Sei sulla pagina 1di 62

MEDIUM VOLTAGE

cables
IEC Standard

RPG CABLES
(A Division of KEC International Limited)
RPG CABLES MANUFACTURES A RANGE OF MEDIUM VOLTAGE AND
HIGH VOLTAGE CABLES AT ITS FACILITY AT VADODARA
The newly commissioned state-of-the-art facility at Vadodara has the capacity to manufacture
3500 kms per annum of cables upto 220 kV and boasts of several Firsts including:

1. Best in class plant and machinery from top manufacturers across the world.
2. Unique High Performance Teams that ensure highest level of productivity through a
Learn and Earn program
3. Platinum Certication from the Indian Green Buildings Council for its environmental
commitment
4. World Class Quality and IT systems

RPG CABLES
(A Division of KEC International Limited)
CONTENTS
Components of Medium Voltage Cables ..................................................................... 1

Cross Sectional Drawings (For Single/Three Core Cables) ............................................. 2

Ratings & Dimension


3.6/6 (7.2)kV Copper/Aluminium Single Core Screened Unarmoured - 2XY/A2XY 3 -4

6/10 (12)kV Copper/Aluminium Single Core Screened Unarmoured - 2XY/A2XY 5-6

8.7/15 (17.5)KV Copper/Aluminium Single Core Screened Unarmoured - 2XY/A2XY 7-8

12/20 (24)kV Copper/Aluminium Single Core Screened Unarmoured - 2XY/A2XY 9 - 10

18/30 (36)kV Copper/Aluminium Single Core Screened Unarmoured - 2XY/A2XY 11 - 12

3.6/6 (7.2)kV Copper/Aluminium Single Core Copper Wire Screened Unarmoured - 2XWcY/A2XWcY 13 - 14

6/10 (12)kV Copper/Aluminium Single Core Copper Wire Screened Unarmoured - 2XWcY/A2XWcY 15 - 16

8.7/15 (17.5)kV Copper/Aluminium Single Core Copper Wire Screened Unarmoured - 2XWcY/A2XWcY 17 - 18

12/20 (24)kV Copper/Aluminium Single Core Copper Wire Screened Unarmoured - 2XWcY/A2XWcY 19 - 20

18/30 (36)kV Copper/Aluminium Single Core Copper Wire Screened Unarmoured - 2XWcY/A2XWcY 21 - 22

3.6/6 (7.2)KV Copper/Aluminium Single Core Screened Armoured - 2XWaY(P)/A2XWaY(P) 23 -24

6/10 (12)kV Copper/Aluminium Single Core Screened Armoured - 2XWaY(P)/A2XWaY(P) 25 - 26

8.7/15 (17.5)kV Copper/Aluminium Single Core Screened Armoured - 2XWaY(P)/A2XWaY(P) 27 - 28

12/20 (24)kV Copper/Aluminium Single Core Screened Armoured - 2XWaY(P)/A2XWaY(P) 29 - 30

18/30 (36)kV Copper/Aluminium Single Core Screened Armoured - 2XWaY(P)/A2XWaY(P) 31 - 32

3.6/6 (7.2)kV Copper/Aluminium Three Core Screened Round Wire Armoured - 2XWY(P)/A2XWY(P) 33 - 34

6/10 (12)kV Copper/Aluminium Three Core Screened Round Wire Armoured - 2XWY(P)/A2XWY(P) 35 - 36

8.7/15 (17.5)kV Copper/Aluminium Three Core Screened Round Wire Armoured - 2XWY(P)/A2XWY(P) 37 - 38

12/20 (24)kV Copper/Aluminium Three Core Screened Round Wire Armoured - 2XWY(P)/A2XWY(P) 39 - 40

18/30 (36)kV Copper/Aluminium Three Core Screened Round Wire Armoured - 2XWY(P)/A2XWY(P) 41 - 42

3.6/6 (7.2)kV Copper/Aluminium Three Core Screened Flat Strip Armoured - 2XFY(P)/A2XFY(P) 43 - 44

6/10 (12)kV Copper/Aluminium Three Core Screened Flat Strip Armoured - 2XFY(P)/A2XFY(P) 45 - 46

8.7/15 (17.5)kV Copper/Aluminium Three Core Screened Flat Strip Armoured - 2XFY(P)/A2XFY(P) 47 - 48

12/20 (24)kV Copper/Aluminium Three Core Screened Flat Strip Armoured - 2XFY(P)/A2XFY(P) 49 - 50

18/30 (36)kV Copper/Aluminium Three Core Screened Flat Strip Armoured - 2XFY(P)/A2XFY(P) 51 - 52

Continuous Current Rating /Emergency Rating/Screen Fault Current Rating / Rating factors for different laying conditions 53-56

Plant Safety & Ordering Information 57

Drum Handling Instructions 58

RPG CABLES
(A Division of KEC International Limited)
COMPONENTS OF MEDIUM VOLTAGE (MV) CABLES

Element Material Standard Cable Construction Coding Chart


Description Abbreviation
(Code)
Conductor Aluminium (Class-2) / Plain or tinned IEC : 60228 Aluminium A
copper (Class-2)
Plain or tinned copper Blank (No code)

Conductor Screen Extruded cross linked, semi-conductive IEC : 60502-2 - -

Insulation XLPE IEC : 60502-2 XLPE 2X

Insulation Screen Extruded cross linked, semi-conductive - -

Metallic screen Copper tape / Copper wire screen IEC : 60502-2 - Wc

Identification of By colored strips (Red, Yellow & Blue) IEC : 60502-2 - -


3 Cores

Laying -up (3 core Non-hygroscopic PVC or Polypropylene IEC : 60502-2 - -


cables only) with suitable binder

Separation sheath PVC type ST- 2 IEC : 60502-2 - -


(For armoured
cables only)

Armour (Optional) Galvanised steel wires (For 3 core IEC : 60502-2 Galvanized steel W
cables) & aluminium wires (For single wires
core cables)
Galvanized steel F
Flat Strip

Aluminium wires Wa

Oversheath PVC type ST- 2 or PE - ST 7 or LSZH or IEC : 60502-2 PVC Y


FR - PVC or FRLS PVC
PE - ST 7 2Y

Water-Blocking Water blocking tapes (Within each IEC : 60502-2 - -


(Optional) layer of conductor) or below metalic
screen or both

RPG CABLES
(A Division of KEC International Limited)

1
CROSS SECTIONAL DRAWINGS (FOR SINGLE / THREE CORE CABLES)

DRAWING 1 : 1 CORE UNARMOURED - A2XY/2XY DRAWING 2 : 1 CORE COPPER WIRE


SCREENED , UNARMOURED - A2XWcY/2XWcY

1 1
2 2
3 3
4 4
6 6
5 5
7

1. Conductor 2. Inner Semicon 3. XLPE Insulation 1. Conductor 2. Inner Semicon 3. XLPE Insulation
4. Outer Semicon 5. Copper Tape Screen 4. Outer Semicon 5. Copper Wire Screen
6. PVC Sheathing 6. Non - Semicon Tape 7. PVC Sheathing

DRAWING NO.3 : 1 CORE ARMOURED - DRAWING NO.4 : 3 CORE ROUND WIRE


A2XW Y(P) / 2XWaY(P)
A2XWa
A2XWaY(P) 2XWaY(P)
2XW ARMOURED - A2XWY(P)/2XWY(P)

1 1
2 2
3 3
4 4
6 6
5 5
8 7 8 7
1. Conductor 2. Inner Semicon 3. XLPE Insulation 1. Conductor 2. Inner Semicon 3. XLPE insulation
4. Outer Semicon 5. Copper Tape Screen 4. Outer Semicon 5. Copper Tape Screen
6. Inner Sheathing 7. Aluminium Round Wire Armour 6. Inner Sheathing 7. G.S Round Wire Armour
8. PVC Sheathing 8. PVC Sheathing

DRAWING NO.5 : 3 CORE FLAT STRIP ARMOURED -


A2XFY(P)/2XFY(P)

1. Conductor 2. XLPE insulation


3. Outer Semicon 4. Copper Tape Screen
5. Inner Sheathing 6. G.S Flat Strip Armour
7. PVC Sheathing
1

3 2
5
4 RPG CABLES
7
6 (A Division of KEC International Limited)

2
3.6/6 (7.2) kv , single Core , Copper ConduCTor , Xlpe insulaTed , sCreened , unarmoured Cables
(2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 2.5 13.1 1.50 18.0 0.52 1.8 270 216 50 65

50 8.1 2.5 14.2 1.60 19.0 0.65 2.5 285 228 50 65

70 9.8 2.5 15.9 1.60 21.0 0.85 3.5 315 252 50 80

95 11.3 2.5 17.4 1.70 22.0 1.11 4.8 330 264 50 80

120 12.9 2.5 19.0 1.70 23.5 1.34 6.0 353 282 50 80

150 13.9 2.5 20.0 1.80 25.0 1.60 7.5 375 300 50 80

185 15.9 2.5 22.0 1.80 27.0 1.95 9.3 405 324 65 100

240 18.1 2.6 24.4 1.90 30.0 2.48 12.0 450 360 65 100

300 19.8 2.8 26.5 2.00 32.0 3.07 15.0 480 384 65 100

400 22.9 3.0 30.0 2.10 36.0 3.88 20.0 540 432 65 125

500 26.4 3.2 33.9 2.20 40.0 4.91 25.0 600 480 65 125

630 29.6 3.2 37.4 2.30 44.0 6.21 31.5 660 528 65 150

800 34.0 3.2 41.8 2.40 48.0 7.83 40.0 720 576 80 150

1000 37.8 3.2 45.6 2.60 52.0 9.62 50.0 780 624 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.524 0.668 0.120 0.135 0.178 0.283 0.32 4.6 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.116 0.130 0.174 0.314 0.36 5.1 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.107 0.121 0.165 0.362 0.41 5.9 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.103 0.117 0.161 0.403 0.46 6.6 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.099 0.113 0.157 0.449 0.51 7.3 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.097 0.112 0.155 0.477 0.54 7.8 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.093 0.107 0.151 0.533 0.60 8.7 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.091 0.105 0.149 0.573 0.65 9.3 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.090 0.104 0.148 0.580 0.66 9.4 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.064 0.087 0.102 0.145 0.618 0.70 10.1 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.051 0.085 0.100 0.143 0.659 0.75 10.7 71.50 0.256 640 635 608 603 942 944 1003

630 0.0283 0.042 0.083 0.098 0.141 0.735 0.83 12.0 90.09 0.256 712 703 676 668 1071 1070 1117

800 0.0221 0.036 0.081 0.096 0.139 0.830 0.94 13.5 114.40 0.256 781 770 742 732 1210 1207 1240

1000 0.0176 0.031 0.080 0.094 0.138 0.913 1.03 14.9 143.00 0.256 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

3
3.6/6 (7.2) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (a2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 2.5 12.9 1.50 18.0 0.31 1.1 270 216 50 65

50 7.9 2.5 14.0 1.60 19.0 0.37 1.5 285 228 50 65

70 9.7 2.5 15.8 1.60 21.0 0.46 2.1 315 252 50 80

95 11.0 2.5 17.1 1.70 22.0 0.56 2.9 330 264 50 80

120 12.6 2.5 18.7 1.70 23.5 0.65 3.6 352.5 282 50 80

150 13.9 2.5 20.0 1.80 25.0 0.76 4.5 375 300 50 80

185 15.6 2.5 21.7 1.80 27.0 0.88 5.6 405 324 65 100

240 17.6 2.6 23.9 1.90 29.0 1.08 7.2 435 348 65 100

300 19.7 2.8 26.4 2.00 32.0 1.31 9.0 480 384 65 100

400 22.6 3.0 29.7 2.10 36.0 1.63 12.0 540 432 65 125

500 25.6 3.2 33.1 2.20 39.0 2.01 15.0 585 468 65 125

630 29.0 3.2 36.8 2.30 43.0 2.48 18.9 645 516 65 150

800 33.0 3.2 40.8 2.40 47.0 3.04 24.0 705 564 80 150

1000 36.8 3.2 44.6 2.60 51.0 3.71 30.0 765 612 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.868 1.113 0.121 0.136 0.180 0.278 0.31 4.5 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.117 0.131 0.175 0.309 0.35 5.0 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.107 0.121 0.165 0.359 0.41 5.9 6.58 0.256 186 192 176 178 230 236 278

95 0.32 0.411 0.104 0.118 0.162 0.396 0.45 6.4 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.099 0.114 0.158 0.441 0.50 7.2 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.097 0.112 0.155 0.477 0.54 7.8 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.093 0.108 0.151 0.525 0.59 8.5 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.162 0.091 0.106 0.149 0.561 0.63 9.1 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.090 0.104 0.148 0.578 0.65 9.4 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.087 0.102 0.145 0.611 0.69 9.9 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.081 0.086 0.100 0.144 0.642 0.73 10.5 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.064 0.084 0.098 0.142 0.722 0.82 11.8 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.052 0.082 0.096 0.140 0.809 0.91 13.2 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.044 0.080 0.095 0.138 0.891 1.01 14.5 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

4
6/10 (12) kv , single Core , Copper ConduCTor , Xlpe insulaTed , sCreened , unarmoured Cables
(2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 3.4 14.8 1.60 20.0 0.57 1.8 300 240 50 65

50 8.1 3.4 15.9 1.60 21.0 0.70 2.5 315 252 50 65

70 9.8 3.4 17.6 1.70 23.0 0.91 3.5 345 276 50 80

95 11.3 3.4 19.1 1.70 24.0 1.16 4.8 360 288 50 80

120 12.9 3.4 20.7 1.80 25.5 1.41 6.0 382.5 306 50 80

150 13.9 3.4 21.7 1.80 27.0 1.66 7.5 405 324 50 80

185 15.9 3.4 23.7 1.90 29.0 2.03 9.3 435 348 65 100

240 18.1 3.4 25.9 2.00 31.0 2.56 12.0 465 372 65 100

300 19.8 3.4 27.6 2.00 33.0 3.11 15.0 495 396 65 100

400 22.9 3.4 30.7 2.10 36.0 3.91 20.0 540 432 65 125

500 26.4 3.4 34.2 2.20 40.0 4.92 25.0 600 480 65 125

630 29.6 3.4 37.7 2.30 44.0 6.22 31.5 660 528 65 150

800 34.0 3.4 42.1 2.50 49.0 7.86 40.0 735 588 80 150

1000 37.8 3.4 45.9 2.60 53.0 9.63 50.0 795 636 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.524 0.668 0.127 0.141 0.185 0.222 0.42 10.0 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.121 0.135 0.179 0.245 0.46 11.1 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.112 0.126 0.170 0.280 0.53 12.7 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.107 0.122 0.165 0.310 0.59 14.0 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.103 0.118 0.161 0.345 0.65 15.6 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.101 0.116 0.159 0.365 0.69 16.5 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.097 0.111 0.155 0.407 0.77 18.4 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.094 0.108 0.152 0.451 0.85 20.4 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.092 0.106 0.150 0.487 0.92 22.0 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.064 0.088 0.103 0.146 0.551 1.04 24.9 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.051 0.085 0.100 0.143 0.622 1.17 28.2 71.50 0.256 640 635 608 603 942 944 1003

630 0.0283 0.042 0.084 0.098 0.142 0.693 1.31 31.4 90.09 0.256 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.082 0.096 0.140 0.783 1.48 35.4 114.40 0.256 781 770 742 732 1210 1207 1240

1000 0.0176 0.031 0.080 0.094 0.138 0.861 1.62 39.0 143.00 0.256 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

5
6/10 (12) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (a2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 3.4 14.6 1.60 19.0 0.37 1.1 285 228 50 65

50 7.9 3.4 15.7 1.60 20.0 0.42 1.5 300 240 50 65

70 9.7 3.4 17.5 1.70 22.0 0.52 2.1 330 264 50 80

95 11.0 3.4 18.8 1.70 24.0 0.61 2.9 360 288 50 80

120 12.6 3.4 20.4 1.80 25.5 0.72 3.6 383 306 50 80

150 13.9 3.4 21.7 1.80 27.0 0.82 4.5 405 324 50 80

185 15.6 3.4 23.4 1.90 29.0 0.96 5.6 435 348 65 100

240 17.6 3.4 25.4 2.00 31.0 1.16 7.2 465 372 65 100

300 19.7 3.4 27.5 2.00 33.0 1.36 9.0 495 396 65 100

400 22.6 3.4 30.4 2.10 36.0 1.66 12.0 540 432 65 125

500 25.6 3.4 33.4 2.20 39.0 2.02 15.0 585 468 65 125

630 29.0 3.4 37.1 2.30 43.0 2.49 18.9 645 516 65 150

800 33.0 3.4 41.1 2.50 48.0 3.07 24.0 720 576 80 150

1000 36.8 3.4 44.9 2.60 52.0 3.72 30.0 780 624 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.868 1.113 0.128 0.142 0.186 0.217 0.41 9.8 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.122 0.136 0.180 0.240 0.45 10.9 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.112 0.127 0.170 0.278 0.52 12.6 6.58 0.256 186 192 176 178 230 236 278

95 0.32 0.411 0.108 0.123 0.166 0.305 0.58 13.8 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.104 0.119 0.162 0.338 0.64 15.3 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.101 0.116 0.159 0.365 0.69 16.5 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.097 0.112 0.156 0.400 0.75 18.1 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.162 0.095 0.109 0.153 0.442 0.83 20.0 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.092 0.106 0.150 0.485 0.91 21.9 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.088 0.103 0.146 0.544 1.03 24.6 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.081 0.086 0.100 0.144 0.606 1.14 27.4 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.064 0.084 0.099 0.142 0.681 1.28 30.8 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.052 0.082 0.097 0.140 0.763 1.44 34.5 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.044 0.080 0.095 0.138 0.841 1.58 38.0 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

6
8.7/15 (17.5) kv , single Core , Copper ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 4.5 17.0 1.70 22.0 0.65 1.8 440 264 50 65

50 8.1 4.5 18.1 1.70 23.0 0.78 2.5 460 276 50 65

70 9.8 4.5 19.8 1.70 25.0 0.99 3.5 500 300 50 80

95 11.3 4.5 21.3 1.80 26.0 1.26 4.8 520 312 50 80

120 12.9 4.5 22.9 1.90 27.5 1.52 6.0 550 330 50 80

150 13.9 4.5 23.9 1.90 29.0 1.77 7.5 580 348 50 80

185 15.9 4.5 25.9 2.00 31.0 2.14 9.3 620 372 65 100

240 18.1 4.5 28.1 2.00 34.0 2.67 12.0 680 408 65 100

300 19.8 4.5 29.8 2.10 36.0 3.24 15.0 720 432 65 100

400 22.9 4.5 32.9 2.20 39.0 4.05 20.0 780 468 65 125

500 26.4 4.5 36.4 2.30 43.0 5.07 25.0 860 516 65 125

630 29.6 4.5 39.9 2.40 46.0 6.39 31.5 920 552 65 150

800 34.0 4.5 44.3 2.50 51.0 8.03 40.0 1020 612 80 150

1000 37.8 4.5 48.1 2.70 55.0 9.83 50.0 1100 660 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.524 0.668 0.134 0.149 0.192 0.181 0.49 17.2 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.128 0.143 0.186 0.199 0.54 18.9 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.118 0.132 0.176 0.226 0.62 21.5 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.113 0.128 0.171 0.249 0.68 23.7 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.109 0.124 0.167 0.275 0.75 26.2 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.107 0.121 0.165 0.291 0.79 27.7 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.102 0.117 0.160 0.322 0.88 30.6 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.098 0.113 0.156 0.356 0.97 33.8 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.096 0.111 0.154 0.383 1.05 36.4 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.092 0.107 0.150 0.431 1.18 41.0 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.051 0.089 0.104 0.147 0.486 1.33 46.2 71.50 0.256 640 635 608 603 942 944 1003

