Sudden Pressure and Bucholz Relays--Application

Response Response
Your Contact Info
Percent Total

Your Name 49
Your Title 48
Your Company Name 49
Total # of respondents 55. Statistics based on 49 respondents; 0 filtered; 6 skipped.

Generator Step-up Transformers

On sealed tank design transformers, which of the following is the current practice at your utility as it
relates to sudden pressure relays?
A B C D E F G H Response
Total

3.6% 23.6% 1.8% 9.1% 34.5% 3.6% 3.6% 20% 55


(2) (13) (1) (5) (19) (2) (2) (11)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Legend for Rank Grid table:On sealed tank design transformers, which of the following is the current
practice at your utility as it relates to sudden pressure relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable

Page 1 of 4
On conservator design transformers, which of the following is the current practice at your utility as it
relates to Bucholz relays?
A B C D E F G H Response
Total

3.6% 10.9% 1.8% 10.9% 36.4% 3.6% 9.1% 23.6% 55


(2) (6) (1) (6) (20) (2) (5) (13)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Legend for Rank Grid table:On conservator design transformers, which of the following is the current
practice at your utility as it relates to Bucholz relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable

Transformers in Transmission Systems

On sealed tank design transformers, which of the following is the current practice at your utility as it
relates to sudden pressure relays?
A B C D E F G H Response
Total

5.5% 23.6% 1.8% 12.7% 34.5% 5.5% 1.8% 14.5% 55


(3) (13) (1) (7) (19) (3) (1) (8)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Page 2 of 4
Legend for Rank Grid table:On sealed tank design transformers, which of the following is the current
practice at your utility as it relates to sudden pressure relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable

On conservator design transformers, which of the following is the current practice at your utility as it
relates to Bucholz relays?
A B C D E F G H Response
Total

7.3% 9.1% 1.8% 14.5% 36.4% 5.5% 9.1% 16.4% 55


(4) (5) (1) (8) (20) (3) (5) (9)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Legend for Rank Grid table:On conservator design transformers, which of the following is the current
practice at your utility as it relates to Bucholz relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable

Transformers in Distribution Systems

Page 3 of 4
On sealed tank design transformers, which of the following is the current practice at your utility as it
relates to sudden pressure relays?
A B C D E F G H Response
Total

9.1% 21.8% 9.1% 10.9% 25.5% 5.5% 1.8% 16.4% 55


(5) (12) (5) (6) (14) (3) (1) (9)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Legend for Rank Grid table:On sealed tank design transformers, which of the following is the current
practice at your utility as it relates to sudden pressure relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable

On conservator design transformers, which of the following is the current practice at your utility as it
relates to Bucholz relays?
A B C D E F G H Response
Total

7.3% 7.3% 7.3% 10.9% 18.2% 1.8% 3.6% 43.6% 55


(4) (4) (4) (6) (10) (1) (2) (24)

Total # of respondents 55. Statistics based on 55 respondents; 0 filtered; 0 skipped.

Legend for Rank Grid table:On conservator design transformers, which of the following is the current
practice at your utility as it relates to Bucholz relays?

Columns:
A - Supervised trip
B - Unsupervised trip
C - Do not trip
D - Alarm only
E - Alarm and unsupervised trip
F - Alarm and supervised trip
G - Do not know
H - Not Applicable