Technical Catalog

for
JU/JW Engine Series
(with English to German Translator Pages)
(Mit Englisch zu Deutsch Ubersetzung Seiten)
(with English to Spanish Translator Pages)
(Traductor del Ingls al Espaol)
(with English to French Canadian Translator Pages)
(Traducteur Anglais > Franais canadien)

This manual covers John Deere Series engines


prepared by Clarke for fire pump service

Clarke UK, Ltd. Clarke Fire Protection Products, Inc.


Unit 1, Grange Works 3133 E. Kemper Road
Lomond Road Cincinnati, OH 45241
Coatbridge U.S.A.
ML5 2NN
United Kingdom
TELE: +44(0)1236 429946 TELE: +1.513.771.2200
FAX: +44(0)1236 427274 FAX: +1.513.771.0726

www.clarkefire.com

C13965 rev P
This page intentionally left blank
CONTENTS
SUBJECT Document No.
English to German I&O Data Translator for German (Englisch zu Deutsch I&O Daten Ubersetzer fr Deutsch) C13973

English to Spanish I&O Data Translator for Spanish (Traductor del Ingls al Espaol) C13986

English to Spanish I&O Data Translator for French (Traducteur Anglais > Franais) C131051

JU4H-UF10/12 (USA) C13663

JU4H-UF10/12 (UK) C131234

JU4H-UF14 (USA) C131262

JU4H-UF14 (UK) C131263

JU4H-UF20/22 (USA) C13611

JU4H-UF20/22 (UK) C131235

JU4H-UF24 (USA) C131264

JU4H-UF24 (UK) C131265

JU4H-UF30/32 (USA) C13664

JU4H-UF30/32 (UK) C131228

JU4H-UFH8 (USA) C131398

JU4H-UFH0 (USA) C131397

JU4H-UFH2 (USA) C131396

JU4H-UF34 (USA) C131266

JU4H-UF34 (UK) C131267

JU4H-UF40/42 (USA) C13665

JU4H-UF40/42 (UK) C131229

JU4H-UF50/52 (USA) C13612

JU4H-UF50/52 (UK) C131230

JU4H-UF54 (USA) C131270

JU4H-UF54 (UK) C131271

JU4R-UF09&11 (USA) C131407

JU4R-UF09&11 (UK) C131651

JU4R-UF13 (USA) C131409

JU4R-UF13 (UK) C131652

JU4R-UF19 & UF21 (USA ) C131408

JU4R-UF19 & UF21 (UK) C131653

JU4R-UF23 (USA) C131410

JU4R-UF23 (UK) C131654

JU4R-UF40 (USA) C131411

JU4R-UF40 (UK) C131655

JU4R-UF49 & UF51 (USA ) C131412

JU4R-UF49 & UF51 (UK) C131656


JU4R-UF53 (USA) C131413

JU4R-UF53 (UK) C131657

JU6H-UFD0 C131394

JU6H-UFD2 C131393

JU6H-UF30/32 (USA) C13507

JU6H-UF30/32 (UK) C131231

JU6H-UFG8 C131392

JU6H-UFM8 C131391

JU6H-UFM0 C131390

JU6H-UFM2 C131389

JU6H-UF34 (USA) C131274

JU6H-UF34 (UK) C131275

JU6H-UF50/52 (USA) C13508

JU6H-UF50/52 (UK) C131232

JU6H-UF54 (USA) C131276

JU6H-UF54 (UK) C131277

JU6H-UF58 C131388

JU6H-UF60/62 (USA) C13509

JU6H-UF60/62 (UK) C131223

JU6H-UF68 C131387

JU6H-UF84 (USA) C131278

JU6H-UF84 (UK) C131279

JW6H-UF38 (USA) C131386

JW6H-UF30 (USA) C13426

JW6H-UF30 (UK) C132031

JW6H-UF48 (USA) C131385

JW6H-UF40 (USA) C13427

JW6H-UF40 (UK) C132032

JW6H-UF58 (USA) C131384

JW6H-UF50 (USA) C13613

JW6H-UF50 (UK) C132033

JW6H-UFH8 (USA) C132024

JW6H-UF60 (USA) C13614

JW6H-UF60 (UK) C132034

JU4H-NL14 C131253

JU4H-NL20/22 C13735

JU4H-NL24 C131254
JU4H-NL34 C131255

JU4H-NL50/52 C13738

JU4H-NL54 C131257

JU4R-NL09/11 C132009

JU4R-NL13 C132010

JU4R-NL19/21 C132011

JU4R-NL23 C132012

JU4R-NL40 C132013

JU4R-NL49/51 C132014

JU4R-NL53 C132015

JU6H-NL30/32 C13739

JU6H-NL34 C131259

JU6H-NL50/52 C13742

JU6H-NL54 C131260

JU6H-NL60 C13743

JU6H-NL74 C131383

JU6H-NL84 C131261

JW6H-NL30 C13997

JW6H-NL40 C13998

JW6H-NL50 C13999

JW6H-NL60 C131000

JU4H-LP20 C131244

JU4H-LP24 C131252

JU4H-LP50 C131245

JU4H-LP54 C131249

JU6H-LP50 C131246

JU6H-LP54 C131251

JU6H-LP60 C131247

JU6H-LP84 C131248

JU4H-AP50 C132129

JU4H-AP54 C132184

JU6H-AP30 C132130

JU6H-AP34 C131286

JU6H-AP50 C132131

JU6H-AP54 C131287

JU6H-AP60 C132132

JU6H-AP84 C131288
English to French Translator for C13977 (Traducteur Anglais > Franais ) C131052

NFPA 20 Cooling Loop Piping Detail C13977

NFPA 20 Exhaust Piping Detail C06918

English to Spanish Translator for C07575 (Traductor del Ingls al Espaol) C13995

English to French Translator for C07575 (Traducteur Anglais > Franais ) C131060

NFPA 20 and FM Engine Gauge Panel (DC Voltage) JU Engines C07575

English to German Translator for C07602 (Englisch zu Deutsch bersetzung fr C07602) C13969

English to Spanish Translator for C07602 (Traductor del Ingls al Espaol) C13987

English to French Translator for C07602 (Traducteur Anglais > Franais ) C131062

NFPA 20 and FM Engine Gauge Panel (DC Voltage) JW Engines C07602

English to Spanish Translator for C07591 (Traductor del Ingls al Espaol) C13994

English to French Translator for C07591 (Traducteur Anglais > Franais ) C131061

Engine Kim Jacket Water Heater (AC Voltage) (JU Engines) C07591

English to German Translator for C07651 (Englisch zu Deutsch bersetzung fr C07651) C13972

English to Spanish Translator for C07651 (Traductor del Ingls al Espaol) C13988

English to Frech Translator for C07651(Traducteur Anglais > Franais ) C131053

Engine Jacket Water Heater (AC Voltage) (JW/JD Engines) C07651

Parts Illustration (JU Engines) C13513

Parts Illustration (JW/JD Engines) C13340


Clarke Installation and Operation Datasheets Clarke Betriebs-und Wartungshandbuch
English to German I&O Data Translator Englisch zu Deutsch I&O Daten Ubersetzer

English Text German Text


Basic Engine Description Grundlegende Motorbeschreibung
Engine Manufacturer Motorhersteller
Iveco Aifo Iveco Aifo
Ignition Type Art der Zndung
Compression (Diesel) Verdichtung (Diesel)
Number of Cylinders Anzahl der Zylinder
Bore and Stroke Zylinderbohrung und Hub
Displacement Verdichtungsverhltnis
Compression Ratio Druck Verhltniss
Valves per Cylinder - Intake Ventile pro Zylinder Ansaugen
- Exhaust Abgas
Combustion System Verbrennungssystem
Direct Injection Direkteinspritzung
Engine Type Motortyp
In-Line, 4 Stroke Cycle Reihenbauweise, Hubzyklus
Aspiration Ansaugung
Natural Direkt
Firing Order (CW Rotation) Zndfolge (Drehung im Uhrzeigersinn)
Charge Air Cooling Type Raw Water Cooled Luft Khlung Typ Roh Wasser Khlung
Rotation (Viewed from Front) Clockwise Drehung (von vorn gesehen)
Clockwise Standard Im Uhrzeigersinn Standard
Counter-Clockwise Im Gegenuhrzeigersinn
Not Available Nicht verfgbar
Engine Crankcase Vent System Belftungssystem Kurbelwellengehuse
Closed Geschlossen
Installation Drawing Installationszeichnung
Cooling System Heat Exchanger Khlsystem - Wrmetauscher
Engine H20 Heat Motor H20 Wrme
Engine Radiated Heat Vom Motor abgestrahlte Wrme
Heat Exchanger Minimum Flow Mindeststrmung Wrmetauscher
Raw H20 Roh H20
Heat Exchanger Maximum Cooling H20 Maximalkhlung Wrmetauscher H20
Inlet Pressure Eingangsdruck
Flow Strmung
Thermostat, Start to Open C (F) Thermostat Starten zum ffnen C (F) degrees
Fully Opened Voll geffnet
Engine Coolant Capacity Motorkhlmittelmenge
Coolant Pressure Cap Khlmitteldruckdose
Maximum Engine H20 Temperature Maximalmotor H20 temperatur
Minimum Engine H20 Temperature Mindestmotor H20 temperatur
Cooling System Radiator Khlsystem Khler
Engine H20 Heat Motor H20 Wrme
Engine Radiated Heat Vom Motor abgestrahlte Wrme
Radiator Minimum Ventilation Flow Khler Mindestluftstrom
Thermostat, Start to Open Thermostat Starten zum ffnen
Fully Opened Voll geffnet
Engine Coolant Capacity Motorkhlmittelmenge
Coolant Pressure Cap Khlmitteldruckdose
Maximum Engine Temperature Maximalmotortemperatur
Minimum Engine Temperature Mindestmotortemperatur
Electric System DC Elektrosystem Gleichstrom
System Voltage (Nominal) Systemspannung (Nennspannung)
Battery Capacity for Ambients Above 0 Batteriekapazitt fr Ambient uber** 0 Degress
Umgebungsbedingungen
Voltage (Nominal) Spannung (Nennspannung)
Qty. per Battery Bank Menge pro Batteriespeicher
SAE size per SAE Gre pro
Reserve Capacity Minutes Reservekapazitt Minuten
Battery Cable Circuit*, Max Resistance - ohm Batteriekabelkreis* - Maximaler Widerstand Ohm
Battery Cable Minimum Size Mindestgre Batteriekabel
Circuit* Length Stromkreis*lnge
Charging Alternator Output Amp Ausgang Ladealternator - Ampere
Starter Cranking Amps Ampere Anlasserkurbel
*Positive and Negative Cables Combined Length *Gesamtlnge positive nd negative Kabel

Page 1 of 2
Clarke Installation and Operation Datasheets Clarke Betriebs-und Wartungshandbuch
English to German I&O Data Translator Englisch zu Deutsch I&O Daten Ubersetzer

English Text German Text


(Continued) Fortsetzung
NOTE: This engine is Intended for Indoor Installation Or In a HINWEIS: Diese Maschine ist fr Installation im Raum oder in
Weatherproof Enclosure. einem wettergeschtzten Gehuse bestimmt.

Exhaust System Abgassystem


Exhaust Flow Abgasstrom
Exhaust Temperature Abgastemperatur
Maximum Allowable Back Pressure Maximal zulssiger Gegendruck
Minimum Exhaust Pipe Dia. Mindestauspuffrohrdurchmesser
Fuel System Kraftstoffsystem
Fuel Consumption Kraftstoffverbrauch
Fuel Return Kraftstoffrckfluss
Total Supply Fuel Flow Gesamtzufuhrstrmung Kraftstoff
Fuel Pressure Kraftstoffdruck
Minimum Line Size Supply Mindestleitungsgre Zufuhr
Maximum Line Size Return Maximalleitungsgre Rcklauf
Maximum Allowable Fuel Pump Suction Maximal zulssige Kraftsstoffpumpensaugkraft
With Clean Filter mit sauberem Filter
Maximum Allowable Fuel Head above Fuel Pump, Maximal zulssiger Kraftstoffdruck ber der
Supply or Return Kraftstoffpumpe, Zufuhr oder Rcklauf
Fuel Filter Micron Size Mikrongre Kraftstofffilter
Heater System Erhitzersystem
Jacket Water Heater Mantelwassererhitzer
Optional Optional
Wattage (Nominal) Wattleistung (Nennwert)
Voltage AC, 1P Spannung Wechselstrom, 1P
Optional Voltage AC, 1P Optionale Spannung Wechselstrom, 1P
Lube Oil Heater Wattage Schmierlerhitzer Wattleistung
(Required Option When Ambient is Below) (erforderliche Option wenn
Umgebungsbedingungen darunter liegen)
Induction Air System Induktionsluftsystem
Air Cleaner Type Luftfiltertyp
Canister Dry Type Drip Proof Kanister-Trockentyp tropfsicher
Air Intake Restriction Maximum Limit Maximalgrenze fr Ansaugluftbegrenzung
Dirty Air Cleaner Schmutziger Luftfilter
Clean Air Cleaner Sauberer Luftfilter
Engine Air Flow Motorluftdurchsatz
Maximum Allowable Temperature (Air to Engine Inlet) Maximal zulssige Temperatur (Luft zum
Motoreingang)
Lubrication System Schmiersystem
Oil Pressure normal ldruck normalen
In Pan Oil Temperature ltemperatur in der Wanne
Oil Pan Capacity High lwannenkapazitt hoch
Total Oil Capacity with Filter Gesamtlmenge mit Filter
Performance Leistung
BMEP BMEP
Piston Speed Kolbendrehzahl
Sound Pressure Level Schalldruckpegel
Power Curve Leistungskurve
** Based On Nominal System. Flow Analysis Must Be Done To *Basierend auf Nennsystem. Strmungsanalyse muss
Assure Adherence To System Limitations. durchgefhrt werden, um Einhaltung der Systembegrenzungen zu
gewhrleisten.
(Minimum Exhaust pipe Diameter is based on 1m of flexible (Mindestauspuffrohrdurchmesser basiert auf 1 m flexiblem Stck,
section, 2m of rigid section, 1 90 elbow, and a silencer (as 2 m starrem Stck, einem 90 Krmmer und einem
supplied by Clarke). Schalldmpfer (wie von Clarke geliefert).
*** Review for Power Deration If Air Entering Engine Exceeds *** Prfe auf Leistungsabminderung wenn die in den Motor
25C (77 F) eindringende Luft berschreitet

C13973 rev A

Page 2 of 2
Clarke Installation and Operation Datasheets Hoja de Datos de Instalacin y Operacin de Clarke
English to Spanish I&O Data Translator Traductor de Datos de I&O del Ingls al Alemn

