TR Supply CFMDeh CFMReturn CFMFresh Air CFM

Blender 2 4.17 2,996 1,308 3,172 150


Blender 3 3.12 2,337 953 2,513 117
Fan CFM Bleed CFMReheat kWAHU Capacity
3,322 326 8.97 4000
2,630 293 4.18 3000
Table : 1 :: Building Constructions & "U"-Factors

Id. Summer U- Winter U-


Item Material of Construction Remarks (if any)
No Factor Factor
Exp. Glass Exp. Glass 5.5 mm thk. Clear Sheet Glass 1.13 1.13
Exp. Glass (R) Exp. Glass (R) 5.5 mm thk. Clear Sheet Glass 1.00 1.00 Radiation Factor
Part. Glass Part. Glass 5.5 mm thk. Toughened / Clear Sheet Glass 1.13 1.13
Exp. Wall Exp. Wall 225 mm thk. Brick Wall + 10 mm thk. Sand Plaster on 0.34 0.35
both sides.
Part. Wall Part. Wall 100mm thk. Brick Wall + 10 mm thk. Sand Plaster on 0.42 0.42
both sides.
Part. Wall 2 Part. Wall2 450 mm thk. Brick Wall + 20 mm thk. Sand Plaster on 0.20 0.20
both sides.
Roof Exposed 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.13 0.13
sides.50mm EPS insulation
Ceiling Ceiling 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.31 0.31
sides.
Floor Floor 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.35 0.35
sides.

Table : 2 :: Solar Heat Gain Thru' Glass


Solar Gain (FPS Unit)
Direction
For Summer-(May) For Monsoon-(July) For Winter-(January)
East Exp. GlassEast 12.00 12.00 8.00
West Exp. GlassWest 163.00 163.00 128.00
North Exp. GlassNorth 23.00 23.00 8.00
South Exp. GlassSouth 12.00 12.00 69.00
NE Exp. GlassNE 12.00 12.00 8.00
SE Exp. GlassSE 12.00 12.00 8.00
NW Exp. GlassNW 138.00 138.00 26.00
SW Exp. GlassSW 113.00 113.00 144.00
SW Exp. GlassSW 113.00 113.00 144.00

Table : 3 :: Equivalent Temp. Diff. Thru' Wall & Roof


Solar Gain (FPS Unit)
Item / Direction
For Summer For Monsoon For Winter
Exp. Wall
East Exp. WallEast 25.00 20.00 -22.00 Shaded Walls
West Exp. WallWest 19.00 14.00 -20.00 Shaded Walls
North Exp. WallNorth 11.00 6.00 -27.00 Shaded Walls
South Exp. WallSouth 23.00 18.00 -23.00 Shaded Walls
NE Exp. WallNE 17.00 12.00 -23.00
SE Exp. WallSE 25.00 20.00 -21.00
NW Exp. WallNW 13.00 8.00 -23.00
SW Exp. WallSW 21.00 16.00 -23.00
Roof
Shaded RoofShaded 15.00 10.00 -30.00
Exposed RoofExposed 57.00 44.00 -37.25
ZYDUS WELLNESS-EXAMPLE
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Blender 2 Room No AHU NO. :
Site Data : Location Latitude (N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 41.75 m Height 6.1 m Volume 8,988 ft Eq. Load 7.6 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 150 cfm ST. PR 5 inch
Exhaust Air From Room - cfm Exhaust Thru' Min. Air Changes 20.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 2.0 C Relative Humidity 45.0 5 % Pressure Level 25.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door Area ft m Percentage Free 100.0 % 15.0 Pa 0 cfm Exfiltration1
Door Area m m Percentage Free 100.0 % Pa 0 cfm
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
0
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door 1 Area 0.0168 m m Percentage Free 100.0 % 40 Pa 176 cfm Infiltration1
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % Pa
(176)
Selected Fresh Air Qty : 150 cfm
Outside & Inside Conditions
PARAMETER DB, F WB, F RH, % DP, F Gr / lb TIME OF DAY D.RANGE,F MONTH REMARKS
Outside
Summer 98.6 86.2 61.5 190.6 16.00 hrs 27.0 May
Monsoon 84.9 82.4 90 182.2 16.00 hrs 16.0 August
Winter 50.7 48.6 8705 52.4 5.00 hrs 20.0 j$anuary
Inside 73.4 60.9 50.0 67.4 24 Hrs All Months
Differences
Summer 25.2 123.2
Monsoon 11.5 114.8
Winter -22.7 -15.0
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x 0.80 0.80
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Exp. Wall ft x x
Roof ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling 449.2 ft x 25.20 11.50 -22.70 x 0.15 0.15 1,698 775 -1,530
Part. Wall 483.00 ft x 25.20 11.50 -22.70 x 0.15 0.15 1,826 833 -1,645
Part. Glass ft x 25.20 11.50 -22.70 x
Floor 449.2 ft x 25.20 11.50 -22.70 x 0.35 0.35 3,962 1,808
Gain From Internal Sources
People 1 nos x 269.0 269 269 269
Equipment 7.60 kW 0.30 0.30 0.30 x 3400.0 xUF 7,752 7,752 7,752
Lights 898 W x 3.4 xBl.F 1.25 3,818 3,818 3,818
Hot Surface W x 1.00 1.00 1.00 x 3.41
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 19,325 15,256 8,665
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 1,449 1,144 650
Draw Thru' AHU Motor 2.9 HP x % 10,052 10,052
Bypassed FA 150 cfm x 25.20 11.50 -22.70 x 1.08 x BF 0.06 245 112 -220
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 31,071 26,563 9,095
Latent Heat
People 1 nos x 231.0 231 231 231
Appliances kW x 3400.0 xUF
Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 cfm x x 0.68
Infiltration cfm x x 0.68
Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 231 231 231

