WhatisArcFlash?
ArcFlashistheresultofarapidreleaseofenergyduetoanarcingfault
betweenaphasebusbarandanotherphasebusbar,neutraloraground.
Duringanarcfaulttheairistheconductor.Arcfaultsaregenerallylimitedto
systemswherethebusvoltageisinexcessof120volts.Lowervoltagelevels
normallywillnotsustainanarc.Anarcfaultissimilartothearcobtained
duringelectricweldingandthefaulthastobemanuallystartedbysomething
creatingthepathofconductionorafailuresuchasabreakdownininsulation.
Thecauseoftheshortnormallyburnsawayduringtheinitialflashandthearc
faultisthensustainedbytheestablishmentofahighlyconductiveplasma.
Theplasmawillconductasmuchenergyasisavailableandisonlylimitedby
theimpedanceofthearc.Thismassiveenergydischargeburnsthebusbars,
vaporizingthecopperandthuscausinganexplosivevolumetricincrease,the
arcblast,conservativelyestimated,asanexpansionof40,000to1.Thisfiery
explosiondevastateseverythinginitspath,creatingdeadlyshrapnelasit
dissipates.
Thearcfaultcurrentisusuallymuchlessthantheavailableboltedfault
currentandbelowtheratingofcircuitbreakers.Unlessthesedeviceshave
beenselectedtohandlethearcfaultcondition,theywillnottripandthefull
forceofanarcflashwilloccur.Theelectricalequationforenergyisvoltsx
currentxtime.Thetransitionfromarcfaulttoarcflashtakesafinitetime,
increasinginintensityasthepressurewavedevelops.Thechallengeisto
sensethearcfaultcurrentandshutoffthevoltageinatimelymannerbeforeit
developsintoaseriousarcflashcondition.
WhythefocusonArcFlash?
Intheearly1980'sapaper"TheOtherElectricalHazard:ElectricArcBlastBurns"byRalphLeewaspublishedintheIEEE
TransactionsonIndustrialApplications.Theeffectofthispaperwastorealizetheneedtoprotectpeoplefromthehazards
ofarcflash.Fourseparateindustrystandardsconcernthepreventionofarcflashincidents:
OSHA29CodeofFederalRegulations(CFR)Part1910SubpartS.
NFPA702002NationalElectricalCode.
NFPA70E2000StandardforElectricalSafetyRequirementsforEmployeeWorkplaces.
IEEEStandard15842002GuideforPerformingArcFlashHazardCalculations.
CompliancewithOSHAinvolvesadherencetoasixpointplan:
Afacilitymustprovide,andbeabletodemonstrate,asafetyprogramwithdefinedresponsibilities.
Calculationsforthedegreeofarcflashhazard.
Correctpersonalprotectiveequipment(PPE)forworkers.
Trainingforworkersonthehazardsofarcflash.
Appropriatetoolsforsafeworking.
Warninglabelsonequipment.Notethatthelabelsareprovidedbytheequipmentowners,notthemanufacturers.It
isexpectedthatthenextrevisionoftheNationalElectricCodewillrequirethatthelabelscontaintheequipment's
flashprotectionboundary,itsincidentenergylevel,andtherequiredpersonalprotectiveequipment(PPE).
Companieswillbecitedandfinedfornotcomplyingwiththesestandards.
PersonalProtectiveEquipment(PPE)
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 1/9
3/13/2017 WhatisArcFlash?
CategoriesofPPEasdescribedinNFPA70Eare:
0 1.2 UntreatedCotton
1 5 Flameretardant(FR)shirtandFRpants
2 8 CottonunderwearFRshirtandFRpants
3 25 CottonunderwearFRshirt,FRpantsandFRcoveralls
CottonunderwearFRshirt,FRpantsanddoublelayerswitchingcoat
4 40
andpants
Cal/cm2aretheunitsofincidentenergythatthePPEcanwithstand.Notethatahardhatwithfullfaceshieldandthe
appropriateglovesarerequiredalso.