English Text Texto en Espaol


Basic Engine Description Descripcin de Motor Bsico
Engine Manufacturer Fabricante del Motor
Iveco Aifo Iveco Aifo
Ignition Type Tipo de Ignicin
Compression (Diesel) Compresin (Diesel)
Number of Cylinders Nmero de Cilindros
Bore and Stroke Dimetro y Carrera
Displacement Desplazamiento
Compression Ratio Relacin de Compresin
Valves per Cylinder - Intake Vlvulas por Cilindro - Admisin
- Exhaust - Escape
Combustion System Sistema de Combustin
Direct Injection Inyeccin Directa
Engine Type Tipo de Motor
In-Line, 4 Stroke Cycle En Lnea, Ciclo de Carrera
Aspiration Aspiracin
Natural Natural
Firing Order (CW Rotation) Orden de Encendido (Rotacin en sentido contrario a las manecillas del reloj)
Charge Air Cooling Type Raw Water Cooled
Rotation (Viewed from Front) Clockwise Rotacin (Vista desde la parte delantera)
Clockwise Standard Estndar
Counter-Clockwise Sentido contrario a las manecillas del reloj
Not Available No Disponible
Engine Crankcase Vent System Sistema de Ventilacin del Crter del Motor
Closed Cerrado
Installation Drawing Diagrama de Instalacin
Cooling System Heat Exchanger Sistema de Enfriamiento - Intercambiador de Calor
Engine H20 Heat Calor de Motor
Engine Radiated Heat Calor Irradiado por el Motor
Heat Exchanger Minimum Flow Flujo Mnimo del Intercambiador de Calor
Raw H20 No Tratado
Heat Exchanger Maximum Cooling H20 Enfriamiento Mximo del Intercambiador de Calor
Inlet Pressure Presin de Entrada
Flow Flujo
Thermostat, Start to Open C (F) Termostato, Inicio de Abertura
Fully Opened Totalmente Abierto
Engine Coolant Capacity Capacidad de Refrigerante del Motor
Coolant Pressure Cap Tapn de Presin del Refrigerante
Maximum Engine H20 Temperature Temperatura Mxima del Motor
Minimum Engine H20 Temperature Temperatura Mnima del Motor
Cooling System Radiator Sistema de Enfriamiento - Radiador
Engine H20 Heat Calor del Motor
Engine Radiated Heat Calor Irradiado por el Motor
Radiator Minimum Ventilation Flow Flujo de Ventilacin Mnimo del Radiador
Thermostat, Start to Open Termostato Inicio de Abertura
Fully Opened Totalmente Abierto
Engine Coolant Capacity Capacidad de Refrigerante del Motor
Coolant Pressure Cap Tapn de Presin de Refrigerante
Maximum Engine Temperature Temperatura Mxima del Motor
Minimum Engine Temperature Temperatura Mnima del Motor
Electric System DC Sistema Elctrico - DC
System Voltage (Nominal) Voltaje de Sistema (Nominal)
Battery Capacity for Ambients Above 0 Capacidad de Batera para Ambientes que exceden
el Voltaje (Nominal)
Voltage (Nominal) Cantidad por Banco de Bateras
Qty. per Battery Bank Tamao SAE por
SAE size per Capacidad de Reserva - Minutos
Reserve Capacity Minutes Circuito de Cable de Batera*, Resistencia Mxima - ohm
Battery Cable Circuit*, Max Resistance - ohm Tamao Mnimo de Cable de Batera
Battery Cable Minimum Size Largo de Circuito*
Circuit* Length Salida del Alternador - Amp
Charging Alternator Output Amp Amperaje de Giro del Arrancador
Starter Cranking Amps *Largo Combinado de los Cables Positivo y Negativo*
*Positive and Negative Cables Combined Length NOTA: El motor es para instalacin en interiores o en una Cubierta a Prueba
NOTE: This engine is Intended for Indoor Installation Or In A Wetherproof de Intemperie.
Enclosure.
Page 1 of 2
Clarke Installation and Operation Datasheets Hoja de Datos de Instalacin y Operacin de Clarke
English to Spanish I&O Data Translator Traductor de Datos de I&O del Ingls al Alemn

English Text Texto en Espaol


(Continued) (Contina)
Exhaust System Sistema de Escape
Exhaust Flow Flujo de Escape
Exhaust Temperature Temperatura de Escape
Maximum Allowable Back Pressure Contrapresin Mxima Permitida
Minimum Exhaust Pipe Dia. Dimetro mnimo de Tubo de Escape

Fuel System Sistema de Combustible


Fuel Consumption Consumo de Combustible
Fuel Return Retorno de Combustible
Total Supply Fuel Flow Flujo Total de Suministro de Combustible
Fuel Pressure Presin de Combustible
Minimum Line Size Supply Tamao Mnimo de Lnea - Suministro
Maximum Line Size Return Tamao Mximo de Lnea - Retorno
Maximum Allowable Fuel Pump Suction Mxima Succin Permitida de la Bomba de Combustible
With Clean Filter Con Filtro Limpio
Maximum Allowable Fuel Head above Fuel Pump, Mxima Presin Permitida del Combustible Permitida de la
Supply or Return Bomba, Suministro o Retorno
Fuel Filter Micron Size Tamao en Micras del Filtro de Combustible

Heater System Sistema Calentador


Jacket Water Heater Calentador de Agua de Chaqueta
Optional Opcional
Wattage (Nominal) Wattaje (Nominal)
Voltage AC, 1P Voltaje - A.C., 1P
Optional Voltage AC, 1P Voltaje Opcional - AC, 1P
Lube Oil Heater Wattage Wattaje de Calentador de Aceite Lubricante
(Required Option When Ambient is Below) (Opcin Requerida cuando el Ambiente es Inferior a)

Induction Air System Sistema de Aire de Induccin


Air Cleaner Type Tipo de Purificador de Aire
Canister Dry Type Drip Proof De Tipo Seco de Recipiente - A Prueba de Escurrimiento
Air Intake Restriction Maximum Limit Lmite Mximo de Restriccin de Aire
Dirty Air Cleaner Purificador de Aire Sucio
Clean Air Cleaner Purificador de Aire Limpio
Engine Air Flow Flujo de Aire de Motor
Maximum Allowable Temperature (Air to Engine Inlet) Temperatura Mxima Permitida (Entrada de Aire al Motor)

Lubrication System Sistema de Lubricacin


Oil Pressure normal Presin de Aceite - Normal
In Pan Oil Temperature Temperatura de Aceite del Colector
Oil Pan Capacity High Capacidad del Colector de Aceite - Alta
Total Oil Capacity with Filter Capacidad Total de Aceite con Filtro

Performance Operacin
BMEP BMEP
Piston Speed Velocidad de Pistones
Sound Pressure Level Nivel de Presin de Sonido
Power Curve Curva de Potencia
** Based On Nominal System. Flow Analysis Must Be Done To **Basado en un Sistema Nominal - El anlisis del flujo deber
Assure Adherence To System Limitations. analizarse para asegurarse que hay apego a las limitaciones del
sistema.
(Minimum Exhaust pipe Diameter is based on 1m of flexible (El dimetro mnimo de tubo de escape se basa en 1m de
section, 2m of rigid section, 1 90 elbow, and a silencer (as seccin flexible, 2m de seccin rgida, 1 codo de 900 y un
supplied by Clarke). silenciador (suministrado por Clarke).
*** Review for Power Deration If Air Entering Engine Exceeds ***Revise la reduccin de potencia si el aire que ingresa al motor
25C (77 F) excede

C13986 rev A

Page 2 of 2
Clarke Installation and Operation Datasheets Fiches techniques dinstallation et dutilisation de Clarke
English to French-Canadian I&O Data Translator Traducteur Anglais > Franais des donnes d'installation et d'utilisation

English Text Texte en franais canadien


Basic Engine Description Description lmentaire du moteur
Engine Manufacturer Fabricant du moteur
John Deere Co. John Deere Co.
Ignition Type Type dallumage
Compression (Diesel) Compression (Diesel)
Number of Cylinders Nombre de cylindres
Bore and Stroke Alsage et course
Displacement Cylindre
Compression Ratio Rapport de compression
Valves per Cylinder - Intake Soupapes par cylindre - Admission
- Exhaust - chappement
Combustion System Systme de combustion
Direct Injection Injection directe
Engine Type Type de moteur
In-Line, 4 Stroke Cycle En ligne 4 temps
Aspiration Aspiration
Naturally Aspirated Aspiration naturelle
Turbocharged Turbocompresseur
Firing Order (CW Rotation) Ordre dallumage (rotation anti-horaire)
Charge Air Cooling Type Type de refroidissement air
None Aucun
Raw Water Cooled Refroidissement eau brute
Jacket Water Cooled Refroidissement eau chemise
Rotation (Viewed from Front) Rotation (vue de lavant)
Clockwise Sens des aiguilles dune montre
Standard Standard
Counter-Clockwise Sens inverse des aiguilles dune montre
Not Available Non disponible
Engine Crankcase Vent System Systme de respiration du carter de moteur
Open Ouvert
Installation Drawing Plan dinstallation

Cooling System Systme de refroidissement


Engine Heat Chaleur du moteur
Engine Radiated Heat Chaleur mise par le moteur
Heat Exchanger Minimum Flow coulement minimal de lchangeur de chaleur
Raw Brut
Heat Exchanger Maximum Cooling Refroidissement maximal de lchangeur de chaleur
Inlet Pressure Pression dentre
Flow coulement
Thermostat, Start to Open Thermostat, Dbut douverture
Fully Opened Ouverture totale
Engine Coolant Capacity Capacit de liquide de refroidissement du moteur
Coolant Pressure Cap Bouchon de radiateur
Maximum Engine Temperature Temprature maximale du moteur
Minimum Engine Temperature Temprature minimale du moteur

Electric System DC Systme lectrique courant continu


System Voltage (Nominal) Tension du systme (nominale)
Battery Capacity for Ambients Above Capacit de la batterie pour les conditions ambiantes ci-dessus
Voltage (Nominal) Tension (nominale)
Qty. per Battery Bank Qt. par jeu de batteries
SAE size per J537 Taille SAE selon J537
Reserve Capacity Minutes Capacit de rserve minutes
Battery Cable Circuit*, Max Resistance - ohm Circuit de cblage de la batterie*, rsistance maximale ohms
Battery Cable Minimum Size Taille minimale des cbles de batterie
Circuit* Length Longueur du circuit*
Charging Alternator Output Amp Courant de sortie de lalternateur de charge ampres
Starter Cranking Amps Courant de lancement du dmarreur

*Positive and Negative Cables Combined Length * Longueurs combines des cbles positif et ngatif

NOTE: This engine is Intended for Indoor Installation Or In A REMARQUE : Ce moteur est prvu pour une installation en
Weatherproof Enclosure. (Continued) intrieur ou dans un caisson protg des intempries. (suite)
Page 1 sur 2
Clarke Installation and Operation Datasheets Fiches techniques dinstallation et dutilisation de Clarke
English to French-Canadian I &O Data Translator Traducteur Anglais>Franais des donnes d'installation et d'utilisation

English Text Texte en franais canadien

Exhaust System Systme dchappement


Exhaust Flow Dbit dchappement
Exhaust Temperature Temprature dchappement
Maximum Allowable Back Pressure Contre-pression maximale admissible
Minimum Exhaust Pipe Dia. Diamtre minimal du tuyau dchappement

Fuel System Systme dalimentation en carburant


Fuel Consumption Consommation de carburant
Fuel Return Retour du carburant
Total Supply Fuel Flow Dbit du carburant dalimentation
Fuel Pressure Pression du carburant
Minimum Line Size Supply Taille minimale des conduites alimentation
Maximum Line Size Return Taille maximale des conduites retour
Maximum Allowable Fuel Pump Suction Aspiration maximale admissible de la pompe carburant
With Clean Filter Avec filtre propre
Maximum Allowable Fuel Head above Fuel Pump, Hauteur de charge de carburant maximale admissible
Supply or Return au-dessus de la pompe, alimentation ou retour
Fuel Filter Micron Size Taille du filtre carburant en microns

Heater System Systme de rchauffage


Jacket Water Heater Rchauffage deau chemise
Optional En option
Wattage (Nominal) Puissance (nominale)
Voltage AC, 1P Tension alternatif, monophas
Optional Voltage AC, 1P Tension en option alternatif, monophas

Induction Air System Systme dair dinduction


Air Cleaner Type Type de filtre air
Indoors Service Only - Washable Service en intrieur uniquement lavable
Air Intake Restriction Maximum Limit Limite maximale de la restriction dentre dair
Dirty Air Cleaner Filtre air sale
Clean Air Cleaner Filtre air propre
Engine Air Flow Dbit dair du moteur
Maximum Allowable Temperature (Air to Engine Inlet) Temprature maximale admissible (air dentre du moteur)

Lubrication System Systme de lubrification


Oil Pressure normal Pression dhuile normale
In Pan Oil Temperature Temprature de lhuile dans le carter
Oil Pan Capacity High Capacit du carter dhuile niveau lev
- Low niveau bas
Total Oil Capacity with Filter Capacit dhuile totale avec le filtre

Performance Performances
BMEP BMEP
Piston Speed Vitesse du piston
Mechanical Noise - Bruit mcanique -
Power Curve Courbe de puissance
** Based On Nominal System. Flow Analysis Must Be Done To ** Bas sur le systme nominal. Une analyse du dbit doit tre
Assure Adherence To System Limitations. effectue pour assurer le respect des limitations du systme.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one (Le diamtre minimal du tuyau dchappement est bas sur 4,5 m
elbow, and a silencer pressure drop no greater than one half the (15 pieds) de tuyau, un coude et une chute de pression dans le
max. allowable back pressure.) silencieux infrieure la moiti de la contre-pression maximale
admissible.)

*** Review for Power Deration If Air Entering Engine Exceeds *** Rviser la baisse si lair d'admission du moteur dpasse
C131051 revA

Page 2 sur 2
CLARKE
Fire Protection Products
JU4H-UF10 & JU4H-UF12
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L).... 275 (4.5)
Compression Ratio.. 17.0:1
Valves per cylinder - Intake... 1
Exhaust... 1
Combustion System.. Direct Injection
Engine Type... Rotary, 4 Stroke Cycle
Aspiration.. Naturally Aspirated
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System... Open
Installation Drawing. D-534
Weight - lb (kg) 910 (413)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)... 19 (20) 28 (30) 40 (42) 42 (44)
Engine Radiated Heat - Btu/sec.(kW)..
9 (10) 11 (12) 12 (13) 13 (14)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..
6 (23) 7 (26) 8 (30) 9 (34)
95F (35C) Raw H2O - gal/min. (L/min.)..
8 (30) 9 (34) 10 (38) 11 (42)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
4 (60) (400)
Flow - gal./min (L/min.).......
. 40 (151)
Thermostat, Start to Open - F (C).187 (86)
Fully Opened - F (C)...
196 (91)
Engine Coolant Capacity - qt. (L)... 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa)...
10 (69)
Maximum Engine H20 Temperature - F (C)...
200 (93)
Minimum Engine H20 Temperature - F (C)...
160 (71)