4
ZYDUS WELLNESS-EXAMPLE
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Blender 2 Room No AHU NO. :
Site Data : Location Latitude (N) Altitude (mt) Estimate by :
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 17 17 17
Bypassed FA 150 cfm x 123.19 114.79 -15.01 x 0.68 x BF 0.06 753 702 -92
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,001 950 157
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 32,073 27,513 9,251
Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass ft x x
Part. Wall ft x x
Ceiling ft x x
RA & AHU Room Heat Sub-Total : 0 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0 0
Outside (Fresh) Air Heat on Coil
Sensible Part 150 cfm x 25.20 11.50 -22.70 x 1.08 x BF 0.94 3,832 1,749 -3,452
Bypassed FA 150 cfm x 123.19 114.79 -15.01 x 0.68 x BF 0.94 11,796 10,992 -1,437
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 15,628 12,741 -4,889
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 47,701 40,254 4,362
Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor x 10.0 % 0 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 2,385 2,013 218
GRAND TOTAL HEAT (GTH) IN BTU / HR : 50,086 42,267 4,580
GRAND TOTAL HEAT (GTH) IN TR : 4.17 3.52 0.38
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.97 0.97 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHFmin - -
Indicated Apparatus Dew Point From Psychrometric Chart F -
Selected Apparatus Dew Point ADP F 50.00 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR F 22.00 22.00 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 1,308 1,118 -
Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ac cfm 2,996
Preliminary Selected Air Qty = Highest of DAsum, DAmon, SAac DA max cfm 2,996
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No No
Reheater Capacity for Winter Heating RH winter kW
Reheater to Increase ESHF to Achievable Limit RH latent kW
Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR rev TR 4.17 3.52 0.38
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA rev cfm 1,308 1,118
FINAL SYSTEM SELECTION
Tonnage TR 4.17
Supply Air Qty CFM 2,996
Dehumidified Air Qty CFM 1,308
Return Air Qty CFM 3,172
Fresh Air Qty CFM 150
Reheater / Heating Coil Capacity kW 8.97