630 0.0283 0.042 0.087 0.102 0.145 0.539 1.47 51.3 90.09 0.256 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.084 0.099 0.142 0.608 1.66 57.8 114.40 0.256 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.083 0.097 0.141 0.667 1.82 63.4 143.00 0.256 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

7
8.7/15 (17.5) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (a2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 4.5 16.8 1.70 22.0 0.45 1.1 440 264 50 65

50 7.9 4.5 17.9 1.70 23.0 0.51 1.5 460 276 50 65

70 9.7 4.5 19.7 1.70 25.0 0.60 2.1 500 300 50 80

95 11.0 4.5 21.0 1.80 26.0 0.71 2.9 520 312 50 80

120 12.6 4.5 22.6 1.90 27.5 0.83 3.6 550 330 50 80

150 13.9 4.5 23.9 1.90 29.0 0.93 4.5 580 348 50 80

185 15.6 4.5 25.6 2.00 31.0 1.08 5.6 620 372 65 100

240 17.6 4.5 27.6 2.00 33.0 1.27 7.2 660 396 65 100

300 19.7 4.5 29.7 2.10 35.0 1.49 9.0 700 420 65 100

400 22.6 4.5 32.6 2.20 39.0 1.80 12.0 780 468 65 125

500 25.6 4.5 35.6 2.30 42.0 2.18 15.0 840 504 65 125

630 29.0 4.5 39.3 2.40 46.0 2.65 18.9 920 552 65 150

800 33.0 4.5 43.3 2.50 50.0 3.24 24.0 1000 600 80 150

1000 36.8 4.5 47.1 2.70 54.0 3.92 30.0 1080 648 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.868 1.113 0.135 0.150 0.193 0.178 0.49 16.9 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.129 0.144 0.187 0.196 0.53 18.6 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.118 0.133 0.176 0.224 0.61 21.3 6.58 0.256 186 192 176 178 230 236 278

95 0.32 0.411 0.114 0.129 0.172 0.245 0.67 23.3 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.110 0.124 0.168 0.270 0.74 25.7 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.107 0.121 0.165 0.291 0.79 27.7 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.103 0.117 0.161 0.317 0.87 30.2 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.099 0.114 0.157 0.349 0.95 33.2 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.096 0.111 0.154 0.382 1.04 36.3 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.092 0.107 0.151 0.427 1.17 40.6 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.090 0.104 0.148 0.473 1.29 45.0 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.064 0.088 0.102 0.146 0.530 1.45 50.4 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.052 0.085 0.100 0.143 0.592 1.62 56.3 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.083 0.098 0.141 0.651 1.78 61.9 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

8
12/20(24) kv , single Core , Copper ConduCTor , Xlpe insulaTed , sCreened , unarmoured Cables
(2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 5.5 19.0 1.70 24.0 0.72 1.8 480 288 50 65

50 8.1 5.5 20.1 1.80 25.0 0.87 2.5 500 300 50 65

70 9.8 5.5 21.8 1.80 27.0 1.09 3.5 540 324 50 80

95 11.3 5.5 23.3 1.90 29.0 1.36 4.8 580 348 50 80

120 12.9 5.5 24.9 1.90 29.5 1.61 6.0 590 354 50 80

150 13.9 5.5 25.9 2.00 31.0 1.88 7.5 620 372 50 80

185 15.9 5.5 27.9 2.00 33.0 2.24 9.3 660 396 65 100

240 18.1 5.5 30.1 2.10 36.0 2.79 12.0 720 432 65 100

300 19.8 5.5 31.8 2.20 38.0 3.37 15.0 760 456 65 100

400 22.9 5.5 34.9 2.30 41.0 4.19 20.0 820 492 65 125

500 26.4 5.5 38.4 2.40 45.0 5.23 25.0 900 540 65 125

630 29.6 5.5 41.9 2.50 48.0 6.56 31.5 960 576 65 150

800 34.0 5.5 46.3 2.60 53.0 8.21 40.0 1060 636 80 150

1000 37.8 5.5 50.1 2.70 57.0 10.00 50.0 1140 684 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.524 0.668 0.140 0.154 0.198 0.158 0.60 28.6 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.134 0.148 0.192 0.173 0.65 31.2 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.123 0.138 0.181 0.195 0.74 35.3 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.119 0.133 0.177 0.214 0.81 38.7 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.113 0.128 0.172 0.236 0.89 42.6 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.111 0.126 0.169 0.249 0.94 45.0 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.106 0.120 0.164 0.274 1.03 49.7 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.102 0.117 0.160 0.302 1.14 54.7 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.100 0.114 0.158 0.325 1.22 58.7 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.096 0.110 0.154 0.364 1.37 65.9 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.051 0.092 0.107 0.150 0.409 1.54 74.0 71.50 0.256 640 635 608 603 942 944 1003

630 0.0283 0.041 0.090 0.105 0.148 0.453 1.71 82.0 90.09 0.256 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.087 0.102 0.145 0.509 1.92 92.1 114.40 0.256 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.085 0.100 0.143 0.557 2.10 100.8 143.00 0.256 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

9
12/20(24) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (a2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 5.5 18.8 1.70 24.0 0.52 1.1 480 288 50 65

50 7.9 5.5 19.9 1.80 25.0 0.59 1.5 500 300 50 65

70 9.7 5.5 21.7 1.80 27.0 0.69 2.1 540 324 50 80

95 11.0 5.5 23.0 1.90 28.0 0.81 2.9 560 336 50 80

120 12.6 5.5 24.6 1.90 29.5 0.91 3.6 590 354 50 80

150 13.9 5.5 25.9 2.00 31.0 1.03 4.5 620 372 50 80

185 15.6 5.5 27.6 2.00 33.0 1.17 5.6 660 396 65 100

240 17.6 5.5 29.6 2.10 35.0 1.39 7.2 700 420 65 100

300 19.7 5.5 31.7 2.20 38.0 1.61 9.0 760 456 65 100

400 22.6 5.5 34.6 2.30 41.0 1.94 12.0 820 492 65 125

500 25.6 5.5 37.6 2.40 44.0 2.33 15.0 880 528 65 125

630 29.0 5.5 41.3 2.50 48.0 2.82 18.9 960 576 65 150

800 33.0 5.5 45.3 2.60 52.0 3.41 24.0 1040 624 80 150

1000 36.8 5.5 49.1 2.70 56.0 4.09 30.0 1120 672 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

35 0.868 1.113 0.141 0.155 0.199 0.155 0.59 28.1 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.135 0.150 0.193 0.170 0.64 30.8 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.124 0.138 0.182 0.194 0.73 35.1 6.58 0.256 186 192 176 178 230 236 278

95 0.32 0.411 0.119 0.134 0.177 0.211 0.79 38.2 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.114 0.129 0.172 0.232 0.87 41.9 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.111 0.126 0.169 0.249 0.94 45.0 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.107 0.121 0.165 0.271 1.02 49.0 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.103 0.118 0.161 0.296 1.12 53.6 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.100 0.115 0.158 0.323 1.22 58.5 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.096 0.111 0.154 0.360 1.36 65.2 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.093 0.108 0.151 0.399 1.50 72.2 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.064 0.091 0.105 0.149 0.445 1.68 80.6 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.052 0.088 0.102 0.146 0.496 1.87 89.8 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.086 0.100 0.144 0.544 2.05 98.5 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

10
18/30(36) kv , single Core , Copper ConduCTor , Xlpe insulaTed , sCreened , unarmoured Cables
(2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

50 8.1 8.0 25.2 1.90 31.0 1.10 2.5 620 372 50 65

70 9.8 8.0 26.9 2.00 33.0 1.35 3.5 660 396 50 80

95 11.3 8.0 28.4 2.10 34.0 1.64 4.8 680 408 50 80

120 12.9 8.0 30.0 2.10 35.5 1.90 6.0 710 426 50 80

150 13.9 8.0 31.0 2.10 37.0 2.16 7.5 740 444 50 80

185 15.9 8.0 33.0 2.20 39.0 2.56 9.3 780 468 65 100

240 18.1 8.0 35.2 2.30 41.0 3.13 12.0 820 492 65 100

300 19.8 8.0 36.9 2.30 43.0 3.71 15.0 860 516 65 100

400 22.9 8.0 40.0 2.50 47.0 4.58 20.0 940 564 65 125

500 26.4 8.0 43.5 2.50 50.0 5.62 25.0 1000 600 65 125

630 29.6 8.0 47.0 2.70 54.0 7.01 31.5 1080 648 65 150

800 34.0 8.0 51.4 2.80 59.0 8.70 40.0 1180 708 80 150

1000 37.8 8.0 55.2 2.90 63.0 10.52 50.0 1260 756 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

50 0.387 0.494 0.146 0.161 0.204 0.136 0.77 55.4 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.135 0.150 0.194 0.152 0.86 61.8 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.130 0.144 0.188 0.165 0.93 67.3 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.124 0.139 0.182 0.180 1.02 73.5 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.121 0.136 0.179 0.190 1.07 77.2 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.127 0.116 0.130 0.174 0.208 1.17 84.5 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.112 0.126 0.170 0.227 1.28 92.4 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.108 0.123 0.166 0.243 1.37 98.8 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.104 0.118 0.162 0.270 1.53 110.0 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.099 0.114 0.158 0.301 1.70 122.6 71.50 0.256 640 635 608 603 942 944 1003

630 0.0283 0.041 0.097 0.111 0.155 0.332 1.87 135.0 90.09 0.256 712 703 676 668 1071 1070 1117

800 0.0221 0.034 0.093 0.108 0.152 0.370 2.09 150.7 114.40 0.256 781 770 742 732 1210 1207 1240

1000 0.0176 0.029 0.091 0.105 0.149 0.404 2.28 164.3 143.00 0.256 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

11
18/30(36) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , sCreened , unarmoured
Cables (2Xy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Approx. Max. Min. bending radius Nominal duct diameter
conductor conductor insulation diameter thickness overall mass pulling
area diameter thickness over of Outer diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation sheath (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

50 7.9 8.0 25.0 1.90 30.0 0.83 1.5 600 360 50 65

70 9.7 8.0 26.8 2.00 32.0 0.96 2.1 640 384 50 80

95 11.0 8.0 28.1 2.10 34.0 1.08 2.9 680 408 50 80

120 12.6 8.0 29.7 2.10 35.5 1.20 3.6 710 426 50 80

150 13.9 8.0 31.0 2.10 37.0 1.32 4.5 740 444 50 80

185 15.6 8.0 32.7 2.20 39.0 1.49 5.6 780 468 65 100

240 17.6 8.0 34.7 2.30 41.0 1.72 7.2 820 492 65 100

300 19.7 8.0 36.8 2.30 43.0 1.95 9.0 860 516 65 100

400 22.6 8.0 39.7 2.50 46.0 2.33 12.0 920 552 65 125

500 25.6 8.0 42.7 2.50 49.0 2.72 15.0 980 588 65 125

630 29.0 8.0 46.4 2.70 53.0 3.26 18.9 1060 636 65 150

800 33.0 8.0 50.4 2.80 58.0 3.89 24.0 1160 696 80 150

1000 36.8 8.0 54.2 2.90 62.0 4.60 30.0 1240 744 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Copper Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) Tape spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ Screen ducts
km) km) km) (kA)

50 0.641 0.822 0.147 0.162 0.206 0.134 0.76 54.6 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.136 0.150 0.194 0.151 0.85 61.5 6.58 0.256 186 192 176 178 230 236 278

95 0.32 0.411 0.131 0.145 0.189 0.163 0.92 66.4 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.125 0.140 0.183 0.178 1.00 72.3 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.121 0.136 0.179 0.190 1.07 77.2 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.117 0.131 0.175 0.205 1.16 83.4 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.112 0.127 0.171 0.223 1.26 90.7 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.129 0.109 0.123 0.167 0.242 1.37 98.4 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.101 0.104 0.119 0.162 0.267 1.51 108.9 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.100 0.115 0.158 0.294 1.66 119.7 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.098 0.112 0.156 0.326 1.84 132.8 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.094 0.109 0.152 0.361 2.04 147.2 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.042 0.092 0.106 0.150 0.395 2.23 160.7 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

12
3.6/6 (7.2) kv , single Core , Copper ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (2XWcy) as per ieC : 60502-2
Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 2.5 13.1 16.0 15.7 1.08 20.0 0.69 1.8 300 240 50 65

50 8.1 2.5 14.2 16.0 16.8 1.08 21.0 0.81 2.5 315 252 50 65

70 9.8 2.5 15.9 16.0 18.5 1.08 23.0 1.01 3.5 345 276 50 80

95 11.3 2.5 17.4 16.0 19.9 1.16 24.0 1.26 4.8 360 288 50 80

120 12.9 2.5 19.0 16.0 21.6 1.24 25.5 1.51 6.0 383 306 50 80

150 13.9 2.5 20.0 25.0 22.6 1.24 27.0 1.84 7.5 405 324 50 80

185 15.9 2.5 22.0 25.0 24.6 1.32 29.0 2.20 9.3 435 348 65 100

240 18.1 2.6 24.4 25.0 26.9 1.32 32.0 2.72 12.0 480 384 65 100

300 19.8 2.8 26.5 25.0 29.1 1.40 34.0 3.30 15.0 510 408 65 100

400 22.9 3.0 30.0 35.0 32.6 1.56 38.0 4.22 20.0 570 456 65 125

500 26.4 3.2 33.9 35.0 36.5 1.64 42.0 5.25 25.0 630 504 65 125

630 29.6 3.2 37.4 35.0 39.9 1.72 46.0 6.55 31.5 690 552 65 150

800 34.0 3.2 41.8 35.0 44.3 1.80 50.0 8.17 40.0 750 600 80 150

1000 37.8 3.2 45.6 35.0 48.1 1.88 54.0 9.93 50.0 810 648 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.128 0.142 0.186 0.283 0.34 5.1 5.01 2.29 166 172 157 159 198 203 238

50 0.387 0.494 0.122 0.137 0.180 0.314 0.38 5.7 7.15 2.29 196 203 186 188 238 243 286

70 0.268 0.342 0.112 0.127 0.170 0.362 0.43 6.6 10.01 2.29 239 246 227 229 296 303 356

95 0.193 0.247 0.108 0.123 0.166 0.403 0.48 7.3 13.59 2.29 285 293 271 274 361 369 434

120 0.153 0.196 0.104 0.119 0.162 0.449 0.54 8.2 17.16 2.29 323 332 308 311 417 426 500

150 0.124 0.159 0.102 0.117 0.160 0.477 0.57 8.7 21.45 3.58 361 366 343 347 473 481 559

185 0.0991 0.128 0.098 0.112 0.156 0.533 0.64 9.7 26.46 3.58 406 410 387 391 543 550 637

240 0.0754 0.098 0.095 0.109 0.153 0.573 0.68 10.4 34.32 3.58 469 470 447 453 641 647 745

300 0.0601 0.079 0.093 0.108 0.151 0.580 0.69 10.5 42.90 3.58 526 524 504 510 735 739 846

400 0.0470 0.063 0.091 0.105 0.149 0.618 0.74 11.2 57.20 5.01 590 572 564 571 845 837 938

500 0.0366 0.051 0.088 0.103 0.146 0.659 0.79 12.0 71.50 5.01 640 635 608 603 942 944 1003

630 0.0283 0.042 0.086 0.101 0.145 0.735 0.88 13.3 90.09 5.01 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.084 0.098 0.142 0.830 0.99 15.1 114.40 5.01 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.082 0.097 0.140 0.913 1.09 16.6 143.00 5.01 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

13
3.6/6 (7.2) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (a2XWcy) as per ieC : 60502-2
Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 2.5 12.9 16.0 15.5 1.08 20.0 0.48 1.1 300 240 50 65

50 7.9 2.5 14.0 16.0 16.6 1.08 21.0 0.53 1.5 315 252 50 65

70 9.7 2.5 15.8 16.0 18.4 1.08 23.0 0.62 2.1 345 276 50 80

95 11.0 2.5 17.1 16.0 19.7 1.16 24.0 0.72 2.9 360 288 50 80

120 12.6 2.5 18.7 16.0 21.3 1.24 25.5 0.82 3.6 383 306 50 80

150 13.9 2.5 20.0 25.0 22.6 1.24 27.0 1.00 4.5 405 324 50 80

185 15.6 2.5 21.7 25.0 24.3 1.32 29.0 1.13 5.6 435 348 65 100

240 17.6 2.6 23.9 25.0 26.5 1.32 31.0 1.32 7.2 465 372 65 100

300 19.7 2.8 26.4 25.0 29.0 1.40 34.0 1.54 9.0 510 408 65 100

400 22.6 3.0 29.7 35.0 32.3 1.56 38.0 1.98 12.0 570 456 65 125

500 25.6 3.2 33.1 35.0 35.7 1.64 41.0 2.36 15.0 615 492 65 125

630 29.0 3.2 36.8 35.0 39.3 1.72 45.0 2.82 18.9 675 540 65 150

800 33.0 3.2 40.8 35.0 43.3 1.80 49.0 3.38 24.0 735 588 80 150

1000 36.8 3.2 44.6 35.0 47.1 1.88 53.0 4.03 30.0 795 636 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.129 0.143 0.187 0.278 0.33 5.0 3.29 2.29 129 134 122 123 154 157 185

50 0.641 0.822 0.123 0.138 0.181 0.309 0.37 5.6 4.70 2.29 152 157 144 146 184 189 222

70 0.443 0.568 0.113 0.127 0.171 0.359 0.43 6.5 6.58 2.29 186 192 176 178 230 236 278

95 0.32 0.411 0.109 0.123 0.167 0.396 0.47 7.2 8.93 2.29 221 229 210 213 280 287 338

120 0.253 0.325 0.105 0.120 0.163 0.441 0.53 8.0 11.28 2.29 252 260 240 242 324 332 391

150 0.206 0.265 0.102 0.117 0.160 0.477 0.57 8.7 14.10 3.58 281 288 267 271 368 376 440

185 0.1640 0.211 0.098 0.113 0.156 0.525 0.63 9.5 17.39 3.58 317 324 303 307 424 432 504

240 0.1250 0.162 0.095 0.110 0.153 0.561 0.67 10.2 22.56 3.58 367 373 351 356 502 511 593

300 0.1000 0.130 0.094 0.108 0.152 0.578 0.69 10.5 28.20 3.58 414 419 397 402 577 586 677

400 0.0778 0.102 0.091 0.106 0.149 0.611 0.73 11.1 37.60 5.01 470 466 451 457 673 676 769

500 0.0605 0.080 0.089 0.104 0.147 0.642 0.77 11.7 47.00 5.01 519 520 493 494 757 764 837

630 0.0469 0.064 0.087 0.101 0.145 0.722 0.86 13.1 59.22 5.01 586 584 557 555 876 882 950

800 0.0367 0.052 0.084 0.099 0.142 0.809 0.97 14.7 75.20 5.01 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.083 0.097 0.141 0.891 1.06 16.2 94.00 5.01 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

14
6/10 (12) kv , single Core , Copper ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 3.4 14.8 16.0 17.3 1.08 21.0 0.73 1.8 315 252 50 65

