Numerical RelayS Series

Feeder Protection Relay


Description
S Series is a numerical type protection relay product with a microprocessor for protecting
high/extra-high-voltage electric power system.
This series of protection relay will allow stable and effective control and monitoring of
electric power systems as well as provide high-reliable protection.

Features
Highly Accurate Digital Computation
The digital computation using high-speed sampling minimizes the effect of harmonics,
etc., and result in highly accurate protection.
Self-diagnosis
The continuaously monitoring electronic circuits from input to output can detect
internal failure before that failure causes damage on the power system, thereby
improving reliability.
Operation time characteristics
Sixteen sorts of operation time characteristics are installed as a time-delayed element.
The optimal operation time characteristic can be chosen with the coordinated
characteristic of the overcurrent relay at the sending distribution substation.
Compactly
Various relay elements are contained compactly. It is the best for replacement of
existing.
Energy saving
It is a low power consumption article. The miniaturization of CT and VT is realizable.

Data display

In service monitor
(RUN) indicator
Display item
selecting switch
Alarm indicator

Alarm hold mode Relay settings


setting switch/
Frequency setting
switch

Indicator
reset switch
Forced operation switch
Operation
indicator

Front view (cover removed)


Common Technical Data
I T E M DESCRIPTION CONDITION STANDARD
Ambient operating
10 to 55 IEC60255-6
temperature
Environment Ambient storage and
transport temperature 25 to 70 IEC60255-6
Damp heat 40,95%RH,4days IEC60068-2-78
110VDC,110VAC
Auxiliary power supply (Applicable to any IEC60255-6
voltage above)
DC:15% to 10%
Operative range of (Temporarily 20% to 30%)
Ratings auxiliary power supply AC:15% to 10% IEC60255-6
(Temporarily 15% to 15%)
Frequency 50/60Hz IEC60255-6
VT
See manual of each relay type
CT
Auxiliary power supply
Burden VT See manual of each relay type
CT
Thermal VT 1.15VN,3h
withstand CT 40IN,1s
110V DC:15A,0.5s
Make 220V DC:10A,0.5s (L/R=0)
For trip
110V DC:0.3A
Break (L/R40ms)
220V DC:0.15A
Contact 10VA (COS=0.4)
capacity Break
10W (L/R=0.007s)
For signaling and alarm
Max. 5A
current
Max. 380VAC/125VDC
Voltage
Circuit of 60V or below 500VAC,1min 1)Between each circuit and the
exposed conductive parts, the
terminals of each independent
circuit being connected
Dielectric test Circuit of more than
60V and 500V or below
2000VAC,1min together
2)Between independent circuits,
IEC60255-5 !
the terminals of each
independent circuit being
connected together
Open contact 1000VAC,1min Between open contact poles
1)Between each circuit and the
exposed conductive parts, the
terminals of each independent
circuit being connected
Impulse voltage test 5kV, 1.2s/50s together IEC60255-5
2)Between independent circuits,
the terminals of each
independent circuit being
connected together
2.5kV peak,1MHz with 200 Between independent
High- Common mode source impedance for 2s Circuits, and between
frequency independent circuit and earth IEC60255-22-1
disturbance class 3
test 1.0kV peak,1MHz with 200 Across terminals of the
Differential mode source impedance for 2s same circuit
8kV Contact discharge IEC60255-22-2
Electrostatic discharge test
15kV Air discharge class 4
Radiated electromagnetic field 38 to 87MHz 146 to 174MHz IEC60255-22-3
disturbance test 420 to 470MHz class 3
Fast transient disturbance test 2.0kV,5ns/50ns,1min IEC60255-22-3
Vibration test Refer to class 1 IEC60255-21-1
class 1
Shock response Refer to class 2 IEC60255-21-2
class 2
Shock withstand Refer to class 1 IEC60255-21-2
class 1
Bump Refer to class 1 IEC60255-21-2
class 1
Enclosure protection IP51 IEC60529
VN : Rated voltage IN : Rated current
Operation Time characteristics of Overcurrent Element
500

NI01Normal inverse time-lag characteristic


0.14 M
100 t 0.02 (s)
I 1 10

VI01Very inverse time-lag characteristic


13.5 M
t (s)
I1 10
Operation time t (s)

EI01Extremely inverse time-lag characteristic


80 M
10 t 2 (s)
I 1 10

LI01Long inverse time-lag characteristic


LI01 54 M
t (s)
I1 10
NI01
DT01 DT01Difinite time-lag characteristic
1 M
t 2 (s)
10
VI01

Oreration time
Input current multiplying factor
EI01 against set value
Operation time multiplier(times)
0.1
1 2 5 10 20

Current (multiple against setting value) I

"

500

NI11Normal inverse time-lag characteristic


0.0515 M

t 0.02
I 1
0.114
10
(s)

100 EI11Extreme inverse time-lag characteristic


19.61 M

t 2
I 1
0.491
10
(s)

EI12Extremely inverse time-lag characteristic


28.2 M

t 2
I 1
0.1217
10
(s)
Operation time t (s)

10
NI21Normal inverse time-lag characteristic
2.4 M

t 0.4
I 1
1.2
10
(s)

LI21
VI21Very inverse time-lag characteristic
NI21
16 M

VI21

t
I1
0.4
10
(s)

1 NI11
LI21Long inverse time-lag characteristic
60 M
EI11 t (s)
I1 10

EI12 Oreration time


Input current multiplying factor
0.1 Against set value
1 2 5 10 20 Operation time multiplier
Currentmultiple against setting valueI
500