5
ZYDUS WELLNESS-EXAMPLE
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Room No AHU NO. :
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 36.12 m Height 5.5 m Volume 7,011 ft Eq. Load 3.7 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 117 cfm ST. PR 5 inch
Exhaust Air From Room - cfm Exhaust Thru' Min. Air Changes 20.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 2.0 C Relative Humidity 45.0 5 % Pressure Level 25.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door Area ft m Percentage Free 100.0 % 25.0 Pa 0 cfm
Door Area m m Percentage Free 100.0 % Pa 0 cfm
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
0
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door 1 Area 0.0168 m m Percentage Free 100.0 % 40 Pa 176 cfm Infiltration1
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % Pa cfm
Door Area m m Percentage Free 100.0 % Pa
(176)
Selected Fresh Air Qty : 117 cfm
Outside & Inside Conditions
PARAMETER DB, F WB, F RH, % DP, F Gr / lb TIME OF DAY D.RANGE,F MONTH REMARKS
Outside
Summer 98.6 86.2 61.5 190.6 16.00 hrs 27.0 May
Monsoon 84.9 82.4 90 182.2 16.00 hrs 16.0 August
Winter 50.7 48.6 8705 52.4 5.00 hrs 20.0 j$anuary
Inside 73.4 60.9 50.0 67.4 24 Hrs All Months
Differences
Summer 25.2 123.2
Monsoon 11.5 114.8
Winter -22.7 -15.0
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x 0.80 0.80
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Exp. Wall ft x x
Roof ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling 388.7 ft x 25.20 11.50 -22.70 x 0.15 0.15 1,469 670 -1,323
Part. Wall 357.45 ft x 25.20 11.50 -22.70 x 0.15 0.15 1,351 617 -1,217
Part. Glass ft x 25.20 11.50 -22.70 x
Floor 388.7 ft x 25.20 11.50 -22.70 x 0.35 0.35 3,428 1,564
Gain From Internal Sources
People 1 nos x 269.0 269 269 269
Equipment 3.70 kW 0.30 0.30 0.30 x 3400.0 xUF 3,774 3,774 3,774
Lights 777 W x 3.4 xBl.F 1.25 3,304 3,304 3,304
Hot Surface W x 1.00 1.00 1.00 x 3.41
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 13,595 10,198 4,806
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 1,020 765 360
Draw Thru' AHU Motor 2.3 HP x % 7,841 7,841 7,841
Bypassed FA 117 cfm x 25.20 11.50 -22.70 x 1.08 x BF 0.06 191 87 -172
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 22,646 18,891 12,836
Latent Heat
People 1 nos x 231.0 231 231 231
Appliances kW x 3400.0 xUF
Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 cfm x x 0.68
Infiltration cfm x x 0.68
Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 231 231 231

6
ZYDUS WELLNESS-EXAMPLE
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Room No AHU NO. :
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) Estimate by :
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 17 17 17
Bypassed FA 117 cfm x 123.19 114.79 -15.01 x 0.68 x BF 0.06 587 547 -72
EFFECTIVE ROOM LATENT HEAT (ERLH) : 836 796 177
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 23,482 19,686 13,012
Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass ft x x
Part. Wall ft x x
Ceiling ft x x
RA & AHU Room Heat Sub-Total : 0 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0 0
Outside (Fresh) Air Heat on Coil
Sensible Part 117 cfm x 25.20 11.50 -22.70 x 1.08 x BF 0.94 2,989 1,364 -2,693
Bypassed FA 117 cfm x 123.19 114.79 -15.01 x 0.68 x BF 0.94 9,201 8,574 -1,121
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 12,191 9,938 -3,814
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 35,673 29,625 9,198
Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor x 10.0 % 0 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 1,784 1,481 460
GRAND TOTAL HEAT (GTH) IN BTU / HR : 37,456 31,106 9,658
GRAND TOTAL HEAT (GTH) IN TR : 3.12 2.59 0.80
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.96 0.96 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHFmin - -
Indicated Apparatus Dew Point From Psychrometric Chart F -
Selected Apparatus Dew Point ADP F 50.00 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR F 22.00 22.00 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 953 795 -
Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ac cfm 2,337
Preliminary Selected Air Qty = Highest of DAsum, DAmon, SAac DA max cfm 2,337
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No No
Reheater Capacity for Winter Heating RH winter kW
Reheater to Increase ESHF to Achievable Limit RH latent kW
Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR rev TR 3.12 2.59 0.80
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA rev cfm 953 795
FINAL SYSTEM SELECTION
Tonnage TR 3.12
Supply Air Qty CFM 2,337
Dehumidified Air Qty CFM 953
Return Air Qty CFM 2,513
Fresh Air Qty CFM 117
Reheater / Heating Coil Capacity kW 4.18

