220~240V-1Ph-50Hz
M2OC-14HRDN1
M2OC-14HRDN1-Q
M2OC-18HRDN1
M2OC1-18HRDN1-Q
M3OC1-21HRDN1-Q
M3OC-27HRDN1
M3OC1-27HRDN1-Q
M4OC-24HRDN1-Q
M4OC1-27HRDN1-Q
M4OC-27HRDN1
M4OC-36HRDN1-Q
M5OA-36HRDN1-Q
CONTENTS
2. Features .................................................................................. 4
3. Dimensions ............................................................................. 5
8. Troubleshooting ................................................................... 24
1. General information of Outdoor Units
Outdoor unit
The hydrophilic fin can improve the heating efficiency at operation mode.
Anti-rust cabinet
MODEL W D H W1 A B
M2OC-14HRDN1-Q
760 285 590 823 530 290
M2OC-14HRDN1
M2OC-18HRDN1 845 320 700 908 560 335
M2OC1-18HRDN1-Q 845 320 700 908 560 335
M3OC1-21HRDN1-Q 845 320 700 908 560 335
M3OC-27HRDN1 845 320 700 908 560 335
M3OC1-27HRDN1-Q 845 320 700 908 560 335
M4OC-24HRDN1-Q 845 320 700 908 560 335
M4OC-27HRDN1
900 315 860 980 590 333
M4OC1-27HRDN1-Q
M4OC-36HRDN1-Q
990 345 965 1075 624 366
M5OA-36HRDN1-Q
4. Wiring Diagram
4.1 M2OC-14HRDN1-Q
4.2 M2OC-14HRDN1
4.3 M2OC1-18HRDN1-Q
4.6 M4OC-24HRDN1-Q
4.7 M4OC1-27HRDN1-QM4OC-27HRDN1
4.8 M4OC-36HRDN1-Q
4.9 M5OA-36HRDN1-Q
5. Refrigeration Cycle Diagram
5.1 Refrigeration circuit drawing of inverter binary type
7.5 Protection
7.5.1 Three minutes delay at restart for compressor.
7.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
----If 102<T5<115, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115 for 10 seconds, the compressor will stop and restart till T5<90.
7.5.3 Under voltage protection
VOLTAGE
VOLREL1
No limit
VOLLIMT1
VOLFRE1 VOLREL2
VOLLIMT2
VOLFRE2 VOLREL3
VOLLIMT3
Off
For M5OA-36HRDN1-Q,
VOLTAGE
No limit
VOLT_RST1_ADD
VOLT_LTM1_ADD
VOLT_LTM_FREQ1_ADD
VOLT_RST2_ADD
VOLT_LTM2_ADD
VOLT_LTM_FREQ2_ADD
VOLT_RST1_ADD=210V, VOLT_LIM1_ADD=200V, VOLT_RST2_ADD=195V, VOLT_LIM2_ADD=185V.
VOLT_LIM_FREQ1_ADD=54Hz, VOLT_LIM_FREQ2_ADD=42Hz.
7.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
For models except M5OA-36HRDN1-Q.
Cooling mode:
Current frequency(Hz) Current limit value(A) Frequency limit
COOL_F10 ICOOLLMT6 Decrease the frequency to COOL_F4 and
run at COOL_F4 for 3 minutes.
COOL_F9 ICOOLLMT5
COOL_F8 ICOOLLMT4 After that, the frequency will be adjusted
COOL_F7 ICOOLLMT3 according to the capacity demand and rise
to the upper level every 3 minutes
COOL_F6 ICOOLLMT2
(When the frequency>COOL_F4 via
COOL_F5 ICOOLLMT1 capacity demand).
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
Heating mode:
Current frequency(Hz) Current limit value(A) Frequency limit
HEAT_F12 IHEATLMT8 Decrease the frequency to HEAT_F4 and
run at HEAT_F4 for 3 minutes.
HEAT_F11 IHEATLMT7
HEAT_F10 IHEATLMT6
After that, the frequency will be adjusted
HEAT_F9 IHEATLMT5 according to the capacity demand and rise
to the upper level every 3 minutes
HEAT_F8 IHEATLMT4
(When the frequency>Heat_F4 via capacity
HEAT_F7 IHEATLMT3 demand).