Stepsrequiredforaflashhazardanalysis
Toperformanarcflashhazardanalysis,dataiscollectedaboutthefacility'spowerdistributionsystem.Thedataincludes
thearrangementofcomponentsonaonelinedrawingwithnameplatespecificationsofeverydevice.Alsorequiredare
detailsofthelengthsandcrosssectionareaofallcables.Theutilityshouldbecontactedforinformationincludingthe
minimumandmaximumfaultcurrentsthatcanbeexpectedattheentrancetothefacility.Oncethedatahasbeen
collected,ashortcircuitanalysisfollowedbyacoordinationstudyshouldbeperformed.Theresultantdatacanthenbefed
intotheequationsdescribedbyeitherNFPA70E2000orIEEEStandard15842002.Theseequationswillproducethe
necessaryflashprotectionboundarydistancesandincidentenergytodeterminetheminimumPPErequirement.
Flashhazardanalysisanewapproach
Oncethedataispreparedandaflashhazardanalysishasbeenperformed,mostlikelyitwillbediscoveredthatcategory4
PPEwillberequiredinmostplaces.ThisismostunfortunateasthistypeofPPEisveryunwieldyandcouldbecostlyin
termsoftimetakentoperformworkandthepotentialformistakes.Priortothenewarcflashregulations,coordination
studiesweretargetedatreliabilitywithallsettingsadjustedtowardsthehighside.Compliancewiththenewarcflash
regulationsmeansthatnotonlydoesthecoordinationstudyneedtobemoreaccuratebutitalsoneedstotakeinto
accountthefactthatthearcfaultcurrentislessthantheboltedfaultcurrent.
Thedatacanbeusedtoperformasensitivitystudytoadjustbreaker/fusecharacteristicstolowerthePPErequirement.To
achievethisgoal,theexistingbreakersmayneedtobereplaced,generallybymoremoderncounterparts.Oldbreakers
haverelativelyslowreactiontimesandwilltripattoohighacurrent.Tolimittheflashhazardthebreakersareadjustedto
tripearlierthanbefore.Itisexpectedthattheoutcomeofthissensitivitystudy,whenimplemented,willresultinmost
category4PPErequirementsbeingdecreasedtocategory1or2.
ShortCircuitStudy
Theshortcircuitstudyisbasedonareviewofonelinedrawings.Thedrawingsmustbecreatediftheydonotexist,and
fieldverifiediftheydo.Maximumavailablefaultcurrentiscalculatedateachsignificantpointinsystem.Eachinterrupting
protectivedeviceisthenanalyzedtodeterminewhetheritisappropriatelydesignedandsizedtointerruptthecircuitinthe
eventofaboltedtypeofshortcircuit.Next,theassociatedequipmentmustbereviewedtoinsurethatthebusbaris
adequatelybracedtohandletheavailablefaultcurrent.Finally,theboltedfaultcurrentsareconvertedintoarcfaultcurrents
foradditionalanalysis.
CoordinationStudy
Acoordinationstudyistheexaminationoftheelectricalsystemandavailabledocumentationwiththegoalofensuringthat
overcurrentprotectiondevicesareproperlydesignedandcoordinated.Overcurrentprotectivedevicesarerated,selected
andadjustedsoonlythefaultcurrentcarryingdevicenearestthefaultopenstoisolateafaultedcircuitfromthesystem.
Thispermitstherestofthesystemtoremaininoperation,providingmaximumservicecontinuity.Thestudyconsistsof
timecurrentcoordinationcurvesthatillustratecoordinationamongthedevicesshownontheonelinediagram.Notethat
protectivedevicesaresetoradjustedsothatpickupcurrentsandoperatingtimesareshortbutsufficienttooverride
systemtransientoverloadssuchasinrushcurrentsexperiencedwhenenergizingtransformersorstartingmotors.
