Sei sulla pagina 1di 174

maxPAC Hardware

Reference Guide
278596 Rev. A7
Refer to this publication for complete and accurate information that helps you better operate and service Metso
Automation equipment. Your comments and suggestions are welcome.
Metso Automation
1180 Church Road
Lansdale, PA 19446
Attention: Manager, Technical Publications

Copyright 2005 by Metso Automation MAX Controls, Inc.


Printed in the United States of America
All Rights Reserved

Metso Automation 278596


Contents
PREFACE ............................................................................................................................III

CHAPTER 1 ...................................................................................................................... 1-1

maxPAC Input/Output Subsystem ............................................................................................................................1-1


Overview ...................................................................................................................................................................1-1
Model IOP I/O Subsystem.....................................................................................................................................1-1
Cabinet...............................................................................................................................................................1-1
Chassis Assembly ..............................................................................................................................................1-2
DPU Mounting ..................................................................................................................................................1-4
I/O Modules.......................................................................................................................................................1-4
I/O Module Types..............................................................................................................................................1-5
Power Supply.........................................................................................................................................................1-6
Field Termination Options.....................................................................................................................................1-7
Local Terminations (standard)...........................................................................................................................1-7
Remote Terminations (option)...........................................................................................................................1-7
Termination Assemblies ....................................................................................................................................1-7
Installing Model IOP I/O Equipment ....................................................................................................................1-8
Sequence of Mounting Operations ........................................................................................................................1-8
Mounting I/O Chassis Assemblies.........................................................................................................................1-9
Cabling, Power, and Ground Wiring .....................................................................................................................1-9
Supplying 24V Power to the I/O Modules ......................................................................................................1-10
Interconnecting I/O Racks ...............................................................................................................................1-10
Summary of Cabling Rules for maxPAC I/O ..................................................................................................1-14
maxPAC I/O Bus Cables .................................................................................................................................1-14
Module Mounting Considerations .......................................................................................................................1-16
I/O Modules ...................................................................................................................................................1-16
DPU Modules ..................................................................................................................................................1-16
Module Addressing .............................................................................................................................................1-17
Backup Configuration Options............................................................................................................................1-17
Shared Configuration.......................................................................................................................................1-17
Redundant Configuration ................................................................................................................................1-18
Mixed Configuration .......................................................................................................................................1-19
Remote I/O ..........................................................................................................................................................1-20
Specifications.......................................................................................................................................................1-22
Environment ....................................................................................................................................................1-22
I/O Bus.............................................................................................................................................................1-22
Inputs/Outputs .................................................................................................................................................1-22

CHAPTER 2 ...................................................................................................................... 2-1

Analog Input Modules Isolated Input Module IOP301............................................................................................2-1

Metso Automation 278596


maxPAC Hardware Reference Guide

Overview .................................................................................................................................................................. 2-1


LED Indication ..................................................................................................................................................... 2-1
Bus Address .......................................................................................................................................................... 2-2
Jumper Configuration ........................................................................................................................................... 2-2
Program Resistors ................................................................................................................................................. 2-2
Module Operation................................................................................................................................................. 2-3
Diagnostics ........................................................................................................................................................... 2-5
Module specifications ........................................................................................................................................... 2-6
Field Wiring.......................................................................................................................................................... 2-7
Field Wiring for Redundant Modules with Common Transmitter........................................................................ 2-8

CHAPTER 3 ...................................................................................................................... 3-1

Analog Input Modules 4-20 mA Input Module IOP302 Voltage Input Module IOP305 ................................... 3-1
Overview .................................................................................................................................................................. 3-1
LED Indication ..................................................................................................................................................... 3-1
Bus Address .......................................................................................................................................................... 3-2
Jumper Configuration ........................................................................................................................................... 3-2
Module Operation................................................................................................................................................. 3-2
Diagnostics ........................................................................................................................................................... 3-4
Module Specifications .......................................................................................................................................... 3-4
Field Wiring for IOP302....................................................................................................................................... 3-5
Field Wiring IOP 305 Analog Input Module..................................................................................................... 3-6
Field Wiring For Redundant Modules with Common Transmitter....................................................................... 3-7

CHAPTER 4 ...................................................................................................................... 4-1

Analog Input Modules 3 Wire RTD Module IOP303.............................................................................................. 4-1


Overview .................................................................................................................................................................. 4-1
LED Indication ..................................................................................................................................................... 4-1
Bus Address .......................................................................................................................................................... 4-2
Jumper Configuration ........................................................................................................................................... 4-2
Module Operation................................................................................................................................................. 4-2
Diagnostics ........................................................................................................................................................... 4-4
Module Specifications .......................................................................................................................................... 4-4
Field Wiring.......................................................................................................................................................... 4-5
Field Wiring For Redundant Modules with Common RTD ................................................................................. 4-6

CHAPTER 5 ...................................................................................................................... 5-1

Analog Input Modules TC Module IOP304 ............................................................................................................. 5-1


Overview .................................................................................................................................................................. 5-1
LED Indication ..................................................................................................................................................... 5-1
Bus Address .......................................................................................................................................................... 5-2
Jumper Configuration ........................................................................................................................................... 5-2
Cold Junction Compensation ................................................................................................................................ 5-2
Module Operation................................................................................................................................................. 5-2
Diagnostics ........................................................................................................................................................... 5-3
Module Specifications .......................................................................................................................................... 5-4
Field Wiring.......................................................................................................................................................... 5-5
Field Wiring For Redundant Modules with Common TC .................................................................................... 5-6

Metso Automation 278596


Contents

CHAPTER 6 ...................................................................................................................... 6-1

Analog Output Modules 4-20 mA Output Module IOP320.....................................................................................6-1


LED Indication ......................................................................................................................................................6-1
Bus Address...........................................................................................................................................................6-2
Jumper Configuration ............................................................................................................................................6-2
Module Operation..................................................................................................................................................6-3
Diagnostics ............................................................................................................................................................6-4
Module Specifications ...........................................................................................................................................6-5
Field Wiring...........................................................................................................................................................6-6
Field wiring for redundant modules with common end element ...........................................................................6-7

CHAPTER 7 ...................................................................................................................... 7-1

Digital Input Modules 24V Common Input Module IOP330 48V Common Input Module IOP331..................7-1
Overview ...................................................................................................................................................................7-1
LED Indication ......................................................................................................................................................7-1
Bus Address...........................................................................................................................................................7-2
Module Operation..................................................................................................................................................7-2
Module specifications............................................................................................................................................7-3
Field Wiring...........................................................................................................................................................7-4
Field Wiring For Redundant Modules with Common DI......................................................................................7-5

CHAPTER 8 ...................................................................................................................... 8-1

Digital Input Modules 24V DC Isolated Input Module IOP334 120V AC/DC Isolated Input Module IOP332
240V AC/DC Isolated Input Module IOP333 ...........................................................................................................8-1
Overview ...................................................................................................................................................................8-1
LED Indication ......................................................................................................................................................8-1
Bus Address...........................................................................................................................................................8-2
Jumper Configuration ............................................................................................................................................8-2
Module Operation..................................................................................................................................................8-2
Module Specifications ...........................................................................................................................................8-3
Field Wiring...........................................................................................................................................................8-4
Field Wiring For Redundant Modules with Isolated DI ........................................................................................8-5

CHAPTER 9 ...................................................................................................................... 9-1

Digital Input Modules Counter Timer Module IOP335 ..........................................................................................9-1


LED Indication ......................................................................................................................................................9-1
Bus Address...........................................................................................................................................................9-2
Jumper Configuration ............................................................................................................................................9-2
Module Operation..................................................................................................................................................9-3
Diagnostics ............................................................................................................................................................9-4
Module specifications............................................................................................................................................9-4
Field Wiring...........................................................................................................................................................9-5

CHAPTER 10 .................................................................................................................. 10-1

Digital Output Modules Form A/B Relay Module IOP351 Form C Relay Module IOP350 ..............................10-1
Overview .................................................................................................................................................................10-1
LED Indication ....................................................................................................................................................10-1

v
maxPAC Hardware Reference Guide

Bus Address ........................................................................................................................................................ 10-2


Jumper Configuration ......................................................................................................................................... 10-2
Module Operation............................................................................................................................................... 10-2
Module Specifications ........................................................................................................................................ 10-3
Field Wiring IOP 351 ...................................................................................................................................... 10-5
Wiring IOP350 ................................................................................................................................................ 10-6
Field Wiring For Redundant Modules with Common End Element................................................................... 10-7

CHAPTER 11 ................................................................................................................. 11-1

Bus Extender Unit Module IOP371 ....................................................................................................................... 11-1


Overview ................................................................................................................................................................ 11-1
BEM Front Panel ............................................................................................................................................ 11-2
LED Indication ................................................................................................................................................... 11-2
Link Test............................................................................................................................................................. 11-2
Bus Address ........................................................................................................................................................ 11-2
Jumper Configuration ......................................................................................................................................... 11-2
DPU Compatibility ......................................................................................................................................... 11-4
I/O Bus Loading ............................................................................................................................................. 11-4
BEM Operation................................................................................................................................................... 11-5
Optical Cabling ............................................................................................................................................... 11-7
Model 564 and maxPAC I/O Compatibility ................................................................................................... 11-7
Termination Requirements.............................................................................................................................. 11-7
Redundant Configuration Approaches................................................................................................................ 11-8
Four Configuration Approaches ..................................................................................................................... 11-8
Configuring Remote I/O only ......................................................................................................................... 11-8
Configuring Local Common I/O..................................................................................................................... 11-8
Configuring Mixed Common and Redundant I/O .......................................................................................... 11-9
Single DPU Configurations .......................................................................................................................... 11-10
BEM Configuration Considerations ................................................................................................................. 11-12
Calculating Link Capacities.......................................................................................................................... 11-12
Ensuring Link Availability ............................................................................................................................... 11-13
Detecting Failover Conditions ...................................................................................................................... 11-13
Cabling Recommendations ........................................................................................................................... 11-13
Specifications.................................................................................................................................................... 11-14

CHAPTER 12 ................................................................................................................. 12-1

QuadPAT Module IOP336..................................................................................................................................... 12-1

QuadPAT Termination Module IOP337 ............................................................................................................... 12-1


Overview ................................................................................................................................................................ 12-1
Front Panel...................................................................................................................................................... 12-2
LED Indication ................................................................................................................................................... 12-2
Jumper Configuration ......................................................................................................................................... 12-2
Bus Address ........................................................................................................................................................ 12-4
DPU Compatibility ............................................................................................................................................. 12-4
Module Operation............................................................................................................................................... 12-4
QuadPAT Termination ................................................................................................................................... 12-5
Feedback Options ............................................................................................................................................... 12-6
Output Options ................................................................................................................................................... 12-6
Limit Switch Detection ....................................................................................................................................... 12-6
Redundant Configuration.................................................................................................................................... 12-7

Metso Automation 278596


Contents

Diagnostics ..........................................................................................................................................................12-8
Module Field Connections...................................................................................................................................12-9
Termination Field Connections Channels 1-2 ...................................................................................................12-10
Termination Field Connections Channels 3-4 ...................................................................................................12-11
Group1 Analog I/O Configuration ....................................................................................................................12-12
Group2 Analog I/O Configuration ....................................................................................................................12-13
Digital I/O Configuration Channels 1-2 ............................................................................................................12-14
Digital I/O Configuration Channels 3-4 ............................................................................................................12-15
Digital I/O Configuration - DC Power Switches ...............................................................................................12-16
Specifications.....................................................................................................................................................12-17

CHAPTER 13 ................................................................................................................. 13-1

Turbine Valve Positioner Module IOP341 .............................................................................................................13-1

Turbine Valve Termination Module IOP342.........................................................................................................13-1


Overview .................................................................................................................................................................13-1
Positioner Front Panel .........................................................................................................................................13-2
LED Indication ....................................................................................................................................................13-3
Jumper Configuration ..........................................................................................................................................13-4
Bus Address.........................................................................................................................................................13-5
DPU Compatibility ..............................................................................................................................................13-5
Module Operation................................................................................................................................................13-5
Turbine Valve Termination .............................................................................................................................13-7
Configuration.......................................................................................................................................................13-7
Calibration ...........................................................................................................................................................13-7
Diagnostics ..........................................................................................................................................................13-8
Module Field Connections.................................................................................................................................13-10
Termination Field Connections .........................................................................................................................13-11
Group1 Analog I/O Configuration ....................................................................................................................13-12
Group2 Analog I/O Configuration ....................................................................................................................13-13
Digital I/O Configuration ..................................................................................................................................13-14
Specifications.....................................................................................................................................................13-15

CHAPTER 14 ................................................................................................................. 14-1

Overspeed Trip Module IOP345 .............................................................................................................................14-1

Overspeed Termination Module IOP346 ...............................................................................................................14-1


Overview .................................................................................................................................................................14-1
Overspeed Front Panel.....................................................................................................................................14-2
LED Indication ....................................................................................................................................................14-2
Jumper Configuration ..........................................................................................................................................14-3
Bus Address.........................................................................................................................................................14-4
DPU Compatibility ..............................................................................................................................................14-4
Module Operation................................................................................................................................................14-4
Overspeed Trip Termination...........................................................................................................................14-5
Diagnostics ..........................................................................................................................................................14-6
Module Field Connections...................................................................................................................................14-7
Termination Field Connections ...........................................................................................................................14-8
Group1 Analog I/O Configuration ......................................................................................................................14-9
Group2 Analog I/O Configuration ....................................................................................................................14-10
Digital I/O Configuration ..................................................................................................................................14-11

vii
maxPAC Hardware Reference Guide

Specifications.................................................................................................................................................... 14-12

CHAPTER 15 ................................................................................................................. 15-1

HART Input Module IOP307 .................................................................................................................................. 15-1

HART Output Module IOP322 ............................................................................................................................... 15-1

HART Transceiver Module IOP364 ....................................................................................................................... 15-1


Overview ................................................................................................................................................................ 15-1
LED Indication ................................................................................................................................................... 15-2
Jumper Configuration ......................................................................................................................................... 15-2
Bus Address ........................................................................................................................................................ 15-2
DPU Compatibility ............................................................................................................................................. 15-3
Module Operation............................................................................................................................................... 15-3
Diagnostics ......................................................................................................................................................... 15-4
HART Analog Input Field Connections ............................................................................................................. 15-6
HART Analog Output Field Connections .......................................................................................................... 15-7
HART Transceiver Field Connections ............................................................................................................... 15-8
Transceiver to Analog Input Wiring................................................................................................................... 15-9
Transceiver to Analog Input Wiring................................................................................................................. 15-10
Transceiver to Analog Input Wiring................................................................................................................. 15-11
Transceiver to Analog Input Wiring................................................................................................................. 15-12
Transceiver to Output Driver Wiring................................................................................................................ 15-13
Transceiver to Analog Output Wiring .............................................................................................................. 15-13
HART Analog Input Wiring............................................................................................................................. 15-14
HART Analog Input Wiring............................................................................................................................. 15-15
HART Analog Input Wiring............................................................................................................................. 15-16
HART Analog Output Wiring .......................................................................................................................... 15-17
Specifications.................................................................................................................................................... 15-18

Metso Automation 278596


Preface

This publication, which describes the installation and operation of maxPAC,


assumes familiarity with the DPU and its configuration. For additional
information on related topics, refer to the following publications:

Book No. Book Title


278590 Model PDP Series 200 maxDPU4E Hardware Guide
278705 Model PDP Series 400 maxDPU4F Hardware Guide
278561 System Power and Grounding

Metso Automation 278596


Chapter 1

maxPAC
Input/Output Subsystem

Overview
The maxPAC Input/Output System links the maxDNA Distributed Control
System to real world process control inputs and outputs. The Input/Output
system uses a compact design to provide the system with greatly enhanced
I/O capacity in relatively little space. A close relationship exists, in turn,
between this I/O system and the maxDNA Distributed Processing Unit
(DPU) which it serves.

The DPU and the I/O modules mount in an I/O chassis assembly. The
backplane in the chassis assembly provides the I/O bus connection between
the DPU and the I/O modules. It also provides the system power and field
power connections to the modules. Multiple I/O chassis that share the I/O bus
can be installed in a cabinet.

Model IOP I/O Subsystem


Cabinet
Two standard cabinet types are available for the mounting of I/O system
hardware. The cabinet is available as either a NEMA (National Electrical
Manufacturers Association) type 1 or 12 and consists of the following:

Welded steel construction


Front and Rear access
I/O mounted in front and rear of cabinet (standard)
I/O mounted in front and terminations in rear of cabinet (option)
Other mounting arrangement options are also available
Removable doors
19 rack mount rails with standard E.I.A. hole spacing
Top or bottom Cable access
Size 85 7/8 h x 24 w x 38 7/8d

Optional Cabinet styles and sizes are also available.

Metso Automation 278596


maxPAC Hardware Reference Guide

The following figure shows a typical cabinet arrangement with I/O in both
the front and rear of the cabinet.

Figure 1-1. Typical Cabinet Arrangement, Front and Rear Views

Chassis Assembly

Three chassis assembly types are available for the installation of the I/O
module as follows:

IOP382 Eight-pack assembly to accommodate up to eight maxPAC I/O


modules. The DPU4F can also reside in this chassis.

IOP383 Six-pack assembly to accommodate a DPU4E or a Model 564 I/O


module in the right most position along with six maxPAC I/O modules; the
DPU4E takes up the equivalent of two maxPAC I/O module positions.

IOP381 Four-pack assembly to accommodate four maxPAC or Model 564


I/O modules.

1-2 Metso Automation 278596


maxPAC Input/Output Subsystem

The rack assemblies contain an I/O backplane featuring edge connectors for
I/O modules and connectors for 24V system supply and 24V and 48V loop
power supplies. Input/Output modules connect to the I/O bus through four to
eight connectors on the backplane, depending on chassis style.

The backplane also contains ribbon cable connectors to interconnect chassis


assemblies and extend the I/O bus to the maximum number of modules
supported by the DPU.

System 24V

I/O Bus
I/O Bus
Connector
Connectors

Field 48V
Field 24V

Figure 1-2. Eight-Pack Rack

Figure 1-3. Six Wide Rack with DPU4E

Metso Automation 278596 1-3


maxPAC Hardware Reference Guide

Model Number Description


IOP381 4-wide frame assembly
IOP382 8-wide rack assembly
IOP383 6-wide rack assembly
IOP015 maxPAC Chassis used with IOP381
IOP011,012 Model 564 Chassis used with IOP381

DPU Mounting
DPU4E mounts in the right most position of the six-pack chassis assembly. It
occupies the equivalent of two I/O modules. Refer to Publication 278590 for
DPU4E information. DPU4F mounts in the left most position of the eight-
pack chassis assembly. It occupies the equivalent of one I/O module. Refer to
Publication 278705 for DPU4F information.

I/O Modules
The I/O modules are rugged enclosed printed circuit board assemblies. The
edge connection at the rear of each module provides the interface to the
backplane and the I/O bus. System power and field power, when applicable, is
also available through this connection.

While I/O modules vary by type, they may include one or more of the
following:

A color bar on the module faceplate identifies the module type. Each
module type has a unique color.

Euro-style terminal connector blocks for field wiring; each block contains
16 connectors;

Rotary address switch;

Light Emitting Diodes (LED) for module status indication;

All the modules that require field power include a front mounted fuse
disconnect and a LED fuse status indication;

All discrete modules include front mounted LEDs for input/output logic
state;

The TC module includes front-end connectors with thermistors to measure


the junction temperature for cold junction compensation.

The I/O modules may be inserted and withdrawn safely with 24 Vdc and field
power applied.

1-4 Metso Automation 278596


maxPAC Input/Output Subsystem

Figure 1-4. Typical I/O Module Front Panel

I/O Module Types


Because of the variety of input and output ranges needed in distributed control
applications, the Model IOP I/O offers many types of easily configurable
discrete and analog I/O modules. For a list of modules, along with their
ranges and number of points per module, refer to the following tables.

