Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
IECPub50(446)(7983)
Indian Standard
ELECTROTECHNICALVOCABULARY
PART 9 ELECTRICAL RELAYS
( Second Revision J
@ BIS 1992
CONTENTS
Section Page
446-11 General terms .. . .-. .. . ... ... 1
446-12 Terms relating to energixation ( input and auxiliary ) ... . .. 2
446-13 Terms relating to conditions and operation of a relay .. . .. . 3
446-14 Terms relating to influencing quantities or factors . .. .. I ... 7
446-15 Terms relating to measuring relays ... . .. ... 7
446-16 Terms relating to outputs of the relays ( with or without contact ) ._. ... 8
446-17 Terms relating to times . .. .. . .. . ... 11
446-18 Terms relating to accuracy applicable to a given relay ( measuring relay and specified
time relay ) .. . . .. . .. ... .. . 12
Index ... ... . . . . . . . . . ..* 14
NATIONAL FOREWORD
This Indian Standard ( Part 9 ) ( Second Revision ) which is identical with IEC Pub 50 ( 446 ) ( 1983 )
%ternational electrotechnical vocabulary-Chapter 446 : Electrical relays, issued by the International
Eleetrotechnical Commission ( IEC ) was adopted by the Bureau of Indian Standards on the recom-
mendation of Basic Electrotechnical Standards Sectional Committee and approval of the Electrotechni-
cal Division Council.
This Indian Standard ( Part 9 ) was first published in 1966 and the first revision was done in 1986. This
second revision has been undertaken to align with the international practice.
Only the English text given in the IEC publication has been retained while adopting as Indian Standard,
and as such the page numbers given here are not the same as in IEC Publication.
When adopting the text of the International Standard, the textual errors given below were discovered,
These have been incorporated in the text:
Errors Corrections
i) Complexe Complex
ii) With Which
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
Indian Standard
ELBCTROTECHNICAL VOCABULARY
PART 9 ELECTRICAL RELAYS
( Second Revision )
SECTION 446-11-GENERAL TERMS
A device designed to produce sudden, predeter- A specified-time measuring relay for which
mined changes in one or more electrical output times depend, in a specified manner, on the
circuits when certain conditions are fulfilled in value of the characteristic quantity.
the electrical input circuits controlling the 446-11-07
device.
independent-time measuring relay
Notes 1. - The term relay shall be restricted to a relay
unit haviqg a single relaying function A specified-time measuring relay the specified
between its input circuits and its output time of which can be considered as being
circuits. independent, within specified limits, of the
2.- The term relay includes all the components value of the characteristic quantity.
which are necessary for the specified
operatidn. 446-l l-08
3. - For protection and automatic control pur- electromechanical relay
poses; the name of the single relaying func-
tion I see Note 1 ) shall be added to aualify An electrical relay in which the designed res-
the r&y. In the .case and according io thk ponse is developed by the relative movement
specified function ( defined by the standards
or by the manufacturer 1, the relay may
of mechanical elements under the action of a
include an atixiliary relay in order to perform current in the input circuit.
as required. Examples: differential relays,
impedance relay, tripping relay. 446-l l-09
446-11-02 static relay
all-or-nothing relay An electrical relay in which the designed res-
.. I ponse is developed by electronic, magnetic,
An electrical relay which is intended to be optical or other components without mechanical
energized by a quantity whose value is either motion.
within its operative range or effectively zero.
446-11-10
416-11-03
static relay with output contact
measuring relay
A static relay having a contact in one or more
An electrical relay intended to operate when of its output circuits.
its characteristic quantity, under specified
accuracy attains its operate value. 446-11-11
446-11-04 static relay without output contact
specified-time relay _
A static relay having no contacts in its output
An electrical relay such that one or more of the circuits.
times which characterize it ( e.g. operate time ) 446-11-12
are subject to specified requirements, in parti-
cular concerning accuracy. monostable relay
446-11-05 An electrical relay which, having responded to
non-specified-time relay an input energizing quantity ( or characteristic
quantity ) and having changed its condition,
An electrical relay for which the times are not returns to its previous condition when the
subject to any accuracy specification. quantity is removed.
