Sei sulla pagina 1di 4

EWTR 910

one stage temperature, humidity and


pressure controller

Description Technical Data


EWTR 910 controllers have 1 point of intervention only with Casing: plastic in PC+ABS, V0 selfextinguishing.
ON/OFF and PID function (optional). They can be used for Size: front panel 72x72 mm, depth 102 mm.
temperature (EWTR 910), relative humidity (EWHR 910) and
Mounting: panel-mounting with bracket; 67x67 mm drilling
pressure (EWPR 910) control.
template.
Depending on models, they may have an input for
thermostatic probes (PTC, Ni100, Pt100, TcJ, TcK, 420 mA Connections: screw terminals for 2.5 mm2 leads (one lead
current), humidity probes (EWHS 280/300/310) or pressure per terminal only), which can be disconnected.
probes (EWPA 007/030). Operating temperature: 560C.
The values measured by the probes are displayed with three Storage temperature: 3075C.
or four digits, depending on models. These controllers are
Display: 3 or 4 digits, 12.5 mm high.
available in standard 72x72 mm size with square casing and
230, 115, 24 Va or 12 Va/c. power supplies. Data storage: on permanent memory (EEPROM).
Inputs (depending on model): PTC / RTD (Ni100, Pt100) / Tc
Analogue input Range (J, K) / current (420 mA; Ri = 41 ") for EWTR 910; EWHS
PTC -55...150 280/300/310 for EWHR 910 and EWPA 007/030 for EWPR 910.
Pt100-Ni100 -100...600 / -50...650 Main output: 1 output on 8(3)A 250Va SPDT relay or static
TcJ-TcK 0...600 / 0...999 (SSR) 0/12 Vc/40 mA output.
EWPA 007/030 0,5...0,8 / 0...30 Bar
Programmable analogue output (optional): 420 mA or 05
EWHS 280/300/310 20...100/0...100/20...100 RH%
V, depending on the model.
NOTE: overall range for different kinds of probes (the Resolution: 1 , 0.1 (a resolution of 5 or 0.5 can be selected)
range may be limited with specific types of cables, tips and Accuracy: above 0.5 % of bottom scale.
sensors). Special probes are available on request. Power supply (depending on model): 12 Va/c 15%; 230,
115, 24 Va 10%, 50/60 Hz.

Wiring Diagram Description of Wiring Diagram


56 Analogue output
EWTR 910 EWHR 910 78910 Probe input
8 9 10 8 9 10 8 9 10 7 8 9
910 series
1112 Power supply
11
12
13
PTC Pt100 / Ni100 Pt100 / Ni100 EWHS 280 1315 Relay N.O.
14
7 8 9 10

5
15
8 9 10 8 9 10
1415 Relay N.C.
+ 16
6
+ 17
7
18 + EWHS 310
8
TcJ / TcK 420 mA
9
10
EWPR 910
7 8 9

EWPA 007
EWPA 030

29
EWTR 920
two stage temperature, humidity and
pressure controller

Description Technical Data


EWTR 920 controllers are devices with two points of Casing: plastic, PC+ABS, V0 selfextinguishing.
intervention and can be used to control temperature Size: front panel 72x72 mm, depth 102 mm.
(EWTR 920), relative humidity (EWHR 920), and pressure
Mounting: panel-mounting with bracket; 67x67 mm drilling
(EWPR 920). Depending on models, they may have an input
template.
for thermostatic probes (PTC, Ni100, Pt100, TcJ, TcK, 420
mA current), humidity probes (EWHS 280/300/310) or Connections: screw terminals for 2.5 mm2 leads (one lead
pressure probes (EWPA 007/030). The values measured by only per terminal), which can be disconnected.
the probes are displayed with three or four digits, Operating temperature: 560C.
depending on models. These controllers are available in Storage temperature: 3075C.
standard 72x72 mm size with square casing and 230, 115, 24
Display: 3 or 4 digits, 12.5 mm high.
Va or 12 Va/c. power supplies.
Data storage: on permanent memory (EEPROM).
Analogue input Range Inputs (depending on model): PTC / RTD (Ni100, Pt100) / Tc
PTC -55...150 (J, K) / current (420 mA; Ri = 41 ") for EWTR 920; EWHS
Pt100-Ni100 -100...600 / -50...650 280/300/310 for EWHR 920 and EWPA 007/030 for EWPR
TcJ-TcK 0...600 / 0...999 920.
EWPA 007/030 0,5...0,8 / 0...30 Bar Main outputs: 2 output on 8(3)A 250Va SPDT relay or static
EWHS 280/300/310 20...100/0...100/20...100 RH% (SSR) 0/12 Vc/40 mA output.
Programmable analogue output (optional): 420 mA or 05
NOTE: overall range for different kinds of probes (the
V, depending on model.
range may be limited with specific types of cables, tips and
sensors). Special probes are available on request. Resolution: 1, 0.1 (a resolution of 5 or 0.5 respectively can
also be set).
Accuracy: above 0.5 % of bottom scale.
Power supply (depending on model): 12 Va/c 15%; 230,
115, 24 Va 10%, 50/60 Hz.