TheProblems
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 2/9
3/13/2017 WhatisArcFlash?
Nowthatthehazardsassociatedwitharcflashhavebeenbroughttoourattention,wefacetheproblemoftryingto
eliminateoratleastreducethosehazards.Thefollowingdiscussessomeoftheseproblemsandthesubtletiesin
implementingcorrectiveactions.
ThereareseveralproblemsindealingwithArcFlashAnalysis:
1.BeingoverlyconservativeinyourshortcircuitanalysismayresultintherequiredPPEprotectioncategorybeingset
atalevelhigherthannecessary.
Category4PPE
TheabovefigureisapersoninafullCategory4suit.Thissuitwillprovidethenecessaryprotection,butitiscumbersome
toworkin,itishot,anditprovidespoorvisibility.
Thesuitswillmakemanytasksverydifficult,ifnotimpossible,toperform.Becauseoftheirrestrictionstovisionand
movement,theymayevenmakesometasksmoredangerous.Therearedefinitelytimeswhenthistypeofprotectionis
bothnecessaryandrequired,butbeingoverlyconservativewillresultinexcessivestresstoworkersandunacceptable
timetomakerepairsoradjustments.
2.Relyinguponquickanalysismethodscanexposeyoutounexpectedliabilities.Thereareanumberofshortcuts
beingofferedbyindividualsandcompaniesthatcanhavedisastrousresults.Besurethatyourmethodswillstand
uptoanalysisandpeerreview.
Cureallsolutionsarebeingpromoted,suchastheinstallationofcurrentlimitingfuses.PfeifferEngineeringisafirm
believerintheuseoffuses,particularlycurrentlimitingtypes,butaswillbeshownbelow,theyarenotalwaysthe
answer.Theyaredefinitelynotaquickfixsolution.
3.Beingoverlyconservativewhenperformingashortcircuitanalysisresultsinthemisapplicationofcircuitprotection
equipment,whichinturnhastheconsequenceofcalculatedArcFlashlevelsbeinghigherthantheyactuallyare.
4.Thecalculatedboltedfaultorshortcircuitcurrentisaworstcasecalculationthatassumesverylowshortcircuit
impedance.Itisashortcircuitconnectionbasedupontwoconductorsbeingboltedtogethertoformtheshort.In
reality,mostshortcircuitsarelessthanidealresultinginfaultcurrentsthatarelessthanthealculatedboltedshort
circuitcondition.
5.Ontheotherhand,theArcFaultshouldbeamorepredictableoccurrence.Thearcfaultcalculationsassumethat
thereisaphysicalgapbetweenconductorsthatwasbridgedbysomethingresultingintheformationofanarc.Once
thearcisformedandplasmaisproduced,thearccurrentshouldcloselyapproximatethecalculatedfaultlevels.
TheArcFaultcalculationsareanapproximationbaseduponresearchandtestingsimilartotheshortcircuitanalysis
methods.Theyarenotexactandthereforeoneneedstobecarefulwhenusingtheresults.
Solution
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 3/9
3/13/2017 WhatisArcFlash?
Thesolutionistofirstperform,asaccuratelyaspractical,ashortcircuitanalysis.Thegoalformostpeopleperforminga
shortcircuitanalysishasalwaysbeentoerrortowardtheconservative.Forexample,whenacablelengthwasneeded,itis
thepracticetoalwaysusetheshortestpracticalvalue,whichwouldresultinhighercalculatedshortcircuitcurrentvalues.
Whenthepublicutilityiscontacted,itisthepracticetoonlyaskfortheworsecaseshortcircuitvalue.
Theoverallresultisthattheshortcircuitvaluesarealwayscalculatedonthehighside.Whendoingashortcircuitanalysis
forsizingtheinterruptingcapabilityofprotectionequipment,thisisthebestpractice.But,itisnotthebestpracticewhen
evaluatingequipmentforArcFaultsandestablishingPPErequirements.Thisisextremelysignificant,andquitenon
intuitive,situation.