Electric System - DC
System Voltage (Nominal)... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.......
0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.. 000 000
161 - 200 in. Circuit* Length.. 0000 0000
Charging Alternator Output - Amp..... 40 40
Starter Cranking Amps - @ 60F (15C).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF10 & JU4H-UF12
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 1760 2100 2350 2600
Exhaust Flow - ft.3/min. (m3/min.). 379 (11) 415 (12) 469 (13) 531 (15)
Exhaust Temperature - F (C)........ 740 (393) 918 (492) 1083 (584) 1055 (568)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 2.2 ( 8.3) 2.8 (10.6) 3.1 (11.7) 3.4 (12.9)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 10.1 (38.2) 11.3 (42.8) 12.1 (45.8) 12.9 (48.9)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m).. 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 140 (4.0) 155 (4.4) 166 (4.7) 186 (5.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 67 (462) 70 (483) 67 (462) 65 (448)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13905 (UF10) & C13906 (UF12)
Power Curve C13646 (UF10) & C13647 (UF12)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13663 revJ
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF10 & JU4H-UF12
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders............. 4
Bore and Stroke - mm (in.).......... 4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat - kW (Btu/sec)......... 10.0 (9.0) 12.0 (11.0) 13.0 (12.0) 14.0 (13.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
15 (4) 23 (6) 30 (8) 38 (10)
23 (6)
35C (95F) Raw H2O - L/min. (gal/min.)...... 30 (8) 38 (10) 45 (12)
Heat Exchanger Maximum Cooling H2O
2
4 (60) (400)
Inlet Pressure - bar (lb./in. ) (kPa)..........
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal).........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF10 & JU4H-UF12
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1760 2100 2350 2600
Exhaust Flow - m3/min. (ft.3/min.).............
11.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)
393 (740) 492 (918)
Exhaust Temperature - C (F)............... 584 (1083) 568 (1055)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)....
76 (3)
Minimum Exhaust Pipe Dia. - mm (in.)**..........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............. 8.3 (2.2) 10.6 (2.8) 11.7 (3.1) 12.9 (3.4)
Fuel Return - L/hr. (gal./hr.)........... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.)........... 38.2 (10.1) 42.8 (11.3) 45.8 (12.1) 48.9 (12.9)
Fuel Pressure - kPa (lb./in.2)........... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)................ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)......... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....1.4 (4.5)
Fuel Filter Micron Size................ 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............1500
Voltage - AC, 1P.............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)........ 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).......
241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........ 8 (7.5)
Low - L (qt.).. 7 (6.5)
Total Oil Capacity with Filter - L (qt.)...9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2)............. 4.8 (67) 4.9 (70) 4.8 (67) 4.5 (65)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131933 (UF10) C131934 (UF12)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131234 revF
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF14
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.00)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 32 (30) 34 (32) 36 (34) 38 (36)
Engine Radiated Heat - kW (Btu/sec)....... 12 (13) 13 (14) 14 (15) 15 (16)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)....... 4 (60) (400)
Flow - L/min. (gal./min)......... 100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF14
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)........ 13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F)...........584 (1083) 568 (1055) 556 (1033) 543 (1010)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr)......... 11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)
Fuel Return - L/hr. (gal./hr.)....... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr).......45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2)
Fuel Pressure - kPa (lb./in. 2)............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20).......0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size........... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type...........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)............ 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).......... 241-345 (35-50)
In Pan Oil Temperature - C (F)............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........... 7.5 (8)
Low - L (qt.)....6.5 (7)
Total Oil Capacity with Filter - L (qt.)........ 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............ 462 (67) 448 (65) 437 (63) 426 (62)
Piston Speed - m/min (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve.............. C131943

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
C131263 revF
18DEC07 DSP
CLARKE
Fire Protection Products
JU4H-UF14
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.00)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 32 (30) 34 (32) 36 (34) 38 (36)
Engine Radiated Heat - kW (Btu/sec)....... 12 (13) 13 (14) 14 (15) 15 (16)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)....... 4 (60) (400)
Flow - L/min. (gal./min)......... 100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF14
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)........ 13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F)...........584 (1083) 568 (1055) 556 (1033) 543 (1010)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr)......... 11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)
Fuel Return - L/hr. (gal./hr.)....... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr).......45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2)
Fuel Pressure - kPa (lb./in. 2)............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20).......0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size........... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type...........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)............ 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).......... 241-345 (35-50)
In Pan Oil Temperature - C (F)............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........... 7.5 (8)
Low - L (qt.)....6.5 (7)
Total Oil Capacity with Filter - L (qt.)........ 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............ 462 (67) 448 (65) 437 (63) 426 (62)
Piston Speed - m/min (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve.............. C131943

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
C131263 revF
18DEC07 DSP
CLARKE
Fire Protection Products
JU4H-UF20 & JU4H-UF22
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L).... 275 (4.5)
Compression Ratio.. 17.0:1
Valves per cylinder - Intake... 1
Exhaust... 1
Combustion System.. Direct Injection
Engine Type... Rotary, 4 Stroke Cycle
Aspiration.. Naturally Aspirated
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System... Open
Installation Drawing. D-534
Weight- lb (kg) 910 (413)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)... 19 (20) 28 (30) 40 (42) 42 (44)
Engine Radiated Heat - Btu/sec.(kW)..
13 (14) 15 (16) 16 (17) 17 (18)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..
6 (23) 7 (26) 8 (30) 9 (34)
95F (35C) Raw H2O - gal/min. (L/min.)..
8 (30) 9 (34) 10 (38) 11 (42)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)....... 4 (60) (400)
Flow - gal./min (L/min.).... 40 (151)
Thermostat, Start to Open - F (C).187 (86)
Fully Opened - F (C)...
196 (91)
Engine Coolant Capacity - qt. (L)... 15 (14)
Coolant Pressure Cap - lb./in.2(kPa)...
10 (69)
Maximum Engine H20 Temperature - F (C)...
200 (93)
Minimum Engine H20 Temperature - F (C)...
160 (71)

Electric System - DC
System Voltage (Nominal)... 12(Standard) 24(Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.......
0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.. 000 000
161 - 200 in. Circuit* Length.. 0000 0000
Charging Alternator Output - Amp..... 40 40
Starter Cranking Amps - @ 60F (15C).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF20 & JU4H-UF22
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 379 (11) 415 (12) 469 (13) 531 (15)
Exhaust Temperature - F (C)........1021 (549) 1016 (547) 1076 (580) 1095 (591)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 3.8 (14.4) 5.3 (20.1) 5.6 (21.2) 5.8 (22.0)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 11.7 (44.3) 13.8 (52.3) 14.6 (55.3) 15.3 (58.0)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 140 (4.0) 155 (4.4) 166 (4.7) 186 (5.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 98 (677) 92 (634) 88 (608) 83 (573)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13907 (UF20) & C13908 (UF22)
Power Curve C13476 (UF20) & C13561 (UF22)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13611 rev J
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF20 & JU4H-UF22
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat - kW (Btu/sec)......... 14.0 (13.0) 16.0 (15.0) 17.0 (16.0) 18.0 (17.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
15 (4) 23 (6) 30 (8) 38 (10)
23 (6)
35C (95F) Raw H2O - L/min. (gal/min.)...... 30 (8) 38 (10) 45 (12)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF20 & JU4H-UF22
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........11.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)
Exhaust Temperature - C (F)............. 549 (1021) 547 (1016) 580 (1076) 591 (1095)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
76 (3)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 14.4 (3.8) 20.1 (5.3) 21.2 (5.6) 22.0 (5.8)
Fuel Return - L/hr. (gal./hr.).......... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 44.3 (11.7) 52.3 (13.8) 55.3 (14.6) 58.0 (15.3)
Fuel Pressure - kPa (lb./in.2)........... 21-41 (3-6)
Minimum Line Size - Supply - (in.)............. .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .033 (.848)
Minimum Line Size - Return - (in.)............. .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).................. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).......... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type.......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).............
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)............
Engine Air Flow - m3/min. (ft.3/min.)........ 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........
241-345 (35-50)
In Pan Oil Temperature - C (F).......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......... 8 (7.5)
Low - L (qt.)..7 (6.5)
Total Oil Capacity with Filter - L (qt.)....9 (8.5 )

Performance
BMEP - kg/cm2 (lb./in.2).............6.9 (98) 6.5 (92) 6.1 (88) 5.9 (83)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131935 (UF20) & C131936 (UF22)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131235 revF
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF24
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type...................... Compression (Diesel)
Number of Cylinders............. 4
Bore and Stroke - in. (mm).......... 4.19 (106) x 5.00 (127)
3
Displacement - in. (L).......... 275 (4.5)
Compression Ratio............ 17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-534
Weight - lb (kg).......
910 (413)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 40 (42) 42 (44) 44 (46) 45 (47)
Engine Radiated Heat - Btu/sec (kW)......... 16 (17) 17 (18) 18 (19) 19 (20)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
8 (30) 9 (34) 10 (37) 11 (40)
95F (35C) Raw H2O - gal/min. (L/min.)......
10 (38) 11 (42) 12 (45) 13 (48)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.)..............40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa)....... 10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
160 (71)
Minimum Engine H20 Temperature - F (C).....

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm........... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF24
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..469 (13) 531 (15) 581 (16) 630 (18)
Exhaust Temperature - F (C)...
.......... 1076 (580) 1095 (591) 1110 (599) 1125 (607)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 5.6 (21.2) 5.8 (22.0) 6.0 (22.7) 6.2 (23.5)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 14.6 (55.3) 15.3 (58.0) 15.9 (60.2) 16.5 (62.5)
Fuel Pressure - lb./in.2 (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m 3/min.)...166 (4.7) 186 (5.3) 202 (5.7) 218 (6.2)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
104-118 (220-245)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
. 88 (608) 83 (573) 79 (545) 75 (517)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2334 (711) 2501 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve. C131089

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131264 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-UF24
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 40 (42) 42 (44) 44 (46) 45 (47)
Engine Radiated Heat - Btu/sec (kW)......... 16 (17) 17 (18) 18 (19) 19 (20)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.)......
38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..................
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (14)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF24
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F)............. 580 (1076) 591 (1095) 599 (1110) 607 (1125)
Maximum Allowable Back Pressure - kPa (in. H20)...7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr.)............ 21.2 (5.6) 22.0 (5.8) 22.7 (6.0) 23.5 (6.2)
Fuel Return - L/hr. (gal./hr.).......... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 55.3 (14.6) 58.0 (15.3) 60.2 (15.9) 62.5 (16.5)
Fuel Pressure - kPa (lb./in.2)............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).........
1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)..............
2.5 (10)
Clean Air Cleaner - kPa (in. H20).............
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).........
241-345 (35-50)
In Pan Oil Temperature - C (F)........... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......... 7.5 (8)
Low - L (qt.)...6.5 (7)
Total Oil Capacity with Filter - L (qt.).....8.5 (9)

Performance
BMEP - kPa (lb./in. 2)............. 608 (88) 573 (83) 545 (79) 517 (75)
597 (1958) 661 (2167) 711 (2334) 762 (2501)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.............. Consult Factory
Power Curve................ C131944

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131265 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF30 & JU4H-UF32
INSTALLATION & OPERATION DATA
USA Production

Basic Engine Description


Engine Manufacturer..... John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders... 4
Bore and Stroke - in.(mm)....4.19(106) x 5.00(127)
3
Displacement - in. (L).........
275 (4.5)
Compression Ratio.... 17.0:1
Valves per cylinder - Intake....
1
Exhaust....
1
Combustion System.. Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration.... Turbocharged
Firing Order (CW Rotation)...1-3-4-2
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise Standard
Counter-Clockwise. Not Available
Engine Crankcase Vent System. Open
Installation Drawing. D-534
Weight - lb (kg)
935 (424)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)..... 40 (42) 47 (50) 47 (50) 53 (56)
Engine Radiated Heat - Btu/sec.(kW). 14 (15) 18 (19) 19 (20) 19 (20)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
8 (30) 10 (38) 10 (38) 10 (38)
95F (35C) Raw H2O - gal/min. (L/min.)...
10 (38) 11 (42) 11 (42) 14 (53)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
4 (60) (400)
Flow - gal./min (L/min.).. 40 (151)
Thermostat, Start to Open - F (C)...
187 (86)
Fully Opened - F (C)...
196 (91)
Engine Coolant Capacity - qt. (L)....15 (14)
2
Coolant Pressure Cap - lb./in. (kPa)...
10 (69)
Maximum Engine H20 Temperature - F (C)....
200 (93)
Minimum Engine H20 Temperature - F (C).....
160 (71)

Electric System - DC
System Voltage (Nominal)... 12(Standard) 24(Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537..... 4D-640 4D-640
CCA @ 0F (-18C).... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length. 0000 0000
Charging Alternator Output - Amp...... 40 40
Starter Cranking Amps - @ 60F (15C). 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF30 & JU4H-UF32
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 330 (9) 448 (13) 518 (15) 572 (16)
Exhaust Temperature - F (C)........ 744 (396) 781 (416) 761 (405) 731 (388)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 1.7 (6.4) 2.2 (8.3) 2.7 (10.2) 3.5 (13.2)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 9.6 (36.3) 10.7 (40.5) 11.7 (44.3) 13.0 (49.2)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 147 (4.2) 194 (5.5) 227 (6.4) 252 (7.1)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 105 (724) 108 (745) 104 (717) 94 (648)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13909 (UF30)
Power Curve C13648 (UF30) & C13649 (UF32)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13664 revJ
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF30 & JU4H-UF32
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat - kW (Btu/sec)......... 15.0 (14.0) 19.0 (18.0) 20.0 (19.0) 20.0 (19.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 38 (10) 45 (12)
38 (10)
35C (95F) Raw H2O - L/min. (gal/min.)...... 42 (11) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF30 & JU4H-UF32
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........... 9.0 (330) 13.0 (448) 15.0 (518) 16.0 (572)
Exhaust Temperature - C (F)............. 396 (744) 416 (781) 405 (761) 388 (731)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 6.4 (1.7) 8.3 (2.2) 10.2 (2.7) 13.2 (3.5)
Fuel Return - L/hr. (gal./hr.).......... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 36.3 (9.6) 40.5 (10.7) 44.3 (11.7) 49.2 (13.0)
Fuel Pressure - kPa (lb./in.2)............. 21-41 (3-6)
Minimum Line Size - Supply - (in.)........... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)...................033 (.848)
Minimum Line Size - Return - (in.)................ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)...................026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)......... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............1500
Voltage - AC, 1P............. 115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type.......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)......... 4.2 (147) 5.5 (194) 6.4 (227) 7.1 (252)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....... 241-345 (35-50)
In Pan Oil Temperature - C (F)......... .
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......... 8 (7.5)
Low - L (qt.).. 7 (6.5)
Total Oil Capacity with Filter - L (qt.).... 9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2)............. 7.3 (105) 7.6 (108) 7.3 (104) 6.6 (94)
Piston Speed - m/min. (ft./min.).......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131937 (UF30) C131938 (UF32)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131228 revF
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UFH8
INSTALLATION & OPERATION DATA
USA Production

Basic Engine Description


Engine Manufacturer.. . John Deere Co.
Ignition Type..
. Compression (Diesel)
Number of Cylinders. . 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L)... . 275 (4.5)
Compression Ratio. . 17.0:1
Valves per cylinder - Intake..
. 1
Exhaust..
. 1
Combustion System. . Direct Injection
Engine Type..
. In-Line, 4 Stroke Cycle
Aspiration.
. Turbocharged
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type. . None
Rotation (Viewed from Front) - Clockwise . Standard
Counter-Clockwise. .. Not Available
Engine Crankcase Vent System.. . Open
Installation Drawing . D-534
Weight - lb (kg) 935 (424)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW).. . 34 (36) 40 (42)
Engine Radiated Heat - Btu/sec.(kW)........ 14 (15) 16 (17)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)... 6 (24) 8 (30)
95F (35C) Raw H2O - gal/min. (L/min.)... 9 (35) 10 (38)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).
. 4 (60) (400)
Flow - gal./min (L/min.). .
. 40 (151)
Thermostat, Start to Open - F (C) . 187 (86)
Fully Opened - F (C)... 196 (91)
Engine Coolant Capacity - qt. (L)....... 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa)... 10 (69)
Maximum Engine H20 Temperature - F (C)....... 200 (93)
Minimum Engine H20 Temperature - F (C).. .. 160 (71)