7
HVAC SYSTEMS FOR - ADCOCK INGRAM HEALTHCARE (Pty) Ltd.
JOB REF. NO. :
CUSTOMER CONSULTANT
Adcock Ingram Healthcare (Pty) Ltd., Clayville, SOUTH AFRICA Doshi Consultants (P) Ltd. DATE : 07-03-2009
AIR-CONDITIONING HEAT LOAD :
Rooms : CHANGING ROOM Room No F-51 AHU NO. : 25A
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) 1,700 Estimate by : V.SAHU
Specified Inside / Room Data
Floor Area 8.79 m Height 3.0 m Volume 924 ft
FA Qty (if given) cfm Min.FA Circulation 2.0 ac / hr Min. FA Qty 31 cfm
Exhaust Air From Room - cfm Exhaust Thru' Min. Air Changes 20.0 per hr
Dry Bulb Temperature 23.0 2.0 C Relative Humidity 55.0 5 % Pressure Level 30.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door Area 0.028 m m Percentage Free 100.0 % Pa cfm
Door Area 0.020 m m Percentage Free 100.0 % Pa cfm
Door 1 Area 0.018 m m Percentage Free 100.0 % 45.0 Pa 126 cfm Infiltration1
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
-126
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door Area 0.0280 m m Percentage Free 100.0 % Pa cfm
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
Door 1 Area 0.018 m m Percentage Free 100.0 % 0.0 Pa 178 cfm Exfiltration1
Door Area 0.300 m m Percentage Free 100.0 % Pa
178
Selected Fresh Air Qty : 178 cfm
Outside & Inside Conditions
PARAMETER DB, F WB, F RH, % DP, F Gr / lb TIME OF DAY D.RANGE,F MONTH REMARKS
Outside
Summer 95.0 82.1 60 78.3 185.9 16.00 hrs 20.0 May
Monsoon 16.00 hrs 16.0 August
Winter 37.4 29.1 40 14.8 16.1 5.00 hrs 20.0 j$anuary
Inside 73.4 61.7 55.0 56.3 83.2 24 Hrs All Months
Differences
Summer 21.6 102.7
Monsoon
Winter -30.6 -46.5
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x 0.80 0.80
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Exp. Wall ft x x
Roof ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling 94.6 ft x 21.60 0.00 -30.60 x 0.31 0.31 631 -893
Part. Wall 125.9 ft x 21.60 0.00 -30.60 x 0.42 0.42 1,152 -1,632
Part. Glass ft x 21.60 0.00 -30.60 x
ft x x
Gain From Internal Sources
People 1 nos x 255.0 255 255
Equipment kW 0.70 0.70 0.30 x 3400.0 xUF
Lights 142 W x 3.4 xBl.F 1.25 603 603
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,641 858 -2,526
SA Duct Heat Gain & Leak Loss (%) : 1.50 % Safety : 5.00 % 172 56
Blow Thru' AHU Motor x %
Bypassed FA 178 cfm x 21.60 0.00 -30.60 x 1.08 x BF 0.05 208 -294
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 3,020 914 -2,820
Latent Heat
People 1 nos x 245.0 245 245
Appliances kW x 3400.0 xUF
Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 cfm x x 0.68
Infiltration cfm x x 0.68
Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 245 245 0