Digital Input (AC/DC)*


Part Number Description
IOP330 24 Vdc common input; 16 channels
IOP334 24 Vdc isolated input; 16 channels
IOP331 48 Vdc common input; 16 channels
IOP332 120 Vac/dc isolated input; 16 channels
IOP333 240 Vac/Vdc isolated input; 16 channels
IOP350 Form C relay; 10 channels
IOP351 Form A/B relay; 16 channels
IOP335 Pulse I/O , 8 channels
*ac Voltages/currents are RMS

Metso Automation 278596 1-5


maxPAC Hardware Reference Guide

Analog Input
Part Number Description
IOP301 Isolated analog input; 16 channels
IOP302 4-20mA common input; 16 channels
IOP303 3-wire RTD input; 8 channels
IOP304 Thermocouple/emf input; 16 channels
IOP305 Voltage common input; 16 channels
IOP306 Kit with sixteen 100 Ohm resistors

Analog Output
Part Number Description
IOP320 4-20 mA common output, 8 channels

Other
Part Number Description
IOP371 Optical bus extender
IOP336 QuadPAT, 4 channels
IOP341 Turbine Valve Positioner
IOP345 Turbine Overspeed

Power Supply
The maxDNA Input/Output System uses the Model APS Power Supply
Assembly, which provides 24V dc power for Distributed Processing Units
and I/O. This Power Supply Assembly consists of a 19-inch rack mount or
flush mount chassis accommodating up to six independent 10 amp power
supply modules. Metso Automation typically installs the power supply
modules in an N + 1 redundancy configuration. Because each module is
individually isolated, the chassis can be split to provide both system power
and loop power.

Power supply features consists of the following:


Redundant AC power inputs
250 Watt power supply modules
Hot replaceable
Current Sharing
Power factor correction
Front panel indicators on each module
AC input
Output voltage status
Output current level
External status signals

1-6 Metso Automation 278596


maxPAC Input/Output Subsystem

Field Termination Options


A maxPAC system uses three field cable termination approaches:

Local Terminations Field cables terminate directly on the I/O


module.
Remote Terminations Field cables terminate on terminal blocks
remotely to the I/O module with an
interconnecting cable back to the I/O module.
Termination Assemblies The QuadPAT, Turbine Valve and Overspeed
modules require a DIN rail mounted termination
assembly. Field cables terminate on this
assembly with an interconnecting cable back to
the I/O module.

Local Terminations (standard)


Each I/O module is supplied with two 16 point, Euro-Style screw clamp
plugs that mate to the Printed Circuit Board Header on the module. Field
cables would be routed directly to these Euro-Style plugs, which can accept
up to a #12awg conductor.

Remote Terminations (option)


Many remote field cable termination options are possible. Listed below are a
few examples:

I/O in front of cabinet, terminations in the rear of cabinet.


Termination cabinet mounted adjacent to I/O cabinet.
Termination cabinet located remotely from I/O cabinet.

The types of terminal blocks installed in the termination facility are too
numerous to list; typically these terminations are DIN rail style. The cabling
back to the I/O module is typically made using two multi-conductor cables,
one to each of the Euro-Style plugs supplied with the individual I/O module.

Termination Assemblies
Part Number Description
IOP337 QuadPAT Termination Assembly
IOP342 Turbine Valve Termination Assembly
IOP346 Turbine Overspeed
CTO301 QuadPAT Module to Termination Assembly Cable
CTO302 Turbine Valve Module to Termination Assembly Cable
CTO303 Turbine Overspeed Module to Termination Assembly
Cable

Metso Automation 278596 1-7


maxPAC Hardware Reference Guide

Installing Model IOP I/O Equipment


This section covers the physical mounting and installation of the Model IOP
I/O equipment. See "Module Mounting Considerations," before mounting
any equipment.

The following tools and hardware are required:

Screwdriver
Hex Key Wrench, Metso Part No. 064598
Mounting Screws, Metso Part No. 030162 (8 per unit supplied)
Nut Retainers, Metso Part No. 003530 (8 per unit supplied)
Crimp Tool for field connectors, Weidmuller Part No. 906480
Crimp Contact Removal Tool, Weidmuller Part No. 906481

Before mounting any hardware, see "Cabling, Power, and Ground Wiring."

Sequence of Mounting Operations


Mounting the parts of the Model IOP I/O in proper order can save time and
duplication of effort.

Follow this sequence as closely as possible for best results:

1. Refer to field wiring instructions that can influence mounting locations


for chassis assemblies and chassis assembly/module replacement.

2. Mount the chassis assemblies; see "Mounting I/O Chassis Assemblies."

3. Perform all steps as outlined in "Cabling, Power, and Ground Wiring."

5. Complete field wiring.

6. Refer to "Module Addressing" for switch settings and jumper selections.

7. Install I/O modules.

If your field wiring enters through the bottom of the cabinet, mount the
Model IOP I/O units from top to bottom. This will make wiring of future
units easier, since you will not have to pull wires from the bottom of the
cabinet past existing Model IOP I/O units. This same reasoning applies to
field wiring entering the top of the cabinet. Here you mount the Model IOP
units from bottom to top.

1-8 Metso Automation 278596


maxPAC Input/Output Subsystem

Mounting I/O Chassis Assemblies


The Model IOP I/O chassis assembly attaches to the rear mounting rails in
standard 19-inch maxDNA I/O cabinets. Three chassis styles are available.
See Chassis Assembly. Up to seven chassis assemblies may be installed in
a standard cabinets.

Usually, the Model IOP I/O units are supplied already mounted in cabinets,
but if you are mounting them yourself, follow this procedure.

Note: before you mount an I/O chassis, it should contain the I/O backplane.

To attach the chassis assembly:

1. At the desired chassis assembly mounting location in the cabinet, place


eight 10-32 nut retainers (Metso Part No. 003530) in the rear mounting
rail holes that correspond to the eight screw slots on the Model IOP
chassis assembly.

2. The holes in the maxDNA cabinet rear mounting rails are arranged in a
repeating pattern of two holes close together separated by a single hole.
To make sure all chassis assembly mounting screw cutouts line up to
corresponding mounting rail holes, you must align the top mounting
screw cutouts (left and right) of the chassis assembly with the top holes
(left and right) of two hole pair.

3. Position the chassis assembly (two ribbon connectors to the right) so that
the screw slots align with the nut retainers. Insert eight 10-32 mounting
screws (Metso Part No. 030162) and tighten securely.

Cabling, power wiring, and chassis assembly to cabinet frame grounding


should be completed before mounting the I/O modules. See next section.

Cabling, Power, and Ground Wiring


This section describes power wiring, Model IOP I/O connection, and
connection to other Model IOP I/O units. The connections covered in this
section should be done after the chassis assemblies are in place and before
the I/O modules are mounted. Some cabling can be done when the I/O
modules are mounted, but the job is easier when they are removed. (See also
Interconnecting I/O Racks).

Cables used in the maxDNA Distributed Control Systems are labeled at both
ends with the device and connector number. Interconnecting ribbon cables
are designed for specific orientation, however, the connectors still prohibit
wrong electrical connection.

Refer to Publication 278561, System Power and Grounding, for a discussion


of cabinet grounding.

Metso Automation 278596 1-9


maxPAC Hardware Reference Guide

Supplying 24V Power to the I/O Modules


The I/O system requires a 24 Vdc 4.0 Vdc power supply. Normally, this is a
maxDNA power supply mounted in the cabinet holding the DPU; to ensure
reliability, Metso Automation recommends using a maxDNA power supply
exclusively. If another 24 Vdc power supply is used, it must meet the same
specification requirements as the maxDNA supply. All modules are
individually fused. The CMOS technology in the Model IOP I/O design
results in low module power consumption.

Whether the power source is the standard maxDNA supply or another


supply, the +24 Volts connector plugs into the 24V connector on the right
side of the I/O backplane.

Caution: The +24 Vdc power supply used to power any maxDNA hardware
should never be used for external relay contact wetting or to power any other
field equipment. Use a separate supply for contact wetting to provide noise
and interference protection for the maxDNA hardware.

Interconnecting I/O Racks


Use a ribbon cable to interconnect, in a daisy chain manner, two or more
adjacent I/O chassis assemblies in the same maxDNA I/O cabinet group. The
cables should be installed in a manner that minimizes the total I/O bus length.
This is done by utilizing the I/O bus connectors on both ends of the racks so
that the bus flows through the racks.

For example, consider the two-cabinet system shown in Figure 1-5a. A


maxDPU4F pair is installed in the leftmost slots of the top two racks in
cabinet 1. The bus begins at the DPU and flows through the rack to the
connectors on the right side of the rack (P9 & P10). A ribbon cable connects
the right side of rack 1 to the right side of rack 2. The bus flows through
rack 2 to connector P11. Another ribbon cable connects the left side of rack
2 to the left side of rack 3. The bus flows through rack 3 to connectors P9
and P10. This same pattern is repeated until the last rack has been reached.

Notice that the bottom rack of cabinet #1 is connected to the bottom rack of
cabinet #2 by a cable that runs from P11 to P9. This is because that results in
a shorter cable length than it would be had it run from P11 to P11. It is also a
much shorter cable length than if it had been run from the bottom of cabinet
1 to the top rack in cabinet 2.

To reiterate, when cabling the I/O racks together, the goal is to keep the I/O
bus length as short as possible. Connecting the cables on alternate sides of
the racks so that the I/O bus flows through from one rack to the next does
this.

Note that the ribbon cable connectors are keyed. The color stripe on the
ribbon cable should match pin 1 on the backpanel connector. Connector pin
1 is indicated by a white triangle symbol on the backpanel adjacent to the
connector.

1-10 Metso Automation 278596


maxPAC Input/Output Subsystem

A bus terminator (CPO402) must be installed at the end of the I/O bus
farthest from the DPU. The bus terminator is a small PC card assembly that
is designed to plug in to the I/O bus connector. When installing a terminator,
be sure to match its pin 1 indication to the pin 1 indication on the backpanel.
In Figure 1-5a, the terminator is shown inserted into connector P9 of the top
rack in cabinet 2. That is the point on the bus that is farthest from the DPU.

If you add I/O racks to your system at a later date, remember to move the
terminator from its old location to the new end of the bus.

I/O Bus Terminators are not used to provide impedance matching. They are
simply pull-up resistors that are used to improve the rise time of the open
collector I/O bus signals. For that reason, in some instances (e.g., a system
with both maxPAC and 564-style I/O connected with long cable runs), an
additional terminator at the DPU end might be required. Monitor the I/O Bus
Errors and, if your system seems to have an excessive amount, try adding the
additional terminator.

Refer to the Bus Extender Module chapter in this manual for information on
how to install terminators when BEMs are present in the system.

Cabinet #2 Cabinet #1
Terminator
D
P9 P P9
P11 P11
P10 U P10

D
P9 P P9
P11 P11
P10 U P10

P9 P9
P11 P11
P10 P10

P9 P9
P11 P11
P10 P10

Figure 1-5a. Interconnecting maxPAC I/O Racks (Shared I/O)

Metso Automation 278596 1-11


maxPAC Hardware Reference Guide

Terminating systems with Redundant or Mixed (Shared + Redundant) I/O is


a little more complicated than a system with only Shared I/O. Refer to the
following figures for examples. Additional information on Shared,
Redundant and Mixed I/O is contained in the Backup Configuration Options
section of this manual.

Redundant I/O P9
P11 DPU
Primary

P10

Redundant I/O P9
P11 DPU
Secondary

P10
I/O Bus Cable
Terminator
Redundant I/O P9
P11 Primary

P10

Terminator
Redundant I/O P9
P11 Secondary
I/O Backup Cable
P10
(047472)

Figure 1-5b. Terminating & Cabling Redundant I/O

1-12 Metso Automation 278596


maxPAC Input/Output Subsystem

Redundant P9
P11 DPU
I/O - Primary

P10

Redundant P9
P11 DPU
I/O - Secondary

P10
I/O Bus Cable
Terminator
Redundant P9
P11 I/O - Primary

P10 Pri

Com
Terminator
Redundant P9
P11 Sec
I/O - Secondary
Y-Cable
P10

Terminator
Shared P9
P11
I/O

P10

Notes:
1. Keep the redundant I/O racks close to the DPUs that drive them.
2. Place the Y-Cable close to the I/O bus connectors (P10) on the redundant racks.

Figure 1-5c. Terminating & Cabling Mixed I/O

Metso Automation 278596 1-13


maxPAC Hardware Reference Guide

Summary of Cabling Rules for maxPAC I/O


Keep the total I/O bus length (cables + backpanels) as short as possible.
The following techniques will do this.

Use flow through cabling.

When connecting columns of racks together, connect the bottom


rack of column 1 to the bottom rack in column 2 or the top rack
of column 1 to the top rack of column 2. In other words, do not
cable a top rack to a bottom rack.

Put the DPU at one end of the I/O bus. Never put the DPU in the middle.

Terminate the far end of the I/O bus (the end farthest from the DPU).

In a system with Common (shared) I/O, the terminator should be


placed at the far end of the common I/O bus. In a system with
Redundant I/O, install a terminator at the far end of both redundant
I/O bus segments. In a system with mixed (common + redundant)
I/O, terminate all segments.

The maximum number of maxPAC modules supported by the


maxDPU4E or maxDPU4F within a cabinet or adjacent cabinet pair is
60. This number of modules is reduced when the electrical I/O bus is
extended to other cabinets.

The limit of 60 modules per bus segment is based upon the electrical
characteristics of the bus drivers. Other considerations such as the
types of modules used, the use of BEMs and the availability of DPU
resources may change the number and types of modules permitted.
Thus, it is very important that the user verify the correctness of the
proposed configuration by running the I/O Configuration Tool. Refer
to Publication 278609 for more information on the tool.

maxPAC I/O Bus Cables


A variety of different maxPAC I/O bus cables are available. Use the cables
that are appropriate for your application based upon the positions of your I/O
racks. Due to the orientation and location of the connectors, different cables
are used for connections to P9/P10 vs. P11 when the racks are spaced
relatively close together. For longer runs, the same types of cables may be
used for all connectors.

Cables for maxPAC Connections to P9 & P10

Part Number Description

CPO301 10 inches - 0 rack units between racks

CPO303 12 inches - 1 rack unit between racks

1-14 Metso Automation 278596


maxPAC Input/Output Subsystem

CPO304 14 inches - 2 rack units between racks

CPO305 26 inches - 10 rack units between racks

Cables for maxPAC Connections to P11

Part Number Description

CPO323 12 inches 0 or 1 rack units between racks

CPO324 14 inches 2 rack units between racks

CPO325 28 inches 10 rack units between racks

Long Cables for maxPAC Connections to P9, P10 or P11

For I/O bus connections to a cabinet outside the cabinet group, use the
following cables:

Part Number Description

CPO307 7-foot cable

CPO315 15-foot cable

CPO400-LL Custom length cable (about 20 feet maximum)

Cables for Connections between maxPAC and 564 Racks

For applications that require I/O bus connections between maxPAC racks
and Model 564 I/O racks, the following cables are available. Note that
Model 564 I/O racks do not support flow through cabling so they will
connect to the I/O bus as stubs.

Part Number Description

CPO504 13 inches - 2 rack units between racks (use P9 or P10)

CPO507 7-foot cable

CPO515 15-foot cable

CPO500-LL Custom length cable (about 20 feet maximum)

Metso Automation 278596 1-15


maxPAC Hardware Reference Guide

Module Mounting Considerations


I/O Modules
As you determine how modules are positioned in a cabinet, give some thought
to the signal levels that are to be wired to the modules. High and low signal
levels and AC and DC wiring should be kept separate. In general, wherever
possible, modules receiving the same type and level of signals should be
grouped together, with similar signal types arranged in vertical columns.

DPU Modules
The DPU4E requires the use of the six-wide chassis and is mounted in the
right most position. DPU4F is mounted in the left most position of the 8-
wide chassis to take advantage of the airflow. Likewise, when using a
second DPU for backup, it is mounted on a second chassis beneath the
primary DPU.

Before mounting I/O modules, you should complete power and grounding
and field wiring and any I/O module preparation and adjustment. See
appropriate chapters in this publication to check correct addressing and
jumper selection on the modules.

Before installing an I/O module in the right-most position of a chassis


assembly, make sure the +24Vdc is connected to the chassis assembly as well
as the I/O bus cable. Additionally, connect the cabinet frame ground to the
Model IOP I/O chassis assembly before installing an I/O module in the
extreme left position of a chassis assembly. Refer to "Cabling, Power, and
Ground Wiring."

Before installing any modules, complete all field wiring.

Model IOP I/O is designed to allow module installation and removal with the
+24Vdc power supply ON.

To mount modules:

1. With chassis assembly in place and all wiring completed, position


module into top and bottom card guides of the chassis. Gently slide
module forward, verifying that the connector pins on the side of the
module board engage the corresponding contact guides on the chassis
assembly.

2. When the contacts are engaged and resistance is felt, firmly press on the
front panel of the module front plate to make the simultaneous
connections at the front and rear. Apply pressure to the left of the LEDs
to place the force directly in line with the printed circuit card of the
module.

3. Secure module to chassis assembly with the top and bottom lock-down
screws on the front of the module.

1-16 Metso Automation 278596


maxPAC Input/Output Subsystem

Module Addressing
You must set addresses for each I/O module using rotary switches mounted
in the lower or upper right corner of the printed circuit board of the module,
depending on module type. These hexadecimal switches permit 255 logical
addresses (hexadecimal FF is not available). The lower switch is the low
order address and the upper switch is the high order address.

maxPAC modules use one, two, four or eight addresses. The address set on
the module is its base address. For the eight-address module the base address
is the address of channel 1. The module will automatically occupy an address
for each of its channels, starting with its base address.

To convert the hexadecimal address to the equivalent logical (decimal)


address:

1. Multiply the low order switch setting by 1 to get the decimal equivalent,
where switch positions A to F correspond to 10 to 15, respectively.

2. Multiply the high order switch setting by 16 to get the decimal


equivalent, where switch positions A to F correspond to 10 to 15,
respectively.

3. Add the two decimal equivalents for logical (decimal) module address.

For example, a 2 setting of S2 (2 x 16 = 32) and an A setting of S1 (10) gives


a module a logical (decimal) address of 42, the decimal equivalent of the
hexadecimal word 2A formed by the switch setting.

Module addressing is completely independent of module physical locations.


Each module address must be different from all other module addresses in
the system. Digital input modules must have an address less than 32
decimal. Addresses are determined by the system designer during system
planning.

Backup Configuration Options


Three input/output configuration options are available: shared, redundant, and
mixed.

Shared Configuration

Metso Automation 278596 1-17


maxPAC Hardware Reference Guide

A shared I/O configuration uses a primary DPU, a secondary DPU, and one set
of Model IOP parallel modules. See Figure 1-6. Both DPUs share the I/O bus
but only the active DPU (primary or secondary) receives data from, and sends
data to, the set of common I/O modules.

Redundant network

D D
P P
U U

I/O Bus

I I I I I I I I I I
O O O O O O O O O O

Figure 1-6. Shared Configuration

Redundant Configuration
A redundant I/O configuration uses a primary DPU, a secondary DPU, and
two identical sets of Model IOP parallel modules. See Figure 1-7. The
primary and secondary DPUs receive data from, and send data to, their set of
I/O modules. Outputs from the inactive string of modules are inhibited until
they become active. It is necessary to install a Part No. CPO309 cable
between the two I/O strings as shown; this cable inverts the output-enable
signal so that outputs of the inactive I/O string are disabled.