HEAT_F6 IHEATLMT2
HEAT_F5 IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
COOL_F10 ICOOLLMT6
COOL_F9 ICOOLLMT5
COOL_F8 ICOOLLMT4
COOL_F7 ICOOLLMT3
COOL_F6 ICOOLLMT2
COOL_F5 ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
Heating mode:
Current frequency Current limit valueA Frequency limit
Hz
HEAT_F16 IHEATLMT12 Decrease the frequency to HEAT_F4 and run at
HEAT_F4 for 3 minutes.
HEAT_F15 IHEATLMT11
HEAT_F14 IHEATLMT10 After that, the frequency will be adjusted according to
the capacity demand and rise to the upper level every
HEAT_F13 IHEATLMT9 3 minutes
HEAT_F12 IHEATLMT8 (When the frequency>Heat_F4 via capacity
demand).
HEAT_F11 IHEATLMT7
HEAT_F10 IHEATLMT6
HEAT_F9 IHEATLMT5
HEAT_F8 IHEATLMT4
HEAT_F7 IHEATLMT3
HEAT_F6 IHEATLMT2
HEAT_F5 IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
When T3<52, the protection will release and the compressor will restart after 3 minutes.
7.5.7 Outdoor unit anti-freezing protection
When T2B<0 for 250 seconds, the indoor unit capacity demand will be zero and resume to normal when
T2B>10.
If T4(outdoor ambient temperature)3 and the machine connects to power supply no longer than 5
seconds or if T43 and compressor has stopped for over 3 hours, the compressor heating cable will
work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
P5 Mode conflict
Cassette series:
X X X Full-water malfunction
X Mode conflict
X X X Full-water malfunction
X Mode conflict
X X X Full-water malfunction E3
X X Mode conflict P5
Console series:
Operation Timer De-frost LED STATUS
X Mode conflict
No
No
Check wiring on the outdoor
and indoor terminal follow Reconnect the wiring
the wiring diagram. Is all
connecting correctly?
Yes
Yes
No
A: Is all the wiring
between terminal
and Indoor PCB
No connect ok?
Turn off the all indoor change
units. Is IPM power LED IPM
lamp On? Refer PIC 3
Yes
Yes
No
Is PFC power LED lamp change change the
off? Refer PIC 3. PFC Indoor PCB
Yes
Power on by remote
No controller, Is the E1
extinguish after 3
Reconnect the wiring
minutes?
No No
Is Main board Is the Reactor Yes
" lamp on? connection.
Refer PIC 4.
Yes
No second time
No fist time
A
Change outdoor unit PCB
assembly(include wiring) totally
Pic 1: Measure the voltage of L2 to S (Vs), is
it moving alternately between positive value
and negative value?
Off is OK
Power on
Self-Check OK
Operati
PIC4 :Main board LED when power on and unit standby.
Yes
Yes
Yes
Full-water malfunction
No
Check whether the water-level switch is inserted well Insert the water-level switch well
Yes
Yes
Check whether the water-level switch is broken Replace the water-level switch
No
No
Check whether the water pump is normal Replace the water pump
Yes
Yes
Check the voltage of outdoor unit power supply, whether the voltage No
between L(1) and N is about 220VAC Check the power supply
No
Yes
Yes
Replace the power board, then check whether the system can run Trouble is solved
normally
No
No
Yes
Replace bridge rectifiers, then check whether the
Trouble is solved
system can run normally
No
No
Yes
Check whether the IPM board has error display Replace
No IPM board
No
Yes
Insert the connecting wiring between the IPM module and the main Trouble is solved
board well over again
No
Yes
Replace the IPM board Trouble is solved
No
Yes
Replace outdoor PCB Trouble is solved
Yes
Check whether the compressor discharge temp. is more than 115C ?