50 8.1 3.4 15.9 16.0 18.4 1.16 23.0 0.86 2.5 345 276 50 65

70 9.8 3.4 17.6 16.0 20.1 1.16 25.0 1.07 3.5 375 300 50 80

95 11.3 3.4 19.1 16.0 21.5 1.24 26.0 1.33 4.8 390 312 50 80

120 12.9 3.4 20.7 16.0 23.2 1.24 27.5 1.57 6.0 413 330 50 80

150 13.9 3.4 21.7 25.0 24.2 1.32 29.0 1.92 7.5 435 348 50 80

185 15.9 3.4 23.7 25.0 26.2 1.32 31.0 2.26 9.3 465 372 65 100

240 18.1 3.4 25.9 25.0 28.3 1.40 33.0 2.80 12.0 495 396 65 100

300 19.8 3.4 27.6 25.0 30.1 1.48 35.0 3.37 15.0 525 420 65 100

400 22.9 3.4 30.7 35.0 33.2 1.56 39.0 4.25 20.0 585 468 65 125

500 26.4 3.4 34.2 35.0 36.7 1.64 42.0 5.26 25.0 630 504 65 125

630 29.6 3.4 37.7 35.0 40.1 1.72 46.0 6.56 31.5 690 552 65 150

800 34.0 3.4 42.1 35.0 44.5 1.80 51.0 8.18 40.0 765 612 80 150

1000 37.8 3.4 45.9 35.0 48.3 1.88 55.0 9.95 50.0 825 660 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.133 0.147 0.191 0.222 0.26 4.0 5.01 2.29 166 172 157 159 198 203 238

50 0.387 0.494 0.127 0.142 0.185 0.245 0.29 4.4 7.15 2.29 196 203 186 188 238 243 286

70 0.268 0.342 0.117 0.132 0.175 0.280 0.33 5.1 10.01 2.29 239 246 227 229 296 303 356

95 0.193 0.247 0.113 0.127 0.171 0.310 0.37 5.6 13.59 2.29 285 293 271 274 361 369 434

120 0.153 0.196 0.108 0.123 0.166 0.345 0.41 6.3 17.16 2.29 323 332 308 311 417 426 500

150 0.124 0.159 0.106 0.121 0.164 0.365 0.44 6.6 21.45 3.58 361 366 343 347 473 481 559

185 0.0991 0.128 0.101 0.116 0.159 0.407 0.49 7.4 26.46 3.58 406 410 387 391 543 550 637

240 0.0754 0.098 0.098 0.112 0.156 0.451 0.54 8.2 34.32 3.58 469 470 447 453 641 647 745

300 0.0601 0.079 0.096 0.110 0.154 0.487 0.58 8.8 42.90 3.58 526 524 504 510 735 739 846

400 0.0470 0.063 0.092 0.106 0.150 0.551 0.66 10.0 57.20 5.01 590 572 564 571 845 837 938

500 0.0366 0.051 0.089 0.103 0.147 0.622 0.74 11.3 71.50 5.01 640 635 608 603 942 944 1003

630 0.0283 0.042 0.087 0.101 0.145 0.693 0.83 12.6 90.09 5.01 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.084 0.099 0.142 0.783 0.94 14.2 114.40 5.01 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.082 0.097 0.140 0.861 1.03 15.6 143.00 5.01 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

15
6/10 (12) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (a2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 3.4 14.6 16.0 17.1 1.08 21.0 0.53 1.1 315 252 50 65

50 7.9 3.4 15.7 16.0 18.2 1.16 23.0 0.59 1.5 345 276 50 65

70 9.7 3.4 17.5 16.0 20.0 1.16 24.0 0.68 2.1 360 288 50 80

95 11.0 3.4 18.8 16.0 21.3 1.24 26.0 0.78 2.9 390 312 50 80

120 12.6 3.4 20.4 16.0 22.9 1.24 27.5 0.88 3.6 413 330 50 80

150 13.9 3.4 21.7 25.0 24.2 1.32 29.0 1.07 4.5 435 348 50 80

185 15.6 3.4 23.4 25.0 25.9 1.32 31.0 1.20 5.6 465 372 65 100

240 17.6 3.4 25.4 25.0 27.9 1.40 33.0 1.40 7.2 495 396 65 100

300 19.7 3.4 27.5 25.0 30.0 1.48 35.0 1.61 9.0 525 420 65 100

400 22.6 3.4 30.4 35.0 32.9 1.56 38.0 2.01 12.0 570 456 65 125

500 25.6 3.4 33.4 35.0 35.9 1.64 42.0 2.37 15.0 630 504 65 125

630 29.0 3.4 37.1 35.0 39.5 1.72 45.0 2.83 18.9 675 540 65 150

800 33.0 3.4 41.1 35.0 43.5 1.80 50.0 3.39 24.0 750 600 80 150

1000 36.8 3.4 44.9 35.0 47.3 1.88 54.0 4.04 30.0 810 648 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.134 0.148 0.192 0.217 0.26 3.9 3.29 2.29 129 134 122 123 154 157 185

50 0.641 0.822 0.128 0.143 0.186 0.240 0.29 4.4 4.70 2.29 152 157 144 146 184 189 222

70 0.443 0.568 0.118 0.132 0.176 0.278 0.33 5.0 6.58 2.29 186 192 176 178 230 236 278

95 0.32 0.411 0.114 0.128 0.172 0.305 0.36 5.5 8.93 2.29 221 229 210 213 280 287 338

120 0.253 0.325 0.109 0.123 0.167 0.338 0.40 6.1 11.28 2.29 252 260 240 242 324 332 391

150 0.206 0.265 0.106 0.121 0.164 0.365 0.44 6.6 14.10 3.58 281 288 267 271 368 376 440

185 0.1640 0.211 0.102 0.116 0.160 0.400 0.48 7.3 17.39 3.58 317 324 303 307 424 432 504

240 0.1250 0.161 0.099 0.113 0.157 0.442 0.53 8.0 22.56 3.58 367 373 351 356 502 511 593

300 0.1000 0.130 0.096 0.110 0.154 0.485 0.58 8.8 28.20 3.58 414 419 397 402 577 586 677

400 0.0778 0.102 0.092 0.107 0.150 0.544 0.65 9.9 37.60 5.01 470 466 451 457 673 676 769

500 0.0605 0.080 0.089 0.104 0.147 0.606 0.72 11.0 47.00 5.01 519 520 493.05 494 757 764 837

630 0.0469 0.064 0.087 0.102 0.145 0.681 0.81 12.4 59.22 5.01 586 584 557 555 876 882 950

800 0.0367 0.052 0.085 0.099 0.143 0.763 0.91 13.8 75.20 5.01 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.083 0.097 0.141 0.841 1.00 15.3 94.00 5.01 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

16
8.7/15 (17.5) kv , single Core , Copper ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 4.5 17.0 16.0 19.5 1.16 24.0 0.81 1.8 480 288 50 65

50 8.1 4.5 18.1 16.0 20.6 1.16 25.0 0.94 2.5 500 300 50 65

70 9.8 4.5 19.8 16.0 22.3 1.24 27.0 1.16 3.5 540 324 50 80

95 11.3 4.5 21.3 16.0 23.7 1.24 28.0 1.41 4.8 560 336 50 80

120 12.9 4.5 22.9 16.0 25.4 1.32 29.5 1.67 6.0 590 354 50 80

150 13.9 4.5 23.9 25.0 26.4 1.32 31.0 2.01 7.5 620 372 50 80

185 15.9 4.5 25.9 25.0 28.4 1.40 33.0 2.38 9.3 660 396 65 100

240 18.1 4.5 28.1 25.0 30.5 1.48 36.0 2.92 12.0 720 432 65 100

300 19.8 4.5 29.8 25.0 32.3 1.48 38.0 3.48 15.0 760 456 65 100

400 22.9 4.5 32.9 35.0 35.4 1.64 41.0 4.39 20.0 820 492 65 125

500 26.4 4.5 36.4 35.0 38.9 1.72 45.0 5.42 25.0 900 540 65 125

630 29.6 4.5 39.9 35.0 42.3 1.80 48.0 6.73 31.5 960 576 65 150

800 34.0 4.5 44.3 35.0 46.7 1.88 53.0 8.37 40.0 1060 636 80 150

1000 37.8 4.5 48.1 35.0 50.5 1.96 57.0 10.15 50.0 1140 684 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.140 0.154 0.198 0.181 0.22 3.3 5.01 2.29 166 172 157 159 198 203 238

50 0.387 0.494 0.133 0.148 0.191 0.199 0.24 3.6 7.15 2.29 196 203 186 188 238 243 286

70 0.268 0.342 0.123 0.138 0.181 0.226 0.27 4.1 10.01 2.29 239 246 227 229 296 303 356

95 0.193 0.247 0.118 0.132 0.176 0.249 0.30 4.5 13.59 2.29 285 293 271 274 361 369 434

120 0.153 0.196 0.113 0.128 0.171 0.275 0.33 5.0 17.16 2.29 323 332 308 311 417 426 500

150 0.124 0.159 0.111 0.125 0.169 0.291 0.35 5.3 21.45 3.58 361 366 343 347 473 481 559

185 0.0991 0.128 0.106 0.120 0.164 0.322 0.38 5.8 26.46 3.58 406 410 387 391 543 550 637

240 0.0754 0.098 0.102 0.117 0.160 0.356 0.42 6.5 34.32 3.58 469 470 447 453 641 647 745

300 0.0601 0.079 0.099 0.114 0.158 0.383 0.46 7.0 42.90 3.58 526 524 504 510 735 739 846

400 0.0470 0.063 0.096 0.110 0.154 0.431 0.52 7.8 57.20 5.01 590 572 564 571 845 837 938

500 0.0366 0.051 0.092 0.107 0.150 0.486 0.58 8.8 71.50 5.01 640 635 608 603 942 944 1003

630 0.0283 0.041 0.090 0.104 0.148 0.539 0.64 9.8 90.09 5.01 712 703 676 668 1071 1070 1117

800 0.0221 0.035 0.087 0.102 0.145 0.608 0.73 11.0 114.40 5.01 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.085 0.099 0.143 0.667 0.80 12.1 143.00 5.01 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

17
8.7/15 (17.5) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (a2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 4.5 16.8 16.0 19.3 1.16 24.0 0.61 1.1 480 288 50 65

50 7.9 4.5 17.9 16.0 20.4 1.16 25.0 0.66 1.5 500 300 50 65

70 9.7 4.5 19.7 16.0 22.2 1.24 27.0 0.77 2.1 540 324 50 80

95 11.0 4.5 21.0 16.0 23.5 1.24 28.0 0.86 2.9 560 336 50 80

120 12.6 4.5 22.6 16.0 25.1 1.32 29.5 0.98 3.6 590 354 50 80

150 13.9 4.5 23.9 25.0 26.4 1.32 31.0 1.16 4.5 620 372 50 80

185 15.6 4.5 25.6 25.0 28.1 1.40 33.0 1.31 5.6 660 396 65 100

240 17.6 4.5 27.6 25.0 30.1 1.48 35.0 1.52 7.2 700 420 65 100

300 19.7 4.5 29.7 25.0 32.2 1.48 37.0 1.72 9.0 740 444 65 100

400 22.6 4.5 32.6 35.0 35.1 1.64 41.0 2.15 12.0 820 492 65 125

500 25.6 4.5 35.6 35.0 38.1 1.72 44.0 2.52 15.0 880 528 65 125

630 29.0 4.5 39.3 35.0 41.7 1.80 48.0 3.00 18.9 960 576 65 150

800 33.0 4.5 43.3 35.0 45.7 1.88 52.0 3.58 24.0 1040 624 80 150

1000 36.8 4.5 47.1 35.0 49.5 1.96 56.0 4.24 30.0 1120 672 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.141 0.155 0.199 0.178 0.21 3.2 3.29 2.29 129 134 122 123 154 157 185

50 0.641 0.822 0.134 0.149 0.192 0.196 0.23 3.5 4.70 2.29 152 157 144 146 184 189 222

70 0.443 0.568 0.124 0.138 0.182 0.224 0.27 4.1 6.58 2.29 186 192 176 178 230 236 278

95 0.32 0.411 0.119 0.133 0.177 0.245 0.29 4.4 8.93 2.29 221 229 210 213 280 287 338

120 0.253 0.325 0.114 0.129 0.172 0.270 0.32 4.9 11.28 2.29 252 260 240 242 324 332 391

150 0.206 0.265 0.111 0.125 0.169 0.291 0.35 5.3 14.10 3.58 281 288 267 271 368 376 440

185 0.1640 0.211 0.106 0.121 0.165 0.317 0.38 5.8 17.39 3.58 317 324 303 307 424 432 504

240 0.1250 0.161 0.103 0.118 0.161 0.349 0.42 6.3 22.56 3.58 367 373 351 356 502 511 593

300 0.1000 0.130 0.100 0.114 0.158 0.382 0.46 6.9 28.20 3.58 414 419 397 402 577 586 677

400 0.0778 0.102 0.096 0.110 0.154 0.427 0.51 7.7 37.60 5.01 470 466 451 457 673 676 769

500 0.0605 0.080 0.093 0.107 0.151 0.473 0.57 8.6 47.00 5.01 519 520 493 494 757 764 837

630 0.0469 0.064 0.090 0.105 0.149 0.530 0.63 9.6 59.22 5.01 586 584 557 555 876 882 950

800 0.0367 0.052 0.088 0.102 0.146 0.592 0.71 10.7 75.20 5.01 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.086 0.100 0.144 0.651 0.78 11.8 94.00 5.01 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

18
12/20 (24) kv , single Core , Copper ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 5.5 19.0 16.0 21.5 1.24 26.0 0.89 1.8 520 312 50 65

50 8.1 5.5 20.1 16.0 22.6 1.24 27.0 1.02 2.5 540 324 50 65

70 9.8 5.5 21.8 16.0 24.3 1.32 29.0 1.25 3.5 580 348 50 80

95 11.3 5.5 23.3 16.0 25.7 1.32 31.0 1.51 4.8 620 372 50 80

120 12.9 5.5 24.9 16.0 27.4 1.40 31.5 1.77 6.0 630 378 50 80

150 13.9 5.5 25.9 25.0 28.4 1.40 33.0 2.11 7.5 660 396 50 80

185 15.9 5.5 27.9 25.0 30.4 1.48 36.0 2.49 9.3 720 432 65 100

240 18.1 5.5 30.1 25.0 32.5 1.48 38.0 3.03 12.0 760 456 65 100

300 19.8 5.5 31.8 25.0 34.3 1.56 40.0 3.61 15.0 800 480 65 100

400 22.9 5.5 34.9 35.0 37.4 1.64 43.0 4.51 20.0 860 516 65 125

500 26.4 5.5 38.4 35.0 40.9 1.72 47.0 5.55 25.0 940 564 65 125

630 29.6 5.5 41.9 35.0 44.3 1.80 50.0 6.87 31.5 1000 600 65 150

800 34.0 5.5 46.3 35.0 48.7 1.96 55.0 8.55 40.0 1100 660 80 150

1000 37.8 5.5 50.1 35.0 52.5 2.04 59.0 10.34 50.0 1180 708 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.145 0.160 0.203 0.158 0.19 2.9 5.01 2.29 166 172 157 159 198 203 238

50 0.387 0.494 0.139 0.153 0.197 0.173 0.21 3.1 7.15 2.29 196 203 186 188 238 243 286

70 0.268 0.342 0.128 0.143 0.186 0.195 0.23 3.5 10.01 2.29 239 246 227 229 296 303 356

95 0.193 0.247 0.123 0.137 0.181 0.214 0.26 3.9 13.59 2.29 285 293 271 274 361 369 434

120 0.153 0.196 0.118 0.132 0.176 0.236 0.28 4.3 17.16 2.29 323 332 308 311 417 426 500

150 0.124 0.159 0.115 0.130 0.173 0.249 0.30 4.5 21.45 3.58 361 366 343 347 473 481 559

185 0.0991 0.128 0.110 0.124 0.168 0.274 0.33 5.0 26.46 3.58 406 410 387 391 543 550 637

240 0.0754 0.098 0.106 0.120 0.164 0.302 0.36 5.5 34.32 3.58 469 470 447 453 641 647 745

300 0.0601 0.079 0.103 0.118 0.161 0.325 0.39 5.9 42.90 3.58 526 524 504 510 735 739 846

400 0.0470 0.063 0.099 0.113 0.157 0.364 0.43 6.6 57.20 5.01 590 572 564 571 845 837 938

500 0.0366 0.051 0.095 0.109 0.153 0.409 0.49 7.4 71.50 5.01 640 635 608 603 942 944 1003

630 0.0283 0.041 0.093 0.107 0.151 0.453 0.54 8.2 90.09 5.01 712 703 676 668 1071 1070 1117

800 0.0221 0.034 0.090 0.104 0.148 0.509 0.61 9.2 114.40 5.01 781 770 742 732 1210 1207 1240

1000 0.0176 0.030 0.087 0.102 0.145 0.557 0.67 10.1 143.00 5.01 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

19
12/20 (24) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (a2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 5.5 18.8 16.0 21.3 1.24 26.0 0.69 1.1 520 312 50 65

50 7.9 5.5 19.9 16.0 22.4 1.24 27.0 0.75 1.5 540 324 50 65

70 9.7 5.5 21.7 16.0 24.2 1.32 29.0 0.86 2.1 580 348 50 80

95 11.0 5.5 23.0 16.0 25.5 1.32 30.0 0.96 2.9 600 360 50 80

120 12.6 5.5 24.6 16.0 27.1 1.40 31.5 1.08 3.6 630 378 50 80

150 13.9 5.5 25.9 25.0 28.4 1.40 33.0 1.27 4.5 660 396 50 80

185 15.6 5.5 27.6 25.0 30.1 1.48 35.0 1.43 5.6 700 420 65 100

240 17.6 5.5 29.6 25.0 32.1 1.48 37.0 1.62 7.2 740 444 65 100

300 19.7 5.5 31.7 25.0 34.2 1.56 40.0 1.85 9.0 800 480 65 100

400 22.6 5.5 34.6 35.0 37.1 1.64 43.0 2.27 12.0 860 516 65 125

500 25.6 5.5 37.6 35.0 40.1 1.72 46.0 2.65 15.0 920 552 65 125

630 29.0 5.5 41.3 35.0 43.7 1.80 50.0 3.14 18.9 1000 600 65 150

800 33.0 5.5 45.3 35.0 47.7 1.96 54.0 3.75 24.0 1080 648 80 150

1000 36.8 5.5 49.1 35.0 51.5 2.04 58.0 4.43 30.0 1160 696 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.147 0.161 0.205 0.155 0.19 2.8 3.29 2.29 129 134 122 123 154 157 185

50 0.641 0.822 0.140 0.154 0.198 0.170 0.20 3.1 4.70 2.29 152 157 144 146 184 189 222

70 0.443 0.568 0.129 0.143 0.187 0.194 0.23 3.5 6.58 2.29 186 192 176 178 230 236 278

95 0.32 0.411 0.124 0.138 0.182 0.211 0.25 3.8 8.93 2.29 221 229 210 213 280 287 338

120 0.253 0.325 0.119 0.133 0.177 0.232 0.28 4.2 11.28 2.29 252 260 240 242 324 332 391

150 0.206 0.265 0.115 0.130 0.173 0.249 0.30 4.5 14.10 3.58 281 288 267 271 368 376 440

185 0.1640 0.211 0.111 0.125 0.169 0.271 0.32 4.9 17.39 3.58 317 324 303 307 424 432 504

240 0.1250 0.161 0.107 0.121 0.165 0.296 0.35 5.4 22.56 3.58 367 373 351 356 502 511 593

300 0.1000 0.130 0.103 0.118 0.161 0.323 0.39 5.9 28.20 3.58 414 419 397 402 577 586 677

400 0.0778 0.102 0.099 0.114 0.157 0.360 0.43 6.5 37.60 5.01 470 466 451 457 673 676 769

500 0.0605 0.080 0.096 0.110 0.154 0.399 0.48 7.2 47.00 5.01 519 520 493 494 757 764 837

630 0.0469 0.063 0.093 0.108 0.151 0.445 0.53 8.1 59.22 5.01 586 584 557 555 876 882 950

800 0.0367 0.051 0.090 0.105 0.148 0.496 0.59 9.0 75.20 5.01 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.088 0.102 0.146 0.544 0.65 9.9 94.00 5.01 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

20
18/30 (36) kv , single Core , Copper ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 8.0 24.1 16.0 26.7 1.32 32.0 1.12 1.8 640 384 50 65