1-18 Metso Automation 278596


maxPAC Input/Output Subsystem

R ed u nd ant netw ork

D D
P P
U U

I/O B us

I I I I I I I I I I
O O O O O O O O O O

C P O 3 09

Figure 1-7. Redundant Configuration

Mixed Configuration
A mixed configuration uses a primary DPU, a secondary DPU, a Y adapter,
two identical sets of redundant Model IOP parallel modules, and various other
common Model IOP modules. See Figure 1-8. The primary and secondary
DPUs receive data from, and send data to, the redundant modules. The active
DPU (primary or secondary) also receives data from, and sends data to, the
common set of I/O modules.

The output-enable signal to the modules is handled internally by the mixed


backup adapter; Part No. CPO401.

In redundant or mixed configurations, the inactive DPU polls its redundant


modules for hardware failures when it is not performing control actions. No
transfer of control will occur if a failure is detected by the inactive DPU. The
inactive DPU also continuously updates its analog output modules with current
values so that bumpless transfer occurs when the inactive DPU becomes active.

Metso Automation 278596 1-19


maxPAC Hardware Reference Guide

Redundant network

D D
P P
U U

I/O Bus I/O Bus

I I I I I I I I I I
O O O O O O O O O O

Backup
Adapter

Common I/O Bus

I I I I I
O O O O O

Figure 1-8. Mixed Configuration

Remote I/O
A Bus Expander Module (BEM) permits the I/O bus to be extended up to
2,000 meters using highly reliable and noise immune fiber optic cables.

BEMs, configured in pairs, support both locally and remotely mounted I/O
cards. In a typical configuration using redundant Distributed Processing
Units (DPUs), an I/O cabinet installed locally in a control room contains I/O
modules, a DPU pair, and a BEM pair. This is connected via I/O optical
cable to a ruggedized remote cabinet containing I/O modules, and a second
BEM pair. The optical link is established between the local and remote
expander modules. Any DPU or redundant pair of DPUs, can communicate
with I/O that are locally and/or remotely mounted. Figure 1-9 shows a
typical configuration with both redundant and common local I/O and

1-20 Metso Automation 278596


maxPAC Input/Output Subsystem

common remote I/O. The Y adapter would also be required at the remote
end to support both common and redundant remote I/O.

redundant network

D D
Y
P ADAPTER P
U U
B B
E E
M M Control
backplane backplane
Room

I I I I I I I I
O O O O O O O O
Optical
Cable

Remote
B B location
E E
M M
I I I I I I
O O O O O O

I I I I I I I I
O O O O O O O O

Figure 1-9. Typical Bus Expander Module Configuration

Metso Automation 278596 1-21


maxPAC Hardware Reference Guide

Specifications
Environment
The Model IOP I/O operates in the temperature range of 0C to 60C at a
relative humidity range of 0 to 90%, noncondensing.

I/O Bus
The Model IOP I/O uses an 8-bit parallel asynchronous I/O bus, capable of
10 microsecond transfers. The I/O bus interface uses LSI circuitry for better
reliability. Parity checks are performed on all inputs and outputs, with
additional security provided for outputs using a check-before-execute control
strategy.

To further enhance reliability, I/O incorporates module address verification


and multiple module detection checks. Bus fault detection is also performed
by automatic confirmation of input data on every module.

Inputs/Outputs
All modules, both analog and digital types, withstand the normal or common
mode connection (IEEE-472, ANSI c37.90) and still maintain correct
operation. Common mode transients are bypassed to chassis metal work. All
points are optically isolated from the maxDNA I/O bus. Channel to channel
isolation allows series or parallel connection between channels or external
relay systems. All digital modules have logic state indication on the front
panel, one indication per point.

In addition to logic state indication, digital output modules contain fused


outputs and a front-panel blown fuse indicator. Each output also has a
deadman timer (approximately 1 second) that can be optionally used to
freeze or drop out all outputs if the module is not updated by the DPU.

1-22 Metso Automation 278596


Chapter 2

Analog Input Modules


Isolated Input Module IOP301

Overview
This module, featuring 16 isolated input channels, can be configured for any
mix of voltage or current inputs. The current loop can be powered from a
field supply or from a system loop supply provided via the backplane edge
connector. For current inputs, this module is pin and function compatible
with the IOP302 input module.

LED Indication
A green LED, labeled Active at the bottom of the module front panel, is on
when system power is present and the module is communicating with the
DPU. This LED blinks on and off when the module is not being scanned by
the DPU.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module supports two modes of operation selected by jumper setting. For
use as a replacement for a Model 564 module this module requires 16 bus
addresses and provides 15 channels. The addressing rules specified in the
Model 564 manuals still apply.

When used as a maxPAC module, the module only requires two bus
addresses and provides 16 channels. Each module address must be on an
even boundary (i.e. 32, 34 50 etc.) in the range of 32 to 252. Addresses 0 to
31 are reserved for digital input modules.

Jumper Configuration
The module contains two jumpers, located near the address switches. Refer
to the following table for jumper setting information.

Jumper Installed Not Installed


W1 50 Hz 60Hz
W6 Model 564 maxPAC

In addition, five jumpers per channel determine the type of input connected
to the channel.

Input Type A B C D E
4-20 mA powered by Metso IN IN IN IN OUT
Automation
4-20 mA powered by user IN IN OUT OUT IN
Voltage input OUT OUT OUT OUT IN

Program Resistors
Jacks are provides at the front of the module for the installation of a pair of
resistors per channel. These resistors can be used to scale a voltage input to
the 2.4V span of the A/D measurement. These resistors are identified as
follows:

Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Series R 1 7 26 32 51 57 78 85 113 120 142 148 175 193 211 233
Shunt R 3 10 29 35 53 60 80 88 115 123 144 151 177 196 215 234

The input circuit configuration for each type of input is shown in the
following sketch. An electronic fuse protects the 24-volt loop power to the
transmitter. A 200-Ohm thermistor in series with the 4-20 mA input provides
current limiting for voltages up to 100 Volts. The 24-volt loop supply is

2-2 Metso Automation 278596


Analog Input Modules
Isolated Input Module IOP301

available to the module from the backplane. For current inputs with external
shunt the channel is configured for voltage input and Rs = 0.

24V(+)

24V(-)
From backplane
1A 1B
200

2
Rs
+
100 A/D
Xmitter Rp

1
1D -
24V 1E
1C
4-20 ma powered by system

200 1A 1B
2

+ +
Rs 100 A/D
Voltage Rp
1D -
- 1
1E
1C
Voltage input

200 1A 1B

+ Rs
+
A/D
100
Xmitter Rp

1 1D -
-
1E
1C
4-20 ma powered externally,
internal shunt

Module Operation
This microprocessor-based module supports up to 16 isolated high level
inputs. A sigma delta A/D and precision reference is provided for each pair
of inputs. The A/D reads the voltage generated by the selected input and
converts the differential measurement to a 15-bit plus sign binary value

Metso Automation 278596 2-3


maxPAC Hardware Reference Guide

representing the voltage input, which is read by the microcontroller. The


microcontroller initiates the conversion and waits for the conversion to
complete.

The digital filter in the oversampling A/D provides excellent 50/60 Hz


normal mode rejection. Prior to starting each conversion, the microcontroller
selects one of the two input channels by means of two solid-state, optically
coupled relays. The two inputs are multiplexed with optical relays to provide
channel to channel isolation. Immediately following each measurement, open
input and over range conditions are checked.

A separate DC/DC converter provides isolated power to each A/D converter


measuring circuit. Communication between the microcontroller and each
A/D is serial at 100kHz. A separate group of optical isolators provide the
isolation between each A/D and the serial logic circuits. The microprocessor
provides the input data to the DPU on demand via the bus FPGA. The FPGA
provides the I/O bus interface logic; its program is loaded from the FLASH
on power up.

Module calibration is done automatically at power up following startup


diagnostics. Calibration is repeated periodically online to compensate for
temperature effects.

2-4 Metso Automation 278596


Analog Input Modules
Isolated Input Module IOP301

5V - logic
Regulator 24V
DC/DC

REF FLASH
Channel 1
Multiplexer OPTO
A/D 1
Channel 2

uC
FPGA
Optical isolation I/O Bus
between each pair
of channels

DC/DC

REF
Channel 15
Multiplexer
OPTO
A/D 8
Channel 16

optical isolation
field to logic

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


A/D send fault 0x12
A/D receive fault 0x13
A/D self calibration failure 0x14
Bad A/D communication 0x15
A/D does not complete conversion 0x16
RAM Test Failure (power-on) 0x22

Metso Automation 278596 2-5


maxPAC Hardware Reference Guide

CPU Stack Error (power-on) 0x23


CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32

Module specifications
Resolution 15 bits plus sign
Scan Rate 100 msec.
Temperature Sensitivity 0.004% of reading/oC 1.5uv/oC RTI
Accuracy 0.1% of full scale at 25oC
Source Impedance Effect 10 Mohm operational, 20K Ohms on loss of power
Conversion method Sigma Delta oversampling. Single A/D per
channel
Span 4 to 20 mA, 0-2.4V
Calibration Self-calibration on power up. Periodically on line
to compensate for temperature effects
Input Impedance - 4-20 mA input 300 Ohms
- voltage input 1 Mohm
Normal Mode Voltage 50 Volts
Normal Mode Rejection 60db @ 50/60 Hz
Common Mode Voltage 500 Volts dc or peak ac
Common Mode Rejection 120db @ 50/60 Hz, 100 Ohm imbalance
Isolation 1500 Vac (field to logic)
500 Vac (channel to channel)
Input Power 400 mA
(from 24V system supply)

2-6 Metso Automation 278596


Analog Input Modules
Isolated Input Module IOP301

Field Wiring

P2 P3

1 1
24V,In(-) 24V,In(-)
Channel 1 Channel 9
2 2
In(+) In(+)
3 3
24V,In(-) 24V,In(-)
4
Channel 2 Channel 10
4
In(+) In(+)
5 5
24V,In(-) 24V,In(-)
6 Channel 3 6 Channel 11
In(+) In(+)
7 7
24V,In(-) 24V,In(-)
8 Channel 4 8 Channel 12
In(+) In(+)
9 9
24V,In(-) 24V,In(-)
10 Channel 5 10 Channel 13
In(+) In(+)
11 11
24V,In(-) 24V,In(-)
12 Channel 6 12 Channel 14
In(+) In(+)
13 13
24V,In(-) 24V,In(-)
14 Channel 7 14 Channel 15
In(+) In(+)
15 15

24V,In(-) 24V,In(-)
16 Channel 8 16 Channel 16
In(+) In(+)

Metso Automation 278596 2-7


maxPAC Hardware Reference Guide

Field Wiring for Redundant Modules with Common Transmitter


The following figure shows the recommended wiring for two redundant
IOP301 analog input modules that share a common two-wire or four-wire
transmitter.

Redundant inputs must be configured as voltage inputs with an external 100-


Ohm shunt resistor. The recommended maximum distance between the shunt
and the I/O module is 10 meters. The +24V connection should be
independently fused to each transmitter.

The connection to the (-) terminal of the 24v supply must be made at the (-)
side of the shunt resistor. The voltage that is developed across each 100-Ohm
shunt by the 4-20 mA signal from the transmitter is wired to the AI module
using twisted pair cables. A PTC thermistor is recommended between the
transmitter output and the 100-Ohm shunt. This protects the 100-Ohm shunt
against over voltage and provides additional resistance to increase the
transmitter load to 250 Ohms. Kit IOP306 supplies 16 pairs of 100-Ohm
shunts and thermistors to support two IOP301 analog input modules.

Twisted pair
(-)
4 wire
Transmitter 100
(+)
thermistor Primary
IOP301
AI Module

(-)

(+)

Secondary
IOP301
AI Module

Four Wire Transmitter

2-8 Metso Automation 278596


Analog Input Modules
Isolated Input Module IOP301

(-) Twisted pair


(-)
24V (+) 100
Supply
(+)
thermistor
Primary
IOP301
AI Module
2 wire
Transmitter

(-)

(+)

Secondary
IOP301
AI Module

Two Wire Transmitter

Metso Automation 278596 2-9


Chapter 3
Analog Input Modules
4-20 mA Input Module IOP302
Voltage Input Module IOP305

Overview
The IOP302 module features sixteen 4-20 mA common input channels. The
IOP305 module features 16 voltage input (not current input) channels.
Transmitter loop power is available to the module via the backplane,
providing individually fused 24V transmitter power for each channel.

LED Indication
A green LED, labeled Active at the bottom of the module front panel, is on
when system power is present and the module is communicating with the

Metso Automation 278596


maxPAC Hardware Reference Guide

DPU. This LED blinks on and off at a constant rate when the module is not
being scanned by the DPU.

Bus Address
This module supports two modes of operation selected by jumper setting. For
use as a replacement for a Model 564 module this module requires 16 bus
addresses and provides 15 channels. The addressing rules specified in the
Model 564 manuals still apply.

When used as a maxPAC module, the module only requires two bus
addresses and provides 16 channels. Each module address must be on an
even boundary (i.e. 32, 34 50 etc.) in the range of 32 to 252. Addresses 0 to
31 are reserved for digital input modules.

Jumper Configuration
The module contains two jumpers. Refer to the following table for jumper
setting information.

Jumper Installed Not Installed


W1 50 Hz 60Hz
W6 Model 564 maxPAC

Module Operation
This microprocessor-based module supports up to 16 4-20 mA inputs, all
powered from a local 24V loop supply. A sigma delta A/D and reference are
provided for each input. Each A/D constantly reads the voltage generated by
the input and converts the differential measurement to a 15-bit plus sign
binary value, which is read by the microcontroller.

The digital filter in the oversampling A/D provides excellent 50/60 Hz


normal mode rejection. Immediately following each measurement, open
input and over range conditions are checked. A DC/DC converter provides
isolated power to the A/D measuring circuit. Communication between the
microcontroller and the A/D is serial at 100kHz. Optical isolators provide the
isolation between the A/D and the serial logic circuits.

The microprocessor provides the input data to the DPU on demand via the
bus FPGA. The FPGA provides the I/O bus interface logic; its program is
loaded from the FLASH on power up. Module calibration is done
automatically at power up following startup diagnostics. Calibration is
repeated periodically online to compensate for temperature effects.

3-2 Metso Automation 278596


Analog Input Modules
4-20 mA Input Module IOP 302
Voltage Input Module IOP 305

5V - field 5V - logic
DC/DC Regulator 24V

REF FLASH

Signal
Channel 1 Conditioning A/D

OPTO uC
FPGA
I/O Bus

REF optical isolation


field to logic

Signal
Channel 16 Conditioning A/D

The input circuit for each channel of the 4-20 mA input module is shown in
the following sketch. An electronic fuse protects the 24V loop power to the
transmitter. A 200-Ohm thermistor in series with the input provides current
limiting for overvoltage conditions up to 100 Volts. The 24-volt supply is
available to the module from the backplane.

Current Limit

200

100 A/D

24V(-)
From backplane
24V(+)
Fuse

The following sketch shows the input circuit for the voltage-input module.

Metso Automation 278596 3-3


maxPAC Hardware Reference Guide

A/D

Voltage Input Module

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


A/D send fault 0x12
A/D receive fault 0x13
A/D self calibration failure 0x14
Bad A/D communication 0x15
A/D does not complete conversion 0x16
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power on) 0x32

Module Specifications
Resolution 15 bits plus sign
Scan Rate 20 msec.
Temperature Sensitivity 0.004% of reading/oC 1.5uv/oC RTI
Accuracy 0.1% of full scale at 25oC
Source Impedance Effect 10 Mohm operational, 20K Ohms on loss of power
Conversion method Sigma Delta oversampling. Single A/D per channel
Span 4 to 20 mA, 0-2.4V.
Calibration Self-calibration on power up. Periodically on line to
compensate for temperature effects
Input Impedance IOP302, 300 Ohms; IOP305, 1mOhm
Normal Mode Voltage IOP302, 50 Volts; IOP305, 24 Volts
Normal Mode Rejection 60db @ 50/60 Hz
Common Mode Voltage 100 volts dc or peak ac for the group
Common Mode Rejection 120db @ 50/60 Hz, 100 Ohm imbalance
Isolation 1,500 Vac field to logic
Input Power 125 mA
(from 24V system supply)

3-4 Metso Automation 278596


Analog Input Modules
4-20 mA Input Module IOP 302
Voltage Input Module IOP 305

Field Wiring for IOP302


P2 P3

1 1
24V 24V
Channel 1 Channel 9
Transmitter 2 Transmitter 2
Iin Iin
3 3
24V 24V
Channel 2 Transmitter
Channel 10
Transmitter 4 4
Iin Iin
5 5
24V 24V
Transmitter 6 Channel 3 Transmitter 6 Channel 11
Iin Iin
7 7
24V 24V Channel 12
Channel 4
Transmitter 8 Transmitter 8
Iin Iin
9 9
24V 24V
Channel 5 Transmitter
Channel 13
Transmitter 10 10
Iin Iin

11 11
24V 24V
Channel 6 Transmitter
Channel 14
Transmitter 12 12
Iin Iin
13 13
24V 24V
Transmitter Channel 7 Transmitter 14 Channel 15
14
Iin Iin

15 15
24V 24V
Transmitter 16 Channel 8 Transmitter 16 Channel 16
Iin Iin

Metso Automation 278596 3-5


maxPAC Hardware Reference Guide

Field Wiring IOP 305 Analog Input Module

P2 P3

1 1
(-) (-)
Channel 1 Channel 9
0-2.4V 0-2.4V 2
2
(+) (+)
3 3
(-) (-)
0-2.4V Channel 2 0-2.4V
Channel 10
4 4
(+) (+)
5 5
(-) (-)
0-2.4V Channel 11
0-2.4V 6 Channel 3 6
(+) (+)
7 7
(-) (-)
Channel 4 Channel 12
0-2.4V 0-2.4V 8
8
(+) (+)
9 9
(-) (-)
0-2.4V Channel 5 0-2.4V 10 Channel 13
10
(+) (+)

11 11
(-) (-)
Channel 6 0-2.4V Channel 14
0-2.4V 12 12
(+) (+)
13 13
(-) (-)
0-2.4V Channel 7 0-2.4V 14 Channel 15
14
(+) (+)

15 15
(-) (-)
0-2.4V Channel 8 0-2.4V 16 Channel 16
16
(+) (+)

3-6 Metso Automation 278596


Analog Input Modules
4-20 mA Input Module IOP 302
Voltage Input Module IOP 305
Field Wiring For Redundant Modules with Common Transmitter
The following figure shows the recommended wiring for two redundant
IOP305 analog input channels that share a common transmitter.

The recommended maximum distance between the shunt resistor and the I/O
module is 10 meters. The +24V connection is independently fused to each
transmitter. The voltage that is developed across each 100-Ohm shunt by the
4-20 mA signal from the transmitter is wired to the AI module using twisted
pair cables.

The (-) terminal of the loop supply is connected to the (-) side of the shunt
resistors so that the 4-20 mA current does not flow through the twisted pairs
wires. A PTC thermistor is recommended between the transmitter output and
the 100-Ohm shunt. This protects the 100-Ohm shunt against over voltage
and provides additional resistance to increase the transmitter load to 250
Ohms. Kit IOP306 supplies 16 pairs of 100-Ohm shunts and thermistors to
support two IOP305 analog input modules.

(+)
DCS 24V
Loop Supply
(-)
Twisted pair
(-)
100
Transmitter
(+)
2-wire
thermistor
Primary
IOP305
AI Module

(-)

(+)

Secondary
IOP 305
AI Module

Metso Automation 278596 3-7


Chapter 4

Analog Input Modules


3 Wire RTD Module IOP303

Overview
This module features 8 isolated 3-wire RTD input channels.