1
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 448 ) ( 1983 )
446-11-13 of which depends upon the polarity of its input
bistable relay energizing quantity(ies).
2
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-12-11 446-12-13
limiting dynamic value of an energiziog quantity rated power of an energizing circuit
The highest value of an energizing quantity that rated burden of an energizing curcuit
a relay can withstand under specified conditions
of waveform and duration without permanent The power or burden ( voltamperes if a.c. )
degradation of the specified characteristics due absorbed under the reference conditions by a
to the resultant dynamic effect. given energizing circuit of a relay and deter-
mined under specified conditions.
446-12-12
operative range of an energizing quantity 446-12-14
The range of values of a given energizing rated impedance of an energizing circuit
quantity for which the relay under specified
conditions is able to perform its intended func- The value of the *complexe impedance of a
tion(s) according to the specified requirements. given energizing circuit of relay determined
under specified conditions.
ivolt,. -For measuring relays and when accuracy
requirements have to be met, see effective range. *See National Foreword for details of textual error.
446-U-01 446-13-05
release condition to operate
For a nionostable relay, the specified condition ( for an electrical relay >
of the relay when it is not energized.
To change:
For a bistable relay, a specified condition, as
declared by the madufacturer . - either from its release condition to its
operate condition ( general case ).
446-13-02
- or from an initial condition to a final condi-
initial condition tion ( case of some measuring relays or
Any specified condition which the relay leaves specified-time relays ).
tn order to complete its designated function in
a given output circuit. Note. - The term to operate includes both the term
to start and the term to switch.
Note. - This term is used mainly for measuring relays 446_13_06
and specified-time relays.
to release
446-l 3-03
( for an electrical relay )
operate condition
To chauge:
nor a monostable relay, the specified condition
of the relay when it is energized in a specified - either from its operate condition to its
manner. release condition.
For a bistable relay the condition other than -. or from a final condition to an initial condi-
the release condition as declared by the manu- tion ( case of some measuring or specified
facturer. time relays ).
446-l 3-04 Note - The term to release includes both the term
to disengage and the term to reset.
final condition
446-13-07
Any specified condition reached by a relay in
order to complete its designated function in a to change over
given output circuit.
( for an electrical relay )
Note. - This term is used mainly for measuring relays
and specified-time relays. Either to operate or to release.
3
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-13-08 446-13-15
to cycle operate value
( for an electrical relay ) The value of the input energizing quantity ( or
characteristic quantity ) at which a relay
To operate and then to release or vice-versa. operates under specified condition+.
446-13-09 446-13-16
to start
non-operate value
( for an electrical relay )
The value of the input energizing quantity ( or
( see Figure 1 ) characteristic quantity ) at which a relay does
not operate under specified condition@).
To leave an initial condition or release condi-
tion. 446-13-17
446-13-10 release value
to switch The value of the input energizing quantity ( pr
characteristic quantity) at which a relay reIeases
(for an electrical relay ) under specified conditions).
( see Figure 1 ) 446-13-18
To complete the designated function in a given non-release value
output circuit.
The value of the input energizing quantity ( or
446-13-11 characteristic quantity ) at which a relay do&
to reset not release under specified conditicnsl).
To re-attain an initial condition or release con- For a certain type of polarized ( d-c. ) relay, tl!l:
dition. value of the input energizing quantity at which
the relay being in a release condition by an
446-13-12 appropriate energization operates by increasing
to disengage the value of this energizing quantity under speci-
fied condition@.
( for an electrical relay )
NATIONAL NOTE - Read to operate value in place,
( see Figure 1 ) of revert-reverse value.
446-13-14 446-13-21
For a certain type of polarized ( d.c. ) relay For a certain type of polarized ( d.c. ) relay, the
being in a release condition by reverting to value of input energizing quantity at which the
change from this condition to the operate con- relay, being in an operate condition, releases by
dition by increasing the value of the energizing increasing the value of this energizing quantity
quantity. under specified conditions]).
