Is IGBT Rectifier UPS still "New and Reliable" ?

Below is to clarify and to make a fair comparison between IGBT Rectifier Industrial UPS Vs Thyristor Rectifier Industrial UPS and IGBT Rectifier IT/Commercial
UPS based on the advanced technology and modern development today. Many of such arguments were done using a IGBT Rectifier UPS in IT/Commercial used
and the traditional Thyristor Rectifier UPS for comparison and was carried out quite some times ago (late '90).

Description IGBT Rectifier Industrial UPS Thyristor Rectifier Industrial UPS IGBT Rectifier IT/Commercial UPS

Three phase (4W or 3W) Yes 400/230, can 3W or 4W Yes 400/230, can 3W or 4W Yes 400/230, only 4W with N
Isolation Transformer (built-in) Yes Yes transformerless
Input Power Factor 0.97 - 0.99 0.8 >0.99
< 30% for 6-pulse bridge connection
and < 15% with H.filters 6-pulse bridge.
< 3% (because without input isolation
Total Harmonic Distortion(THDi) < 5%
tranformer)
< 15% for 12-pulse bridge connection,
and < 10% with H.filters 12-pulse bridge.

400/230V +/-20 to 25%(Std), less-


400/230V +/- 15%(std), protected against 400/230V +/-10% (Std), protected against
protected against high transient, voltage
Input Voltage Range and Protection high transient, voltage surge with isolation high transient, voltage surge with isolation
surge without input isolation tranformer.
tranformer. tranformer.
(acts on the mains actively ---> Risk)

Online Double Conversion, as acc. IEC Online Double Conversion as acc. IEC on line double converstion, design with
Functional Principle
62040-3 Class VFI 111 SS. 62040-3 Class VFI 111 SS. charger and booster with ECO mode

Intermediate DC Circuirt / Voltage 220VDC (std) 220VDC (std) High DC voltage


approx. 150,000Hrs dpending on the approx. 150,000Hrs dpending on the lower MTBF due to the use of DC/DC
Rectifier MTBF
design factor of the bridge design factor of the bridge converter / booster & more battery cells
Maintenance & MTTR within 24 hours within 24 hours within 24 hours
Bigger rectifier rating and can aslo be up- Bigger rectifier rating and can aslo be up- normally rectifier rating is smaller and
Rectifier Rating sized to bigger rating for higher re- sized to bigger rating for higher re- fixed. Bigger UPS is needed to provide
charging capability charging capability higher rectifier rating
Description IGBT Rectifier Industrial UPS Thyristor Rectifier Industrial UPS IGBT Rectifier IT/Commercial UPS

Rectifier Output DC Ripple Voltage approx. 2 % with LC filter approx. 5% with LC filter small with high DC

approx. 92% to 96% depending on approx. 89% to 94% depending on


Rectifier efficiency > 93% because transformer less
rectifier size & isolation transformer rectifier size & isolation transformer.

Rectifier Heat Loss less higher smaller without input transfomer


Battery Type Design for VRLA & Ni-Cd Design for VRLA & Ni-Cd Normally design based on VRLA
108 - 110 cells (VRLA) 108 - 110 cells (VRLA)
Battery Cells More battery cells are used (high DC)
170 to 182 cells (Ni-Cd) 170 - 182 cells (Ni-Cd)
lower due to VRLA battery cells, approx.
(Rectifier + Battery) MTBF With Ni-Cd, MTBF is > 100,000Hrs With Ni-Cd, MTBF is > 100,000Hrs
35,000Hrs
EMC Compliance & standard Yes, IEC 62040 for UPS Yes, IEC 62040 for UPS Yes, IEC 62040 for UPS
Overload Capability 150% for 1 min / 125% for 10mins 150% for 1 min / 125% for 10mins less over-current capability
Short Circuit Current 200% for 3sec (3Ph) approx. the same lower
smaller due to less heatloss and normally bigger with higher heatloss and top-
Ventilation / Fans smaller but back access in most cases
will be front access loaded with accessibility
IGBT has been used for decades in the
old design technology for AC/DC is being long established, used mostly in
Experience / Establishment inverter and extended to rectifier with
converter and more traditional telco, IT and data centres.
modern and advanced technology.
Total Cost of Onwership (TCO) higher

size as per electrical practice 1.2 times of need to size 2.5 times (6-pulse) & 2 times
Generator size for UPS approx. 1.2 times bigger
US rating (THDi < 5%) bigger for 12-pulse

Input Harmonic Filter for THDi <5% No Yes, even for 12-pulse No
Cooling / ventilation for room smaller cooling bigger cooling required smaller cooling
simplest (cascaded replacement) / non-
Maintenance & Accessibility Simple / front access Moderate / front access
front access.
Environmental higher efficiency, less heat & CO2 lower efficiency and higher heatloss highest efficiency, lower heatloss.