Electric System - DC
System Voltage (Nominal)... 12(Standard) 24(Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C).. . 640 640
Reserve Capacity - Minutes....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length
. 00 00
121 - 160 in. Circuit* Length.
. 000 000
161 - 200 in. Circuit* Length.
. 0000 0000
Charging Alternator Output - Amp.... .. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UFH8
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1470 1760


Exhaust Flow - ft.3/min. (m3/min.). 264 (7.5) 362 (10)
Exhaust Temperature - F (C)........ 780 (416) 794(423)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102) 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 1.8 (6.8) 2.1 (7.9)
Fuel Return - gal./hr. (L/hr.) 7.4 (28.0) 7.9(29.9)
Total Supply Fuel Flow - gal./hr. (L/hr.)9.2 (34.8) 10 (37.8)
Fuel Pressure - lb./in.2 (kPa)..3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 103 (2.9) 154 (4.4)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 119 (821) 120 (825)
Piston Speed - ft./min. (m/min.)1240(378) 1467 (447)
Mechanical Noise - dB(A) @ 1m........... C131495
Power Curve C131297

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131398 revH
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UFH0
INSTALLATION & OPERATION DATA
USA Production

Basic Engine Description


Engine Manufacturer.. . John Deere Co.
Ignition Type..
. Compression (Diesel)
Number of Cylinders. . 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L)... . 275 (4.5)
Compression Ratio. . 17.0:1
Valves per cylinder - Intake..
. 1
Exhaust..
. 1
Combustion System. . Direct Injection
Engine Type..
. In-Line, 4 Stroke Cycle
Aspiration.
. Turbocharged
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type. . None
Rotation (Viewed from Front) - Clockwise . Standard
Counter-Clockwise. ..
Not Available
Engine Crankcase Vent System.. . Open
Installation Drawing . D-534
Weight - lb (kg)
935 (424)

Cooling System 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW).. . 40 (42) 47 (50) 47 (50)
Engine Radiated Heat - Btu/sec.(kW)................................... 16 (17) 20 (21) 22 (23)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)... 8 (30) 10 (38) 10 (38)
95F (35C) Raw H2O - gal/min. (L/min.)... 10 (38) 11 (42) 11 (42)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).
.
4 (60) (400)
Flow - gal./min (L/min.). .
.
40 (151)
Thermostat, Start to Open - F (C) .
187 (86)
Fully Opened - F (C)...
196 (91)
Engine Coolant Capacity - qt. (L).. . 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa)....
10 (69)
Maximum Engine H20 Temperature - F (C).. ..
200 (93)
Minimum Engine H20 Temperature - F (C).. ..
160 (71)

Electric System - DC
System Voltage (Nominal)... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C).. . 640 640
Reserve Capacity - Minutes....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length
. 00 00
121 - 160 in. Circuit* Length.
. 000 000
161 - 200 in. Circuit* Length.
. 0000 0000
Charging Alternator Output - Amp.... .. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UFH0
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350


Exhaust Flow - ft.3/min. (m3/min.). 362 (10) 477 (13) 561 (16)
Exhaust Temperature - F (C)........ 794(423) 811 (433) 799 (426)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 2.1 (7.9) 2.5 (9.5) 2.9 (11.0)
Fuel Return - gal./hr. (L/hr.) 7.9(29.9) 8.5 (32.2) 9.0 (34.1)
Total Supply Fuel Flow - gal./hr. (L/hr.) 10 (37.8) 11.0 (41.7) 11.9 (45.1)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 154 (4.4) 214 (6.1) 239 (6.8)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 119.7 (825) 120.5 (831) 120 (828)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597)
Mechanical Noise - dB(A) @ 1m........... C131494
Power Curve C131298

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131397 revG
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UFH2
INSTALLATION & OPERATION DATA
USA Production

Basic Engine Description


Engine Manufacturer.. . John Deere Co.
Ignition Type..
. Compression (Diesel)
Number of Cylinders. . 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L)... . 275 (4.5)
Compression Ratio. . 17.0:1
Valves per cylinder - Intake..
. 1
Exhaust..
. 1
Combustion System. . Direct Injection
Engine Type..
. In-Line, 4 Stroke Cycle
Aspiration.
. Turbocharged
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type. . None
Rotation (Viewed from Front) - Clockwise . Standard
Counter-Clockwise. ..
Not Available
Engine Crankcase Vent System.. . Open
Installation Drawing . D-534
Weight - lb (kg)
935 (424)

Cooling System 2350 2600


Engine H2O Heat -Btu/sec.(kW).. 47 (50) 53 (56)
Engine Radiated Heat - Btu/sec.(kW).............................. 22.1 (23.3) 22.3 (23.5)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)... 10 (38) 10 (38)
95F (35C) Raw H2O - gal/min. (L/min.)... 11 (42) 14 (53)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).
. 4 (60) (400)
Flow - gal./min (L/min.). .
. 40 (151)
Thermostat, Start to Open - F (C) . 187 (86)
Fully Opened - F (C)... 196 (91)
Engine Coolant Capacity - qt. (L)..... 15 (14)
Coolant Pressure Cap - lb./in.2(kPa).... 10 (69)
Maximum Engine H20 Temperature - F (C).............................. 200 (93)
Minimum Engine H20 Temperature - F (C).. .. 160 (71)

Electric System - DC
System Voltage (Nominal)... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C).. . 640 640
Reserve Capacity - Minutes....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length
. 00 00
121 - 160 in. Circuit* Length.
. 000 000
161 - 200 in. Circuit* Length.
. 0000 0000
Charging Alternator Output - Amp.... .. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UFH2
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 2350 2600


Exhaust Flow - ft.3/min. (m3/min.).561 (15.9) 618 (16.2)
Exhaust Temperature - F (C)........ 799 (426) 776 (414)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 2.9 (11.0) 3.6 (13.8)
Fuel Return - gal./hr. (L/hr.) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 11.9 (45.1) 13.1 (49.8)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 239 (6.8) 267 (7.6)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 120 (828) 109 (754)
Piston Speed - ft./min. (m/min.) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C131493
Power Curve C131299

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131396 revG
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF34
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
Displacement - in.3 (L)..........275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-534
Weight - lb (kg) 935 (424)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 40 (42) 42 (44) 51 (54) 58 (61)
Engine Radiated Heat - Btu/sec (kW)......... 19.2 (20.2) 19.2 (20.2) 23.7 (25) 26.1 (27.5)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
7 (25) 7 (25) 9 (32) 9 (33)
95F (35C) Raw H2O - gal/min. (L/min.)......
10 (38) 10 (38) 12 (45) 14 (53)
2
Heat Exchanger Maximum Cooling H O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.).............. 40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 15 (14)
Coolant Pressure Cap - lb./in.2 (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C)..... 160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF34
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..
602 (17.1) 631 (17.9) 788 (22.3) 910 (25.8)
Exhaust Temperature - F (C)...
.......... 966 (519) 901 (483) 952 (511) 949 (509)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 4.5 (17.0) 7.8 (29.5) 9.1 (34.4) 8.6 (32.6)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 13.5 (51.1) 17.3 (65.5) 19.0 (71.9) 18.9 (71.6)
Fuel Pressure - lb./in.2 (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m 3/min.)...231.6 (6.6) 255 (7.2) 305.2 (8.6) 352.9 (10.0)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
. 103 (710) 93 (641) 105 (724) 108 (745)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (660) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve. C131090

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131266 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-UF34
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 44 (42) 54 (51) 61 (58)
Engine Radiated Heat - kW (Btu/sec)......... 20.2 (19.2) 20.2 (19.2) 25 (23.7) 27.5 (26.1)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
25 (7) 25 (7) 32 (9) 33 (9)
38 (10)
35C (95F) Raw H2O - L/min. (gal/min.)...... 38 (10) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF34
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........17.1 (602) 17.9 (631) 22.3 (788) 25.8 (910)
Exhaust Temperature - C (F)............. 519 (966) 483 (901) 511 (952) 509 (949)
Maximum Allowable Back Pressure - kPa (in. H20)...7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 17.0 (4.5) 29.5 (7.8) 34.4 (9.1) 32.6 (8.6)
Fuel Return - L/hr. (gal./hr.).......... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 51.1 (13.5) 65.5 (17.3) 71.9 (19.0) 71.6 (18.9)
2
Fuel Pressure - kPa (lb./in. )............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.).............375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)......
1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)..............
2.5 (10)
Clean Air Cleaner - kPa (in. H20).............
1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 6.6 (231.6) 7.2 (255) 8.6 (305.2) 10.0 (352.9)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).......... 241-345
(35-50)
In Pan Oil Temperature - C (F)...........104-118 (220-245)
Oil Pan Capacity - High - L (qt.)..........7.5 (8)
Low - L (qt.)..6.5 (7)
Total Oil Capacity with Filter - L (qt.)........8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............. 710 (103) 641 (93) 724 (105) 745 (108)
597 (1958) 660 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.............. Consult Factory
Power Curve................ C131945

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131267 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF40 & JU4H-UF42
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 435 (12) 531 (15) 588 (17) 641 (18)
Exhaust Temperature - F (C)........ 911 (488) 868 (464) 823 (439) 799 (426)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 3.0 (11.4) 3.2 (12.1) 3.1 (11.7) 3.7 (14.0)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 10.9 (41.3) 11.7 (44.3) 12.1 (45.8) 13.2 (50.0)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 170 (4.8) 214 (6.1) 246 (7.0) 274 (7.8)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 154 (1062) 144 (993) 130 (896) 117 (807)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13910 (UF40) & C13911 (UF42)
Power Curve C13650 (UF40) & C13651 (UF42)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13665 revK
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF40 & JU4H-UF42
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 435 (12) 531 (15) 588 (17) 641 (18)
Exhaust Temperature - F (C)........ 911 (488) 868 (464) 823 (439) 799 (426)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 3.0 (11.4) 3.2 (12.1) 3.1 (11.7) 3.7 (14.0)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 10.9 (41.3) 11.7 (44.3) 12.1 (45.8) 13.2 (50.0)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 170 (4.8) 214 (6.1) 246 (7.0) 274 (7.8)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 154 (1062) 144 (993) 130 (896) 117 (807)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13910 (UF40) & C13911 (UF42)
Power Curve C13650 (UF40) & C13651 (UF42)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13665 revK
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF40 & JU4H-UF42
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat - kW (Btu/sec)......... 22.0 (21.0) 25.0 (24.0) 25.0 (24.0) 25.0 (24.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 38 (10) 45 (12)
35C (95F) Raw H2O - L/min. (gal/min.)......
38 (10) 42 (11) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)........... 4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF40 & JU4H-UF42
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........... 12.0 (435) 15.0 (531) 17.0 (588) 18.0 (641)
Exhaust Temperature - C (F)............. 488 (911) 464 (868) 439 (823) 426 (799)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 11.4 (3.0) 12.1 (3.2) 11.7 (3.1) 14.0 (3.7)
Fuel Return - L/hr. (gal./hr.)..........29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.)..........41.3 (10.9) 44.3 (11.7) 45.8 (12.1) 50.0 (13.2)
Fuel Pressure - kPa (lb./in.2)............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)..........50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)......... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type.........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)........ 4.8 (170) 6.1 (214) 7.0 (246) 7.8 (274)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....... 241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........ 8 (7.5)
Low - L (qt.)... 7 (6.5)
Total Oil Capacity with Filter - L (qt.).... 9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2)............. 10.8 (154) 10.1 (144) 9.1 (130) 8.2 (117)
Piston Speed - m/min. (ft./min.)..........447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve................ C131939 (UF40) C131940 (UF42)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131229 Rev. F
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF50 & JU4H-UF52
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - in.(mm)....4.19(106) x 5.00(127)
3
Displacement - in. (L)......275 (4.5)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust....
1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)...1-3-4-2
Charge Air Cooling Type.... None
Rotation (Viewed from Front) - Clockwise Standard
Counter-Clockwise. Not Available
Engine Crankcase Vent System..Open
Installation Drawing. D-534
Weight - lb (kg)
935 (424)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)..... 40 (42) 47 (50) 47 (50) 53 (56)
Engine Radiated Heat - Btu/sec.(kW). 25 (26) 29 (31) 28 (30) 28 (30)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
10 (38) 13 (49) 13 (49) 13 (49)
95F (35C) Raw H2O - gal/min. (L/min.)...
13 (49) 14 (53) 14 (53) 18 (68)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
4 (60) (400)
Flow - gal./min (L/min.).. 40 (151)
Thermostat, Start to Open - F (C)...
187 (86)
Fully Opened - F (C)...
196 (91)
Engine Coolant Capacity - qt. (L)....15 (14)
Coolant Pressure Cap - lb./in.2(kPa)...10 (69)
Maximum Engine H20 Temperature - F (C)....200 (93)
Minimum Engine H20 Temperature - F (C).....160 (71)

Electric System - DC
System Voltage (Nominal)...12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.....0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp......40 40
Starter Cranking Amps - @ 60F (15C).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Clarke
Fire Protection Products
JU4H-UF50 & JU4H-UF52
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 554 (16) 698 (20) 752 (21) 839 (24)
Exhaust Temperature - F (C)........1108 (598) 1076 (580) 998 (537) 966 (519)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)3.8 (14.4) 4.5 (17.0) 4.9 (18.5) 7.9 (29.9)
Fuel Return - gal./hr. (L/hr.)7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 11.7 (44.3) 13.0 (49.2) 13.9 (52.6) 17.4 (65.9)
Fuel Pressure - lb./in.2 (kPa)..3-6 (21-41)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)........ .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)........ .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.)..190 (5.4) 244 (6.9) 277 (7.8) 316 (8.9)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C)..220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 180 (1241) 178 (1229) 156 (1073) 141 (970)
Piston Speed - ft./min. (m/min.)1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13912 (UF50)
Power Curve C13477 (UF50) & C13562 (UF52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13612 revJ
DSP 25FEB08
CLARKE
Fire Protection Products
JU4H-UF50 & JU4H-UF52
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat - kW (Btu/sec)......... 26.0 (25.0) 31.0 (29.0) 30.0 (28.0) 30.0 (28.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 38 (10) 45 (12)
35C (95F) Raw H2O - L/min. (gal/min.)......
38 (10) 42 (11) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)........... 4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF50 & JU4H-UF52
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........... 16.0 (554) 20.0 (698) 21.0 (752) 24.0 (839)
Exhaust Temperature - C (F).............598 (1108) 580 (1076) 537 (998) 519 (966)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)....
Minimum Exhaust Pipe Dia. - mm (in.)**.........102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 14.4 (3.8) 17.0 (4.5) 18.5 (4.9) 29.9 (7.9)
Fuel Return - L/hr. (gal./hr.)..........29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.)..........44.3 (11.7) 49.2 (13.0) 52.6 (13.9) 65.9 (17.4)
Fuel Pressure - kPa (lb./in.2)................ 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).....
1.4 (4.5)
Fuel Filter Micron Size...............5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type.......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)........ 5.4 (190) 6.9 (244) 7.8 (277) 8.9 (316)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....... 241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........ 8 (7.5)
Low - L (qt.). 7 (6.5)
Total Oil Capacity with Filter - L (qt.)..... 9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2)............. 12.7 (180) 12.5 (178) 11.0 (156) 9.9 (141)
Piston Speed - m/min. (ft./min.)..........447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve................ C131941 (UF50) & C131942 (UF52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131230 revF
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-UF54
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
Displacement - in.3 (L).......... 275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-534
Weight - lb (kg) 935 (424)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 57 (60) 69 (73) 80 (76) 86 (82)
Engine Radiated Heat - Btu/sec (kW)......... 27.6 (29.1) 31.6 (33.3) 32.8 (34.6) 32.8 (34.6)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
7 (27) 7 (25) 8 (31) 9 (34)
95F (35C) Raw H2O - gal/min. (L/min.)......
8 (30) 11 (42) 12 (45) 13 (48)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.).............. 40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
196 (91)
Fully Opened - F (C).............
Engine Coolant Capacity - qt. (L).......... 15 (14)
Coolant Pressure Cap - lb./in.2 (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C).....
160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF54
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..768 (21.8) 934 (26.4) 1061 (30.0) 1193 (33.8)
Exhaust Temperature - F (C)...
.......... 1129 (609) 1132 (611) 1124 (607) 1098 (592)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 7.2 (27.3) 10.3 (39.0) 10.0 (37.9) 11.0 (41.6)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 16.2 (61.4) 19.8 (75.0) 19.9 (75.4) 21.3 (80.6)
Fuel Pressure - lb./in.2 (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m 3/min.)... 259 (7.3) 315 (8.9) 362 (10.3) 413 (11.7)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
2
BMEP - lb./in. (kPa)
.. 150 (1034) 155 (1068) 150 (1034) 139 (958)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve... C131092