50 8.1 8.0 25.2 16.0 27.8 1.40 33.0 1.27 2.5 660 396 50 65

70 9.8 8.0 26.9 16.0 29.5 1.40 35.0 1.50 3.5 700 420 50 80

95 11.3 8.0 28.4 16.0 30.9 1.48 36.0 1.79 4.8 720 432 50 80

120 12.9 8.0 30.0 16.0 32.6 1.48 37.5 2.05 6.0 750 450 50 80

150 13.9 8.0 31.0 25.0 33.6 1.56 39.0 2.42 7.5 780 468 50 80

185 15.9 8.0 33.0 25.0 35.6 1.56 41.0 2.79 9.3 820 492 65 100

240 18.1 8.0 35.2 25.0 37.7 1.64 43.0 3.36 12.0 860 516 65 100

300 19.8 8.0 36.9 25.0 39.5 1.72 45.0 3.96 15.0 900 540 65 100

400 22.9 8.0 40.0 35.0 42.6 1.80 49.0 4.90 20.0 980 588 65 125

500 26.4 8.0 43.5 35.0 46.1 1.88 52.0 5.96 25.0 1040 624 65 125

630 29.6 8.0 47.0 35.0 49.5 1.96 56.0 7.32 31.5 1120 672 65 150

800 34.0 8.0 51.4 35.0 53.9 2.04 61.0 9.01 40.0 1220 732 80 150

1000 37.8 8.0 55.2 35.0 57.7 2.20 65.0 10.86 50.0 1300 780 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.157 0.172 0.215 0.125 0.15 2.3 5.01 2.29 166 172 157 159 198 203 238

50 0.387 0.494 0.151 0.165 0.209 0.136 0.16 2.5 7.15 2.29 196 203 186 188 238 243 286

70 0.268 0.342 0.139 0.154 0.197 0.152 0.18 2.8 10.01 2.29 239 246 227 229 296 303 356

95 0.193 0.247 0.133 0.148 0.192 0.165 0.20 3.0 13.59 2.29 285 293 271 274 361 369 434

120 0.153 0.196 0.128 0.142 0.186 0.180 0.22 3.3 17.16 2.29 323 332 308 311 417 426 500

150 0.124 0.159 0.125 0.140 0.183 0.190 0.23 3.4 21.45 3.58 361 366 343 347 473 481 559

185 0.0991 0.127 0.119 0.133 0.177 0.208 0.25 3.8 26.46 3.58 406 410 387 391 543 550 637

240 0.0754 0.098 0.115 0.129 0.173 0.227 0.27 4.1 34.32 3.58 469 470 447 453 641 647 745

300 0.0601 0.079 0.112 0.126 0.170 0.243 0.29 4.4 42.90 3.58 526 524 504 510 735 739 846

400 0.0470 0.063 0.106 0.121 0.164 0.270 0.32 4.9 57.20 5.01 590 572 564 571 845 837 938

500 0.0366 0.050 0.102 0.117 0.160 0.301 0.36 5.5 71.50 5.01 640 635 608 603 942 944 1003

630 0.0283 0.041 0.099 0.114 0.157 0.332 0.40 6.0 90.09 5.01 712 703 676 668 1071 1070 1117

800 0.0221 0.034 0.096 0.110 0.154 0.370 0.44 6.7 114.40 5.01 781 770 742 732 1210 1207 1240

1000 0.0176 0.029 0.093 0.108 0.151 0.404 0.48 7.3 143.00 5.01 841 827 799 786 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

21
18/30 (36) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , Copper Wire sCreened ,
unarmoured Cables (a2XWcy) as per ieC : 60502-2

Nominal Nominal Nominal Nominal Nominal Nominal Minimum Nominal Approx. mass Max. pulling Min. bending radius Nominal duct diameter
conductor conductor insulation diameter screen area diameter thickness of overall (Kg/m) tension
area diameter thickness over (mm2) over wire Over sheath diameter (kN) During Set in
(mm2) (mm) (mm) insulation screen (mm) (mm) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

50 7.9 8.0 25.0 16.0 27.6 1.40 33.0 0.99 1.5 660 396 50 65

70 9.7 8.0 26.8 16.0 29.4 1.40 34.0 1.11 2.1 680 408 50 80

95 11.0 8.0 28.1 16.0 30.7 1.48 36.0 1.23 2.9 720 432 50 80

120 12.6 8.0 29.7 16.0 32.3 1.48 37.5 1.35 3.6 750 450 50 80

150 13.9 8.0 31.0 25.0 33.6 1.56 39.0 1.57 4.5 780 468 50 80

185 15.6 8.0 32.7 25.0 35.3 1.56 41.0 1.72 5.6 820 492 65 100

240 17.6 8.0 34.7 25.0 37.3 1.64 43.0 1.96 7.2 860 516 65 100

300 19.7 8.0 36.8 25.0 39.4 1.72 45.0 2.20 9.0 900 540 65 100

400 22.6 8.0 39.7 35.0 42.3 1.80 48.0 2.65 12.0 960 576 65 125

500 25.6 8.0 42.7 35.0 45.3 1.88 52.0 3.06 15.0 1040 624 65 125

630 29.0 8.0 46.4 35.0 48.9 1.96 55.0 3.58 18.9 1100 660 65 150

800 33.0 8.0 50.4 35.0 52.9 2.04 60.0 4.21 24.0 1200 720 80 150

1000 36.8 8.0 54.2 35.0 56.7 2.20 64.0 4.94 30.0 1280 768 80 190

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

50 0.641 0.822 0.152 0.166 0.210 0.134 0.16 2.4 4.70 2.29 152 157 144 146 184 189 222

70 0.443 0.568 0.140 0.154 0.198 0.151 0.18 2.7 6.58 2.29 186 192 176 178 230 236 278

95 0.32 0.411 0.134 0.149 0.193 0.163 0.19 3.0 8.93 2.29 221 229 210 213 280 287 338

120 0.253 0.325 0.129 0.143 0.187 0.178 0.21 3.2 11.28 2.29 252 260 240 242 324 332 391

150 0.206 0.265 0.125 0.140 0.183 0.190 0.23 3.4 14.10 3.58 281 288 267 271 368 376 440

185 0.1640 0.211 0.120 0.134 0.178 0.205 0.24 3.7 17.39 3.58 317 324 303 307 424 432 504

240 0.1250 0.161 0.115 0.130 0.174 0.223 0.27 4.0 22.56 3.58 367 373 351 356 502 511 593

300 0.1000 0.129 0.112 0.126 0.170 0.242 0.29 4.4 28.20 3.58 414 419 397 402 577 586 677

400 0.0778 0.101 0.107 0.121 0.165 0.267 0.32 4.9 37.60 5.01 470 466 451 457 673 676 769

500 0.0605 0.080 0.103 0.118 0.161 0.294 0.35 5.3 47.00 5.01 519 520 493 494 757 764 837

630 0.0469 0.063 0.100 0.114 0.158 0.326 0.39 5.9 59.22 5.01 586 584 557 555 876 882 950

800 0.0367 0.051 0.096 0.111 0.154 0.361 0.43 6.6 75.20 5.01 655 651 622 618 1005 1009 1070

1000 0.0291 0.042 0.094 0.108 0.152 0.395 0.47 7.2 94.00 5.01 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

22
3.6/6 (7.2) kv , single Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWay(p) as
per ieC : 60502-2
Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 2.5 13.1 0.76 1.60 1.16 23.0 0.77 1.8 345 276 50 80

50 8.1 2.5 14.2 0.76 1.60 1.24 24.0 0.92 2.5 360 288 50 80

70 9.8 2.5 15.9 0.76 1.60 1.24 26.0 1.15 3.5 390 312 65 100

95 11.3 2.5 17.4 0.76 1.60 1.32 27.0 1.42 4.8 405 324 65 100

120 12.9 2.5 19.0 0.76 1.60 1.32 29.0 1.68 6.0 435 348 65 100

150 13.9 2.5 20.0 0.76 1.60 1.40 30.0 1.96 7.5 450 360 65 100

185 15.9 2.5 22.0 0.76 2.00 1.40 33.0 2.39 9.3 495 396 65 100

240 18.1 2.6 24.4 0.76 2.00 1.48 35.0 2.96 12.0 525 420 65 125

300 19.8 2.8 26.5 0.76 2.00 1.56 38.0 3.57 15.0 570 456 65 125

400 22.9 3.0 30.0 0.76 2.00 1.64 41.0 4.44 20.0 615 492 65 150

500 26.4 3.2 33.9 0.84 2.50 1.80 47.0 5.70 25.0 705 564 80 150

630 29.6 3.2 37.4 0.92 2.50 1.88 51.0 7.09 31.5 765 612 80 190

800 34.0 3.2 41.8 0.92 2.50 1.96 55.0 8.80 40.0 825 660 100 190

1000 37.8 3.2 45.6 1.00 2.50 2.12 59.0 10.69 50.0 885 708 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.137 0.151 0.195 0.283 0.32 4.61 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.131 0.145 0.189 0.314 0.36 5.12 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.121 0.135 0.179 0.362 0.41 5.90 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.116 0.130 0.174 0.403 0.46 6.56 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.111 0.125 0.169 0.449 0.51 7.32 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.109 0.123 0.167 0.477 0.54 7.77 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.105 0.120 0.163 0.533 0.60 8.68 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.101 0.116 0.160 0.573 0.65 9.33 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.100 0.114 0.158 0.580 0.66 9.45 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.096 0.111 0.154 0.618 0.70 10.06 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.095 0.109 0.153 0.659 0.75 10.74 71.50 0.256 640 635 608 603.25 942 944 1003

630 0.0283 0.041 0.093 0.107 0.151 0.735 0.83 11.96 90.09 0.256 712 703 676.4 667.85 1071 1070 1117

800 0.0221 0.034 0.090 0.104 0.148 0.830 0.94 13.52 114.40 0.256 781 770 741.95 731.5 1210 1207 1240

1000 0.0176 0.029 0.088 0.102 0.146 0.913 1.03 14.87 143.00 0.256 841 827 798.95 785.65 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

23
3.6/6 (7.2) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables a2XWay(p) as
per ieC : 60502-2
Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 2.5 12.9 0.76 1.60 1.16 22.0 0.56 1.1 330 264 50 80

50 7.9 2.5 14.0 0.76 1.60 1.24 24.0 0.64 1.5 360 288 50 80

70 9.7 2.5 15.8 0.76 1.60 1.24 26.0 0.74 2.1 390 312 65 100

95 11.0 2.5 17.1 0.76 1.60 1.32 27.0 0.86 2.9 405 324 65 100

120 12.6 2.5 18.7 0.76 1.60 1.32 29.0 0.98 3.6 435 348 65 100

150 13.9 2.5 20.0 0.76 1.60 1.40 30.0 1.10 4.5 450 360 65 100

185 15.6 2.5 21.7 0.76 2.00 1.40 33.0 1.31 5.6 495 396 65 100

240 17.6 2.6 23.9 0.76 2.00 1.48 35.0 1.55 7.2 525 420 65 125

300 19.7 2.8 26.4 0.76 2.00 1.56 38.0 1.81 9.0 570 456 65 125

400 22.6 3.0 29.7 0.76 2.00 1.64 41.0 2.19 12.0 615 492 65 150

500 25.6 3.2 33.1 0.84 2.50 1.80 46.0 2.79 15.0 690 552 80 150

630 29.0 3.2 36.8 0.92 2.50 1.88 50.0 3.34 18.9 750 600 80 190

800 33.0 3.2 40.8 0.92 2.50 1.96 54.0 3.99 24.0 810 648 100 190

1000 36.8 3.2 44.6 1.00 2.50 2.12 58.0 4.75 30.0 870 696 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.137 0.152 0.199 0.278 0.31 4.5 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.131 0.146 0.190 0.309 0.35 5.0 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.120 0.135 0.179 0.359 0.41 5.9 6.58 0.256 186 192 176 178 230 236 278

95 0.320 0.411 0.116 0.131 0.174 0.396 0.45 6.4 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.111 0.126 0.169 0.441 0.50 7.2 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.108 0.123 0.166 0.477 0.54 7.8 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.105 0.120 0.163 0.525 0.59 8.5 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.102 0.117 0.160 0.561 0.63 9.1 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.100 0.114 0.158 0.578 0.65 9.4 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.096 0.111 0.154 0.611 0.69 9.9 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.096 0.110 0.154 0.642 0.73 10.5 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.093 0.108 0.151 0.722 0.82 11.8 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.090 0.105 0.148 0.809 0.91 13.2 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.088 0.103 0.146 0.891 1.01 14.5 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

24
6/10 (12) kv , single Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed , aluminium
round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWay(p) as per ieC :
60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 3.4 14.8 0.76 1.60 1.24 24.0 0.84 1.8 360 288 50 80

50 8.1 3.4 15.9 0.76 1.60 1.24 26.0 0.98 2.5 390 312 50 80

70 9.8 3.4 17.6 0.76 1.60 1.32 27.0 1.22 3.5 405 324 65 100

95 11.3 3.4 19.1 0.76 1.60 1.32 29.0 1.49 4.8 435 348 65 100

120 12.9 3.4 20.7 0.76 1.60 1.40 31.0 1.76 6.0 465 372 65 100

150 13.9 3.4 21.7 0.76 2.00 1.48 33.0 2.10 7.5 495 396 65 100

185 15.9 3.4 23.7 0.76 2.00 1.48 35.0 2.49 9.3 525 420 65 100

240 18.1 3.4 25.9 0.76 2.00 1.56 37.0 3.06 12.0 555 444 65 125

300 19.8 3.4 27.6 0.76 2.00 1.56 39.0 3.64 15.0 585 468 65 125

400 22.9 3.4 30.7 0.76 2.00 1.72 42.0 4.49 20.0 630 504 65 150

500 26.4 3.4 34.2 0.84 2.50 1.80 47.0 5.71 25.0 705 564 80 150

630 29.6 3.4 37.7 0.92 2.50 1.88 51.0 7.10 31.5 765 612 80 190

800 34.0 3.4 42.1 0.92 2.50 1.96 55.0 8.81 40.0 825 660 100 190

1000 37.8 3.4 45.9 1.00 2.50 2.12 60.0 10.71 50.0 900 720 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.141 0.155 0.199 0.222 0.42 10.0 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.135 0.149 0.193 0.245 0.46 11.1 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.124 0.139 0.182 0.280 0.53 12.7 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.119 0.133 0.177 0.310 0.59 14.0 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.114 0.129 0.172 0.345 0.65 15.6 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.114 0.128 0.172 0.365 0.69 16.5 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.108 0.123 0.166 0.407 0.77 18.4 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.104 0.119 0.162 0.451 0.85 20.4 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.101 0.116 0.159 0.487 0.92 22.0 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.097 0.112 0.155 0.551 1.04 24.9 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.095 0.110 0.153 0.622 1.17 28.2 71.50 0.256 640 635 608 603.25 942 944 1003

630 0.0283 0.041 0.093 0.108 0.151 0.693 1.31 31.4 90.09 0.256 712 703 676.4 667.85 1071 1070 1117

800 0.0221 0.034 0.090 0.104 0.148 0.783 1.48 35.4 114.40 0.256 781 770 741.95 731.5 1210 1207 1240

1000 0.0176 0.029 0.088 0.102 0.146 0.861 1.62 39.0 143.00 0.256 841 827 798.95 785.65 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

25
6/10 (12) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables a2XWay(p) as
per ieC : 60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 3.4 14.6 0.76 1.60 1.24 24.0 0.63 1.1 360 288 50 80

50 7.9 3.4 15.7 0.76 1.60 1.24 25.0 0.70 1.5 375 300 50 80

70 9.7 3.4 17.5 0.76 1.60 1.32 27.0 0.83 2.1 405 324 65 100

95 11.0 3.4 18.8 0.76 1.60 1.32 29.0 0.94 2.9 435 348 65 100

120 12.6 3.4 20.4 0.76 1.60 1.40 30.0 1.07 3.6 450 360 65 100

150 13.9 3.4 21.7 0.76 2.00 1.48 33.0 1.26 4.5 495 396 65 100

185 15.6 3.4 23.4 0.76 2.00 1.48 34.0 1.42 5.6 510 408 65 100

240 17.6 3.4 25.4 0.76 2.00 1.56 36.0 1.65 7.2 540 432 65 125

300 19.7 3.4 27.5 0.76 2.00 1.56 39.0 1.88 9.0 585 468 65 125

400 22.6 3.4 30.4 0.76 2.00 1.72 42.0 2.25 12.0 630 504 65 150

500 25.6 3.4 33.4 0.84 2.50 1.80 46.0 2.80 15.0 690 552 80 150

630 29.0 3.4 37.1 0.92 2.50 1.88 50.0 3.35 18.9 750 600 80 190

800 33.0 3.4 41.1 0.92 2.50 1.96 54.0 4.00 24.0 810 648 100 190

1000 36.8 3.4 44.9 1.00 2.50 2.12 59.0 4.78 30.0 885 708 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.142 0.157 0.204 0.217 0.41 9.8 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.136 0.150 0.194 0.240 0.45 10.9 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.125 0.139 0.183 0.278 0.52 12.6 6.58 0.256 186 192 176 178 230 236 278

95 0.320 0.411 0.120 0.134 0.178 0.305 0.58 13.8 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.115 0.130 0.173 0.338 0.64 15.3 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.114 0.128 0.172 0.365 0.69 16.5 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.109 0.123 0.167 0.400 0.75 18.1 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.105 0.120 0.163 0.442 0.83 20.0 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.102 0.116 0.160 0.485 0.91 21.9 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.098 0.112 0.156 0.544 1.03 24.6 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.096 0.111 0.154 0.606 1.14 27.4 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.094 0.108 0.152 0.681 1.28 30.8 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.090 0.105 0.149 0.763 1.44 34.5 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.088 0.103 0.147 0.841 1.58 38.0 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

26
8.7/15(17.5) kv , single Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWay(p) as
per ieC : 60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 4.5 17.0 0.76 1.60 1.32 27.0 0.95 1.8 540 324 50 80

50 8.1 4.5 18.1 0.76 1.60 1.32 28.0 1.10 2.5 560 336 50 80

70 9.8 4.5 19.8 0.76 1.60 1.32 30.0 1.34 3.5 600 360 65 100

95 11.3 4.5 21.3 0.76 2.00 1.40 32.0 1.68 4.8 640 384 65 100

120 12.9 4.5 22.9 0.76 2.00 1.48 34.0 1.97 6.0 680 408 65 100

150 13.9 4.5 23.9 0.76 2.00 1.48 35.0 2.23 7.5 700 420 65 100

185 15.9 4.5 25.9 0.76 2.00 1.56 37.0 2.64 9.3 740 444 65 100

240 18.1 4.5 28.1 0.76 2.00 1.64 39.0 3.21 12.0 780 468 65 125

300 19.8 4.5 29.8 0.76 2.00 1.64 41.0 3.80 15.0 820 492 65 125

400 22.9 4.5 32.9 0.84 2.50 1.80 46.0 4.81 20.0 920 552 65 150

500 26.4 4.5 36.4 0.84 2.50 1.88 49.0 5.90 25.0 980 588 80 150

630 29.6 4.5 39.9 0.92 2.50 1.96 53.0 7.32 31.5 1060 636 80 190

800 34.0 4.5 44.3 1.00 2.50 2.04 58.0 9.07 40.0 1160 696 100 190

1000 37.8 4.5 48.1 1.08 2.50 2.20 62.0 10.99 50.0 1240 744 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.147 0.161 0.205 0.181 0.49 17.2 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.140 0.155 0.198 0.199 0.54 18.9 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.129 0.144 0.187 0.226 0.62 21.5 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.126 0.140 0.184 0.249 0.68 23.7 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.121 0.135 0.179 0.275 0.75 26.2 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.118 0.132 0.176 0.291 0.79 27.7 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.112 0.127 0.170 0.322 0.88 30.6 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.108 0.123 0.166 0.356 0.97 33.8 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.105 0.120 0.163 0.383 1.05 36.4 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.102 0.117 0.160 0.431 1.18 41.0 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.098 0.113 0.156 0.486 1.33 46.2 71.50 0.256 640 635 608 603.25 942 944 1003