LED Indication
A green LED, labeled Active at the bottom of the module front panel, is on
when system power is present and the module is communicating with the
DPU. This LED blinks on and off when the module is not being scanned by
the DPU. It is also used to display errors detected by diagnostics.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module supports two modes of operation selected by jumper setting. For
use as a replacement for a Model 564 module this module requires 8 bus
addresses and provides 7 channels. The addressing rules specified in the
Model 564 manuals still apply.

When used as a maxPAC module, the module only requires two bus
addresses and provides 8 channels. Each module address must be on an
even boundary (i.e. 32, 34 50 etc.) in the range of 32 to 252. Addresses 0 to
31 are reserved for digital input modules.

Jumper Configuration
The module contains three jumpers. Refer to the following table for jumper
setting information.

Jumper Installed Not Installed


W2 Common I/O Redundant I/O
W3 50 Hz 60 Hz
W4 Not used
W6 Model 564** maxPAC
** For version B or earlier, W7 must be installed for model 564 operation

Module Operation
This microprocessor-based module supports up to 8 RTD inputs, which can
be independently configured. A reference excitation current is provided for
each input. A sigma delta A/D reads the voltage generated by one of the eight
inputs and converts the differential measurement to a 15-bit plus sign binary
value representing the millivolt input, which is read by the microcontroller.

Multiple readings are done for each channel to compensate for the error
introduced by the field wiring in 3-wire RTDs. The microcontroller initiates
the conversion and waits for the conversion to complete. The digital filter in
the oversampling A/D provides excellent 50/60 Hz normal mode rejection.
The A/D also provides a variable gain amplifier function. Prior to starting
each conversion, the microcontroller sets the gain required in the A/D and
selects the RTD excitation current based on the configuration for that input.
It also selects the input channel by means of four solid-state optically
coupled relays.

The inputs are multiplexed with optical relays to provide channel to channel
isolation. Immediately following each measurement, open RTD and over
range conditions are checked. A DC/DC converter provides isolated power to
the field side of the measuring circuit. Communication between the
microcontroller and the A/D is serial at 100kHz.

4-2 Metso Automation 278596


Analog Input Modules
3 Wire RTD Module IOP 303

Optical isolators provide the isolation between the A/D and the serial logic
circuits. The microprocessor provides the input data to the DPU on demand
via the bus FPGA. The FPGA provides the I/O bus interface logic; its
program is loaded from the FLASH on power up.

Module calibration is done automatically at power up following startup


diagnostics. Calibration is repeated periodically online to compensate for
temperature effects.

5V - logic
5V - field DC/DC Regulator 24V

Excitation
FLASH
Current

Channel 1 REF

Field A/D OPTO uC Field


Interface Interface
Circuits Circuits I/O Bus

Channel 8
optical isolation
field to logic

Metso Automation 278596 4-3


maxPAC Hardware Reference Guide

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


A/D send fault 0x12
A/D receive fault 0x13
A/D self calibration failure 0x14
Bad A/D communication 0x15
A/D does not complete conversion 0x16
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power on) 0x32

Module Specifications
Resolution 15 bits plus sign
Scan Rate 8 points converted in 1.6 seconds
Input Type 10 ohm Cu, 10 ohm Pt, 25 ohm Pt, 100 ohm Cu,
100 ohm Pt, 100 ohm Ni, 1000 ohm Pt
Input Range 0 1000 ohms
Temperature Sensitivity 0.004% of reading/oC 1.5uv/oC RTI
Accuracy 0.15% of reading 0.5oC
Input Multiplexer Solid-state FET, optical isolation
Conversion method Sigma Delta oversampling
Linearization Digital in DPU. RTD ranges may be randomly
mixed.
Calibration Self-calibration on power up. Periodically on
line to compensate for temperature effects.
Maximum Lead Resistance 5 Ohms each lead
Compensation
Backup Conversions disabled if common RTD is
connected to redundant modules.
Conformity Error 0.3oC, 0.5oF
Normal Mode Rejection 60db @ 50/60 Hz
Common Mode Rejection 120db @ 50/60Hz, 100 Ohm imbalance
Common Mode Voltage 240V rms, 350V dc peak
Input Power 125 mA
(from 24V system supply)

4-4 Metso Automation 278596


Analog Input Modules
3 Wire RTD Module IOP 303

Field Wiring
P2 P3

1 1

2 2

3 Channel 1 3 Channel5

4 4

5 5

6 6

7 Channel 2 Channel 6
7

8 8

9 9

10 10

11 Channel 3 11 Channel 7

12 12

13 13

14 14
Channel 4 Channel 8
15 15

11
16 11
16

Note: Field wires must be of equal length

Metso Automation 278596 4-5


maxPAC Hardware Reference Guide

Field Wiring For Redundant Modules with Common RTD

Twisted pair, same length


(+)

(-)
Primary
IOP303
RTD Module
Ret
W2 not installed

(+)

(-) Secondary
IOP 303
RTD Module
Ret

W2 - not installed

4-6 Metso Automation 278596


Chapter 5

Analog Input Modules


TC Module IOP304

Overview
This module features 16 isolated thermocouple of emf input channels

LED Indication
A green LED, labeled Active at the bottom of the module front panel, is on
when system power is present and the module is communicating with the
DPU. This LED blinks on and off at a constant rate when the module is not
being scanned by the DPU.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module supports two modes of operation selected by jumper setting. For
use as a replacement for a Model 564 module this module requires 16 bus
addresses and provides 15 channels. The addressing rules specified in the
Model 564 manuals still apply.

When used as a maxPAC module, the module only requires two bus
addresses and provides 16 channels. Each module address must be on an
even boundary (i.e. 32, 34, 50 etc.) in the range of 32 to 252. Addresses 0
to 31 are reserved for digital input modules.

Jumper Configuration
The module contains three jumpers. These jumpers are located at the rear of
the module above the edge connector. Refer to the following table for jumper
setting information.

Jumper Installed Not Installed


W3 50 Hz 60Hz
W2 Common I/O Redundant I/O
W6 Model 564 maxPAC

Cold Junction Compensation


If this module is configured by the DPU to perform cold junction
compensation, a thermistor (Metso Part No. 074566) must be installed in
connectors P4 and P5 at the front of the module, above and below the input
connectors.

Module Operation
This microprocessor-based module supports up to 16 TC or emf inputs,
which may be independently configured. A sigma delta A/D reads the
voltage generated by one of the 16 TC or emf inputs and converts the
differential measurement into a 15 bit plus sign binary value representing the
millivolt input, which is read by the microcontroller. The microcontroller
initiates the conversion and waits for the conversion to complete.

The digital filter in the oversampling A/D provides excellent 50/60 Hz


normal mode rejection. The A/D also provides a variable gain amplifier
function. Prior to starting each conversion, the microcontroller sets the gain
required in the A/D for each configured input measurement, and selects the
input channel by means of two solid state, optically coupled relays.

5-2 Metso Automation 278596


Analog Input Modules
TC Module IOP304

The inputs are multiplexed with optical relays to provide channel to channel
isolation. Immediately following each measurement, open TC and over range
conditions are checked. A DC/DC converter circuit provides isolated power
to the field side of the measuring circuit. Communication between the
microcontroller and the A/D is serial at 100kHz. Optical isolators provide the
isolation between the field side and the serial logic circuits. The
microprocessor provides the input data to the DPU on demand via the bus
FPGA. The FPGA provides the I/O bus interface logic; its program is loaded
from the FLASH on power up.

Module calibration is done automatically at power up following startup


diagnostics. Calibration is repeated periodically online to compensate for
temperature effects.

When thermocouples are measured, the module monitors the TC cold


junction temperature and the input value read is compensated for the cold
junction temperature. Thermistors, installed at the terminal blocks provided
above and below the field connectors, are used to measure the TC cold
junction temperature. When remote terminations are used, these thermistors
must be removed from the module and moved to the wiring connections at
the remote terminations. The microcontroller schedules periodic
measurements of the thermistors and uses these measurements to calculate a
cold junction temperature for each channel.

5V - logic
5V - field DC/DC Regulator 24V

FLASH

Channel 1 REF

A/D OPTO uC
Field Interface FPGA
Circuits I/O Bus

OPEN
TC
Channel 16
optical isolation
field to logic

Diagnostics

Metso Automation 278596 5-3


maxPAC Hardware Reference Guide

The module executes diagnostics on power up. When an error is detected on


power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


A/D send fault 0x12
A/D receive fault 0x13
A/D self calibration failure 0x14
Bad A/D communication 0x15
A/D does not complete conversion 0x16
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32

Module Specifications
Resolution 15 bits plus sign
Scan Rate 16 points converted in 1 seconds
Input Type Types B, D, E, G, J, K, N, R, S, T, Platinell II
Input Range +/-10mv, +/-25mv, +/-60mv, +/-100mv,
+/-250mv, +600/-250mv
Temperature Sensitivity 0.004% of reading/oC 1.5uv/oC RTI
Accuracy 0.15% of reading 0.5oC
Input Multiplexer Solid-state FET, optical isolation
Conversion method Sigma Delta oversampling
Linearization Digital in DPU. RTD ranges may be randomly
mixed.
Calibration Self-calibration on power up. Periodically on
line to compensate for temperature effects
RJ Compensation Digital in module
Open TC Detection Performed each reading (1,000 0hm
threshold)
Backup Conversions disabled if common TC is
connected to redundant modules
Conformity Error 0.3oC, 0.5oF
Reference Junction Error 0.25oC
Normal Mode Rejection 60db @ 50/60 Hz
Common Mode Rejection 120db @ 50/60 Hz, 100 Ohm imbalance
Common Mode Voltage 240V rms, 350V dc peak
Input Power 125 mA
(from 24V system supply)

5-4 Metso Automation 278596


Analog Input Modules
TC Module IOP304

Field Wiring
P2 P3

1 1
+ +
Channel 1 Channel 9
2 2
- -
3 3
+ +
4 Channel 2 4 Channel 10
- -
5 5
+ +
6 Channel 3 6 Channel 11
- -
7 7
+ +
8 Channel 4 8 Channel 12
- -
9 9
+ +
Channel 5 Channel 13
10 10
- -
11 11
+ +
12 Channel 6 Channel 14
12
- -
13 13
+ +
14 Channel 7 14 Channel 15
- -
15 15
+ +
11
16 Channel 8 11 Channel 16
16
- -

Metso Automation 278596 5-5


maxPAC Hardware Reference Guide

Field Wiring For Redundant Modules with Common TC

(+)

(-)

Primary
IOP304
TC Module

TC extension wire W2 not installed

(+)

(-)
Secondary
IOP 304
TC Module

W2- not installed

Note: Thermistors must be installed in both modules.

5-6 Metso Automation 278596


Chapter 6

Analog Output Modules


4-20 mA Output Module IOP320

This module, featuring eight 4-20 mA output channels, receives power from
the 24V-system supply via the backplane edge connector. Loop power is also
available to the module via the backplane and is individually fused 24V for
each channel.

LED Indication
A green LED, labeled Active at the bottom of the module front panel, is on
when system power is present and the module is communicating with the
DPU. This LED blinks on and off when the module is not being scanned by
the DPU. A second green LED provides the status of the loop power fuse
disconnect.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module requires eight bus addresses and provides eight channels. Each
module address must be on a 0 or eight boundary (i.e. 32, 40, 48, etc.) in the
range of 32 to 240. Addresses 0 to 31 are reserved for digital input modules.

Jumper Configuration
The module contains four jumpers. Refer to the following table for jumper
setting information. Note: this is for the newer modules that have two rotary
address switches.

Jumper Installed Not Installed


W1 Run Mode Calibrate Mode
W2 Hold Output Reset Output
W3 Secondary Primary
W4 Common I/O Redundant I/O
W6 8 addresses N/A

6-2 Metso Automation 278596


Analog Output Modules
4-20mA Output Module IOP320

Module Operation
This microprocessor-based module supports up to eight 4-20 mA output
channels. Communication between the microcontroller and each output is
serial. The output request received from the I/O bus is translated by the
microcontroller into a pulse width modulated signal, which is transmitted to
each output circuit via a high-speed optical isolator. This optical isolator
provides the isolation between the logic and the field.

The duty cycle of the serialized output is proportional to the output level. The
output circuit converts this signal into 4-20 mA. Open load is detected and
reported to the DPU.

The FPGA provides the I/O bus interface logic; its program is loaded from
the FLASH on power up.

A watchdog timer function is included to monitor communications on the I/O


bus. The watchdog timers will timeout if there is no communications on the
I/O bus for longer than 0.7 seconds. When this occurs, the outputs will either
reset or remain in their last state depending on the position of the onboard
program jumper.

Module calibration is done automatically at power up following startup


diagnostics.

The 24-Volt loop supply is available to the module from the backplane. All
the outputs are connected to the loop supply.

Metso Automation 278596 6-3


maxPAC Hardware Reference Guide

AO Module
5V - logic
Regulator 24V

FLASH

4-20 ma
Channel 1 out D/A 1 OPTO

uC
Powered from field FPGA
24V supply I/O Bus

4-20 ma
Channel 8 out D/A 8 OPTO

optical isolation
field to logic

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

6-4 Metso Automation 278596


Analog Output Modules
4-20mA Output Module IOP320

Error Condition Code


RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32
Calibration Error (channel 1 to 8) 0x41 0x48

Module Specifications
Resolution 12 bits
Rise Time 750 msec.
Temperature Sensitivity 0.004% of reading/oC
1.5uv/oC RTI
Accuracy 0.1% of reading .05% of
span at 25oC
Span 4 to 20 mA.
Calibration Self-calibration on power up
with calibration jumper set
Load Impedance 0 800 Ohms
Input Power 175 mA
(from 24V system supply)

Metso Automation 278596 6-5


maxPAC Hardware Reference Guide

Field Wiring
P2

1
Iout
Channel 1
Load 2
Return
3
Iout
Channel 2
Load 4
Return
5
Iout
Load 6 Channel 3
Return
7
Iout
Channel 4
Load 8
Return
9
Iout
Load
Channel 5
10
Return
11
Iout
Load
Channel 6
12
Return
13
Iout
Load 14 Channel 7
Return
15
Iout
Load 16 Channel 8
Return

6-6 Metso Automation 278596


Analog Output Modules
4-20mA Output Module IOP320

Field wiring for redundant modules with common end element

Current (+)
Loop
Controlled (-)
Device Primary
IOP320
AO Module

W2 not installed
W3 not installed
W4 - not installed

(+)

(-)
Secondary
IOP 320
AO Module

W2 not installed
W3 installed
W4 not installed

Metso Automation 278596 6-7


Chapter 7

Digital Input Modules


24V Common Input Module IOP330
48V Common Input Module IOP331

Overview
These modules feature 16 digital common inputs.

LED Indication
Individual red front-panel LEDs provide the input status indication for each
channel. A green LED, labeled Active at the bottom of the module front
panel, is on when system power is present and the module is communicating
with the DPU. This LED blinks on and off when the module is not being

Metso Automation 278596


maxPAC Hardware Reference Guide

scanned by the DPU. A second green LED provides the status of the loop
power fuse disconnect.

Bus Address
This module requires one bus address. The address range for digital input
modules is 0 to 31 (0 1F). The address range for digital input modules
configured as slow DIs is 32 to 254.

Module Operation
The following is a simplified sketch of the circuit for one channel. The
signal-conditioning block provides filtering, current limiting circuit, and an
input threshold. It also includes the input status LED. The optical isolator
provides isolation between the field circuits and the logic circuits. The input
status is buffered and latched in the I/O bus interface circuit. The data is
presented to the I/O bus as a 16-bit word when the module is scanned by the
DPU. A watchdog timer in the I/O bus interface circuit controls the operation
of the active LED, causing it to blink when the module is not scanned for 0.7
seconds.

The 24V/48V(+) and 24V/48V(-) loop power signals are connected to all the
channels. They are routed to the module from the backplane via a fuse
disconnect which is accessible from the front of the module.

24V/48V(-) 24V/48V(+)

Fuse disconnect

Signal I/O BUS


Conditioning Interface
Circuit Circuit

To other channels

7-2 Metso Automation 278596


Digital Input Modules
24V Common Input Module IOP330
48V Common Input Module IOP331

Module specifications
IOP 330 24V IOP331 48V
Rated Input Voltage 24Vdc nominal, 40 Vdc 48Vdc nominal, 60V dc
maximum maximum
Input current per point 5 mA @ 24 Volts 5 mA @ 48 Volts
On-State Voltage 8.5 Volts 22 Volts
Isolation 250 VAC continuous, 1,500 VAC for 1 minute
User input to logic
Indicators 1 LED per point provides status indication.
LED provides power and communication indication.
LED provides loop power disconnect status
I/O Bus Address One address
Input Power 50 mA
(from 24V system supply)

Metso Automation 278596 7-3


maxPAC Hardware Reference Guide

Field Wiring
P2 P3

1 1
Channel 1 Channel 9
2 2

3 3

4 Channel 2 Channel 10
4

5 5

6 Channel 3 6 Channel 11

7 7
Channel 4 Channel 12
8 8

9 9

Channel 5 Channel 13
10 10

11 11

12 Channel 6 12 Channel 14

13 13

14 Channel 7 14 Channel 15

15 15

11
16 Channel 8 11 Channel 16
16

7-4 Metso Automation 278596


Digital Input Modules
24V Common Input Module IOP330
48V Common Input Module IOP331
Field Wiring For Redundant Modules with Common DI

(+)

(-)

Primary
IOP30,331
DI Module

(+)

(-)

Secondary
IOP 330,331
DI Module

Metso Automation 278596 7-5


Chapter 8

Digital Input Modules


24V DC Isolated Input Module IOP334
120V AC/DC Isolated Input Module IOP332
240V AC/DC Isolated Input Module IOP333

Overview
These modules provide16 isolated digital inputs

LED Indication
Individual red front-panel LEDs provide the input status indication for each
channel. A green LED, labeled Active at the bottom of the module front
panel, is on when system power is present and the module is communicating

Metso Automation 278596


maxPAC Hardware Reference Guide

with the DPU. This LED blinks on and off when the module is not being
scanned by the DPU.

Bus Address
This module requires one bus address. The address range for digital input
modules is 0 to 31 (0 1F). The address range for digital input modules
configured as slow DIs is 32 to 254.

Jumper Configuration
For IOP332 and IOP333, jumpers (W1W16) must be installed for AC
inputs.

Note: IOP334 does not include jumpers.

Module Operation
The following is a simplified sketch of the circuit for one channel. The
signal-conditioning block provides filtering, current limiting circuit, and an
input threshold. It also includes the LED. The optical isolator provides
isolation between the field circuits and the logic circuits. The input status is
buffered and latched in the I/O bus interface circuit. The data is presented to
the I/O bus as a 16-bit word when the module is scanned by the DPU. A
watchdog timer in the interface circuit controls the operation of the active
LED, causing it to blink when the module is not scanned for 0.7 seconds.