ArcFaultcurrent(Ifc)isderivedfromtheavailableboltedshortcircuitorfaultcurrent(Isc)andisalwayssubstantiallyless
thanitscorrespondingshortcircuitcurrent.TheIEEEhasestablishedformulaforcalculating(estimating)theIfcandthey
provideaspreadsheet.Thefollowingareexampleresultsfromusingtheirformula:
BoltedFaultCurrent ArcFaultCurrent
@480V
10kA =6.56kA
20kA =11.85kA
30kA =16.76kA
40kA =21.43kA
Whatisnowimportantistoobtain:
1.Theexpectedmaximum(worsecase)boltedshortcircuitcurrent.
2.Theminimumandmaximumvoltagetothefacility.
3.Theminimumexpectedshortcircuitcurrent.
Alsoneededaredefinitionsoftheoperatingmodesofthefacilitysuchas:
1.Whataretheminimumandmaximummotorloadsexpectedduringnormaloperationandoffhouroperation.
2.Variationinthesourcesofsupplytotheplant,suchasalternatefeedersorcogeneration.
Thedatafromthepublicutilityandthedeterminationofthefacility'smodesofoperationshouldbeconvertedintothe
maximumandminimumArcFaultcurrentatvariouslocationsintheplant.Theseresultsareappliedtoprotectivedevice
coordinationstudies,wheretheprotectivedevicesareevaluated,andadjusted,ifnecessary,allowingtheproperPPE
categoriestobedetermined.
Thefollowingcoordinationcurveillustratesthepoint:
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 4/9
3/13/2017 WhatisArcFlash?
Thefigureaboveshowsthecoordinationcurveforthesecondaryofa1000kVA480Vtransformer.Thecurveshowstwo
typesofsecondaryprotection,afuseandacircuitbreaker,eachselectedbasedupontheNationalElectricalCode
requirements.ThefuseisaKLPC1600AandthecircuitbreakerisaWestinghouseHNDbreakerwithaDigitrip.
Alltransformerslimittheamountoffaultcurrentthatcanpassthroughthetransformer.Thisisafunctionofthe
transformer'simpedance.ThecoordinationcurveshowsalinefortheIsc,themaximumshortcircuitcurrentthatcanpass
throughthistransformer(20,741amps).TheIscvalueusedassumesthatthereactuallyissufficientcurrentavailableat
theprimarytoprovide20,741ampsonthesecondary.
BasedupontheIEEEformula,thecalculatedArcFaultcurrentIfcis12,230amps.Usingthesetwocurrentsandthe
coordinationcurveonecanestimatethetimethecircuitbreakerandthefusewilltaketoclearthefault.
BoltedFaultCondition:
Fuseclearsin0.22seconds
CircuitBreakerclearsin0.02seconds
ArcFaultCondition
Fuseclearsin1.80seconds
CircuitBreakerclearsin0.02seconds
FromthesecurrentlevelsandclearingtimesthePPEcategorycanbedetermined.
Emb(Maximumincubicboxincidentenergy)
Fuse74cal/cm2Category4PPE
CircuitBreaker0.8cal/cm2Category0PPE
Clearly,inthisexamplethecircuitbreakeroutperformsthecurrentlimitingfuseresultinginaminimal"workerfriendly"PPE
requirement.
IntheaboveexampleboththeArcFaultcurrentandtheBoltedFaultcurrentarelessthanthecurrentlimitingpointforthe
fuse,whichisapproximately28,000amps.Thus,thereisnocurrentlimiteffectfromusingthefuse.Currentlimitingfuses
oftendoprovideadditionalprotectionandtheyareverygooddevicesbuttheymustbeappliedproperly.Inthisexample,
thecircuitbreakerprovidesthebestprotection.
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 5/9
3/13/2017 WhatisArcFlash?
