BENEFITS OF CONTINUOUS
MONITORING
Motors, generators and iso-
phase bus are highly reliable.
However, studies indicate
that approximately 40% of
all failures can be attributed
to the gradual aging and
deterioration of the stator
winding insulation. On-line,
periodic partial discharge
testing has been successfully
Installed
Capacitive employed 1951 in diagnosing
Couplers accumulated winding related
problems in different types of
generators. Unlike periodic on-
Features line PD testing, the Iris Power
Sophisticated monitoring and analysis system reduces false indications BusTracII monitor provides
by digitally separating partial discharges from electrical noise, on a maintenance professionals with
pulse-by-pulse basis. the opportunity to:
Proven filtering and pattern recognition enhances noise separation, automate the measurement
allowing for a reliable and objective detection of poor impregnation, (on site or remotely)
overheated windings, coil movement in the slot, ineffective or integrate the key trending
deteriorating grading/semi-conductive material problems and parameters within the plant
contamination. SCADA
The systems compatibility with the Iris Power TGA-BTM technology trigger a remote alarm
allows users with existing sensor installations to commission the system indicating the need for a
without an additional outage. Data can be easily confirmed and further more detailed review of the
analyzed with Iris Powers TGA-B portable monitor. collected data
Ensures a consistent testing interval, thereby improving the quality of maximize collection of PD
the trends. The Iris Power BusTracII instrument continuously collects PD activity
data and archives data which are used to produce 2D and 3D (phase
resolved) plots as well as summary numbers (Qm and NQN), which maximize warning of pending
are used for trending and comparison with similar machines. Using the problems
Windows-based software, the archived PD data can be downloaded create a smoother trend
locally over a USB port, or remotely using Ethernet (TCP/IP) network curve
communication.
lower testing cost.
Important operating conditions such as humidity, stator winding or
equipment temperature, stator voltage, and real and reactive power can The monitor uses the same
be recorded and stored with the archived PD data. These parameters are sensors that have been
useful for in-depth analysis and trending of the partial discharge activity. permanently installed on over
12,000 motors and generators
Qualitrol-Iris Power has extensive experience with continuous on-line around the world over the last
PD monitoring. Over 2,000 continuous PD monitors have been installed. three decades; and provides
Networking with an Ethernet port for remote diagnostics, downloading, the reliability that comes with
configuration with Iris Power software. over 2000 installed continuous
PD monitors.
Modbus over Ethernet protocol included for interfacing to third party
applications to obtain machine operating state and provide summary
PD data.
QUALITROL-IRIS POWER HAS BEEN THE WORLD LEADER IN MOTOR AND GENERATOR WINDING DIAGNOSTICS SINCE 1990,