Led (number) Indication Meaning
Channel A (1) A(1) and B(2), Off Module not initialized
Channel B (2) A(1) and B(2), Red Fault, module must be restarted or repaired
A(1) and B(2), Alternating Red / Green Bus controller selftest
A(1) and B(2), Flashing Red Incorrect node configuration; e.g. duplicate MacID etc.
A(1) or B(2), Off Channel disabled, depends on network configuration
A(1) or B(2), Green Normal operation of channel
A(1) or B(2), Flashing Green Temporary error or node not configured to go online
ControlNet
A(1) or B(2), Flashing Red Media fault or no other nodes on the network
A(1) or B(2), Flashing Red / Green Incorrect network configuration
Module Status (3) Flashing Green Waiting for initialisation
Steady Green Initialised
Flashing Red Minor fault, recoverable
Steady Red Major fault, unrecoverable
Module Owned (4) Green A connection has been opened towards the module
Off No connection has been opened
Subnet Status (5) Off Power off
Flashing Green Not running
Green Running
Sub Network
Red Stopped
Device Status (6) Off Power off
Flashing red / green Configuration missing
Green Initialising
Flashing Green Configuration OK
Installation
Accessories Checklist
Anybus Communicator for ControlNet (ABC-CNT)
Power Connector
Anybus Communicator Resource CD, containing Configuration software, manuals, EDS file and
application notes. (Also downloadable from: www.anybus.com)
RS232 Configuration Cable
Sub network connector
Fieldbus Cable and connector (Not included)
1 1
2 2
Functional Overview
For in depth information about this product, please consult the Anybus Communicator User Manual.
(Available for download at HMS web site)
The Anybus Communicator for ControlNet module is classified as a ControlNet adapter, i.e. it can-
not originate connections on its own, but a scanner node can open a connection towards it. The
module is implemented according to the ControlNet specification for a communication adapter, pro-
file number 12.
A connection to the module can be opened from a ControlNet scanner. The size of the connection
can be up to 450 bytes in each direction. The module can be read or written to using UCMM
(Unscheduled) messages from another ControlNet adapter (slave) or scanner (master). Unscheduled
messages are normally only used for information such as configuration data etc.
The minimum Network Update Time (Nut) of the module is 5ms.
3/&PHPRU\
,2 ,2
3/& ,QSXWV 2XWSXWV
&RQWURO1HW
$Q\EXV ,QWHUQDOPHPRU\EXIIHULQ$%&
6HULDO6XE1HWZRUN
6HULDO'HYLFH7HPS5HJXODWRU 6HULDO'HYLFH
6XE1HWZRUN
,QSXWUHJLVWHU
6HW9DOYH7HPSHUDWXUH
'HYLFH
2XWSXWUHJLVWHU
$FWXDO7HPSHUDWXUH
Technical Specification
Dimensions Operating Temperature
120mm x 75mm x 27 mm (L x W x H) +5 to +55 degrees Celsius
4.724 x 2.953 x 1.063 (L x W x H) +41 to +131 degrees Farenheit
Protective Earth
Internal connection to PE via DIN rail
Support
HMS Sweden HMS Germany
Email: support@hms-networks.com Email: ge-support@hms-networks.com
Phone: +46 (0)35-17 29 20 Phone: +49 721 964 7218
Fax: +46 (0)35-17 29 09 Fax: +49 721 964 7210
Online: www.anybus.com Online: www.hms-networks.de
ControlNet International
Technical questions regarding the ControlNet
fieldbus system should be addressed to:
Communicator Downloads
Address: ControlNet International
20423 State Road 7, Suite 315 The latest manuals, configuration software, etc
Boca Raton, FL 33498 are available for download at the address below:
U.S.A www.anybus.com - and go to the support sec-
Online: www.controlnet.org tion.