Studyingthisexamplefurther,letusassumethatthefuseandthecircuitbreakerareatthemainofafacilityandthe
facilityisservedbyamuchlargertransformerwheretheworsecaseboltedshortcircuitcurrentasreportedbytheutilityis
60,000amps.Underthisconditionthearcfaultcurrentwouldbe30,300amps.Inthiscase,thefusewouldopenin1/4
cycleandwouldlimitthefaultcurrent.
TheEmbwouldequal1.15cal/cm2,whichfallsunderacategory0PPE.
Inthenextexamplewehaveafuseandacircuitbreakerprotectinga125Hpmotor.ThefuseisaLLSRK200Aandthe
circuitbreakerisaWestinghouseHKDwithaDigitrip.TherearethreeArcFaultcurrentsanalyzed.
Point1
ArcFaultCurrent3100Amps
BoltedFaultCurrent4200Amps
Point2
ArcFaultCurrent2200Amps
BoltedFaultCurrent2800Amps
Point3
ArcFaultCurrent1800Amps
BoltedFaultCurrent2200Amps
Results:
Point1
CircuitBreakerclearsin.02seconds1.42cal/cm2PPECat.1
Fuseclearsin.02seconds1.42cal/cm2PPECat.1
Point2
CircuitBreakerclearsin.02seconds1.42cal/cm2PPECat.1
Fuseclearsin.1seconds7.7cal/cm2PPECat.2
Point3
CircuitBreakerclearsin.02seconds1.42cal/cm2PPECat.1
Fuseclearsin1.0seconds78.8cal/cm2PPECat.4
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 6/9
3/13/2017 WhatisArcFlash?
AtanArcFaultcurrentof4000ampsthefusewillbegintocurrentlimitandwillopenthecircuitincyclereducingthe
PPEcategoryto0.
Thethreepointsanalyzedshowthatarelativelysmallchangeincalculatedboltedfaultcurrenthasamajoreffectonthe
calculatedarcfaultcurrent.Thissituationcouldeasilyleadtothemisapplicationofcircuitprotectionequipmentor
inappropriateadjustmentofsame.Itshouldalsobenotedthatasthecalculatedarcfaultcurrentisreduced,theclearing
timeincreases,resultingintheincidentenergylevelincreasingandthus,thePPErequirementincreases.
Inreality,thearccurrentisprimarilyeffectedbyfacilityoperatingconditions,i.e.motorcontributionandchangesinthe
faultcurrentcomingfromtheutility.Theexamplesillustratethattheaccuracyrequiredwhencalculatingshortcurrentshas
tobeimprovedovertraditionalmethods.Bothreliabilityandarcfaultconditionsmustnowbeconsideredwhenperforming
coordinationstudies.
TheRisk
Inastudyof33plantswith4892bussesorswitchpointsunder600volts,themedianincidentenergywasonly2.1
cal/cm2,howevermanybusseshadquitehighincidentenergylevels1:
24%ofbussesover8cal/cm2PPE2
12%ofbussesover40cal/cm2PPE4
5%ofbussesover85cal/cm2Deadlynoprotection
1%ofbussesover205cal/cm2Deadlynoprotection
Riskstopersonnelinclude2:
Burns
Damagingsoundlevels
Highpressure720lbs/ft2eardrumsrupture,1728to2160lbs/ft2lungdamage
Conclusions
1.ArcFaultAnalysisisinactuallyRiskManagement.Therearebasicallythreechoices:
BeveryconservativeandrequirePPE4inmostcasesresultinginhighermaintenancecost.
Donothingandsuffertheconsequences(paylater).Performthenecessaryanalysisandmakeadjustmentsto
reducethearcfaultconditionsresultinginreducedPPErequirements.