No
Judge: The discharge temp. sensor is broken Stop leaking and add refrigerant
No
Method: Check whether the resistance of compressor discharge Replace the compressor
temp. sensor is right refer to the Appendix 2 discharge temp. sensor
Yes
No
No
Judge 1: Whether compressor operates? Whether the Reconnect and
connection is good? retest.
Yes
Yes
No
Judge 2: Whether refrigerant circulation volume is Whether protector is Replace the protector.
normal? normal?
No Yes
Yes
Method: Charge refrigerant Check the outdoor Replace the outdoor
main PCB. Is there main PCB
some problem?
No
No
Judge 1: Whether the wiring between the high pressure switch and main
Connect it well
control board is connected well or correctly
Yes
Yes
Method: Short connect the high pressure switch socket, check Replace high pressure switch
whether the system can run normally
No
Yes
Judge 3: Check whether the outdoor ambient temperature is too high Stop the unit
No
Yes
Judge 4: Check whether the outdoor unit is bad ventilation Make the outdoor unit ventilate well
No
Yes
Judge 5: Check whether the heat exchanger is dirty Clean the heat exchanger
No
Yes Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize and
Judge 6: Check whether the refrigerant pipe is blocked
charge the refrigerant again
No
Judge 1: The wiring between the low pressure switch and main control No
board is connected well or correctly Connect it well
Yes
Method: Short connect the low pressure switch socket, check Yes
whether the system can run normally Replace low pressure switch
No
Yes
Judge 3: Check whether the outdoor ambient temperature is too low Stop the unit
No
No
Yes Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize and
Judge 5: The refrigerant pipe is blocked
charge the refrigerant again
No
Judge 1: Check whether the input current of the power supply wire is more
than 8.5A (For 18-21K, it is 15A..For 27K(1x3) , it is 15A .For 27K(1x4), it is
18.5A , For 36K, it is 21.5A)
Yes
Yes
Judge 2: Check whether the outdoor ambient temperature is too high Stop the unit
No
Yes
Judge 3: Check whether the outdoor unit is bad ventilation Make the outdoor unit ventilate well
No
Yes
No
Yes Let the refrigerant out, then use the high pressure
Judge 5: The refrigerant pipe is blocked nitrogen or refrigerant to blow pipe, vacuumize and
charge the refrigerant again
No
Yes
Replace outdoor main board Trouble is solved
Regulate it to correct,
Check whether the voltage range of P-N on then check whether the
No Check whether the input power supply No
IPM module is normal? DC277-356V for system can work
14-27KBtu/h; DC277-410V for 36KBtu/h is correct? 220-240V, 1N, 50Hz
normally?
Yes Yes
No
No
Yes No Yes
Yes No
No
Yes Check whether the single-phase bridge is
normal? Use the multimeter to measure the
resistance between each two terminals, check Yes
Replace the IPM module, check Yes whether there is the condition that value of Replace the
whether the system can work resistance is 0 single-phase bridge
normally?
No Trouble is solved No
Replace the main board, check Check whether the connecting line
whether the system can work of every reactor is normal? If the
normally? Yes Trouble is solved line is broken, the resistance of the
two ports is models except for Yes
Replace the
M5OA-36HRDN1-QCheck
connecting line or
whether the PFC module
reactor or replace
broken(for M5OA-36HRDN1-Q)
the PFC module
When outdoor pipe temp. is more than 65C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52C.
Yes
Check whether the condenser temperature is more than 65C
No
Yes
Yes
Stop the unit Judge1: The outdoor temp. is too high
No
Yes
Clean the heat exchanger Judge 2: Check whether the heat exchanger is dirty
No
Let the refrigerant out, then use the high pressure Yes
nitrogen or refrigerant to blow pipe, vacuumize and
Judge 3: The refrigerant pipe is blocked
charge the refrigerant again
No
8.3.2.11 PFC module protection
No
Yes
Yes
Check whether the voltage between P
and N of IPM module is 380-390VDC Replace the outdoor main board
No
No
Check whether the inductance of PFC module is Replace the inductance
good?
Yes
~ +
- ~
Multi-meter Result
+ _ Infinite Infinite
~ +
- ~ ~1.7M ohm Infinite