MI31Moderately inverse time-lag characteristic

100 NI31Normal inverse time-lag characteristic

VI31Very inverse time-lag characteristic

EI31Extremely inverse time-lag characteristic

B D E
Operation time t (s)

t M A
(I C)2 (I C)3

10 I C

Oreration time
Input current multiplying factor
against set value
MI31 Operation time multiplier

NI31
1 VI31

EI31
MI31 EI31 NI31 VI31
A 0.1735 0.0399 0.0274 0.0615
B 0.6791 0.2294 2.2614 0.7989
C 0.8000 0.5000 0.3000 0.3400
D 0.0800 3.0094 4.1899 0.2840
0.1 1 2 5 10 20 E 0.1271 0.7222 9.1272 4.0505
Currentmultiple against setting valueI

1
Operation time t (s)

DT(INST): Definite time-lag characteristic


t < 0.04 (s)
0.1 t: Operation time
I: Input current multiplying factor
against set value
DT(INST)

0.01
1 2 5 10 20
Currentmultiple against setting valueI
Specifications
Name Overcurrent Relay Voltage Relay
Type COC4-A01S1 CBV2-A01S1 CBV3-A01S1
Frequency 50Hz or 60Hz 50Hz or 60Hz 50Hz or 60Hz
Ratings CTVT 5A 110V/220V 110V/220V
ZCTEVT /V

Phase fault Time-lag (51) Under Voltage (27) Under Voltage (27)
Operation value: Operation value: Operation value:
LOCK... LOCK LOCK
.A
Time multiplier: V V
.... Operation Time: Operation Time:
. INST..... INST.....
Operation characteristic ...... ......
Extremely inverse ....s ....s
Very inverse Over Voltage (59) Over Voltage (59)
Normal inverse Operation value: Operation value:
Long inverse LOCK LOCK
Definite time V V
Phase fault Instantaneous(50) Operation Time: Operation Time:
Operation value: INST..... INST.....
LOCKA ...... ......
Settings Operation Time: ....s ....s
INSTms or less Earth fault Overvoltage (64)
Earth fault Time-lag (51N) Operation value:
Operation value: LOCK
LOCK..... V
.......A Operation Time:
Time multiplier: INST.....
.... ......
Specifications
. ....s
Operation characteristic
$ Extremely inverse
Very inverse
Normal inverse
Long inverse
Definite time
Earth fault Instantaneous(50N)
Operation value:
LOCK.
A
Operation Time:
INSTms or less

I > ()
U < ()
Protection I >> () U < ()
U > ()
Elements Io > (N) U > ()
Uo > ()
Io >> (N)

Measurement Voltage
Current Voltage
Zerophase voltage

Containes 3-phase overcurrent Contains -phase undervoltage Contains an undervoltage, an


element and an earth fault over- element and -phase overvol- overvoltage, and an earth fault
current element; phase fault tage element, being used to de- overvoltage element, being
and earth fault protection of a tect abnormal voltage between used to detect bus voltage ab-
Applications -phase circuit in a resistance lines. normalities.
earthed neutral system can be See figure 2. See figure 3.
achieved with 1 relay.
See figure 1.
Draw out type with automatic Draw out type is also available. Draw out type is also available.
CT shorting mechanism is also (Type CBV2-A01SD) (Type CBV3-A01SD)
Remarks available. (Type COC4-A01SD) Refer to Fig.2 Refer to Fig.3
Refer to Fig.1
Connection Diagram

A B C 01 07
Auxiliary Y Self-diagnosis output
Power supply 08
03
X0 Contact
09 common
17
10 Phase fault
time-lag
IA 18
I
X1 Control
11 Phase fault
instantaneous contacts
19 I
X2
Earth fault
IB 20
12
I

21

IC 22
13
X4 Trip contact
14
15

I0
16

Automatic CT shorting
E E and draw-out mechanism
are available for only type
COC4-A01SD.
Figure1 COC4-A01S1

A B C 01 07
Auxiliary Y Self-diagnosis output
08
power supply 03
X0 Contact
09 common
Undervoltage
15
10
U Control
VT contacts
X1 Overervoltage
16 11
U
V AB

%
17

18
V BC
13
19 X3 Trip contacts
14
V CA 20

E E

Draw-out mechanism is
available for only type
CBV2-A01SD.
Figure2 CBV2-A01S1

01

A Auxiliary 07
B Y Self-diagnosis output
power supply 03 08
C
X0 Contact
09 common
EVT Undervoltage
10
U
X1 Control
Overvoltage
11
U contacts
17 X2
Earth fault
12
V AB U
18

13
X3 Trip contact
15 14

R
V0 16

E E
Draw-out mechanism is
available for only type
CBV3-A01SD.
Figure3 CBV3-A01S1
Numerical Relay
S Series
Mounting and Dimensions

2-5 screw 20

202

155
180

158
180
20 2-6 holes

101 150 85

Front view Side view Panel cutout

HEAD OFFICE : 7-3 MARUNOUCHI 2-CHOME, CHIYODA-KU


TOKYO, 100-8310, JAPAN
CAUTION
TO PREVENT IT FROM THE RISK OF DAMAGE AND MAL FUNCTION,
BE SURE TO READ OPERATING AND MAINTENANCE (SERVICING)
INSTRUCTIONS BEFORE USING.
We are waiting your technical contacts by FAX.
ATTN. Protective relay technimal service
FAX NO. JAPAN +81-78-996-7044

Please note that specifications are subject to change without notice. 605153 0412Y 20