630 0.0283 0.041 0.096 0.110 0.154 0.539 1.47 51.3 90.09 0.256 712 703 676.4 667.85 1071 1070 1117

800 0.0221 0.034 0.093 0.107 0.151 0.608 1.66 57.8 114.40 0.256 781 770 741.95 731.5 1210 1207 1240

1000 0.0176 0.029 0.091 0.105 0.149 0.667 1.82 63.4 143.00 0.256 841 827 798.95 785.65 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

27
8.7/15(17.5) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables a2XWay(p) as
per ieC : 60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 4.5 16.8 0.76 1.60 1.32 27.0 0.74 1.1 540 324 50 80

50 7.9 4.5 17.9 0.76 1.60 1.32 28.0 0.82 1.5 560 336 50 80

70 9.7 4.5 19.7 0.76 1.60 1.32 29.0 0.94 2.1 580 348 65 100

95 11.0 4.5 21.0 0.76 2.00 1.40 32.0 1.13 2.9 640 384 65 100

120 12.6 4.5 22.6 0.76 2.00 1.48 33.0 1.27 3.6 660 396 65 100

150 13.9 4.5 23.9 0.76 2.00 1.48 35.0 1.39 4.5 700 420 65 100

185 15.6 4.5 25.6 0.76 2.00 1.56 37.0 1.57 5.6 740 444 65 100

240 17.6 4.5 27.6 0.76 2.00 1.64 39.0 1.81 7.2 780 468 65 125

300 19.7 4.5 29.7 0.76 2.00 1.64 41.0 2.05 9.0 820 492 65 125

400 22.6 4.5 32.6 0.84 2.50 1.80 45.0 2.56 12.0 900 540 65 150

500 25.6 4.5 35.6 0.84 2.50 1.88 49.0 2.99 15.0 980 588 80 150

630 29.0 4.5 39.3 0.92 2.50 1.96 53.0 3.57 18.9 1060 636 80 190

800 33.0 4.5 43.3 1.00 2.50 2.04 57.0 4.26 24.0 1140 684 100 190

1000 36.8 4.5 47.1 1.08 2.50 2.20 61.0 5.04 30.0 1220 732 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm )2
resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.148 0.163 0.210 0.178 0.49 16.9 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.141 0.156 0.199 0.196 0.53 18.6 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.130 0.144 0.188 0.224 0.61 21.3 6.58 0.256 186 192 176 178 230 236 278

95 0.320 0.411 0.127 0.141 0.185 0.245 0.67 23.3 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.121 0.136 0.180 0.270 0.74 25.7 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.118 0.132 0.176 0.291 0.79 27.7 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.113 0.127 0.171 0.317 0.87 30.2 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.109 0.124 0.167 0.349 0.95 33.2 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.105 0.120 0.163 0.382 1.04 36.3 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.103 0.117 0.161 0.427 1.17 40.6 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.099 0.114 0.157 0.473 1.29 45.0 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.096 0.111 0.155 0.530 1.45 50.4 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.093 0.108 0.151 0.592 1.62 56.3 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.091 0.106 0.149 0.651 1.78 61.9 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

28
12/20(24) kv , single Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWay(p) as
per ieC : 60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 7.0 5.5 19.0 0.76 1.60 1.32 29.0 1.05 1.8 580 348 50 80

50 8.1 5.5 20.1 0.76 1.60 1.40 30.0 1.21 2.5 600 360 50 80

70 9.8 5.5 21.8 0.76 2.00 1.40 33.0 1.51 3.5 660 396 65 100

95 11.3 5.5 23.3 0.76 2.00 1.48 34.0 1.82 4.8 680 408 65 100

120 12.9 5.5 24.9 0.76 2.00 1.48 36.0 2.09 6.0 720 432 65 100

150 13.9 5.5 25.9 0.76 2.00 1.56 37.0 2.37 7.5 740 444 65 100

185 15.9 5.5 27.9 0.76 2.00 1.56 39.0 2.77 9.3 780 468 65 100

240 18.1 5.5 30.1 0.76 2.00 1.64 41.0 3.35 12.0 820 492 65 125

300 19.8 5.5 31.8 0.84 2.50 1.72 44.0 4.10 15.0 880 528 65 125

400 22.9 5.5 34.9 0.84 2.50 1.80 48.0 4.98 20.0 960 576 65 150

500 26.4 5.5 38.4 0.92 2.50 1.88 52.0 6.11 25.0 1040 624 80 150

630 29.6 5.5 41.9 0.92 2.50 2.04 55.0 7.52 31.5 1100 660 80 190

800 34.0 5.5 46.3 1.00 2.50 2.12 60.0 9.29 40.0 1200 720 100 190

1000 37.8 5.5 50.1 1.08 2.50 2.20 64.0 11.19 50.0 1280 768 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.524 0.668 0.151 0.166 0.210 0.158 0.60 28.6 5.01 0.256 166 172 157 159 198 203 238

50 0.387 0.494 0.145 0.160 0.203 0.173 0.65 31.2 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.135 0.150 0.193 0.195 0.74 35.3 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.130 0.144 0.188 0.214 0.81 38.7 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.124 0.139 0.182 0.236 0.89 42.6 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.122 0.136 0.180 0.249 0.94 45.0 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.116 0.130 0.174 0.274 1.03 49.7 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.111 0.126 0.169 0.302 1.14 54.7 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.110 0.125 0.168 0.325 1.22 58.7 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.105 0.120 0.163 0.364 1.37 65.9 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.101 0.116 0.159 0.409 1.54 74.0 71.50 0.256 640 635 608 603.25 942 944 1003

630 0.0283 0.041 0.098 0.113 0.156 0.453 1.71 82.0 90.09 0.256 712 703 676.4 667.85 1071 1070 1117

800 0.0221 0.034 0.095 0.109 0.153 0.509 1.92 92.1 114.40 0.256 781 770 741.95 731.5 1210 1207 1240

1000 0.0176 0.029 0.093 0.107 0.151 0.557 2.10 100.8 143.00 0.256 841 827 798.95 785.65 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

29
12/20(24) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables a2XWay(p) as
per ieC : 60502-2

Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

35 6.8 5.5 18.8 0.76 1.60 1.32 29.0 0.84 1.1 580 348 50 80

50 7.9 5.5 19.9 0.76 1.60 1.40 30.0 0.93 1.5 600 360 50 80

70 9.7 5.5 21.7 0.76 2.00 1.40 32.0 1.12 2.1 640 384 65 100

95 11.0 5.5 23.0 0.76 2.00 1.48 34.0 1.26 2.9 680 408 65 100

120 12.6 5.5 24.6 0.76 2.00 1.48 35.0 1.39 3.6 700 420 65 100

150 13.9 5.5 25.9 0.76 2.00 1.56 37.0 1.53 4.5 740 444 65 100

185 15.6 5.5 27.6 0.76 2.00 1.56 39.0 1.70 5.6 780 468 65 100

240 17.6 5.5 29.6 0.76 2.00 1.64 41.0 1.95 7.2 820 492 65 125

300 19.7 5.5 31.7 0.84 2.50 1.72 44.0 2.34 9.0 880 528 65 125

400 22.6 5.5 34.6 0.84 2.50 1.80 47.0 2.72 12.0 940 564 65 150

500 25.6 5.5 37.6 0.92 2.50 1.88 51.0 3.19 15.0 1020 612 80 150

630 29.0 5.5 41.3 0.92 2.50 2.04 55.0 3.77 18.9 1100 660 80 190

800 33.0 5.5 45.3 1.00 2.50 2.12 59.0 4.47 24.0 1180 708 100 190

1000 36.8 5.5 49.1 1.08 2.50 2.20 63.0 5.26 30.0 1260 756 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

35 0.868 1.113 0.153 0.167 0.215 0.155 0.59 28.1 3.29 0.256 129 134 122 123 154 157 185

50 0.641 0.822 0.146 0.161 0.204 0.170 0.64 30.8 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.136 0.150 0.194 0.194 0.73 35.1 6.58 0.256 186 192 176 178 230 236 278

95 0.320 0.411 0.131 0.145 0.189 0.211 0.79 38.2 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.125 0.140 0.183 0.232 0.87 41.9 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.122 0.136 0.180 0.249 0.94 45.0 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.116 0.131 0.174 0.271 1.02 49.0 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.112 0.127 0.170 0.296 1.12 53.6 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.110 0.125 0.168 0.323 1.22 58.5 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.106 0.120 0.164 0.360 1.36 65.2 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.102 0.117 0.160 0.399 1.50 72.2 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.099 0.114 0.157 0.445 1.68 80.6 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.096 0.110 0.154 0.496 1.87 89.8 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.093 0.108 0.151 0.544 2.05 98.5 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

30
18/30(36) kv , single Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWay(p) as
per ieC : 60502-2
Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

50 8.1 8.0 25.1 0.76 2.00 1.56 36.0 1.61 2.5 720 432 50 80

70 9.8 8.0 26.8 0.76 2.00 1.56 38.0 1.87 3.5 760 456 65 100

95 11.3 8.0 28.3 0.76 2.00 1.64 40.0 2.17 4.8 800 480 65 100

120 12.9 8.0 29.9 0.76 2.00 1.64 41.0 2.46 6.0 820 492 65 100

150 13.9 8.0 30.9 0.84 2.50 1.72 44.0 2.89 7.5 880 528 65 100

185 15.9 8.0 32.9 0.84 2.50 1.80 46.0 3.34 9.3 920 552 65 100

240 18.1 8.0 35.1 0.84 2.50 1.80 48.0 3.92 12.0 960 576 65 125

300 19.8 8.0 36.8 0.92 2.50 1.88 50.0 4.58 15.0 1000 600 65 125

400 22.9 8.0 39.9 0.92 2.50 1.96 53.0 5.49 20.0 1060 636 65 150

500 26.4 8.0 43.4 1.00 2.50 2.04 57.0 6.65 25.0 1140 684 80 150

630 29.6 8.0 46.9 1.00 2.50 2.12 61.0 8.08 31.5 1220 732 80 190

800 34.0 8.0 51.3 1.08 2.50 2.28 66.0 9.92 40.0 1320 792 100 190

1000 37.8 8.0 55.1 1.16 2.50 2.36 70.0 11.85 50.0 1400 840 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

50 0.387 0.494 0.157 0.172 0.215 0.136 0.77 55.4 7.15 0.256 196 203 186 188 238 243 286

70 0.268 0.342 0.145 0.160 0.203 0.152 0.86 61.8 10.01 0.256 239 246 227 229 296 303 356

95 0.193 0.247 0.139 0.154 0.197 0.165 0.93 67.3 13.59 0.256 285 293 271 274 361 369 434

120 0.153 0.196 0.133 0.148 0.191 0.180 1.02 73.5 17.16 0.256 323 332 308 311 417 426 500

150 0.124 0.159 0.132 0.147 0.190 0.190 1.07 77.2 21.45 0.256 361 366 343 347 473 481 559

185 0.0991 0.128 0.126 0.141 0.184 0.208 1.17 84.5 26.46 0.256 406 410 387 391 543 550 637

240 0.0754 0.098 0.121 0.135 0.179 0.227 1.28 92.4 34.32 0.256 469 470 447 453 641 647 745

300 0.0601 0.079 0.118 0.132 0.176 0.243 1.37 98.8 42.90 0.256 526 524 504 510 735 739 846

400 0.0470 0.063 0.112 0.127 0.170 0.270 1.53 110.0 57.20 0.256 590 572 564 571 845 837 938

500 0.0366 0.050 0.108 0.122 0.166 0.301 1.70 122.6 71.50 0.256 640 635 608 603.25 942 944 1003

630 0.0283 0.041 0.104 0.119 0.163 0.332 1.87 135.0 90.09 0.256 712 703 676.4 667.85 1071 1070 1117

800 0.0221 0.034 0.101 0.115 0.159 0.370 2.09 150.7 114.40 0.256 781 770 741.95 731.5 1210 1207 1240

1000 0.0176 0.029 0.098 0.112 0.156 0.404 2.28 164.3 143.00 0.256 841 827 798.95 785.65 1332 1328 1344

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

31
18/30 (36) kv , single Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
aluminium round Wire armoured and pvC overall sheaThed , sCreened Cables a2XWay(p) as
per ieC : 60502-2
Nominal Nominal Nominal Nominal Min. Nominal Minimum Nominal Approx. Max. Min. bending radius Nominal duct diameter(mm)
conductor conductor insulation diameter thickness of diameter thickness of overall mass pulling
area diameter thickness over Inner sheath of armour Over sheath diameter (Kg/m) tension During Set in
(mm2) (mm) (mm) insulation (mm2) wire (mm) (mm) (kN) pulling position
(mm) (mm) (mm) (mm) (mm) (mm)

50 7.9 8.0 24.9 0.76 2.00 1.56 36.0 1.31 1.5 720 432 50 80

70 9.7 8.0 26.7 0.76 2.00 1.56 38.0 1.46 2.1 760 456 65 100

95 11.0 8.0 28.0 0.76 2.00 1.64 39.0 1.60 2.9 780 468 65 100

120 12.6 8.0 29.6 0.76 2.00 1.64 41.0 1.75 3.6 820 492 65 100

150 13.9 8.0 30.9 0.84 2.50 1.72 43.0 2.03 4.5 860 516 65 100

185 15.6 8.0 32.6 0.84 2.50 1.80 45.0 2.24 5.6 900 540 65 100

240 17.6 8.0 34.6 0.84 2.50 1.80 47.0 2.49 7.2 940 564 65 125

300 19.7 8.0 36.7 0.92 2.50 1.88 50.0 2.80 9.0 1000 600 65 125

400 22.6 8.0 39.6 0.92 2.50 1.96 53.0 3.21 12.0 1060 636 65 150

500 25.6 8.0 42.6 1.00 2.50 2.04 56.0 3.71 15.0 1120 672 80 150

630 29.0 8.0 46.3 1.00 2.50 2.12 60.0 4.30 18.9 1200 720 80 190

800 33.0 8.0 50.3 1.08 2.50 2.28 65.0 5.06 24.0 1300 780 100 190

1000 36.8 8.0 54.1 1.16 2.50 2.36 69.0 5.88 30.0 1380 828 100 190

eleCTriCal CharaCTerisTiCs CurrenT raTings (amps)


Nominal Maximum Cond. AC Inductive reactance at Capacitance Charging Dielectric Fault current Buried direct in In single-way In air
conductor Conductor resistance 50Hz and 90C (F/km) current loss per carrying the ground ducts In
area DC at 50Hz per phase phase capacity for 1
(mm2) resistance & 90C (A/km) (W/km) second
at 20C (Ohm/
(Ohm/km) km) Trefoil Flat Flat Cond. Screen Trefoil Flat Trefoil Flat Trefoil Flat Flat
touching touching spaced (kA) (kA) spaced ducts touching touching spaced
(Ohm/ (Ohm/ (Ohm/ ducts
km) km) km)

50 0.641 0.822 0.158 0.173 0.216 0.133 0.50 24.1 4.70 0.256 152 157 144 146 184 189 222

70 0.443 0.568 0.146 0.160 0.204 0.150 0.57 27.1 6.58 0.256 186 192 176 178 230 236 278

95 0.320 0.411 0.140 0.155 0.198 0.162 0.61 29.3 8.93 0.256 221 229 210 213 280 287 338

120 0.253 0.325 0.134 0.149 0.192 0.177 0.67 32.0 11.28 0.256 252 260 240 242 324 332 391

150 0.206 0.265 0.132 0.146 0.190 0.189 0.71 34.1 14.10 0.256 281 288 267 271 368 376 440

185 0.1640 0.211 0.126 0.141 0.185 0.204 0.77 36.9 17.39 0.256 317 324 303 307 424 432 504

240 0.1250 0.161 0.122 0.136 0.180 0.222 0.84 40.2 22.56 0.256 367 373 351 356 502 511 593

300 0.1000 0.130 0.118 0.132 0.176 0.241 0.91 43.6 28.20 0.256 414 419 397 402 577 586 677

400 0.0778 0.102 0.113 0.127 0.171 0.267 1.00 48.2 37.60 0.256 470 466 451 457 673 676 769

500 0.0605 0.080 0.109 0.123 0.167 0.293 1.11 53.0 47.00 0.256 519 520 493 494 757 764 837

630 0.0469 0.063 0.105 0.119 0.163 0.325 1.23 58.9 59.22 0.256 586 584 557 555 876 882 950

800 0.0367 0.051 0.101 0.116 0.159 0.361 1.36 65.2 75.20 0.256 655 651 622 618 1005 1009 1070

1000 0.0291 0.043 0.099 0.113 0.157 0.394 1.49 71.3 94.00 0.256 723 715 687 679 1138 1140 1193

NOTE :
Data for Water tight conductor , Steel/ Aluminium tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

32
3.6/6 (7.2) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 2.5 13.1 0.76 2.00 1.64 41.0 3.06 1.8 615 492 80

50 8.1 2.5 14.2 0.84 2.50 1.80 45.0 3.89 2.5 675 540 80

70 9.8 2.5 15.9 0.92 2.50 1.88 49.0 4.80 3.5 735 588 80

95 11.3 2.5 17.4 0.92 2.50 1.96 52.0 5.69 4.8 780 624 100

120 12.9 2.5 19.0 1.00 2.50 2.04 56.0 6.69 6.0 840 672 100

150 13.9 2.5 20.0 1.00 2.50 2.12 58.0 7.62 7.5 870 696 100

185 15.9 2.5 22.0 1.08 2.50 2.20 63.0 8.94 9.3 945 756 100

240 18.1 2.6 24.4 1.16 2.50 2.36 69.0 11.00 12.0 1035 828 125

300 19.8 2.8 26.5 1.24 3.15 2.60 75.0 13.80 15.0 1125 900 125

400 22.9 3.0 30.0 1.40 3.15 2.84 84.0 16.92 20.0 1260 1008 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.524 0.668 0.109 0.283 0.32 4.61 5.01 0.768 154 134 172

50 0.387 0.494 0.104 0.314 0.36 5.12 7.15 0.768 181 158 205

70 0.268 0.342 0.096 0.362 0.41 5.90 10.01 0.768 220 194 253

95 0.193 0.247 0.093 0.403 0.46 6.56 13.59 0.768 263 232 307

120 0.153 0.196 0.090 0.449 0.51 7.32 17.16 0.768 298 264 352

150 0.124 0.159 0.088 0.477 0.54 7.77 21.45 0.768 332 296 397

185 0.0991 0.128 0.084 0.533 0.60 8.68 26.46 0.768 374 335 453

240 0.0754 0.099 0.083 0.573 0.65 9.33 34.32 0.768 431 387 529

300 0.0601 0.080 0.082 0.580 0.66 9.45 42.90 0.768 482 435 599

400 0.0470 0.064 0.080 0.618 0.70 10.06 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

33
3.6/6 (7.2)kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
a2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 2.5 12.90 0.76 2.00 1.64 40.0 2.42 1.1 600 480 80

50 8.1 2.5 14.00 0.84 2.50 1.80 44.0 3.06 1.5 660 528 80

70 9.8 2.5 15.80 0.92 2.50 1.88 49.0 3.53 2.1 735 588 80

95 11.3 2.5 17.10 0.92 2.50 1.96 51.0 4.04 2.9 765 612 100

120 12.9 2.5 18.70 1.00 2.50 2.04 55.0 4.57 3.6 825 660 100

150 13.9 2.5 20.00 1.00 2.50 2.12 58.0 5.00 4.5 870 696 100

185 15.9 2.5 21.70 1.08 2.50 2.20 62.0 5.72 5.6 930 744 100

240 18.1 2.6 23.90 1.16 2.50 2.36 68.0 6.62 7.2 1020 816 125

300 19.8 2.8 26.40 1.24 3.15 2.60 75.0 8.50 9.0 1125 900 125

400 22.9 3.0 29.70 1.40 3.15 2.84 83.0 10.14 12.0 1245 996 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.868 1.113 0.110 0.278 0.52 12.56 3.29 0.768 119 104 133