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131270 revF
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-UF54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 60 (57) 73 (69) 80 (76) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 29.1 (27.6) 33.3 (31.6) 34.6 (32.8) 34.6 (32.8)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
27 (7) 25 (7) 31 (8) 34 (9)
35C (95F) Raw H2O - L/min. (gal/min.)......
30 (8) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-UF54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
21.8 (768) 26.4 (934) 30.0 (1061) 33.8 (1193)
Exhaust Temperature - C (F)............. 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in. H20)...7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 27.3 (7.2) 39.0 (10.3) 37.9 (10.0) 41.6 (11.0)
Fuel Return - L/hr. (gal./hr.).......... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 61.4 (16.2) 75.0 (19.8) 75.4 (19.9) 80.6 (21.3)
2
Fuel Pressure - kPa (lb./in. ).......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)......
1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.)... 8.5 (9)

Performance
2
BMEP - kPA (lb./in. )............. 1034 (150) 1068 (155) 1034 (150) 958 (139)
Piston Speed - m/min (ft./min.)........ 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131946

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131271 revD
DSP 07AUG4
CLARKE
Fire Protection Products
JU4R-UF09 & JU4R-UF11
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type..Compression (Diesel)
Number of Cylinders.4
Bore and Stroke - in.(mm)..4.19(106) x 5.00(127)
Displacement - in.3 (L)...275 (4.5)
Compression Ratio. 17.0:1
Valves per cylinder - Intake..1
Exhaust..1
Combustion System.Direct Injection
Engine Type..Rotary, 4 Stroke Cycle
Aspiration. Naturally Aspirated
Firing Order (CW Rotation).. 1-3-4-2
Charge Air Cooling Type.None
Rotation (Viewed from Front) - ClockwiseStandard
Counter-Clockwise.
Not Available
Engine Crankcase Vent System.. Open
Installation Drawing D-548
Weight - lb (kg) 956 (434)

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - Btu/sec (kW)....... 19 (20) 28 (30) 40 (42) 42 (44)
Engine Radiated Heat - Btu/sec (kW)...... 10.0 (9.0) 11 (12) 12 (13) 13 (14)
Radiator Minimum Ventilation Flow ft./min. (m/min.). 3839 (109) 4607 (130) 5092 (144) 4777 (135)
Thermostat, Start to Open - F (C)..... 187 (86)
Fully Opened - F (C)......... 196 (91)
Engine Coolant Capacity - qt. (L).......... 16 (15)
Coolant Pressure Cap - lb./in.2 (kPa)........ 10 (69)
Maximum Engine H20 Temperature - F (C)....... 200 (93)
Minimum Engine H20 Temperature - F (C)........... 160 (71)

Electric System - DC
System Voltage (Nominal)..12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)..12 24
Qty. per Battery Bank1 2
SAE size per J537..4D-640 4D-640
CCA @ 0F (-18C).. 640 640
Reserve Capacity - Minutes....285 285
Battery Cable Circuit*, Max Resistance - ohm...... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length00 00
121 - 160 in. Circuit* Length. 000 000
161 - 200 in. Circuit* Length. 0000 0000
Charging Alternator Output - Amp....40 40
Starter Cranking Amps - @ 60F (15C)...380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF09 & JU4R-UF11
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 1760 2100 2350 2600
Exhaust Flow - ft.3/min. (m3/min.). 379 (11) 415 (12) 469 (13) 531 (15)
Exhaust Temperature - F (C)........ 740 (393) 918 (492) 1083 (584) 1055 (568)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 2.2 (8.3) 2.8 (10.6) 3.1 (11.7) 3.4 (12.9)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.) 10.1 (38.2) 11.3 (42.8) 12.1 (45.8) 12.9 (48.9)
Fuel Pressure - lb./in.2 (kPa).. 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 2 (0.2) 155 (4.4) 166 (4.7) 186 (5.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 3 (0.2)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)35-50 (241-345)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 67 (462) 70 (483) 67 (462) 65 (448)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve C131367 (UF09) & C131368 (UF11)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
C131407 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF09 & JU4R-UF11
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - mm (in.)... 106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).... 4.5 (275)
Compression Ratio.. 17.0:1
Valves per cylinder - Intake... 1
Exhaust... 1
Combustion System.. Direct Injection
Engine Type... Rotary, 4 Stroke Cycle
Aspiration.. Naturally Aspirated
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System... Open
Installation Drawing. D-548

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)....... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat - kW (Btu/sec)...... 9 (10) 12 (11) 13 (12) 14 (13)
Radiator Minimum Ventilation Flow - m/min. (ft./min.). 109 (3839) 130 (4607) 144 (5092) 135 (4777)
Thermostat, Start to Open - C (F)..... 86 (187)
Fully Opened - C (F)......... 91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
2
Coolant Pressure Cap - kPa (lb./in. )........ 69 (10)
Maximum Engine H20 Temperature - C (F)....... 93 (200)
Minimum Engine H20 Temperature - C (F)........... 71 (160)

Electric System - DC
System Voltage (Nominal)... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ -18C (0F)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.......
0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.. 000 000
161 - 200 in. Circuit* Length.. 0000 0000
Charging Alternator Output - Amp..... 40 40
Starter Cranking Amps - @ 15C (60F).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF09 & JU4R-UF11
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1760 2100 2350 2600
Exhaust Flow - m3/min. (ft.3/min.)..11 (379) 12 (415) 13 (469) 15 (531)
Exhaust Temperature - C (F)...
..........393 (740) 492 (918) 584 (1083) 568 (1055)
Maximum Allowable Back Pressure - kPa (in. H20).
7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**...
76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.). 8.3 (2.2) 10.6 (2.8) 11.7 (3.1) 12.9 (3.4)
Fuel Return - L/hr (gal./hr.). 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.). 38.2 (10.1) 42.8 (11.3) 45.8 (12.1) 48.9 (12.9)
Fuel Pressure - kPa (lb./in.2)..... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)...................033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)...................026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20).... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)..... 1.4 (4.5)
Fuel Filter Micron Size.... 5

Heater System
Jacket Water Heater
Wattage (Nominal)......... 1500
Voltage - AC, 1P......... 115 (+5%, -10%)
Optional Voltage - AC, 1P......
230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type....... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
2.5 (10)
Dirty Air Cleaner - kPa (in. H20)....................
1.2 (5)
Clean Air Cleaner - kPa (in. H20)................
Engine Air Flow - m3/min. (ft.3/min.)... 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).241-345 (35-50)
In Pan Oil Temperature - C (F)...
104-118 (220-245)
Oil Pan Capacity - High - L (qt.). 7.5 . (8)
Low - L (qt.)... 6.5 (7)
Total Oil Capacity with Filter - L (qt.).8.5 (9)

Performance
BMEP - kPa (lb./in.2)....................................
462 (67) 483 (70) 462 (67) 448 (65)
Piston Speed - m/min. (ft./min.).........
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m....................... Consult Factory
Power Curve............ C131947 (UF09) & C131948 (UF11)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131651 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF13
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
Displacement - in.3 (L).......... 275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548
Weight - lb (kg)....... 956 (434)

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 30 (32) 32 (34) 34 (36) 36 (38)
Engine Radiated Heat - Btu/sec (kW)......... 12 (13) 13 (14) 14 (15) 15 (16)
3 3
Radiator Minimum Ventilation Flow - ft /min. (m /min.). 4303 (122) 4777 (135) 5110 (145) 5426 (154)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 16 (15)
Coolant Pressure Cap - lb./in.2 (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C)..... 160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 in Circuit* Length............ 00 00
121 - 160 in Circuit* Length............. 000 000
161 - 200 in Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15 C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF13
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.).. 469 (13) 531 (15) 581 (16) 630 (18)
Exhaust Temperature - F (C)...
.......... 1083 (584) 1055 (568) 1033 (556) 1010 (543)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 3.1 (11.7) 3.4 (12.9) 3.6 (13.6) 3.9 (14.8)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 12.1 (45.8) 12.9 (48.9) 13.5 (51.1) 14.2 (53.8)
Fuel Pressure - lb./in.2 (kPa)... 3-6(21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m 3/min.)...166 (4.7) 186 (5.3) 202 (5.7) 218 (6.2)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
. 67 (462) 65 (448) 63 (437) 62 (426)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve. C131369

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131409 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF13
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 32 (30) 34 (32) 36 (34) 38 (36)
Engine Radiated Heat - kW (Btu/sec)......... 13 (12) 14 (13) 15 (14) 16 (15)
3 3
Radiator Minimum Ventilation Flow - m /min.(ft /min.). 122 (4303) 135 (4777) 145 (5110) 154 (5426)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F)..... 71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ 0C (-18F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 in Circuit* Length............ 00 00
121 - 160 in Circuit* Length............. 000 000
161 - 200 in Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15 C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF13
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)............
13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F)............. 584 (1083) 568 (1055) 556 (1033) 543 (1010)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)
Fuel Return - L/hr. (gal./hr.).......... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr (gal./hr.)....... 45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2)
Fuel Pressure - kPa (lb.in2)........... 21-41 (3-6)
Minimum Line Size - Supply - (in.)............ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)......
1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)..............
2.5 (10)
Clean Air Cleaner - kPa (in. H20).............
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in ).........
241-345 (35-50)
In Pan Oil Temperature - C (F)...........
104-118 (220-245)
Oil Pan Capacity - High - L (qt.)..........7.5
(8)
Low - L (qt.).6.5 (7)
Total Oil Capacity with Filter - L (qt.)... 8.5 (9)

Performance
BMEP - kPa (lb./in. 2).............462 (67) 448 (65) 437 (63) 426 (62)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.............. Consult Factory
Power Curve................ C131949

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131652 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF19 & JU4R-UF21
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - in.(mm)... 4.19(106) x 5.00(127)
3
Displacement - in. (L).... 275 (4.5)
Compression Ratio.. 17.0:1
Valves per cylinder - Intake... 1
Exhaust... 1
Combustion System.. Direct Injection
Engine Type... Rotary, 4 Stroke Cycle
Aspiration.. Naturally Aspirated
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System... Open
Installation Drawing. D-548
Weight - lb (kg) 956 (434)

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - Btu/sec (kW)....... 19 (20) 28 (30) 40 (42) 42 (44)
Engine Radiated Heat - Btu/sec (kW)...... 13 (14) 15 (16) 16 (17) 17 (18)
Radiator Minimum Ventilation Flow - ft3/min. (m3/min.).. 3839 (109) 4607 (130) 5092 (144) 4777 (135)
Thermostat, Start to Open - F (C)..... 187 (86)
Fully Opened - F (C)......... 196 (91)
Engine Coolant Capacity - qt. (L).......... 16 (15)
2
Coolant Pressure Cap - lb./in. (kPa)........ 10 (69)
Maximum Engine H20 Temperature - F (C)....... 200 (93)
Minimum Engine H20 Temperature - F (C)........... 160 (71)

Electric System - DC
System Voltage (Nominal)... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ 0F (-18C)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.......
0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.. 000 000
161 - 200 in. Circuit* Length.. 0000 0000
Charging Alternator Output - Amp..... 40 40
Starter Cranking Amps - @ 60F (15C).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF19 & JU4R-UF21
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.)..
379 (11) 415 (12) 469 (13) 531 (15)
Exhaust Temperature - F (C)...
..........
1021 (549) 1016 (547) 1076 (580) 1095 (591)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**...
3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 3.8 (14.4) 5.3 (20.1) 5.6 (21.2) 5.8 (22.0)
Fuel Return - gal./hr. (L/hr.). 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 11.7 (44.3) 13.8 (52.3) 14.6 (55.3) 15.3 (58)
Fuel Pressure - lb./in.2 (kPa).. . 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size. 5

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.)... 140 (4.0) 155 (4.4) 166 (4.7) 186 (5.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
... 98 (677) 92 (634) 88 (608) 83 (573)
Piston Speed - ft./min. (m/min.).1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m.............. Consult Factory
Power Curve.... C131370 (UF19) & C131371 (UF21)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131408 rev E
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF19 & JU4R-UF21
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - mm (in.)... 106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).... 4.5 (275)
Compression Ratio.. 17.0:1
Valves per cylinder - Intake... 1
Exhaust... 1
Combustion System.. Direct Injection
Engine Type... Rotary, 4 Stroke Cycle
Aspiration.. Naturally Aspirated
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System... Open
Installation Drawing. D-548

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)....... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat - kW (Btu/sec)...... 14 (13) 16 (15) 17 (16) 18 (17)
Radiator Minimum Ventilation Flow m3/min.(ft3/min.). 109 (3839) 130 (4607) 144 (5092) 135 (4777)
Thermostat, Start to Open - C (F)..... 86 (187)
Fully Opened - C (F)......... 91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
Coolant Pressure Cap - kPa (lb./in.2)........ 69 (10)
Maximum Engine H20 Temperature - C (F)....... 93 (200)
Minimum Engine H20 Temperature - C (F)........... 71 (160)

Electric System - DC
System Voltage (Nominal)... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)... 12 24
Qty. per Battery Bank. 1 2
SAE size per J537... 4D-640 4D-640
CCA @ -18C (0F)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.......
0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.. 000 000
161 - 200 in. Circuit* Length.. 0000 0000
Charging Alternator Output - Amp..... 40 40
Starter Cranking Amps - @ 15C (60F).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF19 & JU4R-UF21
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)..
11 (379) 12 (415) 13 (469) 15 (531)
Exhaust Temperature - C (F)...549 (1021) 547 (1016) 580 (1076) 591 (1095)
Maximum Allowable Back Pressure - kPa (in. H20) .
7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**... 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.). 14.4 (3.8) 20.1 (5.3) 21.2 (5.6) 22.0 (5.8)
Fuel Return - L/hr (gal./hr.).... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr. (gal./hr.).... 44.3 (11.7) 52.3 (13.8) 55.3 (14.6) 58.0 (15.3)
Fuel Pressure - kPa (lb./in.2).. . 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20). 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....
1.4 (4.5)
Fuel Filter Micron Size.... 5

