA (Persero) Tbk.

LOKASI PROYEK : PRABUMULIH, SUMATERA SELATAN

JUDUL DOKUMEN : PROCESS CONTROL

NOMOR DOKUMEN : S-250-A224-001

1 11-12-14 IFB AR/ACH ARF DS


PREPARED BY CHECKED BY APRROVED BY CHECKED BY APRROVED BY
REV DATE DESCRIPTION
PT. WIJAYA KARYA (PERSERO) Tbk. PMC PDG

LIST OF REVIEW

Page
Rev. No. Paragrap Number Description of change
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 2 / 6

A. OBJECTIVE :
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 3 / 6

Dehydration Unit is used to reduce the water content of the natural gas inlet so that the natural gas
outlet (sales gas) meet the specification as describe below.

B. PROCESS CRITERIA :
1. The gas dehydration system for SP Beringin-A will be installed downstream of HP Gas Scrubber
and therefore, the inlet gas to the gas dehydration unit is saturated at the operating conditions.
2. The gas dehydration unit shall be designed to reduce the water present in the inlet gas stream to
meet the water dew point. The water content in the outlet gas stream should be less than 7 lb/MMscf
of gas.
3. The allowable pressure drop of dehydration unit is not greater than 20 psi.
4. If glycol based dehydration unit is offered, then the following design criteria shall be considered for
the design of gas dehydration unit.
(a) The absorbent shall be TEG (Triethylene Glycol)
(b) TEG Losses shall not exceed 0.1 US Gallon/MMscf.
(c) The glycol inlet temperature shall be maintained 10 deg F above the inlet gas temeperature to
prevent condensation where the glycol enters the contactor and foaming inside the contactor.
(d) To minimize glycol degradation, the glycol reboiler temperature shall not exceed 400 deg F.
(e) The heating medium for the TEG reboiler is fuel gas.
(f) To prevent glycol degradation, the temperature of fuel gas entering the glycol reboiler shall not
exceed 440 deg F.
(g) The gas dehydration unit shall include the complete Glycol Regeneration system also.
5. The gas dehydration unit shall be designed for reliable and efficient operation for a turndown ratio
of 1:4.
6. Properties of C7+
API Gravity at 60 oF : 51.86
Specific Gravity : 0.7636
Molecullar Weight : 114

C. OPERATION DATA

UNITS
CASE 1
CASE 2
GAS INLET TO UNIT :

Design Pressure
psig
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 4 / 6

1015
1015
Design Temperature
o
F
155 (STC)
155 (STC)
Operating Pressure
psig
845
821
Operating Temperature
o
F
105
105
Gas flow rate
lb/hr
48080
36220

MMSCFD
20
15
Gas Composition

Mole fraction
Mole fraction
CO2

0.067775
0.067702
H2S

0.000000
0.000000
N2

0.010241
0.010036

C1

0.758249
0.751231
C2
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 5 / 6

0.085465
0.086120
C3

0.053884
0.056572
n-C4

0.009104
0.010559
i-C4

0.006975
0.007801
n-C5

0.001455
0.001998
i-C5

0.001780
0.002320
n-C6

0.001543
0.002172
C7+

0.001858
0.001782
H2O

0.001672
0.001707

GAS OUTLET :

Operating Pressure
psig
839
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 6 / 6

816
Operating Temperature
o
F
STA
STA
Max Water content
lb/MMSCF
7
7
STA - Supplier to advise

STC- Supplier to confirm

D. UTILITIES :

Instrument Air/Utility Air Instrument Air Utility Air


Normal supply pressure, psig 150 150
Min supply pressure, psig 90 -
Temperature Ambient Ambient
Dew Point -40 deg F -
Oil free and max. 1 micron dust/impurities. Oil free

Electrical
(1) Motors above 250 HP 6600 V AC, 3 phase, 50 Hz
(2) Motors up to 250HP 400 V AC, 3 phase, 50 Hz
(3) Fractional motors 230 V AC,1 phase, 50 Hz
(4) Instrument 230 V AC, 1 phase, 50 Hz
230 V AC, 1 phase, 50 Hz
(5) Electrical Control 230 V AC, 1 phase, 50 Hz
(6) Instrument Control 24 V DC

Fuel Gas
Pressure (psig) 60
Temperature (F) 84

Composition : Mole fraction


CO2 0.074619
H2S 0.000000
N2 0.008280
C1 0.692096
C2 0.106025
C3 0.079547
n-C4 0.014143
SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 7 / 6

i-C4 0.010759
n-C5 0.002218
i-C5 0.002729
n-C6 0.002259
C7+ 0.002480
H2O 0.004845

E Climatic Conditions:
1. Ambient temperature, deg F. (Max./Average) : 95 / 86.
2. Relative humidity (RH) is 87 %,
3. Ambient Temperature for Air coolers : 95 deg F.

SKETCH SUPPLIERS SCOPE OF SUPPLY :

= SUPPLIERS SCOPE OF SUPPLY


SP BER IN GIN A FIELD
PR AB UM ULIH

REV: 0
S-250-A224-001 SPECIFICATION FOR DHU
PAGES: 8 / 6

Potrebbero piacerti anche