8
HVAC SYSTEMS FOR - ADCOCK INGRAM HEALTHCARE (Pty) Ltd.
JOB REF. NO. :
CUSTOMER CONSULTANT
Adcock Ingram Healthcare (Pty) Ltd., Clayville, SOUTH AFRICA Doshi Consultants (P) Ltd. DATE : 07-03-2009
AIR-CONDITIONING HEAT LOAD :
Rooms : CHANGING ROOM Room No F-51 AHU NO. : 25A
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) 1,700 Estimate by : V.SAHU
SA Duct Heat Gain & Leak Loss (%) : 1.50 % Safety : 5.00 % 16 16 0
Bypassed FA 178 cfm x 102.70 0.00 -46.50 x 0.68 x BF 0.05 622
EFFECTIVE ROOM LATENT HEAT (ERLH) : 882 261 0
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 3,903 1,175 -2,820
Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass ft x x
Part. Wall ft x x
Ceiling ft x x
RA & AHU Room Heat Sub-Total : 0 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0 0
Outside (Fresh) Air Heat on Coil
Sensible Part 178 cfm x 21.60 0.00 -30.60 x 1.08 x BF 0.95 3,945 -5,588
Bypassed FA 178 cfm x 102.70 0.00 -46.50 x 0.68 x BF 0.95 11,809 -5,347
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 15,754 0 -10,935
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 19,657 1,175 -13,755
Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor x 10.0 % 264 264
CHW Pump Motor/Dehum.Pipe Loss 1.50 % GTH Safety : 5.00 % 1,278 76 -894
GRAND TOTAL HEAT (GTH) IN BTU / HR : 21,198 1,515 -14,649
GRAND TOTAL HEAT (GTH) IN TR : 1.77 0.13 -1.22
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.77 0.78 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHFmin - 0.77 0.77 -
Indicated Apparatus Dew Point From Psychrometric Chart F -
Selected Apparatus Dew Point ADP F 52.00 52.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR F 20.33 20.33 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 138 42 -
Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ac cfm 308
Preliminary Selected Air Qty = Highest of DAsum, DAmon, SAac DA max cfm 308
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH winter kW 4.05
Reheater to Increase ESHF to Achievable Limit RH latent kW
Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR rev TR 1.77 0.13
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA rev cfm 138 42
FINAL SYSTEM SELECTION
Tonnage TR 1.77
Supply Air Qty CFM 308
Dehumidified Air Qty CFM 138
Return Air Qty CFM 256
Fresh Air Qty CFM 178
Reheater / Heating Coil Capacity kW 4.05

9
HVAC SYSTEMS FOR - ADCOCK INGRAM HEALTHCARE (Pty) Ltd.
JOB REF. NO. :
CUSTOMER CONSULTANT
Adcock Ingram Healthcare (Pty) Ltd., Clayville, SOUTH AFRICA Doshi Consultants (P) Ltd. DATE : 07-03-2009
AIR-CONDITIONING HEAT LOAD :
Rooms : MATERIAL AIR LOCK Room No F-49 AHU NO. : 25A
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) 1,700 Estimate by : V.SAHU
Specified Inside / Room Data
Floor Area 11.43 m Height 3.0 m Volume 1,202 ft
FA Qty (if given) cfm Min.FA Circulation 2.0 ac / hr Min. FA Qty 40 cfm
Exhaust Air From Room - cfm Exhaust Thru' Min. Air Changes 20.0 per hr
Dry Bulb Temperature 23.0 2.0 C Relative Humidity 55.0 5 % Pressure Level 30.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door 1 Area 0.030 m m Percentage Free 100.0 % 45.0 Pa 208 cfm Infiltration1
Door Area 0.020 m m Percentage Free 100.0 % Pa cfm
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
-208
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (F) Gr / lb
Door 1 Area 0.030 m m Percentage Free 100.0 % 0 Pa 293 cfm Exfiltration1
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
Door Area 0.018 m m Percentage Free 100.0 % Pa cfm
Door Area 0.300 m m Percentage Free 100.0 % Pa
293
Selected Fresh Air Qty : 293 cfm
Outside & Inside Conditions
PARAMETER DB, F WB, F RH, % DP, F Gr / lb TIME OF DAY D.RANGE,F MONTH REMARKS
Outside
Summer 95.0 82.1 60 78.3 185.9 16.00 hrs 20.0 May
Monsoon 16.00 hrs 16.0 August
Winter 37.4 29.1 40 14.8 16.1 5.00 hrs 20.0 j$anuary
Inside 73.4 61.7 55.0 56.3 83.2 24 Hrs All Months
Differences
Summer 21.6 102.7
Monsoon
Winter -30.6 -46.5
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x 0.80 0.80
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Exp. Wall ft x x
Roof ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling 123.0 ft x 21.60 0.00 -30.60 x 0.31 0.31 820 -1,162
Part. Wall 18.3 ft x 21.60 0.00 -30.60 x 0.42 0.42 167 -237
Part. Glass ft x 21.60 0.00 -30.60 x
ft x x
Gain From Internal Sources
People 1 nos x 255.0 255 255
Equipment kW 0.70 0.70 0.30 x 3400.0 xUF
Lights 184 W x 3.4 xBl.F 1.25 784 784
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,026 1,039 -1,399
SA Duct Heat Gain & Leak Loss (%) : 1.50 % Safety : 5.00 % 132 68
Blow Thru' AHU Motor x %
Bypassed FA 293 cfm x 21.60 0.00 -30.60 x 1.08 x BF 0.05 342 -484
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,500 1,107 -1,883
Latent Heat
People 1 nos x 245.0 245 245
Appliances kW x 3400.0 xUF
Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 cfm x x 0.68
Infiltration cfm x x 0.68
Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 245 245 0