Wiring Diagram Description of Wiring Diagram


56 Analogue output
EWTR 920 EWHR 920
78910 Probe input
8 9 10 8 9 10 8 9 10 7 8 9
920 series
11
1112 Power supply
12
13
PTC Pt100 / Ni100 Pt100 / Ni100 EWHS 280
1315 Relay 1 N.O.
14
7 8 9 10

+
5
15
16
8 9 10 8 9 10 1415 Relay 1 N.C.
6
+ 17
7
8
18 + EWHS 310 1618 Relay 2 N.O.
TcJ / TcK 420 mA
9
10 1718 Relay 2 N.C.
EWPR 930
7 8 9

EWPA 007
EWPA 030

30
EWTR 930
two stage temperature, humidity and
pressure controller

Description Technical Data


EWTR 930 controllers have two points of intervention with a Casing: plastic, PC+ABS, V0 selfextinguishing.
neutral zone and can be used to Size: front panel 72x72 mm, depth 102 mm.
control temperature (EWTR 930), relative humidity (EWHR
Mounting: panel-mouting; 67x67 mm drilling template.
930), and pressure (EWPR 930). Depending on models, they
may have an input for thermostatic probes (PTC, Ni100, Connections: screw terminals for 2.5 mm2 leads (one lead
Pt100, TcJ, TcK, 420 mA current), humidity probes (EWHS only per terminal), which can be disconnected.
280/300/310) or pressure probes (EWPA 007/030). Operating temperature: 560 C.
The values measured by the probes are displayed with three Storage temperature: 3075 C.
or four digits, depending on models.
Display: 3 or 4 digits, 12.5 mm high.
A programmable optional 4,20mA or 0...5V output may be
provided as optional, depending on models. Data storage: on permanent memory (EEPROM).
These controllers are available in standard 72x72 mm size Inputs (depending on model): PTC / RTD (Ni100, Pt100) / Tc
with square casing and 230, 115, 24 Va or 12 Va/c. power (J, K) / current (420 mA; Ri = 41 ") for EWTR 930; EWHS
supplies. 280/300/310 for EWHR 930 and EWPA 007/030 for EWPR
930.
Analogue input Range Main outputs: 2 output on 8(3)A 250Va SPDT relay or static
PTC -55...150 (SSR) 0/12 Vc/40 mA output.
Pt100-Ni100 -100...600 / -50...650
Programmable analogue output (optional): 420 mA or
TcJ-TcK 0...600 / 0...999
EWPA 007/030 0,5...0,8 / 0...30 Bar 05 V, depending on the model.
EWHS 280/300/310 20...100/0...100/20...100 RH% Resolution: 1, 0.1 (a resolution of 5 or 0.5 respectively can
also be set).
NOTE: overall range for different kinds of probes (the Accuracy: above 0.5 % of bottom scale.
range may be limited with specific types of cables, tips and
Power supply (depending on model): 12 Va/c 15%; 230,
sensors). Special probes are available on request.
115, 24 Va 10%, 50/60 Hz.

Wiring Diagram Description of Wiring Diagram


56 Analogue output
EWTR 930 EWHR 930 78910 Probe input
8 9 10 8 9 10 8 9 10 7 8 9
930 series 1112 Power supply
11
12
PTC Pt100 / Ni100 Pt100 / Ni100 EWHS 280 1315 Relay 1 N.O.
13
14

5
15
7 8 9 10 1415 Relay 1 N.C.
8 9 10 8 9 10
+ 16
6
+
7
17
+ EWHS 310
1618 Relay 2 N.O.
18
8
9
TcJ / TcK 420 mA
1718 Relay 2 N.C.
10
EWPR 930
7 8 9

EWPA 007
EWPA 030

31
EWTR 940
two stage temperature with PID
function controller

Description Technical Data


EWTR 940 controllers have two points of intervention with Size: front panel 72x72 mm, depth 102 mm
ON/OFF, PD, PID function (on relay 1) and Mounting: panel-mounting with bracket; 67x67 mm drilling
SOFT START function, which can be set on the main output. template
They can be used both for heating and cooling applications.
Connections: screw terminals for 2.5 mm2 leads (one lead
Depending on models they may have an input for
only per terminal), which can be disconnected.
thermostatic PTC, Ni100, Pt100, TcJ, TcK probes or 420
mA current signals. The values measured by the probes are Operating temperature: 560 C.
displayed with three or four digits, depending on models. Storage temperature: 3075 C.
A programmable optional 4,20mA or 0...5V output may be Display: 3 or 4 digits, 12.5 mm high.
provided as optional, depending on models.
Data storage: on permanent memory (EEPROM).
These controllers are available in standard 72x72 mm size
with square casing and 230, 115, 24 Va or 12 Va/c power Inputs (depending on model): PTC / RTD (Ni100, Pt100) / Tc
supplies. (J, K) / current (420 mA; Ri = 41 ").
Main outputs: 2 output on 8(3)A 250Va SPDT relay or 0/12
Analogue input Range Vc/40 mA output.
PTC -55...150 Programmable analogue output (optional): 420 mA or 05
Pt100-Ni100 -100...600 / -50...650 V, depending on model.
TcJ-TcK 0...600 / 0...999
Resolution: 1, 0.1 (a resolution of respectively of 5C or
EWPA 007/030 0,5...0,8 / 0...30 Bar
0.5C can be selected).
EWHS 280/300/310 20...100/0...100/20...100 RH%
Accuracy: above 0.5 % of bottom scale.
NOTE: overall range for different kinds of probes (the Power supply (depending on model): 12 Va/c 15%; 230,
range may be limited with specific types of cables, tips and 115, 24 Va 10%, 50/60 Hz.
sensors). Special probes are available on request.

Wiring Diagram Description of Wiring Diagram


56 Analogue output
7 Output 12 V dc
8 9 10 8 9 10 8 9 10
EWTR 940
8910 Probe input
11
12
PTC Pt100 / Ni100 Pt100 / Ni100 1112 Power supply
13
14 1315 Relay 1 N.O.
15
5 8 9 10 8 9 10
+
6
16 1415 Relay 1 N.C.
+ 17
7
8
18 +
1618 Relay 2 N.O.
TcJ / TcK 420 mA
9
10 1718 Relay 2 N.C.

32