Signal I/O BUS


Input Voltage Conditioning Interface
Circuit Circuit

8-2 Metso Automation 278596


Digital Input Modules
24V DC Isolated Input Module IOP334
120V AC/DC Isolated Input Module IOP332
240V AC/DC Isolated Input Module IOP333

Module Specifications
IOP 332 120V IOP333 240V IOP334 24V
Rated Input 120 Volts ac/dc nom. 240 Volts ac/dc nom. 24V dc nominal,
Voltage 180 Volts max 280 Volts max 40V dc max
Input current per 5 mA @ 120 Volts 5 mA @ 240 Volts 5 mA @ 24Volts
point
On-State Voltage 48 Volts dc 70 Volts dc 8.5 Volts dc
100 Volts ac
Isolation 60 VAC; 250 VAC continuous, 125 VAC; 1500 VAC for 1 minute
User input to
logic
Isolation 350 VAC continuous
Channel to
channel
Indicators 1 LED per point provides status indication
LED provides power and communication indication

I/O Bus Address One address


Input Power 50 mA
(from 24V
system supply)

Metso Automation 278596 8-3


maxPAC Hardware Reference Guide

Field Wiring
P2 P3

1 1

AC/DC Channel 1 Channel 9


2 AC/DC 2

3 3

AC/DC 4 Channel 2 AC/DC 4 Channel 10

5 5

AC/DC 6 Channel 3 AC/DC 6 Channel 11

7 7

Channel 4 AC/DC Channel 12


AC/DC 8 8

9 9

AC/DC 10 Channel 5 AC/DC 10 Channel 13

11 11

AC/DC 12 Channel 6 AC/DC 12 Channel 14

13 13

AC/DC 14 Channel 7 AC/DC 14 Channel 15

15 15

AC/DC 11
16 Channel 8 AC/DC 11
16 Channel 16

8-4 Metso Automation 278596


Digital Input Modules
24V DC Isolated Input Module IOP334
120V AC/DC Isolated Input Module IOP332
240V AC/DC Isolated Input Module IOP333
Field Wiring For Redundant Modules with Isolated DI
(+)

(-)
AC/DC
Primary
DI Module

(+)

(-)

Secondary
DI Module

Metso Automation 278596 8-5


Chapter 9

Digital Input Modules


Counter Timer Module IOP335

This module provides eight isolated digital input channels. Each channel
provides a pair of digital inputs, which can be individually programmed to
support 24, or 48 Volt inputs.

Features

Software stored in FLASH

Low Power Dissipatioin

Configuration per channel

LED Indication
A red status LED is provided for each input. A green LED, labeled Active on
the module front panel, is on when system power is present and the module is
communicating with the DPU. This LED blinks on and off when the module
is not being scanned by the DPU.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module only requires two bus addresses and provides 8 channels.
Each module address must be on an even boundary (i.e. 32, 34 50 etc.) in the
range of 32 to 252. Addresses 0 to 31 are reserved for digital input
modules. This module is compatible with DPU4E and DPU4F only.

Jumper Configuration
A two-position jumper is used to select the input voltage for each input. The
input number identifies the jumpers. The two positions are A and B as
follows:

Jumper Installed Not Installed


W1A - 16A 24 V 48V

This microprocessor-based module supports up to eight pulse input channels.


Each channel can be independently configured for both function type and
debounce time. The functions supported are:

Mode 1 Frequency Input

Frequency in counts per second in input1. Input 2 is not used. The


Pulse I/O Buffer in DPU4E supports the following timebase mode
selections for frequency measurement: 20 msecs, 50 msecs, 100
msecs, 250 msecs, 500 msecs, and 1 second. For the selected
timebase, the Pulse I/O module measures frequency for the
specified duration and normalizes each measurement to cycles per
second. The measurement is updated at the end of each interval
and the counts read by the DPU when the module is scanned
represent the average of the last four measurements in
cycles/second. The scan rate of the DPU is asynchronous from
the scan rate by the module. The accuracy of the frequency
measurement is +/-1 count for the one-second timebase. The
accuracy for the other timebases is approximately the normalizing
multiplier divided by 4. Thus for the shortest timebase (20 msecs),
the accuracy is reduced to approximately +/-12 counts.

In applications requiring fast frequecy measurements, a period


measurement (mode 7) can also be used to measure frequency.
Since each count in the period measurement corresponds to 0.5
microseconds, the inverse of the period will yield a fast frequency
measurement with an accuracy of 0.1% for a 2000Hz input and
0.25% for a 5000Hz.

Mode 2 Simple Event Counter (default configuration)

9-2 Metso Automation 278596


Digital Input Modules
Counter Timer Module IOP335

32 bit accumulation of OFF-to-ON transitions in input1. Input2


provides an external accumulator reset.

Mode 3 Up/Down Event Counter

Net counts of OFF to ON transitions in input1 and input2. Input1


counts up and input2 counts down.

Mode 4 On-Time Timer

The timebase frequency (0.5 usec/count) is counted while input1 =


ON. Input 2 provides an external reset.

Mode 5 Up/Down Pulse Timer

Counts corresponding to the on-time difference in input1 and input2.


The timebase frequency (0.5 usec/count) is counted up while
input1 = ON and counted down while input2 is ON.

Mode 6 Pulse Width

ON time of last detected pulse in input1, based on the timebase


frequency (0.5 usec/count). Input2 is not used. The measurement
is updated at the end of each detected pulse (ON to OFF
transition). Counts read by DPU represent the average of the last
four measurements.

Mode 7 Period

Time duration between the last onset of input1and the previous onset
of input1. The timebase frequency (0.5 usec/count) is counted
during this time. Input2 is not used. The measurement is updated at
the end of each detected period. Counts read by DPU represent the
average of the last four measurements.

Module Operation
This microprocessor based module supports up to 16 digital inputs. As
shown in the functional block diagram, the field circuits are used to detect
and optically isolate the digital inputs. High-speed optical isolators support
higher frequency inputs. The processor circuits implement the configured
timing functions and provide the interface to the I/O bus FPGA. The Time
Processor Unit (TPU) included in the 68332 processor is used to process the
timing functions. The TPU operates from microcode masked in 68332 ROM.
The 16 DI inputs are debounced in an FPGA and are available individually to
the processor TPU inputs.

Metso Automation 278596 9-3


maxPAC Hardware Reference Guide

Diagnostics
The module executes diagnostics on power up. To indicate any errors
detected during power-up or on-line operation the LED labeled active blinks
the first digit at a slower rate and the second digit at a faster rate.

During normal operation this LED stays on or flashes at a steady one-second


rate when the module is not being scanned. The diagnostic codes are as
follows:

Error Condition Code


RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power on) 0x32

Module specifications
Input voltage 24V, 48V jumper selectable
Input thresholds 24V 10 Volts
48V 20 Volts
Debounce 0-255 msec dynamically configured per
channel
Accuracy 1 cycle or 0.15%, whichever is greater
Maximum frequency 32KHz
Minimum Pulse Width 10 usecs
Common Mode Voltage 240Vac rms, 350V dc peak
Input Power 150 mA
(from 24V system supply)

9-4 Metso Automation 278596


Digital Input Modules
Counter Timer Module IOP335

Field Wiring
P2 P3

1 1
+ +
Input 1 Input 9
2 2
- -
Channel 1 3 Channel 5 3
+ +
4 Input 2 Input 10
4
- -
5 5
+ +
6 Input 3 6 Input 11
- -
Channel 2 7 Channel 6 7
+ +
Input 4 Input 12
8 8
- -
9 9
+ +
10 Input 5 10
Input 13
- -
Channel 3 11 Channel 7 11
+ +
12 Input 6 12 Input 14
- -
13 13
+ +
14 Input 7 14 Input 15
- -
Channel 4 15 Channel 8 15
+ +
11
16 Input8 11 Input 16
16
- -

Metso Automation 278596 9-5


Chapter 10

Digital Output Modules


Form A/B Relay Module IOP351
Form C Relay Module IOP350

Overview
These modules provide 16 Form A relays or 10 form C relays. The form A
outputs can be converted to form B via on-board jumpers.

LED Indication
Individual red front-panel LEDs provide the output status indication for each
channel. A green LED, labeled Active at the bottom of the module front
panel, is on when system power is present and the module is communicating
with the DPU. This LED blinks on and off when the module is not being
scanned by the DPU.

Metso Automation 278596


maxPAC Hardware Reference Guide

Bus Address
This module requires one I/O one bus address.

This module requires one bus address. The address range for digital output
modules is 32 to 254. Addresses 0 to 31 are reserved for digital input
modules.

Jumper Configuration
Jumper W1 configures all the outputs to either reset or fail in place when
there is no communications in the I/O Bus for more than 0.7 seconds.
Configuration is as follows:

Jumper Position 2-3 Position 1-2


W1 Reset Output Hold Output

For the IOP351 module, each channel can be strapped in the printed circuit
assembly for form A or form B operation per the following table. The default
configuration is form A for all channels.

Channel Number Form A Form B


1 R100 R101
2 R103 R104
3 R106 R107
4 R108 R109
5 R111 R112
6 R114 R115
7 R116 R117
8 R119 R120
9 R122 R123
10 R124 R125
11 R127 R128
12 R130 R131
13 R132 R133
14 R135 R136
15 R138 R139
16 R140 R141

Module Operation
The following is a simplified sketch of the circuit for one channel. The relay
drivers energize the relay coils and control the operation of the output LEDs
to correspond to the data in the I/O bus interface circuit. A watchdog timer in
the interface circuit controls the operation of the active LED, causing it to
blink when the module is not scanned for 0.7 seconds. It also controls the
state of the outputs on loss of communications.

10-2 Metso Automation 278596


Digital Output Modules
Form A/B of Relay Module IOP351
Form C Relay Module IOP350

5V Reg 24V

Channel 1

BUFFER I/O Bus


Interface I/O Bus
Circuit

Channel 16

PROM

optical isolation
field to logic

Module Specifications
IOP 350 Form C IOP351 Form A/B
Maximum Switching 5 amps @ 250 VAC
Capacity 3 amps @ 30 VDC
0.3 amps @ 110 VDC
Number of Channels 10 16
Expected Relay Life Mechanical @ 180cpm - 5X10^6
Electrical @ 20cpm (resistive load) 10^5
Maximum Operating Speed 20cpm
Operating Time 15 msec. Maximum (excluding bounce)
Release Time 5 msec. Maximum (excluding bounce)
LED Indication 1 LED per point provides output status indication
active LED provides power and communication indication
I/O Bus Address One address
Input Power 400 mA
(from 24V system supply)

Metso Automation 278596 10-3


maxPAC Hardware Reference Guide

5V Reg 24V

Channel 1

BUFFER I/O Bus


Interface I/O Bus
Circuit

Channel 16

PROM

optical isolation
field to logic

10-4 Metso Automation 278596


Digital Output Modules
Form A/B of Relay Module IOP351
Form C Relay Module IOP350
Field Wiring IOP 351
P2 P3

1 1

Channel 1 Channel 9
2 2

3 3

Channel 2 4 Channel 10 4

5 5

Channel 3 6 Channel 11 6

7 7
Channel 4 Channel 12
8 8

9 9

Channel 5 10 Channel 13 10

11 11

Channel 6 12 Channel 14 12

13 13

Channel 7 14 Channel 15 14

15 15

Channel 8 11
16 Channel 16 11
16

Metso Automation 278596 10-5


maxPAC Hardware Reference Guide

Wiring IOP350

P2 P3

1 1

Channel 1 2 2
Channel 6
3 3

4 4

5 5
Channel 2 Channel 7
6 6

7 7

8 8
Channel 3 Channel 8
9 9

10 10

11 11
Channel 4 Channel 9
12 12

13 13

14 14
Channel 5 Channel 10
15 15

11
16 11
16

10-6 Metso Automation 278596


Digital Output Modules
Form A/B of Relay Module IOP351
Form C Relay Module IOP350
Field Wiring For Redundant Modules with Common End Element

Power (+)
Source
(-)
Primary
Switched Relay Module
Device

W1 installed

(+)

(-)
Secondary
Relay Module

W1 installed

Metso Automation 278596 10-7


Chapter 11

Bus Extender Unit


Module IOP371

Overview
The Bus Extender Unit (BEM) provides a flexible way to distribute the
system throughout the plant, resulting in reduced cabling costs and
installation time. Placing I/O in remote cabinets closer to a given process
typically reduces tray loading and the number of required junction boxes
since remote I/O cabinets are substituted. It also shortens wiring distances to
field devices, such as thermocouples and RTDs.

Metso Automation 278596


maxPAC Hardware Reference Guide

BEM Front Panel


The BEM front panel contains a pair of optical connectors (optical
transceivers), LEDs to report the status of the two optical links, a push button
for link testing, and an output contact, used to detect and report the failure of
either optical cable when redundant cables are provided (optional).

LED Indication
Individual green front-panel LEDs provide status indication for each channel.
The lower LED, labeled Active at the bottom of the module front panel, is on
when the BEM and its associated DPU are active. The LEDs labeled link1
and link2 indicate which optical link is operational.

Link Test
A link test pushbutton is provided to switch operation between the two
optical links. This can be used to verify that the two links are operational.

Bus Address
This module does not require a bus address.

Jumper Configuration
The module contains two jumpers located in the bottom right corner of the
board. Refer to the following table for jumper setting information.

Jumper Installed Not Installed


W1 Remote Local
W3 Redundant Common

Bus Extender Modules, configured in pairs, support both locally and


remotely mounted I/O cards. The local BEM installed with the DPU plugs
into the I/O backplane to access the DPU's parallel I/O bus. Locally mounted
I/O can share the I/O bus with the BEM. The remote BEM receives the bus
data over the optical link and establishes the I/O bus at the remote location.

A single DPU, or redundant pair of DPUs, can communicate with I/O


modules that are locally and/or remotely mounted. In a typical configuration
using redundant Distributed Processing Units (DPUs), an I/O cabinet

11-2 Metso Automation 278596


Bus Extender Unit Module IOP371

installed locally in a control room contains I/O modules, a DPU pair, and a
BEM pair. This is connected via I/O optical cables to a ruggedized remote
cabinet containing I/O modules and a second BEM pair. The optical link is
established between the local and remote Extender modules as shown in
figure 11-1.

D D
P P
U U

Local I/O Bus

Y Cable

B I I B
E / / E
M O O M

I I
/ /
O O
Optical Links Optical Links

B B
E E
M M

Remote I/O Bus

I I
/ /
O O

Figure 11-1. Optical Link between Local and Remote Extender Modules

Multiple BEMs can be connected to the I/O bus to allow multiple remote
locations for I/O. When multiple BEM modules are connected to different
parts of the system, all BEMs connected to a DPU must share the same I/O
bus as the DPU, as shown in figure 11-2. See also, "Redundant Configuration
Approaches."

Metso Automation 278596 11-3


maxPAC Hardware Reference Guide

Local Model IOP I/O Bus - Up to 60 BEMs and/or I/O Modules

I I B B B D
/ / E E E P
O O M M M U

Redundant Optical Links

Remote I/O Bus Area 1 Remote I/O Bus Area 2 Remote I/O Bus Area 3
Up to 45 Modules Up to 45 Modules Up to 45 Modules

Figure 11-2. The DPU Supports up to 60 Modules Locally and Up to 45 per Remote Location.

In addition to the configuration described in Figure 11-1, BEMs may be non-


redundant, and configured with redundant or non-redundant DPUs. All
options are possible. See " Redundant Configuration Approaches."

DPU Compatibility
The Extender is compatible with 4A, 4B and 4E DPUs, but is not compatible
with the earlier DPU3, DPU4 or controller file models. To use a bus
Extender with DPU 4A and 4B, firmware EPLD may need to be updated.
Contact Metso Automation Customer Care for assistance.

I/O Bus Loading


BEMs may also be used to expand the number of I/O modules that may be
configured locally. The local BEM represents the same bus loading as one
I/O module, regardless of the number of I/O modules attached to the remote
I/O bus. Without the use of BEMs, a single DPU supports up to 60 modules.
When BEMs are used, a DPU could support up to 60 modules locally and up
to 45 modules (including a remote BEM) at each remote location. The DPU
supports a maximum of 255 I/O addresses (local + remote modules).

Important: Remember other factors limit the number of modules you may
configure, such as I/O mix, DPU loading, application requirements, etc. Such

11-4 Metso Automation 278596


Bus Extender Unit Module IOP371

sizing factors need to be considered when planning I/O configurations. See


also "BEM Configuration Considerations."

BEM Operation
Each Extender module is packaged in a Model IOP I/O style printed circuit
board. Each board contains a chipset that includes a transmitter, receiver and
an optical transceiver. The transmitter converts the parallel data into serial
data, appends encoded error checking bits and sends the data serially over a
very fast fiber optic link (160 MBaud). The receiver decodes the serial data,
does error checking and converts the data back to the original parallel form.

The Extender also includes the buffers/darlingtons associated with the Model
IOP bus, bosfet switches to disconnect the backup DPU Extender from the
bus, and a CPLD to provide some small additional logic required to support
the operation of the chip set. The MACK condition (multiple modules on the
bus) is detected by the remote Extender transmitted over the link and
simulated locally for interpretation by the DPU.

Figure 11-3 shows a functional block diagram of the Bus Extender Module.
Operation is as follows:

I/O Bus Interface Buffers to duplicate both the DPU and I/O module bus
interface. The ACK signal from the module is detected at the remote end
transmitted by the link and simulated at the DPU end.

CPLD provides all the logic resources required by the link. This includes
latching and synchronizing the bus data to the frame clock, error detection
and link failover.

Transmitter (Serializer) Converts a snapshot of the parallel bus data into


160Mb TTL level serial stream.

Receiver (Serializer) Converts the received TTL level serial stream into
parallel data.

Frame Clock 8 MHz clock initiates the serial conversion of the I/O bus
data. Thus a snapshot of the Model IOP bus is sent every 125 nsecs. This
corresponds to a serial speed of 160Mb of the optical transceivers.

Metso Automation 278596 11-5


maxPAC Hardware Reference Guide

Local Area Remote area

Primary
DPU

OUT/IN
Local Bus Remote Bus
Expanders Fiber Expanders
LO/HI

ADDR Receiver
Transmitter

DATA B
u
LATCH f
f
INT
e Redundant Remote
Redundant CPLD
r CPLD Fiber Optic
Fiber Optic 564 Bus
s Transceiver B
Transceiver
DATA[8..0] u
M M
A
f
C
Fiber A
f
OUT/IN
C
K K e
Receiver LO/HI
ACK
Transmitter r
s ADDR
XACK
DATA
ALT_IN
LATCH

Status INT
Secondary
DPU
DATA[8..0]
OUT/IN Fiber
B
LO/HI u
Receiver f
ACK
ADDR B Transmitter f
u e XACK
DATA r
f s ALT_IN
LATCH f
INT
e Redundant
Redundant
Fiber Optic
r Transceiver
Fiber Optic CPLD
CPLD Transceiver
s
DATA[8..0]
Fiber M
M
A A
C C
K K
Receiver Transmitter

ACK

XACK

ALT_IN

Status

Figure 11-3. BEM Functional Block Diagram

Optical Transceivers Convert the TTL level transmit serial data into an
optical signal and the received optical signal into a TTL level serial data. A
second transceiver supports redundant links for single DPU applications. The
transmitter/receiver chip pair detects the operational state of the active link.

On power-up transceiver 1 is selected. If a failure is detected, the circuit will


switch the link to transceiver 2, a digital output will be set and an LED will

11-6 Metso Automation 278596


Bus Extender Unit Module IOP371

identify which link is operational. If the link cannot be established using


transceiver 2 the circuit will go back to transceiver 1 and the sequence will
repeat indefinitely until the link is established.

Power on reset The power on reset circuit includes a watchdog timer to


monitor the operation of the CPLD.

Optical Cabling
The two front-accessible optical transceivers, designated Link 1 (top link)
and Link 2 (bottom link), each have two ST type connectors, one to transmit
(Tx) and the other to receive (Rx). The fiber optic cable connects the transmit
output of one BEM to the receive input of the other BEM.

Multimode 62.5-micron cable is used to connect the local and remote


Extender modules. Cable is run between the redundant optical transceivers to
support redundant optical cable pairs. If redundant cables are provided, one
cable pair is always active while the second pair serves as a hot standby link.
See "Ensuring Link Availability.

Model 564 and maxPAC I/O Compatibility


Because the Extender module has the same form factor as the Model IOP I/O
modules, it can be used in either Model 564 or maxPAC applications. The
module installs in an IOP015 4-pack I/O Chassis or any of the maxPAC
chassis described in chapter 1.

Termination Requirements
Two terminations are required on each electrical I/O bus segment; one at
each end of the bus. This rule applies to the local I/O bus (the bus segment
that contains the DPU) as well as to all remote I/O busses (bus segments that
contain only the BEM and I/O modules).