50 0.641 0.822 0.105 0.309 0.58 13.97 4.70 0.768 140 123 159

70 0.443 0.568 0.097 0.359 0.68 16.26 6.58 0.768 171 150 196

95 0.32 0.411 0.093 0.396 0.75 17.91 8.93 0.768 204 180 238

120 0.253 0.325 0.090 0.441 0.83 19.94 11.28 0.768 232 206 274

150 0.206 0.265 0.088 0.477 0.90 21.59 14.10 0.768 259 231 309

185 0.164 0.211 0.085 0.525 0.99 23.74 17.39 0.768 293 262 354

240 0.125 0.162 0.083 0.561 1.06 25.37 22.56 0.768 338 304 415

300 0.1 0.130 0.082 0.578 1.09 26.13 28.20 0.768 380 343 472

400 0.0778 0.102 0.080 0.611 1.15 27.63 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

34
6/10 (12) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed , galvanised
sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWy(p) as per ieC :
60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 3.4 14.80 0.84 2.50 1.80 46.0 3.70 1.8 690 552 80

50 8.1 3.4 15.90 0.92 2.50 1.88 49.0 4.29 2.5 735 588 80

70 9.8 3.4 17.60 0.92 2.50 1.96 52.0 5.15 3.5 780 624 80

95 11.3 3.4 19.05 1.00 2.50 2.12 56.0 6.17 4.8 840 672 100

120 12.9 3.4 20.70 1.08 2.50 2.20 60.0 7.19 6.0 900 720 100

150 13.9 3.4 21.70 1.08 2.50 2.28 62.0 8.06 7.5 930 744 100

185 15.9 3.4 23.70 1.16 2.50 2.36 67.0 9.47 9.3 1005 804 100

240 18.1 3.4 25.85 1.24 3.15 2.52 73.0 12.15 12.0 1095 876 125

300 19.8 3.4 27.60 1.32 3.15 2.68 78.0 14.15 15.0 1170 936 125

400 22.9 3.4 30.70 1.40 3.15 2.84 85.0 17.17 20.0 1275 1020 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.524 0.668 0.116 0.222 0.42 10.02 5.01 0.768 154 134 172

50 0.387 0.494 0.111 0.245 0.46 11.07 7.15 0.768 181 158 205

70 0.268 0.342 0.102 0.280 0.53 12.68 10.01 0.768 220 194 253

95 0.193 0.247 0.098 0.310 0.59 14.04 13.59 0.768 263 232 307

120 0.153 0.196 0.095 0.345 0.65 15.59 17.16 0.768 298 264 352

150 0.124 0.159 0.093 0.365 0.69 16.53 21.45 0.768 332 296 397

185 0.0991 0.128 0.089 0.407 0.77 18.39 26.46 0.768 374 335 453

240 0.0754 0.099 0.086 0.451 0.85 20.40 34.32 0.768 431 387 529

300 0.0601 0.080 0.084 0.487 0.92 22.03 42.90 0.768 482 435 599

400 0.0470 0.064 0.081 0.551 1.04 24.91 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

35
6/10 (12) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
a2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 3.4 14.60 0.84 2.50 1.80 45.0 3.09 1.1 675 540 80

50 8.1 3.4 15.70 0.92 2.50 1.88 48.0 3.41 1.5 720 576 80

70 9.8 3.4 17.50 0.92 2.50 1.96 52.0 3.93 2.1 780 624 80

95 11.3 3.4 18.80 1.00 2.50 2.12 55.0 4.48 2.9 825 660 100

120 12.9 3.4 20.40 1.08 2.50 2.20 59.0 5.07 3.6 885 708 100

150 13.9 3.4 21.70 1.08 2.50 2.28 62.0 5.51 4.5 930 744 100

185 15.9 3.4 23.40 1.16 2.50 2.36 66.0 6.21 5.6 990 792 100

240 18.1 3.4 25.40 1.24 3.15 2.52 72.0 7.85 7.2 1080 864 125

300 19.8 3.4 27.50 1.32 3.15 2.68 78.0 8.84 9.0 1170 936 125

400 22.9 3.4 30.40 1.40 3.15 2.84 84.0 10.31 12.0 1260 1008 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.868 1.113 0.117 0.217 0.41 9.83 3.29 0.768 119 104 133

50 0.641 0.822 0.112 0.240 0.45 10.88 4.70 0.768 140 123 159

70 0.443 0.568 0.103 0.278 0.52 12.58 6.58 0.768 171 150 196

95 0.32 0.411 0.099 0.305 0.58 13.81 8.93 0.768 204 180 238

120 0.253 0.325 0.095 0.338 0.64 15.31 11.28 0.768 232 206 274

150 0.206 0.265 0.093 0.365 0.69 16.53 14.10 0.768 259 231 309

185 0.164 0.211 0.089 0.400 0.75 18.11 17.39 0.768 293 262 354

240 0.125 0.162 0.087 0.442 0.83 19.98 22.56 0.768 338 304 415

300 0.1 0.130 0.084 0.485 0.91 21.93 28.20 0.768 380 343 472

400 0.0778 0.102 0.081 0.544 1.03 24.63 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

36
8.7/15(17.5) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 4.5 17.00 0.92 2.50 1.96 51.0 4.28 1.8 765 612 80

50 8.1 4.5 18.10 1.00 2.50 2.04 54.0 4.87 2.5 810 648 80

70 9.8 4.5 19.80 1.00 2.50 2.12 58.0 5.71 3.5 870 696 80

95 11.3 4.5 21.25 1.08 2.50 2.20 61.0 6.78 4.8 915 732 100

120 12.9 4.5 22.90 1.16 2.50 2.28 65.0 7.81 6.0 975 780 100

150 13.9 4.5 23.90 1.16 2.50 2.36 67.0 8.69 7.5 1005 804 100

185 15.9 4.5 25.90 1.24 3.15 2.52 74.0 10.89 9.3 1110 888 100

240 18.1 4.5 28.05 1.32 3.15 2.68 79.0 12.88 12.0 1185 948 125

300 19.8 4.5 29.80 1.40 3.15 2.76 83.0 14.99 15.0 1245 996 125

400 22.9 4.5 32.90 1.48 3.15 3.00 90.0 18.02 20.0 1350 1080 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.524 0.668 0.124 0.181 0.49 17.22 5.01 0.768 154 134 172

50 0.387 0.494 0.119 0.199 0.54 18.91 7.15 0.768 181 158 205

70 0.268 0.342 0.109 0.226 0.62 21.49 10.01 0.768 220 194 253

95 0.193 0.247 0.105 0.249 0.68 23.68 13.59 0.768 263 232 307

120 0.153 0.196 0.101 0.275 0.75 26.16 17.16 0.768 298 264 352

150 0.124 0.159 0.099 0.291 0.79 27.66 21.45 0.768 332 296 397

185 0.0991 0.128 0.094 0.322 0.88 30.64 26.46 0.768 374 335 453

240 0.0754 0.099 0.091 0.356 0.97 33.85 34.32 0.768 431 387 529

300 0.0601 0.080 0.089 0.383 1.05 36.44 42.90 0.768 482 435 599

400 0.0470 0.064 0.085 0.431 1.18 41.04 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

37
8.7/15 (17.5) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
a2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 4.5 16.80 0.92 2.50 1.96 51.0 3.66 1.1 765 612 80

50 8.1 4.5 17.90 1.00 2.50 2.04 53.0 4.00 1.5 795 636 80

70 9.8 4.5 19.70 1.00 2.50 2.12 57.0 4.52 2.1 855 684 80

95 11.3 4.5 21.00 1.08 2.50 2.20 61.0 5.12 2.9 915 732 100

120 12.9 4.5 22.60 1.16 2.50 2.28 64.0 5.68 3.6 960 768 100

150 13.9 4.5 23.90 1.16 2.50 2.36 67.0 6.14 4.5 1005 804 100

185 15.9 4.5 25.60 1.24 3.15 2.52 73.0 7.60 5.6 1095 876 100

240 18.1 4.5 27.60 1.32 3.15 2.68 78.0 8.58 7.2 1170 936 125

300 19.8 4.5 29.70 1.40 3.15 2.76 83.0 9.68 9.0 1245 996 125

400 22.9 4.5 32.60 1.48 3.15 3.00 90.0 11.25 12.0 1350 1080 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.868 1.113 0.126 0.178 0.49 16.91 3.29 0.768 119 104 133

50 0.641 0.822 0.120 0.196 0.53 18.60 4.70 0.768 140 123 159

70 0.443 0.568 0.110 0.224 0.61 21.34 6.58 0.768 171 150 196

95 0.32 0.411 0.106 0.245 0.67 23.30 8.93 0.768 204 180 238

120 0.253 0.325 0.102 0.270 0.74 25.71 11.28 0.768 232 206 274

150 0.206 0.265 0.099 0.291 0.79 27.66 14.10 0.768 259 231 309

185 0.164 0.211 0.095 0.317 0.87 30.20 17.39 0.768 293 262 354

240 0.125 0.162 0.092 0.349 0.95 33.18 22.56 0.768 338 304 415

300 0.1 0.130 0.089 0.382 1.04 36.30 28.20 0.768 380 343 472

400 0.0778 0.102 0.086 0.427 1.17 40.59 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

38
12/20 (24) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm )2
(mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 5.5 19.00 1.00 2.50 2.04 56.0 4.79 1.8 840 672 80

50 8.1 5.5 20.10 1.08 2.50 2.12 58.0 5.43 2.5 870 696 80

70 9.8 5.5 21.80 1.08 2.50 2.28 62.0 6.36 3.5 930 744 80

95 11.3 5.5 23.25 1.16 2.50 2.36 66.0 7.39 4.8 990 792 100

120 12.9 5.5 24.90 1.16 3.15 2.44 71.0 9.11 6.0 1065 852 100

150 13.9 5.5 25.90 1.24 3.15 2.52 74.0 10.08 7.5 1110 888 100

185 15.9 5.5 27.90 1.32 3.15 2.68 78.0 11.58 9.3 1170 936 100

240 18.1 5.5 30.05 1.40 3.15 2.76 83.0 13.62 12.0 1245 996 125

300 19.8 5.5 31.80 1.40 3.15 2.92 88.0 15.71 15.0 1320 1056 125

400 22.9 5.5 34.90 1.56 3.15 3.08 89.0 17.45 20.0 1335 1068 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm2) DC resistance 50Hz and 90C 90C (Ohm/ phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.524 0.668 0.131 0.158 0.60 28.57 5.01 0.768 154 134 172

50 0.387 0.494 0.125 0.173 0.65 31.23 7.15 0.768 181 158 205

70 0.268 0.342 0.115 0.195 0.74 35.31 10.01 0.768 220 194 253

95 0.193 0.247 0.111 0.214 0.81 38.75 13.59 0.768 263 232 307

120 0.153 0.196 0.106 0.236 0.89 42.64 17.16 0.768 298 264 352

150 0.124 0.159 0.104 0.249 0.94 44.99 21.45 0.768 332 296 397

185 0.0991 0.128 0.099 0.274 1.03 49.67 26.46 0.768 374 335 453

240 0.0754 0.099 0.095 0.302 1.14 54.68 34.32 0.768 431 387 529

300 0.0601 0.080 0.093 0.325 1.22 58.74 42.90 0.768 482 435 599

400 0.0470 0.064 0.089 0.364 1.37 65.92 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

39
12/20 (24) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
a2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm )2
(mm) (mm) (mm) pulling position (mm)
(mm) (mm)

35 7.0 5.5 18.80 1.00 2.50 2.04 55.0 4.17 1.1 825 660 80

50 8.1 5.5 19.90 1.08 2.50 2.12 58.0 4.52 1.5 870 696 80

70 9.8 5.5 21.70 1.08 2.50 2.28 62.0 5.13 2.1 930 744 80

95 11.3 5.5 23.00 1.16 2.50 2.36 65.0 5.69 2.9 975 780 100

120 12.9 5.5 24.60 1.16 3.15 2.44 70.0 6.95 3.6 1050 840 100

150 13.9 5.5 25.90 1.24 3.15 2.52 74.0 7.54 4.5 1110 888 100

185 15.9 5.5 27.60 1.32 3.15 2.68 78.0 8.29 5.6 1170 936 100

240 18.1 5.5 29.60 1.40 3.15 2.76 82.0 9.32 7.2 1230 984 125

300 19.8 5.5 31.70 1.40 3.15 2.92 87.0 10.40 9.0 1305 1044 125

400 22.9 5.5 34.60 1.56 3.15 3.08 88.0 10.65 12.0 1320 1056 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm2) DC resistance 50Hz and 90C 90C (Ohm/ phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

35 0.868 1.113 0.133 0.155 0.59 28.08 3.29 0.768 119 104 133

50 0.641 0.822 0.126 0.170 0.64 30.75 4.70 0.768 140 123 159

70 0.443 0.568 0.116 0.194 0.73 35.07 6.58 0.768 171 150 196

95 0.32 0.411 0.111 0.211 0.79 38.16 8.93 0.768 204 180 238

120 0.253 0.325 0.107 0.232 0.87 41.93 11.28 0.768 232 206 274

150 0.206 0.265 0.104 0.249 0.94 44.99 14.10 0.768 259 231 309

185 0.164 0.211 0.100 0.271 1.02 48.97 17.39 0.768 293 262 354

240 0.125 0.162 0.096 0.296 1.12 53.63 22.56 0.768 338 304 415

300 0.1 0.130 0.093 0.323 1.22 58.51 28.20 0.768 380 343 472

400 0.0778 0.102 0.089 0.360 1.36 65.23 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

40
18/30 (36) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables 2XWy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

50 8.1 8.0 25.20 1.24 3.15 2.52 72.0 7.72 2.5 1080 864 80

70 9.8 8.0 26.90 1.24 3.15 2.60 76.0 8.69 3.5 1140 912 80

95 11.3 8.0 28.35 1.32 3.15 2.68 80.0 9.85 4.8 1200 960 100

120 12.9 8.0 30.00 1.40 3.15 2.76 84.0 10.93 6.0 1260 1008 100

150 13.9 8.0 31.00 1.40 3.15 2.84 86.0 11.94 7.5 1290 1032 100

185 15.9 8.0 33.00 1.48 3.15 3.00 91.0 13.62 9.3 1365 1092 100

240 18.1 8.0 35.15 1.56 3.15 3.08 89.0 14.34 12.0 1335 1068 125

300 19.8 8.0 36.90 1.64 3.15 3.24 93.0 16.43 15.0 1395 1116 125

400 22.9 8.0 40.00 1.72 3.15 3.40 100.0 19.32 20.0 1500 1200 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

50 0.387 0.494 0.140 0.136 0.77 55.35 7.15 0.768 181 158 205

70 0.268 0.342 0.129 0.152 0.86 61.84 10.01 0.768 220 194 253

95 0.193 0.247 0.123 0.165 0.93 67.30 13.59 0.768 263 232 307

120 0.153 0.196 0.118 0.180 1.02 73.46 17.16 0.768 298 264 352

150 0.124 0.159 0.115 0.190 1.07 77.16 21.45 0.768 332 296 397

185 0.0991 0.128 0.110 0.208 1.17 84.52 26.46 0.768 374 335 453

240 0.0754 0.099 0.105 0.227 1.28 92.38 34.32 0.768 431 387 529

300 0.0601 0.080 0.103 0.243 1.37 98.75 42.90 0.768 482 435 599

400 0.0470 0.064 0.098 0.270 1.53 109.98 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

41
18/30 (36) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel round Wire armoured and pvC overall sheaThed , sCreened Cables
a2XWy(p) as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Min. thickness Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal
ductor area conductor insulation diameter over of Inner diameter of thickness of overall mass tension duct
(mm2) diameter thickness insulation sheath armour Over sheath diameter (Kg/m) (kN) During Set in diameter
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position (mm)
(mm) (mm)

50 8.1 8.0 25.00 1.24 3.15 2.52 72.0 6.82 1.5 1080 864 80

70 9.8 8.0 26.80 1.24 3.15 2.60 76.0 7.50 2.1 1140 912 80

95 11.3 8.0 28.10 1.32 3.15 2.68 79.0 8.05 2.9 1185 948 100

120 12.9 8.0 29.70 1.40 3.15 2.76 83.0 8.83 3.6 1245 996 100

150 13.9 8.0 31.00 1.40 3.15 2.84 86.0 9.39 4.5 1290 1032 100

185 15.9 8.0 32.70 1.48 3.15 3.00 90.0 10.32 5.6 1350 1080 100

240 18.1 8.0 34.70 1.56 3.15 3.08 88.0 10.03 7.2 1320 1056 125

300 19.8 8.0 36.80 1.64 3.15 3.24 93.0 11.13 9.0 1395 1116 125

400 22.9 8.0 39.70 1.72 3.15 3.40 100.0 12.48 12.0 1500 1200 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC reactance Capacitance Charging Dielectric Fault current Buried direct In a Buried duct In Air
conductor Conductor resistance at at 50Hz and (F/km) current per loss per carrying capacity in ground
area (mm ) DC resistance 50Hz and 90C 90C (Ohm/
2
phase phase for 1 second
at 20C (Ohm/km) km) (A/km) (W/km)
(Ohm/km)
Cond. (kA) Copper
Tape Screen
(kA)

50 0.641 0.822 0.141 0.134 0.76 54.58 4.70 0.768 140 123 159

70 0.443 0.568 0.129 0.151 0.85 61.46 6.58 0.768 171 150 196

95 0.32 0.411 0.124 0.163 0.92 66.36 8.93 0.768 204 180 238

120 0.253 0.325 0.119 0.178 1.00 72.34 11.28 0.768 232 206 274

150 0.206 0.265 0.115 0.190 1.07 77.16 14.10 0.768 259 231 309

185 0.164 0.211 0.110 0.205 1.16 83.42 17.39 0.768 293 262 354

240 0.125 0.162 0.106 0.223 1.26 90.74 22.56 0.768 338 304 415

300 0.1 0.130 0.103 0.242 1.37 98.39 28.20 0.768 380 343 472

400 0.0778 0.102 0.098 0.267 1.51 108.89 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

42
3.6/6 (7.2) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables 2Xfy(p) as
per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 2.5 13.1 0.76 4 x 0.8 1.64 39.0 2.38 1.8 585 468 80

50 8.1 2.5 14.2 0.84 4 x 0.8 1.72 41.0 2.86 2.5 615 492 80

70 9.8 2.5 15.9 0.92 4 x 0.8 1.80 45.0 3.65 3.5 675 540 80

95 11.3 2.5 17.4 0.92 4 x 0.8 1.88 49.0 4.46 4.8 735 588 100

120 12.9 2.5 19.0 1.00 4 x 0.8 1.96 53.0 5.31 6.0 795 636 100

150 13.9 2.5 20.0 1.00 4 x 0.8 2.04 55.0 6.21 7.5 825 660 100

185 15.9 2.5 22.0 1.08 4 x 0.8 2.12 60.0 7.40 9.3 900 720 100

240 18.1 2.6 24.4 1.16 4 x 0.8 2.28 65.0 9.28 12.0 975 780 125

300 19.8 2.8 26.5 1.24 4 x 0.8 2.44 70.0 11.21 15.0 1050 840 125

400 22.9 3.0 30.0 1.40 4 x 0.8 2.68 79.0 13.99 20.0 1185 948 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.524 0.668 0.109 0.283 0.32 4.61 5.01 0.768 154 134 172