-
NATIONAL NOTE - Read to re-operate in place *)These specified conditions can be expressed by using
to revert reverse. one of the adjectives defined under the items 446-13-27
to 446-l 3-29.
4
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-13-22 446-13-23
non-revert value starting value
For a certain type of polarized ( d.c. ) relay,
the value of the input energizing quantity at The value of the input energizing quantity ( or
which the relay, being in an operate condition, characteristic quantity ) at which a relay starts
does not release by increasing the value of this under specified conditionsl).
energizing quantity under specified condition&.
l) See page 4. l) See Page 4.
5
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983)
446-I 3-26 A value for which the relay shall complp with a
given action during a test. The term is to be
disengaging value used associated with terms 446-12-15 to
The value of the input energizing quan?ity ( or 446-l 3-26.
characteristic quantity ) at which a relay
disengages under specified conditionsl). 446-13-29
final endurance value
h46-X3-27
just value A value which is required throughout th: iife of
a relav or a specified number of cycles. This
A value which is measured on a given relay, at term is to be used associated with the terms
I) See note page 4. 446-13-15 to 446-13-26.
6
IS 1885 (Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-14-01[02] 446-14-06[07]
influencing quantity [ factor J
nominal range of an influencing quantity [factor ]
Any quantity [ factor 1 likely to modify any of
the specified characteristics of a relay ( operat- The range of values of an influencing quantity
ing, releasing, accuracy, etc. ). [ factor ] within which, under specified condi-
tions, the relay meets the specified requirements
446-14-O3[041 ( operating, releasing, error and variations,
reference value of an influencing quantity [factor] etc.).
The specified value of an influencing quantity
[ factor 1 to which are referred the characteris- 446-14-08 [09]
tics of a relay. In the case of measuring relays
and specified-time all-or-nothing relays, these extreme range of a influencing quantity [ factor 1
characteristics particularly include the errors
and their limits. The range of values of an influencing quantity
446-14-05 [factor ] within which the relay suffers only
reference conditions of influencing quantities and spontaneously reversible changes while not
factors necessarily complying with any other require-
ments.
The reference values of all influencing quantities
and factors.
446-15-01 446-15-04
7
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-15-09 446-15-14
effective range
disengaging ratio
That part of the operative range of an input
The ratio of the disengaging value to the energizing quantity ( or characteristic quantity )
operate value. within which the accuracy requirements are
met.
446-S-10 446-15-15
disengaging percentage characteristic angle
For a measuring relay, the angle betwen the
The disengaging ratio expressed as a percentage.
phasors representing two of the relays input
446-15-11 energizing quantities which is used for the
declaration of the performance of the relay.
primary relay 446-15-16
A relay which is directly energized by a current thermal electrical relay
or voltage in a main current without an inter- A dependent-time measuring relay which is in-
mediate instrument transformer or shunt or tended to protect an equipment from electrical
transducer. thermal damage by the measurement of the
current flowing in the protected equipment and
446-15-12 by a characteristrc curve simulating its thermal
secondary relay behaviour.
A relay which is energized by the current or 446-15-17
voltage derived from an instrument transformer correcting quantity
or a transducer.
A quantity modifying the characteristics of the
relay in a-specified manner.
446-H-13
Examples:
shunt relay
For a thermal electrical relay : the oil tempera-
A relay which is enerigized by the current deri- ture of the protected equipment, the air
ved from a shunt in a main circuit. temperature.
446-16-01 446-16-04
output circuit contact member ( see Figure 3 )
The whole of the electrically conductive parts A conductive part of a contact assembly which
within a relay connected to the terminals is electrically isolated from other such parts
between which the predetermined changes is when the contact circuit is open.
produced.