Heater System
Jacket Water Heater
Wattage (Nominal).........
1500
Voltage - AC, 1P.........
115 (+5%, -10%)
Optional Voltage - AC, 1P......
230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type....... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
2.5 (10)
Dirty Air Cleaner - kPa (in. H20).................
1.2 (5)
Clean Air Cleaner - kPa (in. H20)................
Engine Air Flow - m3/min. (ft.3/min.)... 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)
241-345 (35-50)
In Pan Oil Temperature - C (F)...
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).. 7.5 (8)
Low - L (qt.).. 6.5 (7)
Total Oil Capacity with Filter - L (qt.).8.5 (9)

Performance
BMEP - kPa (lb./in.2)..................
. 677 (98) 634 (92) 608 (88) 573 (83)
Piston Speed - m/min. (ft./min.).447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m.................Consult Factory
Power Curve...... C131950 (UF19) & C131951 (UF21)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131653 rev D
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF23
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
3
Displacement - in. (L).......... 275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548
Weight - lb (kg)..... 956 (434)

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 40 (42) 42 (44) 44 (46) 45 (47)
Engine Radiated Heat - Btu/sec (kW)......... 16 (17) 17 (18) 18 (19) 19 (20)
Radiator Minimum Ventilation Flow - ft3/min. (m3/min.).4303 (122) 4777 (135) 5110 (145) 5426 (154)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 16 (15)
2
Coolant Pressure Cap - lb./in. (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C)..... 160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF23
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..469 (13) 531 (15) 581 (16) 630 (18)
Exhaust Temperature - F (C)...
.......... 1076 (580) 1095 (591) 1110 (599) 1125 (607)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
3 (76)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 5.6 (21.2) 5.8 (22.0) 6.0 (22.7) 6.2 (23.5)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 14.6 (55.3) 15.3 (58.0) 15.9 (60.2) 16.5 (62.5)
2
Fuel Pressure - lb./in. (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m 3/min.)...166 (4.7) 186 (5.3) 202 (5.7) 218 (6.2)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
104-118 (220-245)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
. 88 (608) 83 (573) 79 (545) 75 (517)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2334 (711) 2501 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve C131372

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131410 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF23
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 44 (42) 46 (44) 47 (45)
Engine Radiated Heat - kW (Btu/sec)......... 17 (16) 18 (17) 19 (18) 20 (19)
Radiator Minimum Ventilation Flow - m3/min.(ft3/min.). 122 (4303) 135 (4777) 145 (5110) 154 (5426)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F)..... 71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ 0C (-18F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF23
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.).............
13 (469) 15 (531) 16 (581) 18 (630)
580 (1076) 591 (1095) 599 (1110) 607 (1125)
Exhaust Temperature - C (F)................
7.5 (30)
Maximum Allowable Back Pressure - kPa (in. H20)......
76 (3)
Minimum Exhaust Pipe Dia. - mm (in.)**...............

Fuel System
Fuel Consumption - L/hr. (gal.hr.)............... 21.2 (5.6) 22.0 (5.8) 22.7 (6.0) 23.5 (6.2)
Fuel Return - L/hr. (gal./hr.)............. 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
55.3 (14.6) 58.0 (15.3) 60.2 (15.9) 62.5 (16.5)
Total Supply Fuel Flow - L/hr. (gal./hr.).............
Fuel Pressure - kPa (lb.in2)............... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)...........
0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).........
1.4 (4.5)
Fuel Filter Micron Size.................. 2

Heater System
Jacket Water Heater
Wattage (Nominal).................
1500
115 (+5%, -10%)
Voltage - AC, 1P................
230 (+5%, -10%)
Optional Voltage - AC, 1P.............

Induction Air System


Air Cleaner Type.............. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).................
2.5 (10)
Clean Air Cleaner - kPa (in. H20)................
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........... 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.....

Lubrication System
2
Oil Pressure - normal - kPa (lb./in )..........
241-345 (35-50)
In Pan Oil Temperature - C (F)............
220-245 (104-118)
Oil Pan Capacity - High - L (qt.)...........7.5 (8)
Low - L (qt.)......... 6.5 (7)
Total Oil Capacity with Filter - L (qt.)......8.5 (9)

Performance
BMEP - kPa (lb./in. 2)................
608 (88) 573 (83) 545 (79) 517 (75)
597 (1958) 661 (2167) 711 (2334) 762 (2501)
Piston Speed - m/min. (ft./min.).............
Mechanical Noise - dB(A) @ 1m................. Consult Factory
Power Curve................... C131952

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131654 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF40
INSTALLATION & OPERATION DATA
USA Production

Basic Engine Description


Engine Manufacturer... John Deere Co.
Ignition Type . Compression (Diesel)
Number of Cylinders. . 4
Bore and Stroke - in.(mm) . 4.19(106) x 5.00(127)
Displacement - in.3 (L)... . 275 (4.5)
Compression Ratio. . 17.0:1
Valves per cylinder - Intake . 1
Exhaust. 1
Combustion System. . Direct Injection
Engine Type . In-Line, 4 Stroke Cycle
Aspiration . Turbocharged
Firing Order (CW Rotation). 1-3-4-2
Charge Air Cooling Type. None
Rotation (Viewed from Front) - Clockwise . Standard
Counter-Clockwise. .. Not Available
Engine Crankcase Vent System.. . Open
Installation Drawing . D-548
Weight - lb (kg) 982 (445)

Cooling System - Radiator 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW).. . 40 (42) 47 (50) 47 (50)
Engine Radiated Heat - Btu/sec.(kW) .. 21 (22) 24 (25) 24 (25)
3 3
Radiator Minimum Ventilation Flow - ft /min. (m /min.). 9190 (260) 10944(310) 12277 (348)
Thermostat, Start to Open - F (C) . 187 (86)
Fully Opened - F (C) . 196 (91)
Engine Coolant Capacity - qt. (L).. . 18 (17)
Coolant Pressure Cap - lb./in.2(kPa)... 10 (69)
Maximum Engine H20 Temperature - F (C).. .. 200 (93)
Minimum Engine H20 Temperature - F (C).. 160 (71)

Electric System - DC
System Voltage (Nominal) . 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).. 12 24
Qty. per Battery Bank. 1 2
SAE size per J537 . 4D-640 4D-640
CCA @ 0F (-18C). 640 640
Reserve Capacity - Minutes . 285 285
Battery Cable Circuit*, Max Resistance - ohm...... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length
. 00 00
121 - 160 in. Circuit* Length. 000 000
161 - 200 in. Circuit* Length. 0000 0000
Charging Alternator Output - Amp... 40 40
Starter Cranking Amps - @ 60F (15C)... .. 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF40
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350


Exhaust Flow - ft.3/min. (m3/min.). 435 (12) 531 (15) 588 (17)
Exhaust Temperature - F (C)........ 911 (488) 868 (464) 823 (439)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)3.0 (11.4) 3.2 (12.1) 3.1 (11.7)
Fuel Return - gal./hr. (L/hr.) 7.9 (29.9) 8.5 (32.2) 9.0 (34.1)
Total Supply Fuel Flow - gal./hr. (L/hr.)10.9 (41.3) 11.7 (44.3) 12.1 (45.8)
Fuel Pressure - lb./in.2 (kPa)..3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)..1500
Voltage - AC, 1P..115 (+5%, -10%)
Optional Voltage - AC, 1P..230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 10 (2.5)
Clean Air Cleaner - in. H20 (kPa) 5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.).. 170 (4.8) 214 (6.1) 246 (7.0)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 35-50 (241-345)
In Pan Oil Temperature - F (C)..220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 8 (7.5)
Low - qt. (L) 7 (6.5)
Total Oil Capacity with Filter - qt. (L) 9 (8.5)

Performance
BMEP - lb./in.2 (kPa) . 154 (1062) 144 (993) 130 (896)
Piston Speed - ft./min. (m/min.)1467 (447) 1750 (533) 1958 (597)
Mechanical Noise - dB(A) @ 1m........... C131633
Power Curve C131634

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131411 revF
DSP 25FEB08
CLARKE
Fire Protection Products
JU4R-UF40
INSTALLATION & OPERATION DATA
UK Production

Basic Engine Description


Engine Manufacturer................. John Deere Co.
Ignition Type.................... Compression (Diesel)
Number of Cylinders................ 4
Bore and Stroke - mm (in.).................
106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).................4.5 (275)
Compression Ratio................ 17.0:1
Valves per cylinder - Intake.......................
1
Exhaust......................
1
Combustion System................ Direct Injection
Engine Type.................... In-Line, 4 Stroke Cycle
Aspiration................... Turbocharged
Firing Order (CW Rotation).................
1-3-4-2
Charge Air Cooling Type................ None
Rotation (Viewed from Front) - Clockwise.....................
Standard
Counter-Clockwise...................
Not Available
Engine Crankcase Vent System.................
Open
Installation Drawing..................
. D-548

Cooling System - Radiator 1760 2100 2350


Engine H2O Heat - kW (Btu/sec.).................
. 42 (40) 50 (47) 50 (47)
Engine Radiated Heat - kW (Btu/sec.)...............
22 (21) 25 (24) 25 (24)
3 3
Radiator Minimum Ventilation Flow m /min.(ft /min.)....
260 (9190) 310 (10944) 348 (12277)
Thermostat, Start to Open - C (F)...............
86 (187)
Fully Opened - C (F).................
91 (196)
Engine Coolant Capacity - L (qt.)..............
17 (18)
Coolant Pressure Cap - kPa (lb./in.2)...........
69 (10)
Maximum Engine H20 Temperature - C (F)...........
93 (200)
Minimum Engine H20 Temperature - C (F)...........
71 (160)

Electric System - DC
System Voltage (Nominal).............. 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal).................... 12 24
Qty. per Battery Bank.................. 1 2
SAE size per J537.................... 4D-640 4D-640
CCA @ -18C (0F).................... 640 640
Reserve Capacity - Minutes................ 285 285
Battery Cable Circuit*, Max Resistance - ohm...............0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length..................
00 00
121 - 160 in. Circuit* Length...................000 000
161 - 200 in. Circuit* Length...................
0000 0000
Charging Alternator Output - Amp.............
.. 40 40
Starter Cranking Amps - @ 15C (60F)............
.. 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF40
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350


Exhaust Flow - m3/min. (ft.3/min.)................
12 (435) 15 (531) 17 (588)
488 (911) 464 (868)
Exhaust Temperature - C (F)................ 439 (823)
Maximum Allowable Back Pressure - kPa (in. H20)............
7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.................
102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............... 11.4 (3.0) 12.1 (3.2) 11.7 (3.1)
Fuel Return - L/hr (gal./hr.)............... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0)
Total Supply Fuel Flow - L/hr. (gal./hr.)..................
41.3 (10.9) 44.3 (11.7) 45.8 (12.1)
Fuel Pressure - kPa (lb./in.2)..............21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.).............375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)............. 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).....
1.4 (4.5)
Fuel Filter Micron Size................ 5

Heater System
Jacket Water Heater
Wattage (Nominal).......................
1500
Voltage - AC, 1P......................
115 (+5%, -10%)
Optional Voltage - AC, 1P....................
230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type.................. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
2.5 (10)
Dirty Air Cleaner - kPa (in. H20).................
1.2 (5)
Clean Air Cleaner - kPa (in. H20)................
Engine Air Flow - m3/min. (ft.3/min.).................
4.8 (170) 6.1 (214) 7.0 (246)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***....
54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)..........
.. 241-345 (35-50)
In Pan Oil Temperature - C (F).................
104-118 (220-245)
Oil Pan Capacity - High - L (qt.)............. 7.5 (8)
Low - L (qt.)............ 6.5 (7)
Total Oil Capacity with Filter - L (qt.)...........
8.5 (9)

Performance
BMEP - kPa (lb./in.2)..................
.
.. 1062 (154) 993 (144) 896 (130)
Piston Speed - m/min. (ft./min.)...............
447 (1467) 533 (1750) 597 (1958)
Mechanical Noise - dB(A) @ 1m.................Consult Facotry
Power Curve.....................
.
.. C131953

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131655 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF49 & JU4R-UF51
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - in.(mm)....4.19(106) x 5.00(127)
3
Displacement - in. (L)......275 (4.5)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust....
1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)...1-3-4-2
Charge Air Cooling Type.... None
Rotation (Viewed from Front) - Clockwise Standard
Counter-Clockwise. Not Available
Engine Crankcase Vent System..Open
Installation Drawing. D-548
Weight - lb (kg) 982 (445)

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)..... 40 (42) 47 (50) 47 (50) 53 (56)
Engine Radiated Heat - Btu/sec.(kW). 25 (26) 29 (31) 28 (30) 28 (30)
Radiator Minimum Ventilation Flow - ft3/min. (m3/min.). 9190 (260) 10944(310) 12277 (348) 11316 (320)
Thermostat, Start to Open - F (C)... 187 (86)
Fully Opened - F (C)... 196 (91)
Engine Coolant Capacity - qt. (L)....18 (17)
Coolant Pressure Cap - lb./in.2(kPa)...10 (69)
Maximum Engine H20 Temperature - F (C)....200 (93)
Minimum Engine H20 Temperature - F (C).....160 (71)

Electric System - DC
System Voltage (Nominal)...12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.....0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp......40 40
Starter Cranking Amps - @ 60F (15C).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Clarke
Fire Protection Products
JU4R-UF49 & JU4R-UF51
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.)..
554 (16) 698 (20) 752 (21) 839 (24)
Exhaust Temperature - F (C)...
..........
1108 (598) 1076 (580) 998 (537) 966 (519)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**...
4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 3.8 (14.4) 4.5 (17.0) 4.9 (18.5) 7.9 (29.9)
Fuel Return - gal./hr. (L/hr.). 7.9 (29.9) 8.5 (32.2) 9.0 (34.1) 9.5 (36.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 11.7 (44.3) 13.0 (49.2) 13.9 (52.6) 17.4 (65.9)
Fuel Pressure - lb./in.2 (kPa).. 3-6 . (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.).................375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size. 5

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
Engine Air Flow - ft.3/min. (m3/min.)... 190 (5.4) 244 (6.9) 277 (7.8) 316 (8.9)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa) ... 180 (1241) 178 (1229) 156 (1073) 141 (970)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m.................... C131621
Power Curve.......... C131377 (UF49) & C131378 (UF51)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131412 rev E
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF49 & JU4R-UF51
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type.... Compression (Diesel)
Number of Cylinders.. 4
Bore and Stroke - mm (in.).... 106 (4.19) x 127 (5.00)
3
Displacement - L (in. )......4.5 (275)
Compression Ratio....17.0:1
Valves per cylinder - Intake.... 1
Exhaust.... 1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-3-4-2
Charge Air Cooling Type.... None
Rotation (Viewed from Front) - Clockwise.....................
Standard
Counter-Clockwise...................
Not Available
Engine Crankcase Vent System..Open
Installation Drawing. D-548

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec.)..... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat - kW (Btu/sec.). 26 (25) 31 (29) 30 (28) 30 (28)
3 3
Radiator Minimum Ventilation Flow - m /min. (ft /min.). 260 (9190) 310 (10944) 348 (12277) 320 (11316)
Thermostat, Start to Open - C (F)... 86 (187)
Fully Opened - C (F)... 91 (196)
Engine Coolant Capacity - L (qt.)....17 (18)
Coolant Pressure Cap - kPa (lb./in.2)... 69 (10)
Maximum Engine H20 Temperature - C (F)....93 (200)
Minimum Engine H20 Temperature - C (F).....160 (71)