50 0.387 0.494 0.104 0.314 0.36 5.12 7.15 0.768 181 158 205

70 0.268 0.342 0.096 0.362 0.41 5.90 10.01 0.768 220 194 253

95 0.193 0.247 0.093 0.403 0.46 6.56 13.59 0.768 263 232 307

120 0.153 0.196 0.090 0.449 0.51 7.32 17.16 0.768 298 264 352

150 0.124 0.159 0.088 0.477 0.54 7.77 21.45 0.768 332 296 397

185 0.0991 0.128 0.084 0.533 0.60 8.68 26.46 0.768 374 335 453

240 0.0754 0.099 0.083 0.573 0.65 9.33 34.32 0.768 431 387 529

300 0.0601 0.080 0.082 0.580 0.66 9.45 42.90 0.768 482 435 599

400 0.0470 0.064 0.080 0.618 0.70 10.06 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

43
3.6/6 (7.2) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables a2Xfy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 2.5 12.9 0.76 4 x 0.8 1.64 38.0 1.77 1.1 570 456 80

50 8.1 2.5 14.0 0.84 4 x 0.8 1.72 41.0 2.03 1.5 615 492 80

70 9.8 2.5 15.8 0.92 4 x 0.8 1.80 45.0 2.44 2.1 675 540 80

95 11.3 2.5 17.1 0.92 4 x 0.8 1.88 48.0 2.79 2.9 720 576 100

120 12.9 2.5 18.7 1.00 4 x 0.8 1.96 52.0 3.23 3.6 780 624 100

150 13.9 2.5 20.0 1.00 4 x 0.8 2.04 55.0 3.66 4.5 825 660 100

185 15.9 2.5 21.7 1.08 4 x 0.8 2.12 59.0 4.18 5.6 885 708 100

240 18.1 2.6 23.9 1.16 4 x 0.8 2.28 64.0 4.95 7.2 960 768 125

300 19.8 2.8 26.4 1.24 4 x 0.8 2.44 70.0 5.90 9.0 1050 840 125

400 22.9 3.0 29.7 1.40 4 x 0.8 2.68 78.0 7.22 12.0 1170 936 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.868 1.113 0.110 0.278 0.31 4.52 3.29 0.768 119 104 133

50 0.641 0.822 0.105 0.309 0.35 5.03 4.70 0.768 140 123 159

70 0.443 0.568 0.097 0.359 0.41 5.85 6.58 0.768 171 150 196

95 0.32 0.411 0.093 0.396 0.45 6.45 8.93 0.768 204 180 238

120 0.253 0.325 0.090 0.441 0.50 7.18 11.28 0.768 232 206 274

150 0.206 0.265 0.088 0.477 0.54 7.77 14.10 0.768 259 231 309

185 0.164 0.211 0.085 0.525 0.59 8.55 17.39 0.768 293 262 354

240 0.125 0.162 0.083 0.561 0.63 9.13 22.56 0.768 338 304 415

300 0.1 0.130 0.082 0.578 0.65 9.41 28.20 0.768 380 343 472

400 0.0778 0.102 0.080 0.611 0.69 9.95 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

44
6/10 (12) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed , galvanised
sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables 2Xfy(p) as per ieC :
60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 3.4 14.80 0.84 4 x 0.8 1.72 42.0 2.66 1.8 630 504 80

50 8.1 3.4 15.90 0.92 4 x 0.8 1.80 45.0 3.15 2.5 675 540 80

70 9.8 3.4 17.60 0.92 4 x 0.8 1.88 49.0 3.89 3.5 735 588 80

95 11.3 3.4 19.05 1.00 4 x 0.8 1.96 52.0 4.77 4.8 780 624 100

120 12.9 3.4 20.70 1.08 4 x 0.8 2.04 56.0 5.70 6.0 840 672 100

150 13.9 3.4 21.70 1.08 4 x 0.8 2.20 59.0 6.54 7.5 885 708 100

185 15.9 3.4 23.70 1.16 4 x 0.8 2.28 64.0 7.77 9.3 960 768 100

240 18.1 3.4 25.85 1.24 4 x 0.8 2.36 69.0 9.59 12.0 1035 828 125

300 19.8 3.4 27.60 1.32 4 x 0.8 2.52 73.0 11.47 15.0 1095 876 125

400 22.9 3.4 30.70 1.40 4 x 0.8 2.68 80.0 14.15 20.0 1200 960 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm ) DC resistance 50Hz and 90C
2
at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.524 0.668 0.116 0.222 0.42 10.02 5.01 0.768 154 134 172

50 0.387 0.494 0.111 0.245 0.46 11.07 7.15 0.768 181 158 205

70 0.268 0.342 0.102 0.280 0.53 12.68 10.01 0.768 220 194 253

95 0.193 0.247 0.098 0.310 0.59 14.04 13.59 0.768 263 232 307

120 0.153 0.196 0.095 0.345 0.65 15.59 17.16 0.768 298 264 352

150 0.124 0.159 0.093 0.365 0.69 16.53 21.45 0.768 332 296 397

185 0.0991 0.128 0.089 0.407 0.77 18.39 26.46 0.768 374 335 453

240 0.0754 0.099 0.086 0.451 0.85 20.40 34.32 0.768 431 387 529

300 0.0601 0.080 0.084 0.487 0.92 22.03 42.90 0.768 482 435 599

400 0.0470 0.064 0.081 0.551 1.04 24.91 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

45
6/10 (12) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables a2Xfy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 3.4 14.60 0.84 4 x 0.8 1.72 42.0 2.02 1.1 630 504 80

50 8.1 3.4 15.70 0.92 4 x 0.8 1.80 45.0 2.27 1.5 675 540 80

70 9.8 3.4 17.50 0.92 4 x 0.8 1.88 49.0 2.70 2.1 735 588 80

95 11.3 3.4 18.80 1.00 4 x 0.8 1.96 52.0 3.12 2.9 780 624 100

120 12.9 3.4 20.40 1.08 4 x 0.8 2.04 56.0 3.59 3.6 840 672 100

150 13.9 3.4 21.70 1.08 4 x 0.8 2.20 59.0 3.99 4.5 885 708 100

185 15.9 3.4 23.40 1.16 4 x 0.8 2.28 63.0 4.55 5.6 945 756 100

240 18.1 3.4 25.40 1.24 4 x 0.8 2.36 68.0 5.34 7.2 1020 816 125

300 19.8 3.4 27.50 1.32 4 x 0.8 2.52 73.0 6.14 9.0 1095 876 125

400 22.9 3.4 30.40 1.40 4 x 0.8 2.68 79.0 7.34 12.0 1185 948 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm ) DC resistance 50Hz and 90C
2
at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.868 1.113 0.117 0.217 0.41 9.83 3.29 0.768 119 104 133

50 0.641 0.822 0.112 0.240 0.45 10.88 4.70 0.768 140 123 159

70 0.443 0.568 0.103 0.278 0.52 12.58 6.58 0.768 171 150 196

95 0.32 0.411 0.099 0.305 0.58 13.81 8.93 0.768 204 180 238

120 0.253 0.325 0.095 0.338 0.64 15.31 11.28 0.768 232 206 274

150 0.206 0.265 0.093 0.365 0.69 16.53 14.10 0.768 259 231 309

185 0.164 0.211 0.089 0.400 0.75 18.11 17.39 0.768 293 262 354

240 0.125 0.162 0.087 0.442 0.83 19.98 22.56 0.768 338 304 415

300 0.1 0.130 0.084 0.485 0.91 21.93 28.20 0.768 380 343 472

400 0.0778 0.102 0.081 0.544 1.03 24.63 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

46
8.7/15 (17.5) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables 2Xfy(p) as
per ieC : 60502-2
Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 4.5 17.00 0.92 4 x 0.8 1.88 48.0 3.07 1.8 720 576 80

50 8.1 4.5 18.10 1.00 4 x 0.8 1.96 50.0 3.58 2.5 750 600 80

70 9.8 4.5 19.80 1.00 4 x 0.8 2.04 54.0 4.32 3.5 810 648 80

95 11.3 4.5 21.25 1.08 4 x 0.8 2.12 58.0 5.29 4.8 870 696 100

120 12.9 4.5 22.90 1.16 4 x 0.8 2.20 62.0 6.17 6.0 930 744 100

150 13.9 4.5 23.90 1.16 4 x 0.8 2.28 64.0 7.02 7.5 960 768 100

185 15.9 4.5 25.90 1.24 4 x 0.8 2.36 69.0 8.33 9.3 1035 828 100

240 18.1 4.5 28.05 1.32 4 x 0.8 2.52 74.0 10.14 12.0 1110 888 125

300 19.8 4.5 29.80 1.40 4 x 0.8 2.68 78.0 12.09 15.0 1170 936 125

400 22.9 4.5 32.90 1.48 4 x 0.8 2.84 85.0 14.84 20.0 1275 1020 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.524 0.668 0.124 0.181 0.34 8.19 5.01 0.768 154 134 172

50 0.387 0.494 0.119 0.199 0.37 8.99 7.15 0.768 181 158 205

70 0.268 0.342 0.109 0.226 0.43 10.22 10.01 0.768 220 194 253

95 0.193 0.247 0.105 0.249 0.47 11.26 13.59 0.768 263 232 307

120 0.153 0.196 0.101 0.275 0.52 12.44 17.16 0.768 298 264 352

150 0.124 0.159 0.099 0.291 0.55 13.15 21.45 0.768 332 296 397

185 0.0991 0.128 0.094 0.322 0.61 14.58 26.46 0.768 374 335 453

240 0.0754 0.099 0.091 0.356 0.67 16.10 34.32 0.768 431 387 529

300 0.0601 0.080 0.089 0.383 0.72 17.33 42.90 0.768 482 435 599

400 0.0470 0.064 0.085 0.431 0.81 19.52 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

47
8.7/15 (17.5) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables a2Xfy(p)
as per ieC : 60502-2
Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 4.5 16.80 0.92 4 x 0.8 1.88 47.0 2.45 1.1 705 564 80

50 8.1 4.5 17.90 1.00 4 x 0.8 1.96 50.0 2.72 1.5 750 600 80

70 9.8 4.5 19.70 1.00 4 x 0.8 2.04 54.0 3.13 2.1 810 648 80

95 11.3 4.5 21.00 1.08 4 x 0.8 2.12 57.0 3.61 2.9 855 684 100

120 12.9 4.5 22.60 1.16 4 x 0.8 2.20 61.0 4.09 3.6 915 732 100

150 13.9 4.5 23.90 1.16 4 x 0.8 2.28 64.0 4.48 4.5 960 768 100

185 15.9 4.5 25.60 1.24 4 x 0.8 2.36 68.0 5.08 5.6 1020 816 100

240 18.1 4.5 27.60 1.32 4 x 0.8 2.52 73.0 5.90 7.2 1095 876 125

300 19.8 4.5 29.70 1.40 4 x 0.8 2.68 78.0 6.78 9.0 1170 936 125

400 22.9 4.5 32.60 1.48 4 x 0.8 2.84 85.0 8.04 12.0 1275 1020 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.868 1.113 0.126 0.178 0.49 16.91 3.29 0.768 119 104 133

50 0.641 0.822 0.120 0.196 0.53 18.60 4.70 0.768 140 123 159

70 0.443 0.568 0.110 0.224 0.61 21.34 6.58 0.768 171 150 196

95 0.32 0.411 0.106 0.245 0.67 23.30 8.93 0.768 204 180 238

120 0.253 0.325 0.102 0.270 0.74 25.71 11.28 0.768 232 206 274

150 0.206 0.265 0.099 0.291 0.79 27.66 14.10 0.768 259 231 309

185 0.164 0.211 0.095 0.317 0.87 30.20 17.39 0.768 293 262 354

240 0.125 0.162 0.092 0.349 0.95 33.18 22.56 0.768 338 304 415

300 0.1 0.130 0.089 0.382 1.04 36.30 28.20 0.768 380 343 472

400 0.0778 0.102 0.086 0.427 1.17 40.59 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

48
12/20 (24) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables 2Xfy(p) as
per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 5.5 19.00 1.00 4 x 0.8 1.96 52.0 3.45 1.8 780 624 80

50 8.1 5.5 20.10 1.08 4 x 0.8 2.04 55.0 4.02 2.5 825 660 80

70 9.8 5.5 21.80 1.08 4 x 0.8 2.12 59.0 4.80 3.5 885 708 80

95 11.3 5.5 23.25 1.16 4 x 0.8 2.28 63.0 5.74 4.8 945 756 100

120 12.9 5.5 24.90 1.16 4 x 0.8 2.36 66.0 6.66 6.0 990 792 100

150 13.9 5.5 25.90 1.24 4 x 0.8 2.44 69.0 7.55 7.5 1035 828 100

185 15.9 5.5 27.90 1.32 4 x 0.8 2.52 74.0 8.85 9.3 1110 888 100

240 18.1 5.5 30.05 1.40 4 x 0.8 2.68 79.0 10.73 12.0 1185 948 125

300 19.8 5.5 31.80 1.40 4 x 0.8 2.76 83.0 12.60 15.0 1245 996 125

400 22.9 5.5 34.90 1.56 4 x 0.8 3.00 90.0 15.45 20.0 1350 1080 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.524 0.668 0.131 0.158 0.30 7.14 5.01 0.768 154 134 172

50 0.387 0.494 0.125 0.173 0.33 7.81 7.15 0.768 181 158 205

70 0.268 0.342 0.115 0.195 0.37 8.83 10.01 0.768 220 194 253

95 0.193 0.247 0.111 0.214 0.40 9.69 13.59 0.768 263 232 307

120 0.153 0.196 0.106 0.236 0.44 10.66 17.16 0.768 298 264 352

150 0.124 0.159 0.104 0.249 0.47 11.25 21.45 0.768 332 296 397

185 0.0991 0.128 0.099 0.274 0.52 12.42 26.46 0.768 374 335 453

240 0.0754 0.099 0.095 0.302 0.57 13.67 34.32 0.768 431 387 529

300 0.0601 0.080 0.093 0.325 0.61 14.68 42.90 0.768 482 435 599

400 0.0470 0.064 0.089 0.364 0.69 16.48 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

49
12/20 (24) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables a2Xfy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

35 7.0 5.5 18.80 1.00 4 x 0.8 1.96 52.0 2.83 1.1 780 624 80

50 8.1 5.5 19.90 1.08 4 x 0.8 2.04 55.0 3.11 1.5 825 660 80

70 9.8 5.5 21.70 1.08 4 x 0.8 2.12 59.0 3.58 2.1 885 708 80

95 11.3 5.5 23.00 1.16 4 x 0.8 2.28 62.0 4.06 2.9 930 744 100

120 12.9 5.5 24.60 1.16 4 x 0.8 2.36 66.0 4.56 3.6 990 792 100

150 13.9 5.5 25.90 1.24 4 x 0.8 2.44 69.0 5.00 4.5 1035 828 100

185 15.9 5.5 27.60 1.32 4 x 0.8 2.52 73.0 5.62 5.6 1095 876 100

240 18.1 5.5 29.60 1.40 4 x 0.8 2.68 78.0 6.49 7.2 1170 936 125

300 19.8 5.5 31.70 1.40 4 x 0.8 2.76 82.0 7.29 9.0 1230 984 125

400 22.9 5.5 34.60 1.56 4 x 0.8 3.00 90.0 8.61 12.0 1350 1080 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

35 0.868 1.113 0.133 0.155 0.59 28.08 3.29 0.768 119 104 133

50 0.641 0.822 0.126 0.170 0.64 30.75 4.70 0.768 140 123 159

70 0.443 0.568 0.116 0.194 0.73 35.07 6.58 0.768 171 150 196

95 0.32 0.411 0.111 0.211 0.79 38.16 8.93 0.768 204 180 238

120 0.253 0.325 0.107 0.232 0.87 41.93 11.28 0.768 232 206 274

150 0.206 0.265 0.104 0.249 0.94 44.99 14.10 0.768 259 231 309

185 0.164 0.211 0.100 0.271 1.02 48.97 17.39 0.768 293 262 354

240 0.125 0.162 0.096 0.296 1.12 53.63 22.56 0.768 338 304 415

300 0.1 0.130 0.093 0.323 1.22 58.51 28.20 0.768 380 343 472

400 0.0778 0.102 0.089 0.360 1.36 65.23 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

50
18/30 (36) kv , Three Core , Copper ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables 2Xfy(p) as
per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

50 8.1 8.0 25.20 1.24 4 x 0.8 2.36 67.0 5.20 2.5 1005 804 80

70 9.8 8.0 26.90 1.24 4 x 0.8 2.44 71.0 6.06 3.5 1065 852 80

95 11.3 8.0 28.35 1.32 4 x 0.8 2.60 75.0 7.10 4.8 1125 900 100

120 12.9 8.0 30.00 1.40 4 x 0.8 2.68 79.0 8.04 6.0 1185 948 100

150 13.9 8.0 31.00 1.40 4 x 0.8 2.76 81.0 8.96 7.5 1215 972 100

185 15.9 8.0 33.00 1.48 4 x 0.8 2.84 86.0 10.37 9.3 1290 1032 100

240 18.1 8.0 35.15 1.56 4 x 0.8 3.00 91.0 12.28 12.0 1365 1092 125

300 19.8 8.0 36.90 1.64 4 x 0.8 3.08 89.0 12.96 15.0 1335 1068 125

400 22.9 8.0 40.00 1.72 4 x 0.8 3.32 96.0 15.59 20.0 1440 1152 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

50 0.387 0.494 0.140 0.136 0.26 6.15 7.15 0.768 181 158 205

70 0.268 0.342 0.129 0.152 0.29 6.87 10.01 0.768 220 194 253

95 0.193 0.247 0.123 0.165 0.31 7.48 13.59 0.768 263 232 307

120 0.153 0.196 0.118 0.180 0.34 8.16 17.16 0.768 298 264 352

150 0.124 0.159 0.115 0.190 0.36 8.57 21.45 0.768 332 296 397

185 0.0991 0.128 0.110 0.208 0.39 9.39 26.46 0.768 374 335 453

240 0.0754 0.099 0.105 0.227 0.43 10.26 34.32 0.768 431 387 529

300 0.0601 0.080 0.103 0.243 0.46 10.97 42.90 0.768 482 435 599

400 0.0470 0.064 0.098 0.270 0.51 12.22 57.20 0.768 541 492 683

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

51
18/30 (36) kv , Three Core , aluminium ConduCTor , Xlpe insulaTed , pvC inner sheaThed ,
galvanised sTeel flaT sTrip armoured and pvC overall sheaThed , sCreened Cables a2Xfy(p)
as per ieC : 60502-2

Nominal con- Nominal Nominal Nominal Minimum Nominal Minimum Nominal Approx. Max. pulling Min. bending radius Nominal duct
ductor area conductor insulation diameter over thickness of dimension of thickness of overall mass tension diameter
(mm2) diameter thickness insulation Inner sheath armour strip Over sheath diameter (Kg/m) (kN) During Set in (mm)
(mm) (mm) (mm) (mm2) (mm) (mm) (mm) pulling position
(mm) (mm)

50 8.1 8.0 25.00 1.24 4 x 0.8 2.36 67.0 4.36 1.5 1005 804 80

70 9.8 8.0 26.80 1.24 4 x 0.8 2.44 71.0 4.84 2.1 1065 852 80

95 11.3 8.0 28.10 1.32 4 x 0.8 2.60 74.0 5.34 2.9 1110 888 100

120 12.9 8.0 29.70 1.40 4 x 0.8 2.68 78.0 5.94 3.6 1170 936 100

150 13.9 8.0 31.00 1.40 4 x 0.8 2.76 81.0 6.41 4.5 1215 972 100

185 15.9 8.0 32.70 1.48 4 x 0.8 2.84 85.0 7.13 5.6 1275 1020 100

240 18.1 8.0 34.70 1.56 4 x 0.8 3.00 90.0 8.02 7.2 1350 1080 125

300 19.8 8.0 36.80 1.64 4 x 0.8 3.08 89.0 7.65 9.0 1335 1068 125

400 22.9 8.0 39.70 1.72 4 x 0.8 3.32 95.0 8.79 12.0 1425 1140 150

500 Please refer to our technical department for further information

630 Please refer to our technical department for further information

eleCTriCal CharaCTerisTiCs CurrenT raTings


Nominal Maximum Cond. AC Inductive Capacitance Charging Dielectric Fault current Buried direct in In a Buried duct In Air
conductor Conductor resistance at reactance (F/km) current per loss per carrying capacity ground
area (mm2) DC resistance 50Hz and 90C at 50Hz and phase phase for 1 second
at 20C (Ohm/km) 90C (Ohm/ (A/km) (W/km)
(Ohm/km) km)
Cond. (kA) Copper Tape
Screen (kA)

50 0.641 0.822 0.141 0.134 0.76 54.58 4.70 0.768 140 123 159

70 0.443 0.568 0.129 0.151 0.85 61.46 6.58 0.768 171 150 196

95 0.32 0.411 0.124 0.163 0.92 66.36 8.93 0.768 204 180 238

120 0.253 0.325 0.119 0.178 1.00 72.34 11.28 0.768 232 206 274

150 0.206 0.265 0.115 0.190 1.07 77.16 14.10 0.768 259 231 309

185 0.164 0.211 0.110 0.205 1.16 83.42 17.39 0.768 293 262 354

240 0.125 0.162 0.106 0.223 1.26 90.74 22.56 0.768 338 304 415

300 0.100 0.130 0.103 0.242 1.37 98.39 28.20 0.768 380 343 472

400 0.0778 0.102 0.098 0.267 1.51 108.89 37.60 0.768 432 393 545

NOTE :
Data for Water tight conductor , Steel tape armour, Metal sheath, PE - ST 7 sheath can also be provided on customer specic request.