( see 446-11-01 ). 446-16-05
8
LS 1885 ( Part 9 ) : $992
IEC Pub 50 ( 446 ) ( 1983 )
t
I
I
I
I
I
I
I
I
I I I
I
L_______,______-__-____J 1
L______ ___-___-_---__________d
7
h2
446-16-07 M-16-11
contact force effectively conducting output circuit
[ for relays without output contacts )
The force which two contact tips exert against
each other in the closed position under specified An output circuit without contacts which has a
conditions. resistance lower than a specified value.
4-S-16-08 446-16-12
9
ZS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
10
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446~17-03[041 446-17-l 1
closing time of a make contact [output-make disengaging time
circuit ] ( for a given function )
For a relay which is in the release condition, The time interval between the instant a specified
the time interval between the inst.ant a specified change is made in the value of the input energiz-
value of the input energizing quantity is applied ing quantity ( the characteristic quantity for a
under specified conditions and the instant when measuring relay ) which will cause the relay ti>
the make contact [ output-make circuit ] first disengage and the instant it disengages.
closes.
446-17-05[06] 446-17-12
,446~17-09 446-17-14
operate time specified time
For a relay which is in the release condition A time interval which is a specified characteris-
( initial condition ) the time interval between tic of a specified-time relay.
the instant a specified value of the input energiz-
ing quantity ( characteristic quantity ) is applied 446-17-15
under specified condition and the instant when time programme
-the r clay switches.
For a specified-time relay, an intended sequence
Note.- This term is used only when the relay has output of output circuit operations ( making and/or
circuits of the same type and no precision is breaking ) with respect to time.
required according to contact time difference.
446-17-10 446-17-16
release time setting value of a specified time
For a relay which is in the operate con&ion The intended value of tl:e time interval under
( final condition ) the time interval between the specified conditions.
11
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
446-17-17 446-17-22
actual value of a specified time bridging time
The value of a time interval obtained under For a change-over make-before-break contact,
specified conditions. the time interval which elapses between the
instant one contact circuit is closed and the
446-17-18
instant the other opens.
setting range of a specified time
446-17-23
The range of the setting values of a specified
time. transit time
446-17-19 For a break-before-make change-over contact,
the time interval during *with both contact
setting ratio of specified time circuits are open,
The ratio of the maximum setting value of a 446-17-24[25]
specified time to its minimum value.
time to stable closed [open] condition
446-.17-20 The time interval between the instant when a
maximum resetting time specified value of the input energizing quantity
is applied and the instant when a contact is
For a given function, the maximum time between closed [open] and fulfils specified requirements.
the instant when the conditions of energization
permit the relay to reset and the instant it 446-17-26
resets.
contact time difference
446-17-21 For a relay having several contacts of the same
recovery time type ( make contacts or break contacts ), the
difference between the maximum value of the
Far a given function and under specified condi- operate ( release ) time of the slower and the
tions, the time needed by a relay to recover from minimum value of the operate ( release ) time of
an operate condition so that the following the faster.
operating time is within a given percentage of
the previous measuring time. *See Natiollal Foreword for detials of textual error.
446-18-01 446-18-04
mean error
absolute error
For a given relay and for a specified number of
The algebraic difference between a measured measurements made under identical stated
operating value of the characteristic quantity conditions, the quotient of the algebraic sum of
( or an actual value of the specified time ) and the error values ( absolute, relative or conven-
its setting value. tional ) by the number of measurements.
446-18-02 446-18-05
reference mean error
conventional error
The mean error determined under reference
The ratio of the absolute error to a specified conditions.
conventional value.
446-18-06
446-M-03 limiting error
relative error For a given relay, the maximum error to be
The ratio of the absolute error to the setting expected with a given confidence level under
value. identical stated conditions.