Electric System - DC
System Voltage (Nominal)...12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ -18C (0F)... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm.....0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp......40 40
Starter Cranking Amps - @ 15C (60F).... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Clarke
Fire Protection Products
JU4R-UF49 & JU4R-UF51
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.).....
16 (554) 20 (698) 21 (752) 24 (839)
Exhaust Temperature - C (F)........
598 (1108) 580 (1076) 537 (998) 519 (966)
Maximum Allowable Back Pressure - kPa (in. H20)
7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**. 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)... 14.4 (3.8) 17.0 (4.5) 18.5 (4.9) 29.9 (7.9)
Fuel Return - L/hr (gal./hr.). 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr. (gal./hr.). 44.3 (11.7) 49.2 (13.0) 52.6 (13.9) 65.9 (17.4)
Fuel Pressure - kPa (lb./in.2).. 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20).. 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)..
1.4 (4.5)
Fuel Filter Micron Size. 5

Heater System
Jacket Water Heater
Wattage (Nominal)..... 1500
Voltage - AC, 1P.. 115 (+5%, -10%)
Optional Voltage - AC, 1P....
230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type.. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)... 5.4 (190) 6.9 (244) 7.8 (277) 8.9 (316)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)*** .54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...
241-345 (35-50)
In Pan Oil Temperature - C (F).104-118 (220-245)
Oil Pan Capacity - High - L (qt.).7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.)
8.5 (9)

Performance
BMEP - kPa (lb./in.2)..
1241 (180) 1229 (178) 1073 (156) 970 (141)
Piston Speed - m/min. (ft./min.)...
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m.............
Consult Factory
Power Curve.. C131954 (UF49) & C131955 (UF51)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131656 rev D
16AUG07 DSP
CLARKE
Fire Protection Products
JU4R-UF53
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
Displacement - in.3 (L).......... 275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548
Weight - lb (kg) 982 (445)

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 57 (60) 69 (73) 76 (80) 82 (86)
Engine Radiated Heat - Btu/sec (kW)......... 27.6 (29.1) 31.6 (33.3) 32.8 (34.6) 32.8 (34.6)
3 3
Radiator Minimum Ventilation Flow - ft /min. (m /min.).10259 (291) 11315 (320) 12247 (347) 13136 (372)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 18 (17)
Coolant Pressure Cap - lb./in.2 (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C)..... 160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 in Circuit* Length............ 00 00
121 - 160 in Circuit* Length............. 000 000
161 - 200 in Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF53
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..
768 (21.8) 934 (26.4) 1061 (30.0) 1193 (33.8)
Exhaust Temperature - F (C)...
.......... 1129 (609) 1132 (611) 1124 (607) 1098 (592)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
4 (102)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 7.4 (28.0) 10.3 (39.0) 10.6 (40.1) 11.4 (43.2)
Fuel Return - gal./hr. (L/hr.). 9.0 (34.1) 9.5 (36.0) 9.9 (37.5) 10.3 (39.0)
Total Supply Fuel Flow - gal./hr. (L/hr.). 16.4 (62.1) 19.8 (75.0) 20.5 (77.6) 21.7 (82.2)
2
Fuel Pressure - lb./in. (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
.375 Schedule 40 Steel Pipe
Minimum Line Size - Return - (in.)................
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft. (m)....
4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
10 (2.5)
Clean Air Cleaner - in. H20 (kPa).
5 (1.2)
3 3
Engine Air Flow - ft. /min. (m /min.)... 259 (7.3) 315 (8.9) 362 (10.3) 413 (11.7)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
2
BMEP - lb./in. (kPa)
. 150 (1034) 155 (1068) 150 (1034) 139 (958)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... C131622
Power Curve C131379

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131413 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU4R-UF53
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-548

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 60 (57) 73 (69) 80 (76) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 29.1 (27.6) 33.3 (31.6) 34.6 (32.8) 34.6 (32.8)
3 3
Radiator Minimum Ventilation Flow - m /min. (ft /min.).291 (10259) 320 (11315) 347 (12247) 372 (13136)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 17 (18)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F)..... 71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ 0C (-18F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 in Circuit* Length............ 00 00
121 - 160 in Circuit* Length............. 000 000
161 - 200 in Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-UF53
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
21.8 (768) 26.4 (934) 30.0 (1061) 33.8 (1193)
Exhaust Temperature - C (F)............. 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in. H20)...7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 28.0 (7.4) 39.0 (10.3) 40.1 (10.6) 43.2 (11.4)
Fuel Return - L/hr. (gal./hr.).......... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 62.1 (16.4) 75.0 (19.8) 77.6 (20.5) 82.2 (21.7)
2
Fuel Pressure - kPa (lb./in )......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............ 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
130 (54)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
2
BMEP - kPa (lb./in. ).............
1034 (150) 1068 (155) 1034 (150) 958 (139)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131956

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
C131657 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UFD0
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW).....
. 37 (39) 50 (53) 59 (62)
Engine Radiated Heat - Btu/sec.(kW).
.. 25 (26) 32 (34) 33 (35)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 8.9 (34) 10 (39) 11.1 (42)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 10 (36) 12 (44) 13.6 (51)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UFD0
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350


Exhaust Flow - ft.3/min. (m3/min.). 637(18) 873 (25) 982 (30)
Exhaust Temperature - F (C). 952 (511) 935 (502) 862 (515)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)....... 8.2 (31.0) 10.2 (38.6) 10.8 (40.9)
Fuel Return - gal./hr. (L/hr.)....... 4.4 (16.7) 5.7 (21.6) 6.6 (25.0)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 12.6 (47.7) 15.9 (60.2) 17.4 (65.9)
Fuel Pressure - lb.in2 (kPa)........3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 248 (7) 338 (9.6) 422 (11.9)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
BMEP - lb./in.2 (kPa) 120 (827) 130 (898) 130 (898)
Piston Speed - ft./min. (m/min.)...1467(447) 1750 (533) 1958 (597)
Mechanical Noise - dB(A) @ 1m.......... C131491
Power Curve.. C131301
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131394 revJ
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UFD2
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1675(750)

Cooling System 2350 2600


Engine H2O Heat -Btu/sec.(kW).....
. 59 (62) 72 (76)
Engine Radiated Heat - Btu/sec.(kW).
.. 33 (35) 33 (35)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 11.1 (42) 13.1(49)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 13.6 (51) 14.4 (54)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UFD2
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 2350 2600


Exhaust Flow - ft.3/min. (m3/min.) 982 (30) 1174(35)
Exhaust Temperature - F (C) 862 (515) 853 (503)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)...... 10.8 (40.9) 10.7 (40.5)
Fuel Return - gal./hr. (L/hr.)....... 6.6 (25.0) 7.3 (27.6)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 17.4 (65.9) 18.0 (68.1)
Fuel Pressure - lb.in2 (kPa)........3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m).. 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P...230 (+5%, -10%)

Induction Air System


Air Cleaner Type Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 422 (11.9) 481 (13.6)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
BMEP - lb./in.2 (kPa) 130 (896) 117 (807)
Piston Speed - ft./min. (m/min.)... 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m.......... C131490
Power Curve.. C131302
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131393 revJ
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF30 & UF32
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...
1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
Standard
Counter-Clockwise..
Not Available
Engine Crankcase Vent System..Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW)..... 54 (57) 60 (64) 67 (71) 77 (81)
Engine Radiated Heat - Btu/sec.(kW). 31 (33) 36 (38) 36 (38) 36 (38)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
11 (42) 12 (45) 13 (49) 15 (57)
95F (35C) Raw H2O - gal/min. (L/min.)...
13 (49) 14 (53) 16 (60) 17 (64)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...... 4 (60) (400)
Flow - gal./min (L/min.).. 40 (151)
Thermostat, Start to Open - F (C)... 187 (86)
Fully Opened - F (C)... 196 (91)
Engine Coolant Capacity - qt. (L)....20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...10 (69)
Maximum Engine H20 Temperature - F (C)....200 (93)
Minimum Engine H20 Temperature - F (C).....160 (71)

Electric System - DC
System Voltage (Nominal).... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes..... 285 285
Battery Cable Circuit*, Max Resistance - ohm........ 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp....... 40 40
Starter Cranking Amps - @ 60F (15C).... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Clarke
Fire Protection Products
JU6H-UF30 & UF32
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


3 3
Exhaust Flow - ft. /min. (m /min.). 755 (21) 953 (27) 1055 (30) 1236 (35)
Exhaust Temperature - F (C) ........1023 (551) 959 (515) 884 (473) 872 (467)
Maximum Allowable Back Pressure - in. H20 (kPa) 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 9.2 (34.8) 10.7 (40.5) 11.2 (42.4) 11.1 (42.0)
Fuel Return - gal./hr. (L/hr.) 5.0 (18.9) 6.0 (22.7) 6.8 (25.7) 7.5 (28.4)
Total Supply Fuel Flow - gal./hr. (L/hr.)14.2 (53.7) 16.7 (63.2) 18.0 (68.1) 18.6 (70.4)
2
Fuel Pressure - lb./in. (kPa)..3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal).. 1500
Voltage - AC, 1P.. 115 (+5%, -10%)
Optional Voltage - AC, 1P.. 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).. 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
3 3
Engine Air Flow - ft. /min. (m /min.).. 275 (7.8) 361 (10.2) 422 (11.9) 498 (14.1)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***. 130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C).. 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
2
BMEP - lb./in. (kPa). 152 (1048) 145 (1000) 130 (896) 117 (806)
Piston Speed - ft./min. (m/min.) 1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13913(UF30) C13914(UF32)
Power Curve C13479(UF30) C13494(UF32)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13507 revN
25FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF30 & JU6H-UF32
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-538

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 63 (60) 73 (69) 75 (71) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 33 (31) 38 (36) 38 (36) 38 (36)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
45 (12) 53 (14) 61 (16) 68 (18)
57 (15)
35C (95F) Raw H2O - L/min. (gal/min.)...... 64 (17) 72 (19) 79 (21)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)......... 4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF30 & JU6H-UF32
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


3 3
Exhaust Flow - m /min. (ft. /min.)...........
21.0 (755) 27.0 (953) 30.0 (1055) 35.0 (1236)
Exhaust Temperature - C (F).............551 (1023) 515 (959) 473 (884) 467 (872)
Maximum Allowable Back Pressure - kPa (in. H20)....
7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**...........
127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 34.8 (9.2) 40.5 (10.7) 42.4 (11.2) 42.0 (11.1)
Fuel Return - L/hr. (gal./hr.).......... 18.9 (5.0) 22.7 (6.0) 25.7 (6.8) 28.4 (7.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 53.7 (14.2) 63.2 (16.7) 68.1 (18.0) 70.4 (18.6)
Fuel Pressure - kPa (lb./in.2)................ 21-28 (3-4)
Minimum Line Size - Supply - (in.).........50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)......... 0.8 (31)
1.4 (4.5)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P..............
115 (+5%, -10%)
Optional Voltage - AC, 1P..........
230 (+5%, -10%)

Induction Air System


Air Cleaner Type.......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
3 (12)
Dirty Air Cleaner - kPa (in. H20)............
1.5 (6)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)........ 7.8 (275) 10.2 (361) 11.9 (422) 14.1 (498)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........
276-414 (40-60)
In Pan Oil Temperature - C (F)..........
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).........
19 (20)
Low - L (qt.).....
17 (18)
Total Oil Capacity with Filter - L (qt.)....
19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............
10.7 (152) 10.2 (145) 9.1 (130) 8.2 (117)
Piston Speed - m/min. (ft./min.)..........
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131957(UF30) & C131958 (UF32)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131231 revG
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UFG8
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW).....
. 66 (69) 59 (62)
Engine Radiated Heat - Btu/sec.(kW).
.. 29 (31) 34 (36)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 11 (42) 12 (44)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 15 (56) 14 (53)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UFG8
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1470 1760


Exhaust Flow - ft.3/min. (m3/min.). 667 (18.9) 790 (22)
Exhaust Temperature - F (C). 1178 (603) 1044 (562)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)....... 9.1 (34.4) 9.5 (36.0)
Fuel Return - gal./hr. (L/hr.)....... 4.9 (18.5) 5.1 (19.3)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 14.0 (52.9) 14.6 (55.3)
Fuel Pressure - lb.in2 (kPa)........3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 211 (6) 283 (8.0)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
BMEP - lb./in.2 (kPa) 195 (1349) 162 (1114)
Piston Speed - ft./min. (m/min.)...1226 (374) 1467 (447)
Mechanical Noise - dB(A) @ 1m.......... C131489
Power Curve.. C131303
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131392 revJ
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UFM8
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer..... John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio.... 17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System.. Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration.... Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW).....
. 63 (66) 74 (78)
Engine Radiated Heat - Btu/sec.(kW).
.. 30 (32) 40 (42)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 11 (40) 13 (51)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 14 (53) 17 (65)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UFM8
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1470 1760


Exhaust Flow - ft.3/min. (m3/min.) 640 (18) 893 (25)
Exhaust Temperature - F (C) 1170 (645) 1105 (515)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)...... 8.9 (33.7) 10.4 (39.4)
Fuel Return - gal./hr. (L/hr.)....... 4.8 (18.2) 5.6 (21.2)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 13.7 (51.9) 16.0 (60.6)
Fuel Pressure - lb.in2 (kPa)........3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m).. 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P...230 (+5%, -10%)

Induction Air System


Air Cleaner Type Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 202 (6) 307 (8.7)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
BMEP - lb./in.2 (kPa)179 (1237) 167 (1155)
Piston Speed - ft./min. (m/min.)... 1240 (388) 1467 (447)
Mechanical Noise - dB(A) @ 1m.......... C131488
Power Curve.. C131304
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131391 revJ
25FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UFM0
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW).....
. 74 (78) 88 (93) 94 (99)
Engine Radiated Heat - Btu/sec.(kW).
.. 40 (42) 46 (48) 46 (48)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 13 (51) 17 (63) 19 (73)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 17 (65) 21 (78) 24 (91)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE_____________________________________________________
Fire Protection Products

JU6H-UFM0
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350


Exhaust Flow - ft.3/min. (m3/min.).. 893 (21) 1189 (27) 1299 (30)
Exhaust Temperature - F (C)...1105 (515) 1030 (703) 977 (525)
Maximum Allowable Back Pressure - in. H 20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**..5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)....... 10.4 (39.4) 12.2 (46.2) 12.6 (47.7)
Fuel Return - gal./hr. (L/hr.)....... 5.6 (21.2) 6.8 (25.7) 7.7 (29.1)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 16.0 (60.6) 19.0 (71.9) 20.3 (76.8)
Fuel Pressure - lb.in 2 (kPa).........3-4 (21-28)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)........... .848 (0.33)
Minimum Line Size - Return - (in.)......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)........... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type..Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H 20 (kPa) 12 (3)
Clean Air Cleaner - in. H 20 (kPa) 6 (1.5)
Engine Air Flow - ft. 3/min. (m3/min.). 307 (8.7) 429 (12.1) 13.9 (491)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***... 130 (54)

Lubrication System
Oil Pressure - normal - lb./in. 2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L)... 21 (19.5)

Performance
BMEP - lb./in.2 (kPa)..189 (1306) 188 (1298) 163 (1123)
Piston Speed - ft./min. (m/min.)...1467 (447) 1750 (533) 1958 (597)
Mechanical Noise - dB(A) @ 1m.......... C131481 (UFM0)
Power Curve.. C131305 (UFM0)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131390 revJ
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UFM2
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type...
... Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 2350 2600