The DPU itself acts as a terminator so one Terminator card (CPO402) is


required on the other end of the DPU local bus segment. The Local BEM
does not require any more termination than this.

The Remote BEM I/O bus segment does not contain a DPU. Thus, two
terminator cards (CPO402) are required one plugged in to each end of the
Remote BEMs electrical bus. See the figure titled Termination of Local
and Remote BEM Busses.

Metso Automation 278596 11-7


maxPAC Hardware Reference Guide

D
P P9 P9
P11 P11 Terminator
U P10 P10

D B
P P9 P9
P11 P11 E
U P10 M P10

B
P9
P11 E
M P10 Fiber Optic Cables

Terminator P9
P11
P10

Figure 114. Termination of Local and Remote BEM Busses

Redundant Configuration Approaches


In a redundant configuration, I/O may be configured only at the remote end
or both locally and remotely. A redundant configuration consists of a primary
and secondary DPU; each with its own associated BEM.

Four Configuration Approaches


Redundant DPUs and redundant BEMs may be employed in any of the
following configuration schemes:

1. Remote I/O only (redundant, common or mixed).


2. Remote I/O and local redundant I/O.
3. Remote I/O and local common I/O.
4. Remote I/O and mixed local I/O consisting of common and redundant
configurations.

Configuring Remote I/O only


In a redundant configuration using only remote I/O (configuration scheme
No. 1), the local DPUs and associated BEMs are placed in one rack. The
IOP381 4-wide rack is used for this application. The DPU4E chassis are
mounted at either end of the rack. The BEMs are installed next to each DPU
using the IOP015 Chassis. Resistor R1 located in the center of the backplane
must be removed to isolate the active DPU control line.

Configuring Local Common I/O


In a redundant DPU configuration using local common I/O (configuration
scheme No. 3), the I/O bus active control signal from each DPU must be

11-8 Metso Automation 278596


Bus Extender Unit Module IOP371

connected to its associated BEM only. A special cable (Part No. 047374)
must be used to connect the local I/O bus between the racks housing each
DPU. When this cable is used, jumpers in the following module types must
be set up for common I/O as follows:

Analog Output W4 installed


Thermocouple W2 installed
RTD W2 installed

Configuring Mixed Common and Redundant I/O


Configurations with mixed redundant and common I/O can be used at either
the local or remote end. The I/O bus from each DPU at the local end or each
BEM at the remote end is connected separately to the redundant modules. A
mixed backup adapter, (Part No. 080441) is used to combine the redundant
I/O buses into a common I/O bus. See Figure 11-4.

At the remote location, the I/O bus connections to the BEMs end must be
isolated only for redundant I/O applications. For common I/O applications
the two remote BEM modules, connected to primary and secondary DPUs,
are connected to the same Parallel I/O backplane or daisy chained Parallel
I/O backplanes.

Metso Automation 278596 11-9


maxPAC Hardware Reference Guide

D D
Y
P CABLE
P
U U
B B
E E
M M Control
backplane backplane
Room

I I I I I I I I
O O O O O O O O
Optical
Cable

Remote
B B location
E E
M M
I I I I I I
O O O O O O

I I I I I I I I
O O O O O O O O

Figure 11-5. Redundant DPUs with local common and remote common I/O configuration using Y cable.

Single DPU Configurations


For configurations using a single DPU, setup schemes as described in "Four
Configuration Approaches" still apply. However, the special cabling used in
redundant configurations is of course not needed. This applies to Part No.
04374 and the mix cable adapter. Additionally, special jumper considerations
as listed in "Configuring Local Common I/O" do not apply. See Figure 11-5.

11-10 Metso Automation 278596


Bus Extender Unit Module IOP371

backplane

D
P
U
B
I I
E
O O
M
Control
Room

B I I I I
E Optical
Cable O O O O
M

To other
Locations Optical Redundant Cable

B
I I I Remote
E
O O O location
M

I I I I
O O O O

Figure 11-6. Single DPU with common and remote I/O configuration. The redundant optical cables shown in this
illustration are optional but recommended.

Metso Automation 278596 11-11


maxPAC Hardware Reference Guide

BEM Configuration Considerations


Communication between the DPU and the remote I/O occurs in real time
using the existing Model IOP protocol. The remote I/O modules
communicate with the DPU, as if they were local I/O. Extenders are
transparent to the bus.

Although the BEM extends the Model IOP I/O bus up to 2000 meters, a time
delay factor reduces the maximum number of I/O modules that may be
installed beyond 400 meters. The time delay in the Extender circuit is
minimal; however there is a delay in the optical cable, introduced by the
speed of light, which is proportional to distance (approximately 1 x 10-9
sec/ft).

In configurations using a cable link no more than 400 meters in length, I/O
module reduction is minimal. See "Calculating Link Capacities."

Calculating Link Capacities


While as noted, a DPU supports up to 45 modules per remote location, a link
delay that is proportional to distance is introduced by the speed of light. The
Extender circuits themselves introduce very little delay. The distance factor
primarily limits the number of Digital Input modules set for SOE operation
since they must be scanned every 1 msec.

An IO Bus Configuration Limits utility is provided to calculate the effect of


link distance on the number of modules and scan rate supported by the DPU.
Refer to Publication 278609 (System Resources Guide) for a description of
this program.

Links can be connected in series or in parallel, the preferred configuration


approach. In a parallel link, a star approach, each remote location's BEM is
connected to a BEM located on the electrical bus with the DPU.

In a series link, the links can be configured such that one BEM and DPU
connects to a remote's BEM and its rack. This rack then contains another
BEM, which is then connected to a second remote's rack with its BEM. This
configuration approach introduces time delays, which will limit the number
of supported modules. Consult the factory if more than two links are on one
DPU.

11-12 Metso Automation 278596


Bus Extender Unit Module IOP371

Ensuring Link Availability


To ensure link availability, installations may include multiple levels of
redundancy. In configurations using only a single DPU, redundant cables
ensure availability. The loss of either cable pair will automatically route the
signal to the alternate cable pair. Only a momentary loss of the remote I/O,
(milliseconds), will occur while the Extender switches over to the inactive
cable.

To ensure optimal availability, each cable pair should be routed separately to


minimize the probability of damage to both cables. With separate cables, in
the event a cable should break or fail, a second cable is still available.

In configurations using redundant DPUs, each DPU can have its own bus
Extender to the remote location. Any single failure of the Extender or cable
will not result in loss of operation, and the replacement of the failed
component can occur without loss of service.

A failure in the remote location will only affect the remote I/O modules
associated with the remote Extender.

Refer to the front-panel LEDs and digital output to identify fault conditions
detected by the link, specifically loss of lock and receive error.

Detecting Failover Conditions


A Form C relay is provided to indicate a link failure. When a BEM
experiences a failover between the redundant links, a momentary relay
closure occurs. Attach the DI Contact on module front panel to a Digital
Input Module to monitor this logic output. The module produces a logic
output to indicate and report the occurrence of an optical link failover or link
failure.

Use a front panel pushbutton to test the redundant links. The pushbutton
initiates a failover between the two links.

Cabling Recommendations
To augment cable reliability, Metso Automation recommends the following
cabling practices:

For configurations using either single or redundant pairs of BEMs, use two
separate, four-fiber optical cables (Part No. CON064-LLLL). Attach one
cable to Link 1 and the other cable to Link 2. As noted, route cables
separately to minimize the possibility of damage to both cables.

For each link connect two of the four available connector ends to the optical
transceiver connectors. The two extra, unused fibers in each cable serve as
spares in the event that the active fibers are cut or damaged.

Metso Automation 278596 11-13


maxPAC Hardware Reference Guide

Specifications
Model:
IOP371 Bus Extender Module (Part No. 181500)

Distance:
Up to 2000 meters

Speed:
Maintain Model IOP I/O bus communications

I/O addresses:
Up to 255 unique I/O addresses per DPU

Link bus loading:


One module

Number of I/O Modules Per Location:


On the DPU Local Bus: 60 maximum including local BEM(s)
On Each Remote BEM Bus: 45 maximum including remote BEM

Approval Bodies and Standards


The product meets SAMA PMC33.1 EMI/RFI specs at three different
frequencies, and is designed to meet IEC 801-2 static specification (8,000
Volts).

Power Requirements
24 Volts @0.5 amps

Environment
The module operates in the temperature range of 0oC to 60oC at a relative
humidity range of 0 to 90%, noncondensing.

Optical cable
62.5/125 m multimode fiber optic cable
CON062-LLLL Two- fiber optical cable
CON064-LLLL Four-fiber optical cable

Operating wavelength
1300 nm.

11-14 Metso Automation 278596


Chapter 12

QuadPAT
Module IOP336
QuadPAT Termination
Module IOP337

Overview
The maxPAC Quad Position Adjusting (QuadPAT) module in combination
with the maxPAC Quad PAT termination assembly produces PAT increase
and decrease outputs (120V or open collector) for single phase AC drive
units or three-phase power switches. The module accommodates 1000-ohm
slidewires or two-wire rotary position sensors. In addition, the maxPAC
Quad PAT termination includes the DI circuits for sensing the drive unit
limit switches.

Features

Self-calibration on power up
Software stored in FLASH
Field to logic Isolation
Channel-to-channel Isolation
Fast scan time

Metso Automation 278596


maxPAC Hardware Reference Guide

Front Panel
The QuadPAT front panel contains bicolor LEDs to report the status of the
increase and decrease outputs and limit switch for each channel and also
LEDs for module status indication. It also includes the two I/O connectors.
The top connector includes all the digital I/O and the analog signals are
available at the bottom connector.

LED Indication
A pair of bi-color LEDs provides I/O state indication for each QuadPAT
channel. The DO is the first LED of the pair and the DI is the second LED.
For normally closed limit switches (open at a limit) the LED indication for
each digital input and digital output pair is as follows:

LED Color Description


Output Green Decrease
Output Red Increase
Limit Green Decrease Limit
Limit Red Increase Limit
Limit Amber No limit
Limit OFF No Power

For normally open limit switches the LED indication is as follows:

LED Color Description


Output Green Decrease
Output Red Increase
Limit Green Increase Limit
Limit Red Decrease Limit
Limit OFF No limit
Limit OFF No Power

In addition, the lower green LED, labeled Active at the bottom of the front
panel, is on when power is on and the DPU is communicating with the
module. The upper green LED at the bottom of the front panel indicates that
loop power is turned on.

Jumper Configuration
Refer to the following table for the jumper setting information that is
applicable to this module. Bold indicates the default position of the jumper.

12-2 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337
Jumper Installed Not Installed
W1 Not Used
W2 Backup Primary
W3 Not Used
W4 Ignore Limit Stop on Limit
W5 Common I/O Redundant
W6 QuadPAT Other

Channel 1
Jumper Slidewire Rotary sensor
W11 A B
W12 C A,B
W13 A B
W14 Installed Not Installed
W15 A Not Installed
W16 Installed Not Installed
W17 Not Installed Installed

Channel 2
Jumper Slidewire Rotary sensor
W21 A B
W22 C A,B
W23 A B
W24 Installed Not Installed
W25 Installed Not Installed
W26 Not Installed Installed
W29 A Not Installed

Channel 3
Jumper Slidewire Rotary sensor
W31 A B
W32 C A,B
W33 A B
W34 Installed Not Installed
W35 A Not Installed
W36 Installed Not Installed
W37 Not Installed Installed

Channel 4
Jumper Slidewire Rotary sensor
W41 A B
W42 C A,B
W43 A B
W44 Installed Not Installed
W45 Installed Not Installed
W46 Not Installed Installed
W49 Installed Not Installed

Metso Automation 278596 12-3


maxPAC Hardware Reference Guide

Bus Address
This module requires four bus addresses and provides four channels. Each
module address must be a multiple of 4 (i.e. 32, 36, 40, 44, 56, etc.) in the
range of 32 to 248. Addresses 0 to 31 are reserved for digital input modules.
The two address rotary switches can be found at the upper right hand corner
of the module above the edge connector as follows:

Most Significant

Less Significant

DPU Compatibility
This module is only compatible with DPU4E and DPU4F

Module Operation
This microprocessor-based module provides a full complement of I/O. It
includes eight analog inputs, four analog outputs, 8 digital inputs and eight
digital outputs. Successive approximation 14-bit A/D converters digitize the
input signals in microseconds. Sixteen-bit digital to analog output
conversion also provides fast analog outputs. Both the analog inputs and
analog outputs self-calibrate on power up. Optical isolation is provided
between the field circuits and the logic. DC/DC converters provide isolated
power to the A/D converters and analog output circuits. The microprocessor
communicates serially with the field circuits via optical isolators.
The analog outputs provide the reference for the slidewires. The analog
inputs measure each slidewire feedback and reference. The digital outputs
provide increase and decrease signals to the triac circuits, while the digital
inputs monitor the state of the limit switches.

The microprocessor circuit includes a 25Mhz 68332 processor and associated


memory. A FPGA includes the I/O bus control logic and provides support
logic for the other circuits.

12-4 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337
+/-15V
24V DC/DC 24V
4-20ma or
+/-10V D/A
4-20 ma 2 channels
Optical
0-2.5V Isolation
4-20 ma A/D
0-2.5V 4 channels
4-20 ma

5V
DC/DC

24V

+/-15V DC/DC
4-20ma or
+/-10V D/A RAM
2 channels FLASH 64K
4-20 ma Optical Parity
2Mbit
Isolation
0-2.5V
4-20 ma A/D
0-2.5V 4 channels
4-20 ma
68332G CLOCK
Processor
5V
DC/DC 25MHz

DI1 DI8
FPGA
I/O Bus
Open I/O Bus
DO1 DOI8 Collector Interface
Drivers

Output
Virtual
Power

QuadPAT Termination

The IOP346 QuadPAT Termination interfaces with the QuadPAT module via
cable CTO301. It is a DIN rail mounted assembly with two 16-point Euro-
style plugs providing the interface for the field connections. The
QUADPAT module provides 24-volt power for the Termination circuits.
The termination assembly provides the following functions:

It provides four optically isolated TRIAC circuits. Each circuit includes a


pair of TRIACs for the increase and decrease signals as well as the
output suppression circuits

Metso Automation 278596 12-5


maxPAC Hardware Reference Guide

Each channel also includes digital input circuits to monitor the two limit
switches associated with each channel. The state of the limit switches is
provided to the DPU buffer.

Feedback Options

Slidewire: The bottom of the slidewire is connected to ground through a


100-ohm resistor to allow detection of an open slidewire. A reference
current of 2 ma produces an approximate voltage range of 0.5 to 2 volts for
the slidewire. Open wipers are detected through a pulldown resistor on the
slidewire input. If a high or low signal reading is detected when the module
is scanned by the DPU, outputs to the module from the DPU will be
suspended.

Rotary Sensor: Power to the sensor is supplied from the field 24V. The
sensor 4-20ma signal results in a 0.4 to 2V signal across the internal 100 ohm
sensing resistor. Overvoltage protection is provided for the 100 shunt. If a
shorted sensor or an open circuit is detected by the DPU, outputs to the
module are suspended.

Output Options
Single-Phase and Three-Phase Drive Units
TRIAC outputs require the use of the termination assembly.
DC Power Switch
Open collector outputs are wired directly from the module, and the
termination assembly is not required. A commoning strip is required for the
ground connections to the individual power switches. No IEEE surge
suppression is available for the open collector outputs.

Limit Switch Detection

The module detects the state of the drive unit limit switches via the
termination assembly. For Normally Closed switches, the module inhibits
drive unit motion when it detects an open limit switch in the direction of
travel. The module will ignore the limit switches if jumper SW4 is

12-6 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

installed. If Normally Open contacts are used, jumper SW4 must be installed
and any interlock while the limit is exceeded must be done in the control
logic or external hardware.

Note: The QPAT buffer includes status attributes (Out0xLimitHi or


Out0xLimitLo) that represent the state of the High and Low Limit inputs.
These inputs are normally wired to the limit contacts of the drive unit. The
contacts are most often Normally Closed contacts and open when the limit is
reached. In this case, when the contact is open (the limit exceeded) the status
will be equal to one. If Normally Open contacts are used, the status
attributes will be one and go to zero when the limit is reached (contact
closed). The jumper on the card to ignore the limit does not affect these
status attributes

Redundant Configuration
Standby Mode
Standby mode is activated when a QUAD PAT module is one of a redundant
pair in a backup configuration and its DPU is inactive. All outputs from the
module will be suspended while in the standby mode. The slidewire
reference is also disabled in the standby mode.

Metso Automation 278596 12-7


maxPAC Hardware Reference Guide

Jumper Positions
Jumpers must be re-positioned to remove the 100-ohm slidewire end resistor
and the open slidewire detection resistor from the circuit. See jumper table.
These resistors must be mounted externally.
Jumper W2 is set to designate one module as primary and the other as
backup.
Jumper W5 is removed from both modules to defeat force INT.

Terminal Connections
When using the Quad PAT modules in a redundant configuration all
terminals must be wired in parallel.

Backup transfer Bump


The specified backup transfer bump is 0.2%. On insertion or withdrawal of
an inactive module, up to a 1% temporary bump can occur and the drive unit
will return to its original position within a few seconds depending on the
stroke time of the drive. This bump can be avoided by disabling the ac
power to the inactive module termination, while inserting or withdrawing the
inactive module.