RPG CABLES
(A Division of KEC International Limited)

52
CONTINUOUS CURRENT RATING /EMERGENCY RATING/SCREEN FAULT CURRENT RATING / RATING
FACTORS FOR DIFFERENT LAYING CONDITIONS

CONTINUOUS CURRENT RATINGS Table 3 - CorreCTion faCTors for depThs of


laying oTher Than 0.8 m for direCT buried
The continuous current ratings given in this catalogue Cables
have been calculated in accordance with the International
Single-core cables
Electrotechnical Commission Publication (IEC)- 60287 based Three-core
Depth of laying m Nominal conductor size (mm2)
on the following standard operating conditions. cables
<185 (mm2) >185 (mm2)
0.5 1.04 1.06 1.04
Maximum conductor temperature 90C 0.6 1.02 1.04 1.03

Ambient air temperature 30C 1.0 0.98 0.97 0.98


1.25 0.96 0.95 0.96
Ambient soil temperature 20C
1.5 0.95 0.93 0.95
Soil thermal resistivity 1.5Km/W 1.75 0.94 0.91 0.94
Depth of burried 0.8 m 2.0 0.93 0.90 0.93
2.5 0.91 0.88 0.91
3.0 0.90 0.86 0.90
Single core cables are laid in the congurations indicated in
the current rating tables and the screens are bonded to the
earth at both ends.
Table 4 - CorreCTion faCTors for depThs of
EMERGENCY RATING laying oTher Than 0.8 m for Cables in duCTs
Single-core cables
The XLPE insulated cable shall operate under emergency Three-core
Depth of laying m Nominal conductor size (mm2)
conditions with maximum conductor temperature of 130C cables
<105 (mm2) >185 (mm2)
for 100hrs per year and maximum 500 hrs in life time.
0.5 1.04 1.05 1.03
0.6 1.02 1.03 1.02
1.0 0.98 0.97 0.99
Table 1 - CorreCTion faCTors for ambienT
1.25 0.96 0.95 0.97
air TemperaTures oTher Than 30 0C
1.5 0.95 0.93 0.96
1.75 0.94 0.92 0.95
Maximum Ambient air temeprature 0C 2.0 0.93 0.91 0.94
conductor
temperature 0C 2.5 0.91 0.89 0.93
20 25 35 40 45 50 55 60
3.0 0.90 0.88 0.92
90 1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

Table 2 - CorreCTion faCTors for ambienT


ground TemperaTures oTher Than 20 0C Table 5 - CorreCTion faCTors for soil
Thermal resisTiviTies oTher Than 1.5 k.m/W
Maximum
for direCT buried single-Core Cables
Ambient air temeprature 0C
conductor
Nominal Values of soil thermal resistivity (Km/W)
temperature 0C
10 15 25 30 35 40 45 50 area of
conductor 0.7 0.8 0.9 1 2 2.5 3
90 1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76
16 1.29 1.24 1.19 1.15 0.89 0.82 0.75
25 1.30 1.25 1.20 1.16 0.89 0.81 0.76
35 1.30 1.25 1.21 1.16 0.89 0.81 0.75
50 1.32 1.26 1.21 1.10 0.89 0.81 0.74

70 1.33 1.27 1.22 1.17 0.89 0.81 0.74


95 1.34 1.28 1.22 1.18 0.89 0.80 0.74
120 1.34 1.28 1.22 1.18 0.88 0.80 0.74
160 1.35 1.28 1.23 1.18 0.88 0.80 0.74

185 1.35 1.29 1.23 1.15 0.88 0.80 0.74


240 1.38 1.29 1.23 1.18 0.88 0.80 0.73
300 1.38 1.30 1.24 1.19 0.88 0.80 0.73
400 1.37 1.30 1.24 1.19 0.88 0.79 0.73

RPG CABLES
(A Division of KEC International Limited)

53
Table 6 - Correction factors for soil Table 9 - Correction factors for groups of
thermal resistivities other than 1.5 k m/W three CORE cables in horizontal formation
single-core cables in buried ducts laid direct in the ground
Nominal area Values of soil thermal resistivity k m/W Number of Spacing between cable centres mm
of conductor cables
mm2 0.7 0.8 0.9 1 2 2.5 3 in group Touching 200 400 600 800
16 1.20 1.17 1.14 1.11 0.92 0.85 0.79 2 0.80 0.86 0.90 0.92 0.94
25 1.21 1.17 1.14 1.12 0.91 0.85 0.79 3 0.69 0.77 0.82 0.86 0.89
35 1.21 1.18 1.15 1.12 0.91 0.84 0.79 4 0.62 0.72 0.79 0.83 0.87
50 1.21 1.18 1.15 1.12 0.91 0.84 0.78 5 0.57 0.68 0.76 0.81 0.85
6 0.54 0.65 0.74 0.80 0.84
70 1.22 1.19 1.15 1.12 0.91 0.84 0.78
95 1.23 1.19 1.16 1.13 0.91 0.84 0.78 7 0.51 0.63 0.72 0.78 0.83
120 1.23 1.20 1.16 1.13 0.91 0.84 0.78 8 0.49 0.61 0.71 0.78 -
150 1.24 1.20 1.16 1.13 0.91 0.83 0.78 9 0.47 0.60 0.70 0.77 -
10 0.46 0.59 0.69 - -
185 1.24 1.20 1.17 1.13 0.91 0.83 0.78
11 0.45 0.57 0.69 - -
240 1.25 1.21 1.17 1.14 0.90 0.83 0.77
12 0.43 0.56 0.68 - -
300 1.25 1.21 1.17 1.14 0.90 0.83 0.77
400 1.25 1.21 1.17 1.14 0.90 0.83 0.77

Table 7 - Correction factors for soil Table 10 - Correction factors for groups of
thermal resistivities other than 1.5 k m/W three-phase circuits of single-core cables
for direct buried three-core cables laid diRect in the ground
Nominal area Values of soil thermal resistivity (Km/W)
of conductor Number of Spacing between group centres (mm)
(mm2) 0.7 0.8 0.9 1 2 2.5 3 cables
in group
16 1.23 1.19 1.16 1.13 0.91 0.84 0.78 Touchinng 200 400 600 800
25 1.24 1.20 1.16 1.13 0.91 0.84 0.78 2 0.73 0.83 0.88 0.90 0.92
35 1.25 1.21 1.17 1.13 0.91 0.83 0.78 3 0.60 0.73 0.79 0.83 0.86
50 1.25 1.21 1.17 1.14 0.91 0.83 0.77 4 0.54 0.68 0.75 0.80 0.84
5 0.49 0.63 0.72 0.78 0.82
70 1.26 1.21 1.18 1.14 0.90 0.83 0.77
6 0.46 0.61 0.70 0.76 0.81
95 1.26 1.22 1.18 1.14 0.90 0.83 0.77
120 1.26 1.22 1.18 1.14 0.90 0.83 0.77 7 0.43 0.58 0.68 0.75 0.80
150 1.27 1.22 1.18 1.15 0.90 0.83 0.77 8 0.41 0.57 0.67 0.74 -
9 0.39 0.55 0.66 0.73 -
185 1.27 1.23 1.18 1.15 0.90 0.83 0.77
10 0.37 0.54 0.65 - -
240 1.28 1.23 1.19 1.15 0.90 0.83 0.77
11 0.36 0.53 0.64 - -
300 1.28 1.23 1.19 1.15 0.90 0.82 0.77
12 0.35 0.52 0.64 - -
400 1.28 1.23 1.19 1.15 0.90 0.82 0.76

Table 8 - Correction factors for soil


thermal resistivities other than 1.5 k Table 11 - Correction factors for groups
m/W for three-core cables in ducts of three-core cables in single way ducts in
horizontal formation
Nominal area Values of soil thermal resistivity (Km/W)
of conductor
(mm2) 0.7 0.8 0.9 1 2 2.5 3 Number of Spacing between duct centres (mm)
cables
16 1.12 1.11 1.09 1.08 0.94 0.89 0.84 in group
Touchinng 200 400 600 800
25 1.14 1.12 1.10 1.08 0.94 0.89 0.84
2 0.85 0.88 0.92 0.94 0.95
35 1.14 1.12 1.10 1.08 0.94 0.88 0.84
3 0.75 0.80 0.85 0.88 0.91
50 1.14 1.12 1.10 1.08 0.94 0.88 0.84
4 0.69 0.75 0.82 0.86 0.89
70 1.15 1.13 1.11 1.09 0.94 0.88 0.83 5 0.65 0.72 0.79 0.84 0.87
95 1.15 1.13 1.11 1.09 0.94 0.88 0.83 6 0.62 0.69 0.77 0.83 0.87
120 1.15 1.13 1.11 1.09 0.93 0.88 0.83
7 0.59 0.67 0.76 0.82 0.86
150 1.16 1.13 1.11 1.09 0.93 0.88 0.83
8 0.57 0.65 0.75 0.81 -
185 1.16 1.14 1.11 1.09 0.93 0.87 0.83 9 0.55 0.64 0.74 0.80 -
240 1.16 1.14 1.12 1.10 0.93 0.87 0.82 10 0.54 0.63 0.73 - -
300 1.17 1.14 1.12 1.10 0.93 0.87 0.82 11 0.52 0.62 0.73 - -
400 1.17 1.14 1.12 1.10 0.92 0.86 0.81 12 0.51 0.61 0.72 - -

RPG CABLES
(A Division of KEC International Limited)

54
Table 12 - Correction factors for groups of three-phase circuits of single-core
cables in single-way ducts

Spacing between duct group centres (mm)


Number of cables in group
Touchinng 200 400 600 800
2 0.78 0.85 0.89 0.91 0.93
3 0.66 0.75 0.81 0.85 0.91
4 0.59 0.70 0.77 0.82 0.86
5 0.55 0.66 0.74 0.80 0.84
6 0.51 0.64 0.72 0.78 0.83

7 0.48 0.61 0.71 0.77 0.82


8 0.46 0.60 0.70 0.76 -
9 0.44 0.58 0.69 0.76 -
10 0.43 0.57 0.68 - -
11 0.42 0.56 0.67 - -
12 0.40 0.55 0.67 - -

CERTIFICATE CERTIFICATE
This is to certify that This is to certify that

KEC International Ltd. KEC International Ltd.


Village: Godampura (Samlaya)
Village: Godampura (Samlaya)
Ta. Savli, Vadodara 391 520
Ta. Savli, Vadodara 391 520
Gujarat
Gujarat
INDIA
INDIA
has implemented and maintains an Environmental Management System.
has implemented and maintains a Quality Management System.

Scope:
Scope: Environment activities and supporting processes associated with Design & Manufacture of
Design & Manufacture of Power Cables. Power Cables.

Through an audit, documented in a report, it was verified that the management system
Through an audit, documented in a report, it was verified that the management system fulfills the requirements of the following standard:
fulfills the requirements of the following standard:

ISO 14001 : 2004


ISO 9001 : 2008

Certificate registration no. 20006674 UM


Certificate registration no. 20006674 QM08
Date of certification 2014-02-13
Date of certification 2014-02-13 Valid until 2017-02-12
Valid until 2017-02-12

UL DQS Inc.
UL DQS Inc.

Ganesh Rao
Managing Director
Ganesh Rao
Managing Director Accredited Body: UL DQS Inc., 1130 West Lake Cook Road, Suite 340, Buffalo Grove, IL 60089 USA
Administrative Office: UL Management Systems Solutions India Pvt. Ltd., 5th Floor, Anjaneya Techno Park,
Accredited Body: UL DQS Inc., 1130 West Lake Cook Road, Suite 340, Buffalo Grove, IL 60089 USA 147, HAL Airport Road, Kodihalli, Bangalore - 560 017 - India
Administrative Office: UL Management Systems Solutions India Pvt. Ltd., 5th Floor, Anjaneya Techno Park,
147, HAL Airport Road, Kodihalli, Bangalore - 560 017 - India

RPG CABLES
(A Division of KEC International Limited)

55
Table 13 - reduCTion faCTors for groups of more Than one mulTi-Core Cable in air - To be
applied To The CurrenT - Carrying CapaCiTy for one mulTi - Core Cable in free air

Number of Number of cable


Method of installation
trays
1 2 3 4 6 9
1 1.00 0.88 0.82 0.79 0.76 0.73
Touching 2 1.00 0.87 0.80 0.77 0.73 0.68
Cables on 3 1.00 0.86 0.79 0.76 0.71 0.66
perforated trays 1 1.00 1.00 0.98 0.95 0.91 -
Spaced 2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -
1 1.00 0.88 0.82 0.78 0.73 0.72
Touching
Cables on vertical 2 1.00 0.88 0.81 0.76 0.71 0.70
perforated trays 1 1.00 0.91 0.89 0.88 0.87 -
Spaced
2 1.00 0.91 0.88 0.87 0.85 -
1 1.00 0.87 0.82 0.80 0.79 0.78
Touching 2 1.00 0.86 0.80 0.78 0.76 0.73
Cables on Ladder 3 1.00 0.85 0.79 0.76 0.73 0.70
supports, cleats,
etc 1 1.00 1.00 1.00 1.00 1.00 -
Spaced 2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -

NOTE 1: Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5%.
NOTE 2: Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such
installations may be signicantly lower and must be determined by an appropriate method.
NOTE 3: Values are given for vertical spacings between trays of 300 mm and at least 20 mm between trays and wall. For close spacing, the factors should be reduced.
NOTE 4: Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. for closer spacing, the factors should be reduced.

Table 14 - reduCTion faCTors for groups of more Than one CirCuiT of single - Core Cables
(noTe 2) - To be applied To The CurrenT - Carrying CapaCiTy for one CirCuiT of singles - Core
Cables in free air

Number of Number of cable Use as a multiplier


Method of installation
trays to rating for
1 2 3

Cables on 1 0.98 0.91 0.87


Three cables in
perforated trays Touching 2 0.96 0.87 0.81
horizontal formation
(Note 3) 3 0.95 0.85 0.78

Ladder supports, 1 1.00 0.97 0.96


cleats etc 2 0.98 0.93 0.89
(Note 3) 3 0.97 0.90 0.86 Three cables in
Touching
Perforated 1 1.00 0.98 0.96 Horizontal formation
trays 2 0.97 0.93 0.89
(Note 3) 3 0.96 0.92 0.86

Vertical perforated 1 1.00 0.91 0.89


trays Spaced
(Note 4) 2 1.00 0.90 0.86
Three cables in
trefoil formation
Ladder supports, cleats, 1 1.00 1.00 1.00
etc 2 0.97 0.95 0.93
(Note 3) 3 0.96 0.94 0.90

NOTE 1: Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5%.
NOTE 2: Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply when cables are installed in more than one layer touching each other.
Values for such installations may be signicantly lower and should be determined by an appropriate method.
NOTE 3: Values are given for vertical spacings between trays of 300 mm. For closer spacing, the factors should be reduced.
NOTE 4: Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. for closer spacing, the factors should be reduced.
NOTE 5: For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the purpose of this table.

RPG CABLES
(A Division of KEC International Limited)

56
PLANT SAFETY

Our Organization is currently ISO 9001 + ISO 14001 certied. The company is under progress to achieve
OHSAS 18001 Certication. Several safety initiatives are taken place in roadmap of OHSAS 18001. The
company has won 1st runner up in manufacturing category during state level competition "GreenEnvio"
organized by Baroda Productivity Council in Dec. 2014. The competition was focusing on elements of
housekeeping, environmental, CSR & Safety. The organization has already established documented
Integrated management system for Quality, Environmental & Safety in line with ISO 9001, ISO 14001 &
OHSAS 18001.

ORDERING INFORMATION

To serve our customer in minimum time and high efciency, our valuable customers are
requested to provide the following details along with their enquiries and orders:

1. Number of phases/cores (3 or 1). *


2. Conductor required cross - sectional area / system load current. *
3. Metallic screen type (copper tape or copper wire) and area (copper wire screen).
4. System Voltage Rate. *
5. Earth Fault current required.
6. Applicable customer specication or International Standard . *
7. Conductor material (Copper/Aluminum).*
8. Insulation Material (XLPE).*
9. Bedding / Inner Sheathing (Inner Jacketing ( PVC/PE, .. ).
10. Armouring Type (SWA, FSA,AWA or STA).*
11. Cable jacketing material (PVC/PE/LSZH).*
12. Cable special features required, e.g. Flame Retardant Type to IEC 60332-3, Anti-termite
13. Bill of Quantity / Required length of cables (drum schedules).

NOTE : (*) indicates Minimum required data to be provided by customer at enquiry/order


stage.

RPG CABLES
(A Division of KEC International Limited)

57
DRUM HANDLING INSTRUCTIONS

In order to prevent damage to cable drums during


transportation, observe the following six instructions:

1. Always stand upright 4. Lower gently on to a level surface


Otherwise the cable might be damaged or the
cable layers tangled making it impossible to pull
out and use the cable.

2. Crane handling 5. Use blocks during unloading


Always use yoke to avoid damage to the drum Nail the blocks to the floor
flanges and cable.
Always use lifting bar to avoid damage to the
centre hole

3. Fork lift truck handling 6. Leave space between drums


The forks must cover the drum entirely. during unloading
Otherwise the lagging will be destroyed Enough space should be left to prevent damage to
and the cable will get damaged. cable end and drum flange

RPG CABLES
(A Division of KEC International Limited)

58
HEAD OFFICE EXPORTS WEBCONNECT

B-501, 247 Park, L.B.S.Marg,
MUMBAI Vikhroli (W), Mumbai - 400 083 www.rpgcables.com

6th floor, RPG House, exportscables@kecrpg.com
463, Dr.Annie Besant Road,
Worli, Mumbai-400030

powercables@kecrpg.com

RPG CABLES
(A Division of KEC International Limited)

RPG CABLES
(A Division of KEC International Limited)

Potrebbero piacerti anche