2.Areductioninboltedfaultcurrentandthusareductioninarcfaultcurrentcanactuallyresultinaworsesituation.Inthe
motorexampleaboveanarcfaultcurrentreductionfrom4000ampsto1800ampsresultedinanincreaseinarcfault
energyfrom0.6cal/cm2to78.8cal/cm2.Exactlytheoppositeonewouldexpectbeforedoingthemath.Intermsofthe
aboveexamplecoordinationcurves,thisoccursbecausethearcfaultcurrentmovesfromtheinstantaneousportionatthe
bottomofthecoordinationcurvetoapointhigherup,incurringathetimedelaybeforethedevicetrips.
3.Overlyconservativeshortcircuitanalysiswillresultinboltedshortcircuitnumbersthatmaywellresultinthe
misapplicationofcircuitprotectionequipment.
4.Itisveryimportanttoobtaintheminimumavailableshortcircuitcurrentaswellasthemaximumshortcircuitcurrent
fromtheelectricutility.Voltagefluctuationsintheplantsupplyshouldbeconsideredwhendevelopingtheshortcircuit
calculations.Thearcfaultcalculationsneedtobeevaluatedatmorethanjusttheworsecaseandtheminimumcase
conditions.Intheexampleabove,areductioninthearcfaultcurrentactuallyresultedinworseconditions.Thisrepresents
asubtle,butextremelysignificant,changeinthemethodologyofshortcircuitanalysis.
5.Apartfromthefines,nominalcompliancewiththeregulationswillcauseworkerstohavetowearcumbersomePPE.This
willresultinlittleornohighvoltagemaintenancebeingperformed,eventuallycompromisingsafety,equipmentoperation,
andultimatelyproductivity.Arcflashisariskmanagementissue.
6.Havearegisteredprofessionalengineeringfirmperformthecalculationsforarcflashhazardsforthedevicesinyour
facilityandhavethemrecommendanynecessaryplansthatwhenexecutedwouldresultinthelowestcategoryofPPE
beingrequired.
Note:
https://www.mikeholt.com/mojonewsarchive/NECHTML/HTML/WhatisArcFlash~20040512.php 7/9
3/13/2017 WhatisArcFlash?
Shortcircuitanalysisisbaseduponanumberofassumptionsanyorallmaychangeovertime
1.Availableshortcircuitcurrentfromtheutilitymayvary,particularlyinareaswheretherehasbeenasignificant
expansionof,orchangeto,theelectricalsystems.
2.Thenumberofmotorsrunningatthetimeofafaultaffectstheamountofshortcircuitcurrentandarcfaultcurrent
available(motorcontribution).
3.Thefacilityvoltageoftenvariesasafunctionoftimeofday.Theutilityisoftenmoreloadedduringtheday.
Similarly,thearcfaultmayalsobeaffectedbyvariationsinanyofthefollowing:
1.Theavailableshortcircuitcurrent.
2.Dirtbuildupintheequipmentthatmayaffecttheconductivepath.
3.Moisture(humidity).
4.Circuitsupplyvoltage.
5.Amountofmotorcontributionduringafault
Definitions
BoltedFaultShortcircuitcurrentresultingfromconductorsatdifferentpotentialsbecomingsolidlyconnectedtogether.
ArcFaultShortcircuitcurrentresultingfromconductorsatdifferentpotentialsmakingalessthansolidcontact.This
resultsinarelativelyhighresistantconnectionwithrespecttoaboltedfault.
Author
JohnC.Pfeiffer,P.E.,president,PfeifferEngineeringCo.,Inc.,Louisville,Kentucky
1"ASummaryofArcflashHazardCalculations"D.R.Doan&R.A.Sweigart
2"ArcingFlash/BlastReviewwithSafetySuggestionsforDesignandMaintenance"TimCrnko&SteveDyrnes
UnderstandingtheNEC,Volume1Book2002
UnderstandingtheNECVolume1waswrittentoprovideinsightinto,andan
understandingof,manyofthetechnicalrulesoftheNEC.Thisbook,printedinfour
color,containscleargraphics,examples,and1200+summaryquestions.Basedon
the2002NEC.
ProductCode:02UND1
Pages:430