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


ADC Serial Transmit Fault 0x12
ADC Serial Transmit Fault 0x13
ADC Sanity Test Failed 0x15
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Error 0x32
FPGA Download Error (power-on) 0x33
FLASH Erase Error 0x35
FLASH Programming Error 0x36
FPGA Error 0x37
Serial I/O Failure 0x38
Parity Error 0x39

12-8 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

Module Field Connections


P2 P3

1 1
DEC1 (DO01) Reference Out 1
2 2
INC1 (DO02) Feedback1/Field 24V
3 3
HI LIM1 (DI01) Return/AI In
4 4
LO LIM1 (DI02) Field Ground
5 5
DEC2 (DO03) Reference Out 2
6 6
INC2 (DO04) Feedback2/Field 24V
7 7
HI LIM2 (DI03) Return/4-20ma In
8 8
LO LIM2 (DI04) Field Ground
9 9
DEC3 (DO05) Reference Out 3
10 10
INC3 (DO06) Feedback3/Field 24V
11 11
HI LIM3 (DI05) Return/4-20ma In
12 12
LO LIM3 (DI06) Field Ground
13 13
DEC4 (DO07) Reference Out 4
14 14
INC4 (DO08) Feedback/Field 24V
15 15
HI LIM4 (DI07) Return/4-20ma In
16
16
LO LIM4 (DI08) Field Ground
17
24V
11
18
GND

Metso Automation 278596 12-9


maxPAC Hardware Reference Guide

Termination Field Connections Channels 1-2

Field P2 P1 module

1 1
CH1 120V ac CH1 Decrease
2 2
CH1 ac neutral CH1 Increase
3 3
CH1 ac neutral CH1 HI Limit
4 4
CH1 Decrease CH1 LO LIMIT
5 5
CH1 Increase CH2 Decrease
6 6
Hi Limit1 CH2 Increase
7 7
Limit Com CH2 Hi Limit
8 8
Lo Limit1 CH2 Lo Limit
9 9
CH2 120V ac
10 10
CH2 ac neutral
11 11
CH2 ac neutral
12 12
CH2 Decrease
13 13
CH2 Increase
14 14
Hi Limit2
15 15
Limit Com
16 16
Lo Limit2
17
24V

18
Logic Ground

12-10 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

Termination Field Connections Channels 3-4

Field P3 P1 module

1 1
CH3 120V ac
2 2
CH3 ac neutral
3 3
CH3 ac neutral
4 4
CH3 Decrease
5 5
CH3 Increase
6 6
Hi Limit3
7 7
Limit Com
8 8
Lo Limit3
9 9
CH4 120V ac CH3 Decrease
10 10
CH4 ac neutral CH3 Increase
11 11
CH4 ac neutral CH3 Hi Limit
12 12
CH4 Decrease CH3 Lo Limit
13 13
CH4 Increase CH4 Decrease
14 14
Hi Limit4 CH4 Increase
15 15
Limit Com CH4 Hi Limit
16 16
Lo Limit4 CH4 Lo Limit
17
24V

18
Logic Ground

Metso Automation 278596 12-11


maxPAC Hardware Reference Guide

Group1 Analog I/O Configuration


Slidewire Rotary Sensor
P3 P3

AO01(4-20ma) AO01(4-20ma)
1 W15 A 1 W15 A

B B
AO01(+/-10V) AO01(+/-10V)
A A
W11 AuxAI01 W11 AuxAI01
B B

W16 W17
F1
W16 W17
F1
24VF1 24VF1

2 W12 2 W12
A A
AI01 AI01
C B C B
100K 100K

3 A W13 A W13
3
W14 W14
B therm B therm

F1 F1
4 shunt 4 shunt

F1 F1

AO02(4-20ma) AO02(4-20ma)
5 W29 W29
5

W25 W26 W25 W26

A A
AuxAI02 AuxAI02
W21 B W21 B
24VF1 24VF1
F1 F1
6 A 6 A
AI02 AI02
C
W22 B
W22 C B

W23 100K W23 100K


7 A 7 A
B therm W24 B therm W24

F1 F1
shunt shunt
8 8

F1 F1

12-12 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

Group2 Analog I/O Configuration


Slidewire Rotary Sensor
P3 P3

AO03(4-20ma) AO03(4-20ma)
9 W15 A 9 W35 A

B B
AO03(+/-10V) AO03(+/-10V)
A A
W11 AuxAI03 W31 AuxAI03
B B

W36 W37
F2
W36 W37
F2
24VF2 24VF2

10 W12 10 W32
A A
AI03 AI01
C B C B
100K 100K

11 A W13 A W33
11
W14 W34
B therm B therm

F2 F2
12 shunt 12 shunt

F2 F2

AO02(4-20ma) AO04(4-20ma)
13 W49 W49
13

W45 W46 W45 W46

A A
AuxAI04 AuxAI04
W41 B W41 B
24VF1 24VF2
F2 F2
14 A 14 A
AI04 AI04
C
W42 B
W22 C B

W43 100K W43 100K


15 A 15 A
B therm W44 B therm W44

F2 F2
shunt shunt
16 16

F2 F2

Metso Automation 278596 12-13


maxPAC Hardware Reference Guide

Digital I/O Configuration Channels 1-2


Single-Phase and Three-Phase Motors

P2 Termination P1 P2 Module
1
H
120 AC 2
N
3
DEC1 4
M
1 1
5 DO01
INC1

2 2
DO02
3 3
HI LIM 1 DI01
6

7 4 4
DI02
8
LO LIM 1 9
H
120 AC
N 10

11

DEC212
M
5 5
INC2 13 DO03

6 6
DO04
7 7
DI03
HI LIM 2 14

15 8 8
DI04
16
17 17
LO LIM 2 24V
18 18
GND

12-14 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

Digital I/O Configuration Channels 3-4


Single-Phase and Three-Phase Motors

P3 Termination P1 P2 Module
1
H
120 AC 2
N
3
DEC3 4
M
9 9
5 DO05
INC3
10 10
DO06
11 11
DI05
6
HI LIM 3 12
7 12
COM DI06
8
LO LIM 3
9
H
120 AC
N 10
11

DEC4 12
M
13 13
INC4 13 DO07

14 14
DO08
15 15
DI07
HI LIM 4 14
15 16 16
COM DI08
16
LO LIM 4 17
17
24V
18 18
GND

Metso Automation 278596 12-15


maxPAC Hardware Reference Guide

Digital I/O Configuration - DC Power Switches

P2 Module

Dec 1
Power DIO1
Switch Inc 2 DIO2
3

Dec 5
Power DIO3
Commoning Strip
Switch Inc
6 DIO4
7

9
Power DIO5
Switch 10
DIO6

11

12

13
Power DIO3
Switch 14
DIO4

15

16

17
24V
18
GND

12-16 Metso Automation 278596


QuadPAT Module IOP336
QuadPAT Termination IOP337

Specifications

TRIAC Outputs 120VAC:


Maximum Voltage: 200 VAC
Continuous on-state current: 2A
On-state voltage: 1.6 VAC
Off-state current: 3.5 mA
Hold Current: 50 mA

Open Collector Outputs


Maximum Current: 100mA
Maximum Voltage: 28VDC
Maximum on-resistance: 0.2 ohms

Power
24Vdc system supply 400 ma

Temperature 0-60 degrees C


Humidity 0-90% no-condensing
Surge (TRIAC Outputs only) IEEE-472-1974

Metso Automation 278596 12-17


Chapter 13

Turbine Valve Positioner


Module IOP341
Turbine Valve Termination
Module IOP342

Overview
The Turbine Valve Positioner module implements the logic for real-time
closed loop control of a single turbine valve. The module provides two
independent and electrically isolated channels. Each channel includes a coil
drive output and a position feedback input normally receiving inputs from
position transducers. Each channel also includes auxiliary inputs for
loopback measurement of the output signal.
In addition, a turbine speed input is provided as a service with the intent of
bringing back three speed signals, one on each of three Turbine Valve
Positioner modules for triple redundancy of speed input.

The product consists of a maxPAC Positioning Module and a Turbine Valve


Termination card. The Termination card provides both current and voltage
outputs for characterizing the output for different coil types. It also provides
signal conditioning for the frequency input.

The logic shown in the following sketch is programmed in the maxDPU4F


Atom Compiler language and may be modified by a trained engineer via
tools provided. It is one of up to nine personalities that can be downloaded
to the module and stored in flash memory. A cable is provided for
downloading the configuration. Personality selection, the configuration
Tuning constants for the PI loop, I/O status, and other signals are accessible
via the maxDPU4F.

Metso Automation 278596


maxPAC Hardware Reference Guide

Pos
Valve
Pos > 4-20 ma
Pos

Mode

Governor or
Servo
Throttle Valve
Amp
Position Demand
+/- 10 volt or
K+ +/- 40 ma
Pos Servo
Amp
Err
Coil(s)
Status
Turbine
Speed Freq
Speed

Positioner Front Panel


The Turbine Valve Positioner front panel contains LEDs to report the status
of the digital inputs and outputs, and LEDs for module status indication. It
also includes the two I/O connectors and a connector for the configuration
cable.

13-2 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

Features

Self-calibration on power-up
Software stored in FLASH
Field to logic isolation
Channel-to-channel isolation
Fast Scan Time
Fast slew rate
Full complement of I/O
Frequency inputs
On-line diagnostics
Downloadable personality

LED Indication
Individual bicolor front-panel LEDs provide I/O state indication for Trip
output and frequency input. Two bicolor LEDS, Stat 1 and Stat 2 provide
diagnostic indication

In addition, the lower green LED, labeled Active at the bottom of the front
panel, is on when power is on and the DPU is communicating with the
module. The upper green LED at the bottom of the front panel indicates that
loop power is turned on.

Metso Automation 278596 13-3


maxPAC Hardware Reference Guide

Jumper Configuration
The Turbine Valve Positioner module uses a multi-purpose-positioning
module with multiple jumper options as its base. The base module has four
AI/AO and eight DI/DO. Not all the jumpers are used for this application.
Jumpers W1-W4 at the rear of the module are for factory test only and
must not be installed. Refer to the following table for the jumper setting
information that is applicable to this module. Bold indicates the default
position.

Channel 1 Channel 2
Jumper Position Jumper Position
4-20ma +/-10V 4-20ma +/-10V
W11 B W21 A
W12 A, B W22 C
W13 B W23 B
W14 Not Installed W24 Not Installed
W15 A B W29 Not Installed
W16 OUT IN W25 OUT IN
W17 OUT IN W26 OUT IN

Channel 3 Channel 4
Jumper Position Jumper Position
4-20ma +/-10V 4-20ma +/-10V
W31 B W41 A
W32 A, B W42 C
W33 B W43 B
W34 Not Installed W44 Not Installed
W35 A B W49 Not Installed
W36 OUT IN W45 OUT IN
W37 OUT IN W46 OUT IN

13-4 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

Refer to the following table for the Turbine Valve Termination jumpers.
W11 and W12 select the resistance in series with the +/-10V or 4-20 ma
output from the Positioner module. W13 and W14 select the +/-40 ma
output or the output selected in the Positioner module (4-20 ma or +/-10V).
When the +/-40 ma output is selected, the +/-10V output must be selected in
the Positioner module. Bold indicates the default position:

Jumper function A B Installed Not Installed


W1 Wetting Local Remote
Voltage
W2 Frequency 0.2 10V 24V
Voltage
W11 Channel 1 160 ohms 100 ohms 210 ohms
Series R and +/-10V or 4-20ma
W12 Channel 2 160 ohms 100 ohms 210 ohms
Series R and +/-10V or 4-20ma
W13 V/I Out +/- 40 ma +/-10 volts
or 4-20ma
W14 V/I Out +/- 40 ma +/-10 volts
or 4-20ma

Bus Address
This module consumes two bus addresses. The two address rotary switches
can be found at the upper right hand corner of the module above the edge
connector as follows:

Most Significant

Less Significant

DPU Compatibility
This module is only compatible with maxDPU4F

Module Operation
This microprocessor-based module provides a full complement of I/O. It includes
four analog inputs, four analog inputs, 8 digital inputs and eight digital outputs. Four
auxiliary analog inputs are also included for diagnostic use. Successive
approximation 14-bit A/D converters digitize the input signals in microseconds.

Metso Automation 278596 13-5


maxPAC Hardware Reference Guide

Sixteen-bit digital to analog output conversion also provides fast analog output
current or voltage. Both the analog inputs and analog outputs self-calibrate on
power up.

+/-15V
24V DC/DC 24V
4-20ma or
+/-10V D/A
4-20 ma 2 channels
Optical
0-2.5V Isolation
4-20 ma A/D
0-2.5V 4 channels
4-20 ma

5V
DC/DC

24V

+/-15V DC/DC
4-20ma or
+/-10V D/A RAM
2 channels FLASH 64K
4-20 ma Optical Parity
2Mbit
Isolation
0-2.5V
4-20 ma A/D
0-2.5V 4 channels
4-20 ma
68332G CLOCK
Processor
5V
DC/DC 25MHz

DI1 DI8
FPGA RS232
I/O Bus
Open I/O Bus
DO1 DOI8 Collector Interface
Drivers

Output
Virtual
Power

The analog I/O is separated into two electrically isolated groups as shown in the
functional sketch. There is also optical isolation between the field circuits and the
logic. DC/DC converters provide isolated power to the A/D converters and analog
output circuits. The microprocessor communicates serially with the field circuits
via optical isolators.
Each of the four analog output circuits provides 4-20 ma. Two of the circuits
provide 10 to +10 volt outputs. The A/D in each group has four inputs. Two of
the inputs are used as auxiliary inputs for diagnostic monitoring of the analog
outputs.

13-6 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

The microprocessor circuit includes a 25Mhz 68332 processor and associated


memory. The Time Processor Unit (TPU) included in the 68332 processor is used
to process the frequency measurements. A FPGA includes the I/O bus control logic
and provides support logic including parity.

Turbine Valve Termination

The IOP342 Turbine Valve Termination interfaces with the Positioner


module via cable CTO302. It is a DIN rail mounted assembly with an 18-
point Euro-style plug providing the interface for the field connections. The
Positioner module provides 24-volt field power for the Termination circuits.
The termination assembly provides the following functions:

It coverts the +/-10V signals to 0-2 volts plus sign to be fed to the
module for diagnostic loopback.

A voltage-to-current converter converts the +/-10V signals to 40 to 40


ma. Either voltage or current output is available via jumper selection.

A current sense circuit measures the output current and provides a 0-2v
signal proportional to the current to the I/O module.

It conditions and isolates the frequency input and provides a 5-volt TTL
compatible signal to the module.

Configuration
The Turbine Valve Module provides a serial port for downloading the
configuration programs that are generated and compiled with the maxPAC
Positioning Module Compiler Tool. Up to nine programs (personalities) can
reside in the module FLASH. The interpreter code running in the module
executes any one of the nine personalities selected via the DPU. A module
personality typically defines an exchange of variable data between the DPU
POS Buffer and the module I/O and other parameters defined in the module
shell; it also includes the logic sequence that implements the required
application. See the maxPAC Positioning Module Programming Guide.

Calibration
The Turbine Valve Module can be configured via on-board jumper selection
to provide either a current or voltage output. The module is factory
calibrated for 4-20 ma current outputs and the calibration constants are stored
in FLASH. Calibration is only required when the FLASH program is
upgraded.

Metso Automation 278596 13-7


maxPAC Hardware Reference Guide

The Module Compiler provides functions that allow the user to either
override or restore the factory calibration values. When voltage outputs are
used, the factory calibration values for channels 1 and 3 must be changed to 0
and 65535. This can be accomplished by setting AOLo and AOHi for the
two channels in the first pass of the application program, or by downloading
a calibration program that overrides the values stored in FLASH.

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


ADC Serial Transmit Fault 0x12
ADC Serial Transmit Fault 0x13
ADC Sanity Test Failed 0x15
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32
FLASH Erase Error 0x35
FLASH Programming Error 0x36
FPGA Error 0x37
Serial I/O Failure 0x38
Parity Error 0x39

The turbine valve module can also execute on line diagnostics to verify the
integrity of the loop. This test must be defined in the personality program.
The module shell includes four AOs (AO01-AO04), four AIs (AI01-AI04),
four Auxiliary AIs (AuxAI01- AuxAI04), eight DIs (DI01-DI08) and eight
DOs (DO01 DO08). These shell variables are associated with I/O signals
at the module I/O connector. The bipolar analog outputs generated by the
module are converted at the termination assembly to a 0-2V plus sign signal.
As shown in the Group1 Analog I/O configuration sketches at the end of the
chapter, the analog output from the module is buffered by the termination
and fed back to AuxAI02. The coil current is fed back to AI02, while the
sign is available as status DI02 (1 is negative).

The personality program must define the input types to be 0-2V. Also the
analog value read at those inputs must be sign adjusted. For example, the
configuration program includes the following code to define the input types
and adjust the sign.

13-8 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

If FirstPass
AIType01 = 1 ;4-20ma AI
AIType02 = 3 ;0-2V AI
AuxAIType02 = 3
EnableOutputs = 1
EndIf

If DI02 = 0
Coil1ACurRaw = AuxAI02
Coil1V = AI02
Else
Coil1ACurRaw = AuxAI02 * -1.0
Coil1V = AI02 * -1.0
EndIf

Metso Automation 278596 13-9


maxPAC Hardware Reference Guide

Module Field Connections


P2 P3

1 1
DO1 4-20 ma or +/-10V out
2 2
DO2 Ch 1-2 Field Power
3 3
DI1 4-20 ma input
4 4
DI2 Ch 1-2 Field Ground
5 5
DO3 Voltage Feedback
6 6
DO4 Voltage Feedback
7 7
DI3
8 8
DI4
9 9
DO5 4-20 ma or +/-10V out
10 10
DO6 Ch 3-4 Field Power
11 11
DI6 4-20 ma input
12 12
DI7 Ch 3-4 field Ground
13 13
DO7 Voltage Feedback
14 14
DO8 Voltage Feedback
15 15
DI7
16
16
DI8
17
24V
11
18
GND

13-10 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

Termination Field Connections


Field P2 P1 module

1 1
Coil 1 (+) Field 24V_1
2 2
Coil 2 (-) Field Ret_1
3 3
Chassis Gnd 4-20 ma or +/-10V out
4 4
Field 24V_1 +/-10V_1 loopback
5 5
4-20ma input Coil_1 Current loopback
6 6
Coil 1 (+) Ch 1-2 Field Ground
7 7
Coil 2 (-) Field 24V_2
8 8
Chassis Gnd Field Ret_2
9 9
Field 24V_2 4-20 ma or +/-10V out
10 10
4-20ma input +/-10V_2 loopback
11 11
Coil_2 Current loopback
12 12

24V
13 13
frequency
DI2 (+/-10V_1 sign)
14 14
DI3 (+/-10V_2 sign)
0.2-10V
15 15
frequency
DI1 (frequency)
16 16
NO DO1
17
COM 24V
11
18
NC Logic Ground

Metso Automation 278596 13-11


maxPAC Hardware Reference Guide

Group1 Analog I/O Configuration

Termination Module
P2 P1 P3

+/- 40 ma
W13
AO01(4-20ma)
50 50 62 50 3 1 W15 A
1
B
AO01(+/-10V)
Current W11 A
W11 AuxAI01
Sense B

2
Sign 1 Buffer F1
24VF1
F1
3 1 2 W12
A
24VF1 C AI01
B
4
24VF1 100K

4-20 ma 6 3 A W13
5
W14
B therm

F1
shunt
2 4

F1
F1

W29 AO02(4-20ma)
4 5
Output voltage

A
AuxAI02
W21 B
24VF1
F1
Output current 5 6 A C
AI02
W22 B

W23 100K
7 A

B therm W24

F1
shunt
8

F1

13-12 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

Group2 Analog I/O Configuration

Termination Module
P2 P1 P3

+/- 40 ma
W14
AO03(4-20ma)
50 50 62 50 9 9 W35 A
6
B
AO03(+/-10V)
Current W12 A
W31 AuxAI03
Sense B

7
Sign 2 Buffer F1
24VF3
F2
8 7 10 W32
A
24VF2 C AI03
B
9
24VF2 100K

4-20 ma 12 11 A W33
10
W34
B therm

F2
shunt
8 12

F2
F2

AO04(4-20ma)
10 13 W49

Output voltage

A
AuxAI04
W41 B
24VF2
F2
Output current 11 14 A C
AI04
W42 B

W43 100K
15 A

B therm W44

F2
shunt
16

F2

Metso Automation 278596 13-13


maxPAC Hardware Reference Guide

Digital I/O Configuration

Termination Module
P2 P1 P2

W1
24VF2
12
15 3
DIO1
13

13 7
W2 Sign 1 DIO3
14
Conditioning 14 8
15 Circuit Sign 2 DIO4

16

17 16 2
DO02

18

17 17
24V

18 18
GND

13-14 Metso Automation 278596


Turbine Valve Positioner IOP341
Turbine Valve Termination IOP342

Specifications
Turbine valve Outputs
Analog
+/- 10 VDC at 40 ma. or
+/- 40 ma at 200 ohms max
4-20 ma (isolated 24V supplied from the system)
Accuracy:
+/-10V, 4-20 ma: 0.25% of full scale
+/- 40 ma: +/-1% of full scale
Resolution: 16 bits
Slew Time: 5 msecs
Digital
Form C Relay
5A @ 250VAC, 3A @ 30VDC, 0.3A @110VDC

Turbine valve Inputs


Analog:
4-20 ma (isolated 24V supplied from the system)
Accuracy: 0.15%
Resolution: 14 bits
Scan Time: 5 msecs
Frequency:
Frequency: 0 -10KHz
Accuracy: 0.1% for frequency up to 5KHz,
0.25% for 5KHz 50Kz.
Input voltage: 200 mv. to 10V or 24V.

Isolation
Galvanic isolation between two analog I/O groups.
Common mode between groups: 350V dc or peak ac
Galvanic isolation between field and logic: 500V

RS232 Port: 9600 baud

Power
24Vdc system supply 500 ma

Temperature 0-60 degrees C


Humidity 0-90% no-condensing
Surge IEEE-472-1974

Metso Automation 278596 13-15


Chapter 14

Overspeed Trip
Module IOP345
Overspeed Termination
Module IOP346

Overview
The Overtrip module measures and processes turbine speed from three separate
tachometers based speed inputs without intervention from the DPU. If the
overspeed logic determines that two out of the three inputs exceed a defined
threshold, Trip contacts are energized to protect the turbine from an overspeed
condition.