10
HVAC SYSTEMS FOR - ADCOCK INGRAM HEALTHCARE (Pty) Ltd.
JOB REF. NO. :
CUSTOMER CONSULTANT
Adcock Ingram Healthcare (Pty) Ltd., Clayville, SOUTH AFRICA Doshi Consultants (P) Ltd. DATE : 07-03-2009
AIR-CONDITIONING HEAT LOAD :
Rooms : MATERIAL AIR LOCK Room No F-49 AHU NO. : 25A
Site Data : Location CLAYVILLE, SOUTH AFRICA Latitude (N) Altitude (mt) 1,700 Estimate by : V.SAHU
SA Duct Heat Gain & Leak Loss (%) : 1.50 % Safety : 5.00 % 16 16 0
Bypassed FA 293 cfm x 102.70 0.00 -46.50 x 0.68 x BF 0.05 1,023
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,284 261 0
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 3,784 1,368 -1,883
Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass ft x x
Exp. Glass ft x x
Exp. Glass ft x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall ft x x
Roof ft x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass ft x x
Part. Wall ft x x
Ceiling ft x x
RA & AHU Room Heat Sub-Total : 0 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0 0
Outside (Fresh) Air Heat on Coil
Sensible Part 293 cfm x 21.60 0.00 -30.60 x 1.08 x BF 0.95 6,493 -9,199
Bypassed FA 293 cfm x 102.70 0.00 -46.50 x 0.68 x BF 0.95 19,439 -8,801
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 25,932 0 -18,000
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 29,716 1,368 -19,883
Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor x 10.0 % 203 203
CHW Pump Motor/Dehum.Pipe Loss 1.50 % GTH Safety : 5.00 % 1,932 89 -1,292
GRAND TOTAL HEAT (GTH) IN BTU / HR : 31,850 1,659 -21,175
GRAND TOTAL HEAT (GTH) IN TR : 2.65 0.14 -1.76
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.66 0.81 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHFmin - 0.77 0.77 -
Indicated Apparatus Dew Point From Psychrometric Chart F -
Selected Apparatus Dew Point ADP F 52.00 52.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR F 20.33 20.33 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 114 50 -
Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ac cfm 401
Preliminary Selected Air Qty = Highest of DAsum, DAmon, SAac DA max cfm 401
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No Yes No Yes
Reheater Capacity for Winter Heating RH winter kW 5.85
Reheater to Increase ESHF to Achievable Limit RH latent kW 0.53
Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR rev TR 2.80 0.14
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA rev cfm 196 50
FINAL SYSTEM SELECTION
Tonnage TR 2.80
Supply Air Qty CFM 401
Dehumidified Air Qty CFM 196
Return Air Qty CFM 316
Fresh Air Qty CFM 293
Reheater / Heating Coil Capacity kW 5.85