12
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
13
1s 1885 ( Part 9 ) : 1992
7EC Pub 50 ( 446 ) ( 1983 )
INDEX
446-16-25 F
change-over break-before-make contact
change-over contact 446-l 6-23
final condition 446-13-04
change-over make-before-break contact 446-16-24
final endurance value 446-13-29
change-over (to) ( for an electrical relay 446-13-07
change-over with neutral position 446-l 6-26 I
characteristic angle 446-15-I 5
characteristic quantity ( of a measuring 446-l 5-01 independent-time measuring relay 446-11-O?
relay ) influencing factor 446-l 4-02
class index 446-18-12 influencing quantity 446-14-01
closing time of a break contact 446-l 7-07 initial condition 446-13-02
closing time of a make contact 446-17-03 input circuit 446-l 2-05
-closing time of an output-break circuit 446-l 7-08 input energizing quantity 446-l 2-02
closing time of an output-makecircuit 446-l 7-04
consistency 446-18-08 J
contact assembly 446-l 6-03
contact circuit 446-l 6-02 just value 446-l 3-27
contact gap 446-16-06
contact follow 446-16-08 L
contact force 446-16-07
Contact member 446-l 6-04 limiting breaking capacity 446-l 6-20
contact point 446-16-05 limiting continuous current of an output 446-16-17
circuit
.contsct roll 446-16-10
limiting continuous thermal withstand valu e 446-l 2-09
contact time difference 446-17-26 of an energizing quantity
contact tip 446-16-05 limiting cycling capacity 446-16-21
contact wipe 446-16-09 limiting dynamic value of an energizing 446-12-11
conventional error 446-B-02 quantity
correcting quality 446-15-17 limiting error 446-18-06
cycle (to) ( for an:electrical relay 1 446-l 3-08 limiting making capacity 446-16-19
limiting short-time current of an output 446-16-18
D circuit
limiting short-time thermal withstand value 446-12-10,
dependent-time measuring relay 446-11-06 of an energizing quantity
disengage (to) ( for an electrical relay ) 446-l 3-12 limiting value of the characteristic quantity 446-15-03.
14
IS 1885 ( Part 9 ) : 1992
IEC Pub 50 ( 446 ) ( 1983 )
M reference limiting error 446-18-07
reference mean error 446-18-05
make contiict
446-16-1s reference value of an influencing factor 446-f 4-04
maximum resetting rime 446 -17-20 reference value of an inffuencing qusntity 446-14-03
mean error 446-18-04 relative error 446-f 8-03
mnmsuring selny 446-l l-03
monostablc relay release condition 444-13-01
446-11-12
must value rclease time 446-l 7-10
446-13-28
release (to) ( for an electrical relay ) 446-J 3-06
N release value 446-U-17
reset (to) ( for an eJectricaJ relay ) 446-13-1~1
*~ominaJ range of an influencing factor 446-14-07 resetting percentage 446-U-07
nominal range of an influencing quantity 446-14-06 resetting ratio 446-l 5-W
nominal value of an energizing quantity 446-12-07 resetting time ( for a given function ) 446-17-12
non-bridging contact ( deprecated ) 446-16-2s resetting value 446-13-25
non-operate value 446-13-16 revert (to) 446-13-13
non-polarized relay ( d.c. ) 446-l 1-15 revert (to) reverse 446-13-14
non-release value 446-13-18 revert-reverse value 446-13-19
non-revert-reverse value 446-13-20 revert value 446.I3-21
non-revert value 446-13-22
non-specified-time relay 446-11-05 S
15
Standard Mark
The use of the Standard Mark is governed by the provisions of the Bureau of Indian
Standards Act, 2986 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been
produced to comply with the requirements of that standard under a well defined system of
inspection, testing and quality control which is devised and supervised by BIS and operated
by the producer. Standard marked products are also continuously checked by BIS for con-
formity to that standard as a further safeguard. Details of conditions under which a licence
for the use of the Standard Mark may be granted to manufacturers or producers may be
obtained from the Bureau of Indian Standards4
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Stant&ar& Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any
form without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Direcror ( Publications ), BIS.
Revision of Indian Standards
Indian Standards are reviewed periodically and revised, when necessary and amendments, if any, are
issued from time to time. Users of Indian Standards should ascertain that they are in possession of the
latest amendments or edition. Comments on this Indian Standard may be sent to BIS giving the
fo llowing reference:
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams : Manaksanstha
Telephones 8 331 0131, 331 13 75 ( Common to all offices )