Raw Speed3
F

Raw Speed2 Turbine


F Speed
Pulses
Raw Speed1
F

DPU Median Field

Runback Status
Runback
Runback % > Output

Median Speed > Trip


Output
Trip %
Trip Status

The product consists of a maxPAC Overspeed Positioning Module and an Overspeed Termination
card. The Termination card provides signal conditioning and isolation for the frequency inputs and
also two form C relays.

Metso Automation 278596


maxPAC Hardware Reference Guide

The logic shown in the sketch is programmed in the maxDPU4F Atom Compiler
language and may be modified by a trained engineer via tools provided. It is one of
up to nine personalities that can be downloaded to the module and stored in flash
memory. A cable is provided for downloading the configuration. Personality
selection, the configuration, I/O status, and other signals are accessible via the
maxDPUF.

Features

Software stored in FLASH


Field to logic isolation
Fast scan time
Fast frequency measurements
On-line diagnostics
Downloadable personality

Overspeed Front Panel


The Overspeed module front panel contains LEDs to report the status of the
digital inputs and outputs, and LEDs for module status indication. It also
includes the two I/O connectors and a connector for the configuration cable.

LED Indication
Individual bicolor front-panel LEDs provide I/O state indication for Trip
outputs and frequency inputs. Two bicolor LEDS, Stat 1 and Stat 2 provide
diagnostic indication

In addition, the lower green LED, labeled Active at the bottom of the front
panel, is on when power is on and the DPU is communicating with the

14-2 Metso Automation 278596


Overspeed Trip Module IOP345
Overspeed Termination IOP 346

module. The upper green LED at the bottom of the front panel indicates that
loop power is turned on.

Jumper Configuration
The Overspeed module uses a multi-purpose-positioning module with
multiple jumper options. Not all the jumpers are applicable for this
application because the analog I/O is not used. Refer to the following table
for the jumper setting information that is applicable to this module.

Jumper Position Jumper Position


W11 B W21 B
W12 A W22 Not Installed
W13 Not Installed W23 Not Installed
W14 Installed W24 Installed
W15 Not Installed W25 Installed
W16 Installed W26 Installed
W17 Installed W29 Not Installed

Jumper Position Jumper Position


W31 B W41 B
W32 Not Installed W42 Not Installed
W33 Not Installed W43 Not Installed
W34 Installed W44 Installed
W35 Not Installed W45 Not Installed
W36 Installed W46 Installed
W37 Installed W49 Installed

Refer to the following table for the Turbine Valve Termination jumpers.Bold
indicated the default positions:

Jumper function Installed Not Installed


W1 Wetting 1 Local Remote
Voltage
W2 Frequency 1 0.2 10V 24V
Voltage
W3 Wetting 2 Local Remote
Voltage
W4 Wetting 2 0.2 10V 24V
Voltage
W5 Wetting 3 Local Remote
Voltage
W6 Wetting 3 0.2 10V 24V
Voltage

Metso Automation 278596 14-3


maxPAC Hardware Reference Guide

Bus Address
This module consumes two bus addresses.

Most Significant

Less Significant

DPU Compatibility
This module is only compatible with DPU4F

Module Operation
This microprocessor-based module provides a full complement of I/O. It includes
four analog inputs, eight analog inputs, 8 digital inputs and eight digital outputs.
The turbine overspeed application utilizes only the digital I/O portion of the module.
The unused analog portion is shown with dashed lines in the functional sketch.

The microprocessor circuit includes a 25Mhz 68332 processor and associated


memory. The Time Processor Unit (TPU) included in the 68332 processor is used
to process the frequency measurements. A FPGA provides support logic including
parity and the I/O bus control logic.

14-4 Metso Automation 278596


Overspeed Trip Module IOP345
Overspeed Termination IOP 346

Positioning Module
+/-15V

24V DC/DC 24V


4-20ma or
+/-10V D/A
4-20 ma 2 channels
Optical
0-2.5V Isolation
4-20 ma A/D
0-2.5V 4 channels
4-20 ma

5V
DC/DC

24V

+/-15V DC/DC
4-20ma or
+/-10V D/A RAM
2 channels FLASH 64K
4-20 ma Optical Parity
2Mbit
Isolation
0-2.5V
4-20 ma A/D
0-2.5V 4 channels
4-20 ma
68332G CLOCK
Processor
5V 25MHz
DC/DC

DI1 DI8
FPGA RS232
I/O Bus
Open I/O Bus
DO1 DOI8 Collector Interface
Drivers

Output
Virtual
Power

Overspeed Trip Termination

The IOP346 Turbine Overspeed Termination interfaces with the Positioner


module via cable CTO303. It is a DIN rail mounted assembly with an 18-
point Euro-style plug providing the interface for the field connections. The
Positioner module provides 24-volt field power for the Termination circuits.
The termination assembly provides the following functions:

It provides signal conditioning and optical isolation for the three


frequency inputs and provides 5-volt square waves to the module.

Metso Automation 278596 14-5


maxPAC Hardware Reference Guide

Two form C relay outputs are included.

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


ADC Serial Transmit Fault 0x12
ADC Serial Transmit Fault 0x13
ADC Sanity Test Failed 0x15
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32
FLASH Erase Error 0x35
FLASH Programming Error 0x36
FPGA Error 0x37
Serial I/O Failure 0x38
Parity Error 0x39

14-6 Metso Automation 278596


Overspeed Trip Module IOP345
Overspeed Termination IOP 346

Module Field Connections

P2 P3

1 1
DO01
2 2
DO02 24V Field Power
3 3
DI01
4 4
DI02 Field Ground
5 5
DO03
6 6
DO04
7 7
DI03
8 8
DI04
9 9
DO05
10 10
DO06
11 11
DI06
12 12
DI07
13 13
DO07
14 14
DO08
15 15
DI07
16 16
DI08
17
24V
11
18
GND

Metso Automation 278596 14-7


maxPAC Hardware Reference Guide

Termination Field Connections

Field P2 P1 module

1 1
Field 24V
24V
frequency 2 2
Field 24V
3 3
Field Ground
0.2-10V
frequency 4 4
Field Ground
5 5
Frequency 1
24V 6
6
frequency

7 7
Frequency 2
0.2-10V
frequency 8 8

9 9
Frequency 3
24V
10 10
frequency

11 11

0.2-10V 12
frequency 12

13 13
NO DO01
14 14
COM DO02
15 15
NC 24V
16 16
NO 24V
17
COM Logic Ground
11
18
NC Logic Ground

14-8 Metso Automation 278596


Overspeed Trip Module IOP345
Overspeed Termination IOP 346

Group1 Analog I/O Configuration

Termination Module
P2 P1 P3

AO01(4-20ma)
1 W15 A

B
AO01(+/-10V)
A
W11 AuxAI01
B

1 F1
24VF1

2 2 W12
A
24VF1 C AI01
B
100K

3 A W13
W14
3 B therm

F1
4 shunt
4

F1
F1

AO02(4-20ma)
5 W29

A
AuxAI02
W21 B
24VF1
F1
6 A C
AI02
W22 B

W23 100K
7 A

B therm W24

F1
shunt
8

F1

Metso Automation 278596 14-9


maxPAC Hardware Reference Guide

Group2 Analog I/O Configuration


Termination Module
P2 P1 P3

AO03(4-20ma)
9 W35 A

B
AO03(+/-10V)
A
W31 AuxAI01
B

F2
24VF2

10 W32
A
C AI03
B
100K

11 A W33
W34
B therm

F2
12 shunt

F2

AO04(4-20ma)
13 W49

A
AuxAI04
W41 B
24VF2
F2
14 A C
AI04
W42 B

W43 100K
15 A

B therm W44

F2
shunt
16

F2

14-10 Metso Automation 278596


Overspeed Trip Module IOP345
Overspeed Termination IOP 346

Digital I/O Configuration

P2 Termination P1 P2 Module

W1
24VF2
12
5 3
DIO1
13

W2
14
Conditioning
15 Circuit

W3
24VF2
12
7 7
DIO3
13

W4
14
Conditioning
15 Circuit

W5
24VF2
12 9 11
DIO5
13

W6
14
Conditioning
15 Circuit 2
13
DO02
13

14

15
14 6
DO04
16
15
17
16 17
24V
18
17

18 18
GND

Metso Automation 278596 14-11


maxPAC Hardware Reference Guide

Specifications

Frequency Input:
Frequency: 0 -10KHz
Accuracy: 0.1% for frequency up to 5KHz, 0.25% for 5KHz 10KHz.
Input voltage: 200 mv to 10V or 24V.

Digital Output
Form C Relay
5A @ 250VAC, 3A @ 30VDC, 0.3A @110VDC

RS232 Port: 9600 baud

Power
24Vdc system supply 500 ma
Temperature 0-60 degrees C
Humidity 0-90% no-condensing
Surge IEEE-472-1974

14-12 Metso Automation 278596


Chapter 15

HART Input Module IOP307


HART Output Module IOP322
HART Transceiver Module IOP364

Overview
The set of HART maxPAC I/O modules provide eight isolated HART channels with
an independent HART modem/UART per channel. The analog input and output
modules support standard 4-20 ma signals in addition to the digital HART data. The
HART Transceiver card provides the same HART interface without analog input or
output capability; it is intended for adding HART capability to other analog input or
analog output modules.

H
A Features
R
T Fully isolated channels
Hart modem per channel
16 bit A/D and D/A Performance
Standard variables available in
maxDPUF for use in control
Custom interface for special
purpose control

Asset Management through


Metso FieldCare Product line
Hart Module

Metso Automation 278596


maxPAC Hardware Reference Guide

LED Indication
Individual bicolor front-panel LEDs provide I/O state indication for Trip
outputs and frequency inputs. Two bicolor LEDS, Stat 1 and Stat 2 provide
diagnostic indication

In addition, the lower green LED, labeled Active at the bottom of the front
panel, is on when power is on and the DPU is communicating with the
module. The upper green LED at the bottom of the front panel indicates that
loop power is turned on.

Jumper Configuration

The following are the jumper settings for the various HART modules.

Analog Output Module

Jumper Installed Not Installed


W1 MaxPAC-8 address * HART 2 address
W2 Hold Output Reset Output
W3 Secondary Primary
W4 Not used Not used
W5 Common I/O Redundant I/O
* This is a compatibility mode jumper that configures the module to operate
in 8-address mode like the non-HART maxPAC module.

Analog Input and Transceiver Module

Jumper Installed Not Installed


W1 Not used Not used
W2 Not used Not used
W3 Not used Not used
W4 Not used Not used
W5 Common I/O Redundant I/O

Bus Address
These modules normally consume two bus addresses. The HART Output
module consumes eight addresses if set to be compatible with a standard
maxPAC analog output module.

Most Significant

Less Significant

15-2 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364

DPU Compatibility
These modules are only compatible with DPU4F.

Module Operation
These microprocessor-based modules provide eight isolated channels of 4-20 ma
inputs or outputs, including the HART interface for each channel.

The microprocessor circuit includes a 25Mhz 68332 processor and associated


memory. A FPGA provides support logic including parity and the I/O bus control
logic. Optical isolators and a DC/DC converter per channel provide channel to
channel and field to logic isolation as well as field power to each of the channels.
Eight UARTS provide the interface to the HART modems via the optical
isolators. The transceiver module does not include the AI or AO circuits.

Metso Automation 278596 15-3


maxPAC Hardware Reference Guide

Hart Module

DC/DC 24V

***
4-20 ma AI or AO
Optical
Isolation
Hart
Modem

UART I/O Bus


(8) I/O Bus
Interface

DC/DC

*** FPGA RAM


4-20ma AI or AO FLASH 64K
Optical 2Mbit Parity
Isolation
Hart
Modem

68332G CLOCK
Processor
25MHz

*** Not included in Tranceiver Module


RS232

Diagnostics
The module executes diagnostics on power up. When an error is detected on
power-up or during online operation, the front-panel green LED, labeled
Active, blinks the first digit at a slower rate and the second digit at a faster
rate. During normal operation the active LED is on continuously or flashes at
a steady one-second rate when the module is not being scanned. The
diagnostic codes are as follows:

Error Condition Code


ADC Serial Transmit Fault 0x12
ADC Serial Transmit Fault 0x13

15-4 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
ADC Sanity Test Failed 0x15
RAM Test Failure (power-on) 0x22
CPU Stack Error (power-on) 0x23
CPU Error (power-on) 0x24
Checksum Error (power-on) 0x25
Interrupt Error (power-on) 0x26
FPGA Download Error (power-on) 0x32
FLASH Erase Error 0x35
FLASH Programming Error 0x36
FPGA Error 0x37
Serial I/O Failure 0x38
Parity Error 0x39

Metso Automation 278596 15-5


maxPAC Hardware Reference Guide

HART Analog Input Field Connections

P1 P2

1 1
24V 24V
2 2
4-20 ma 4-20 ma
CH1 CH1
3 3

4 4
GND GND
5 5
24V 24V
6 6
4-20 ma 4-20 ma
CH2 CH2 7
7

8 8
GND GND
9 9
24V 24V
10 10
4-20 ma 4-20 ma
CH3 CH3
11 11

12 12
GND GND
13 13
24V 24V

14 14
4-20 ma 4-20 ma
CH4 CH4
15 15

16 16
GND GND

15-6 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
HART Analog Output Field Connections

P1

1
(+)
CH1 4-20 ma in 2
(-)
3
(+)
CH2 4-20 ma in 4
(-)
5
(+)
CH3 4-20 ma in 6
(-)
7
(+)
CH4 4-20 ma in 8
(-)
9
(+)
CH5 4-20 ma in 10
(-)
11
(+)
CH6 4-20 ma in 12
(-)
13
(+)
CH7 4-20 ma in 14
(-)
15
(+)
CH8 4-20 ma in 16
(-)

Metso Automation 278596 15-7


maxPAC Hardware Reference Guide

HART Transceiver Field Connections

P1

1
(+)
CH1 2
(-)
3
(+)
CH2 4
(-)
5
(+)
CH3 6
(-)
7
(+)
CH4 8
(-)
9
(+)
CH5 10
(-)
11
(+)
CH6 12
(-)
13
(+)
CH7 14
(-)
15
(+)
CH8 16
(-)

15-8 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
Transceiver to Analog Input Wiring

Shared IO: Two-wire Transmitter

AI Module - IOP301 24V(+)

1A 1B From Backplane
200
24V(-)
4-20 ma 2
Rs
+
100
Xmitter
Rp A/D
1D -
1
1E
1C

Transceiver Module - IOP361


1

HART
2 MODEM

Metso Automation 278596 15-9


maxPAC Hardware Reference Guide

Transceiver to Analog Input Wiring

Shared IO: Four-wire Transmitter

AI Module - IOP301 24V(+)


From
24V(-) backplane
1A 1B
200

4-20 ma 2
Rs
+
100
Xmitter
Rp A/D
1D -
1
1E
1C

Transceiver Module - IOP361


1

HART
2 MODEM

15-10 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
Transceiver to Analog Input Wiring

Redundant IO: Two-wire Transmitter

(-)
24V
(+) Supply
AI Module - IOP301 24V(+)
From
24V(-) backplane
1A 1B
200

200 2
Rs
Xmitter +
100
100 Rp A/D
1D -
1
1E
1C

AI Module - IOP301 24V(+)


From
24V(-) backplane
1A 1B
200

2
Rs
+
100
Rp A/D
1D -
1
1E
1C

Transceiver Module - IOP361

HART
MODEM
2

Metso Automation 278596 15-11


maxPAC Hardware Reference Guide

Transceiver to Analog Input Wiring

Redundant IO: Four-wire Transmitter

AI Module - IOP301 24V(+)


From
24V(-) backplane
1A 1B
200

200 2
Rs
+
100
100 Rp A/D
Xmitter
1D -
1
1E
1C

AI Module - IOP301 24V(+)


From
24V(-) backplane
1A 1B
200

2
Rs
+
100
Rp A/D
1D -
1
1E
1C

Transceiver Module - IOP361

HART
MODEM
2

15-12 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
Transceiver to Output Driver Wiring

Output Driver- IOP116


4-20 ma 16

Output
Device D/A
17

Transceiver Module - IOP361


1

HART
2 MODEM

Transceiver to Analog Output Wiring

Analog Output IOP320


4-20 ma 1

Output
Device D/A
2

Transceiver Module - IOP361


1

HART
2 MODEM

Metso Automation 278596 15-13


maxPAC Hardware Reference Guide

HART Analog Input Wiring

Two-WireTransmitter
4-20 ma 1
24V HART AI Module

TRANSMITTER Disconnect for redundant


module input

2 200 ohm

100 ohm TO A/D


shunt
4

To HART modem

Four-Wire Transmitter
1
NOT USED
HART AI Module
24V

Disconnect for redundant


module input
4-20 ma 2 200 ohm

Transmitter 100 ohm TO A/D


Power TRANSMITTER
shunt
4

To HART modem

15-14 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
HART Analog Input Wiring

Redundant Modules: Two-Wire Transmitter

1 HART AI Module
24V(+) 24V

Disconnect for redundant module


TRANSMITTER
input. On when DPU active

2 200 ohm

100ohm TO A/D
shunt
4
24V(-)
To HART modem

1 HART AI Module
24V

Disconnect for redundant module


input. On when DPU active

200 ohm
2

100ohm TO A/D
shunt
4

To HART modem

Metso Automation 278596 15-15


maxPAC Hardware Reference Guide

HART Analog Input Wiring

Redundant Modules: Four-Wire Transmitter

1 HART AI Module
24V

Disconnect for redundant module


input. On when DPU active

2 200 ohm

Transmitter 100ohm TO A/D


Power TRANSMITTER shunt
4

To HART modem

1 HART AI Module
24V

Disconnect for redundant module


input. On when DPU active

200 ohm
2

100ohm TO A/D
shunt
4

To HART modem

15-16 Metso Automation 278596


Hart Analog Input IOP307
Hart Analog Output IOP322
Hart Transceiver IOP364
HART Analog Output Wiring

HART AO Module
Disconnect for redundant module
input. Closed when DPU active 24V(+)

1
4-20 ma HART
D/A
MODEM
OUTPUT
DEVICE
2
24V(-)

Redundant Modules

Disconnect for redundant module HART AO Module


input. Closed when DPU active
24V(+)

1
4-20 ma HART
D/A
MODEM
OUTPUT
DEVICE
2
24V(-)

HART AO Module

24V(+)

1
D/A HART
MODEM

2
24V(-)

Metso Automation 278596 15-17


maxPAC Hardware Reference Guide

Specifications

Channels per Module: 8

I/O Bus Address per Module: 2

Input Specifications
Type: 4-20 ma
Resolution: 16 bits, A/D per channel
Scan time: 20 msecs.
Accuracy: 0.15% of full scale.
Normal Mode Voltage: 50 volts
Normal Mode Rejection: 60 db @50/60 Hz
Common Mode Voltage: 500 volts
Common Mode Rejection: 120 db @50/60 Hz
Isolation: Channel to channel and field to logic

Output Specifications
Type: 4-20 ma
Accuracy: 0.25% of full scale.
Resolution: 16 bits, D/A per channel
Slew Time: 10 msecs
Load: 250 600 ohms
Common Mode Voltage: 150 volts
Isolation: Channel to channel and field to logic

HART
Meets the HART Foundation physical layer requirements
Power
24Vdc system supply 500 ma
Temperature 0-60 degrees C
Humidity 0-90% non-condensing
Surge IEEE-472-1974

15-18 Metso Automation 278596

Potrebbero piacerti anche