Engine H2O Heat -Btu/sec.(kW).....
. 94 (99) 92 (97)
Engine Radiated Heat - Btu/sec.(kW).
.. 46 (48) 46 (48)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 19 (73) 21 (81)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 24 (91) 26 (98)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UFM2
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 2350 2600


Exhaust Flow - ft.3/min. (m3/min.). 1299 (30) 1444 (35)
Exhaust Temperature - F (C). 958 (515) 937 (503)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)....... 12.6 (47.7) 12.4 (46.9)
Fuel Return - gal./hr. (L/hr.)....... 7.7 (29.1) 8.4 (31.8)
Total Supply Fuel Flow - gal./hr. (L/hr.)....... 20.3 (76.8) 20.8 (78.7)
Fuel Pressure - lb.in2 (kPa)........3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20)....... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner TypeIndoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 491 (13.9) 554 (15.7)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa) 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L) 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L) 21 (19.5)

Performance
BMEP - lb./in.2 (kPa) 163(1123) 147 (1011)
Piston Speed - ft./min. (m/min.)...1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m.......... C131487
Power Curve.. C131306
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131389 revH
25FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF34
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
3
Displacement - in. (L).......... 415 (6.8)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-536
Weight - lb (kg)..... 1657 (750)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 75 (79) 82 (86) 90 (95) 117 (123)
Engine Radiated Heat - Btu/sec (kW)......... 36.1 (38.1) 36.1 (38.1) 36.1 (38.1) 39.7 (41.9)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
12 (45) 13 (49) 14 (53) 15 (58)
95F (35C) Raw H2O - gal/min. (L/min.)......
13 (49) 14 (54) 16 (61) 17 (65)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.).............. 40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 15 (14)
Coolant Pressure Cap - lb./in.2 (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
Minimum Engine H20 Temperature - F (C).....
160 (71)

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF34
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)..
1081 (30.6) 1243 (35.2) 1365 (38.7) 1614 (45.7)
Exhaust Temperature - F (C)...
.......... 980 (527) 951 (511) 944 (507) 986 (530)
Maximum Allowable Back Pressure - in. H20 (kPa).
30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**...
5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 8.3 (31.4) 11.9 (45.0) 9.9 (37.5) 10.8 (40.9)
Fuel Return - gal./hr. (L/hr.). 6.8 (25.7) 7.5 (28.4) 8.1 (30.7) 8.6 (32.6)
Total Supply Fuel Flow - gal./hr. (L/hr.). 15.1 (57.2) 19.4 (73.4) 18.0 (68.2) 19.4 (73.5)
2
Fuel Pressure - lb./in. (kPa)... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20). 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m)4.5 (1.4)
Fuel Filter Micron Size. 2

Heater System
Jacket Water Heater
Wattage (Nominal)... 1500
Voltage - AC, 1P... 115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)

Induction Air System


Air Cleaner Type. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
12 (3)
Clean Air Cleaner - in. H20 (kPa).
6 (1.5)
Engine Air Flow - ft.3/min. (m 3/min.)...412.9 (11.7) 483.6 (13.7) 533.4 (15.1) 605.1 (17.1)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in.2 (kPa)
. 130 (896) 117 (807) 109 (752) 112 (772)
Piston Speed - ft./min. (m/min.).
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve C131094

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131274 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-UF34
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 79 (75) 86 (82) 95 (90) 123 (117)
Engine Radiated Heat - kW (Btu/sec)......... 38.1 (36.1) 38.1 (36.1) 38.1 (36.1) 41.9 (39.7)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
26 (7) 49 (13) 23 (6) 58 (15)
49 (13)
35C (95F) Raw H2O - L/min. (gal/min.)...... 54 (14) 61 (16) 65 (17)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF34
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
30.6 (1081) 35.2 (1243) 38.7 (1365) 45.7 (1614)
Exhaust Temperature - C (F)............. 527 (980) 511 (951) 507 (944) 530 (986)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 31.4 (8.3) 45.0 (11.9) 37.5 (9.9) 40.9 (10.8)
Fuel Return - L/hr. (gal./hr.).......... 25.7 (6.8) 28.4 (7.5) 30.7 (8.1) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 57.1 (15.1) 73.4 (19.4) 68.2 (18.0) 73.5 (19.4)
Fuel Pressure - kPa (lb./in.2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).... 1.4 (4.5)
Fuel Filter Micron Size............ 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)..........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 11.7 (412.9) 13.7 (483.6) 15.1 (533.4) 17.1 (605.1)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2).............
896 (130) 807 (117) 752 (109) 772 (112)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131963

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131275 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UF50 & JU6H-UF52
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... None
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1657 (750)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW).....
. 79 (83) 90 (95) 101 (106) 96 (101)
Engine Radiated Heat - Btu/sec.(kW).
.. 41 (44) 48 (50) 48 (50) 48 (50)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 14 (53) 17 (64) 21 (79) 23 (87)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 18 (68) 21 (79) 26 (98 28 (106)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250
*Positive and Negative Cables Combined Length

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UF50 & JU6H-UF52


INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


3 3
Exhaust Flow - ft. /min. (m /min.).. 924 (26) 1204 (34) 1359 (38) 1496 (42)
Exhaust Temperature - F (C)...1124 (607) 1034 (557) 977 (525) 953 (512)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 10.7 (40.5) 12.3 (46.6) 12.9 (48.8) 12.7 (48.0)
Fuel Return - gal./hr. (L/hr.) 5.8 (22.0) 6.9 (26.1) 7.9 (29.9) 8.6 (32.6)
Total Supply Fuel Flow - gal./hr (L/hr.) 16.5 (62.5) 19.2 (72.7) 20.8 (78.7) 21.3 (80.6)
Fuel Pressure - lb./in.2 (kPa). 3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type..Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 314 (8.9) 433 (12.3) 508 (14.4) 568 (16.1)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa). 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L).. 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L)... 21 (19.5)

Performance
2
BMEP - lb./in. (kPa)..198 (1365) 191 (1317) 171 (1179) 154 (1062)
Piston Speed - ft./min. (m/min.)...1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13915 (UF50)
Power Curve.. C13480(UF50) C13495(UF52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13508 revQ
25FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF50 & JU6H-UF52
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type...................... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in.).......... 4.19(106) x 5.00(127)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-538

Cooling System - 3 Pass 1470 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 73 (69) 83 (79) 95 (90) 106 (101) 101 (96)
Engine Radiated Heat - kW (Btu/sec)......... 31 (33) 42 (44) 47 (50) 47 (50) 47 (50)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
52 (14) 61 (16) 72 (19) 83 (22) 95 (25)
35C (95F) Raw H2O - L/min. (gal/min.)......
63 (17) 72 (19) 83 (22) 95 (25) 106 (28)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).............
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.)..........14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal).........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 - 3.0 m Circuit* Length............ 00 00
3.1 - 4.0 m Circuit* Length............. 000 000
4.1 - 5.0 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF50 & JU6H-UF52
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1470 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........
19.4 (685) 26.0 (924) 34.0 (1204) 38.0 (1359) 42.0 (1496)
650 (1201)
Exhaust Temperature - C (F)............. 607 (1124) 557 (1034) 525 (977) 512 (953)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
127 (5)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 34.1 (9.0) 40.5 (10.7) 46.6 (12.3) 48.8 (12.9) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.).......... 18.5 (4.9) 22.0 (5.8) 26.1 (6.9) 29.9 (7.9) 32.6 (8.6)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 52.6 (13.9) 62.5 (16.5) 72.7 (19.2) 78.7 (20.8) 80.6 (21.3)
Fuel Pressure - kPa (lb./in.2).............. 21-28 (3-4)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
1.5 (6)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)........ 6.0 (213) 8.9 (314) 12.3 (433) 14.4 (508) 16.1 (568)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 276-414 (40-60)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 19 (20)
Low - L (qt.) 17 (18)
Total Oil Capacity with Filter - L (qt.).. 19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............
14.3 (204) 13.9 (198) 13.4 (191) 12.0 (171) 10.8 (154)
374 (1226)
Piston Speed - m/min. (ft./min.).......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131959 (UF50) & C131960 (UF52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 4.5 meters of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131232 revH
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UF54
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
3
Displacement - in. (L).......... 415 (6.8)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-536
Weight - lb (kg)..... 1657 (750)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 95 (100) 113 (119) 123 (130) 140 (148)
Engine Radiated Heat - Btu/sec (kW)......... 47.6 (50.2) 48.9 (51.5) 48.9 (51.5) 48.9 (51.5)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
8 (30) 9 (34) 11 (42) 13 (49)
95F (35C) Raw H2O - gal/min. (L/min.)......
14 (53) 16 (61) 17 (64) 19 (72)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.).............. 40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
160 (71)
Minimum Engine H20 Temperature - F (C).....

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF54
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)...........
1291 (36.6) 1493 (42.3) 1631 (46.2) 1796 (50.9)
Exhaust Temperature - F(C)............. 1026 (552) 1019 (548) 1018 (548) 1057 (569)
Maximum Allowable Back Pressure - in. H20 (kPa)... 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**......... 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)............ 10.0 (37.9) 11.4 (43.2) 11.9 (45.1) 12.4 (46.9)
Fuel Return - gal./hr. (L/hr.).......... 6.8 (25.7) 7.5 (28.4) 8.2 (31.0) 8.6 (32.6)
Total Supply Fuel Flow - gal./hr. (L/hr.).......... 16.8 (63.6) 18.9 (71.6) 20.1 (76.1) 21.0 (79.5)
Fuel Pressure - lb.in2 (kPa)......... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.).................375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)........ 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
12 (3)
Clean Air Cleaner - in. H20 (kPa).
6 (1.5)
Engine Air Flow - ft.3/min. (m 3/min.)........ 476 (13.5) 555 (15.7) 605 (17.1) 648 (18.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in. 2 (kPa).............
168 (1158) 155.6 (1073) 144 (993) 134 (924)
Piston Speed - ft/.min. (m/min.)..........
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131095

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131276 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-UF54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 50.2 (47.6) 51.5 (48.9) 51.5 (48.9) 51.5 (48.9)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 42 (11) 49 (13)
35C (95F) Raw H2O - L/min. (gal/min.)......
53 (14) 61 (16) 64 (17) 72 (19)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
36.6 (1291) 42.3 (1493) 46.2 (1631) 50.9 (1796)
Exhaust Temperature - C (F)............. 552 (1026) 548 (1019) 548 (1018) 569 (1057)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 37.9 (10.0) 43.2 (11.4) 45.1 (11.9) 46.9 (12.4)
Fuel Return - L/hr. (gal./hr.).......... 25.7 (6.8) 28.4 (7.5) 31.0 (8.2) 32.6 (8.6)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 63.6 (16.8) 71.6 (18.9) 76.1 (20.1) 79.5 (21.0)
Fuel Pressure - kPa (lb./in.2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20).......0.8 . (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size........... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 13.5 (476) 15.7 (555) 17.1 (605) 18.3 (648)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPa (lb./in. 2).............
1158 (168) 1073 (156) 993 (144) 924 (134)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131964

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131277 revE
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UF58
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer...John Deere Co.
Ignition Type . Compression (Diesel)
Number of Cylinders.6
Bore and Stroke - in.(mm). 4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio...17.0:1
Valves per cylinder - Intake 1
Exhaust1
Combustion System.Direct Injection
Engine Type..In-Line, 4 Stroke Cycle
Aspiration...Turbocharged
Firing Order (CW Rotation).1-5-3-6-2-4
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise. Standard
Counter-Clockwise.. Not Available
Engine Crankcase Vent System. Open
Installation Drawing.D-536
Weight - lb (kg) 1657 (750)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW). 70 (73) 79 (83)
Engine Radiated Heat - Btu/sec.(kW).. 31 (33) 42 (44)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).. 11 (43) 14 (53)
95F (35C) Raw H2O - gal/min. (L/min.).. 15 (85) 18 (68)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa). 4 (60) (400)
Flow - gal./min (L/min.) . 40 (151)
Thermostat, Start to Open - F (C) . 187 (86)
Fully Opened - F (C) . 196 (91)
Engine Coolant Capacity - qt. (L) . 20 (19)
2
Coolant Pressure Cap - lb./in. (kPa) .. 10 (69)
Maximum Engine H20 Temperature - F (C).. 200 (93)
Minimum Engine H20 Temperature - F (C).. 160 (71)

Electric System - DC
System Voltage (Nominal) . 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal) 12 24
Qty. per Battery Bank1 2
SAE size per J537 4D-640 4D-640
CCA @ 0F (-18C)640 640
Reserve Capacity - Minutes . 285 285
Battery Cable Circuit*, Max Resistance - ohm..... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length00 00
121 - 160 in. Circuit* Length000 000
161 - 200 in. Circuit* Length0000 0000
Charging Alternator Output - Amp.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UF58
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1470 1760


Exhaust Flow - ft.3/min. (m3/min.).. 685 (19) 924 (26)
Exhaust Temperature - F (C)... 1200 (649) 1124 (607)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)9.0 (34.1) 10.7 (40.5)
Fuel Return - gal./hr. (L/hr.) 4.9 (18.5) 5.8 (22.0)
Total Supply Fuel Flow - gal./hr. (L/hr.)13.9 (52.6) 16.5 (62.5)
Fuel Pressure - lb./in.2 (kPa) 3-4 (21-28)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P. 230 (+5%, -10%)

Induction Air System


Air Cleaner Type.. Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 213 (6.0) 314 (8.9)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)*** 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).40-60 (276-414)
In Pan Oil Temperature - F (C) 220-245 (104-118)
Oil Pan Capacity - High - qt. (L). 19 (20)
Low - qt. (L) 17 (18)
Total Oil Capacity with Filter - qt. (L)... 19.5 (21)

Performance
BMEP - lb./in.2 (kPa).. 204 (1406) 198 (1365)
Piston Speed - ft./min. (m/min.)... 1240 (378) 1467 (447)
Mechanical Noise - dB(A) @ 1m........... C131486
Power Curve.. C131307
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77 o F (25C)

C131388 revH
25FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF58
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer...John Deere Co.
Ignition Type . Compression (Diesel)
Number of Cylinders.6
Bore and Stroke -mm.(in). 106(4.19) x 127(5.00)
3
Displacement -L (in. ).... 6.8 (415)
Compression Ratio...17.0:1
Valves per cylinder - Intake 1
Exhaust1
Combustion System.Direct Injection
Engine Type..In-Line, 4 Stroke Cycle
Aspiration...Turbocharged
Firing Order (CW Rotation).1-5-3-6-2-4
Charge Air Cooling Type.. None
Rotation (Viewed from Front) - Clockwise. Standard
Counter-Clockwise.. Not Available
Engine Crankcase Vent System. Open
Installation Drawing.D-506

Cooling System 1470 1760


Engine H2O Heat - kW (Btu/sec.). . 73 (70) 83 (79)
Engine Radiated Heat - kW (Btu/sec.) .. 33 (31) 44 (42)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - L/min. (gal/min.).. 43 (11) 53 (14)
95F (35C) Raw H2O - L/min. (gal/min.).. 58 (15) 68 (18)
Heat Exchanger Maximum Cooling H2O
2
Inlet Pressure - kPa (lb./in. ) (bar). 4 (60) (400)
Flow - L./min (gal/min.) . 151 (40)
Thermostat, Start to Open - C (F) . 86 (187)
Fully Opened - C (F) . 91 (196)
Engine Coolant Capacity - L (qt.).. . 19 (20)
Coolant Pressure Cap - kPa (lb./in.2).. 69 (10)
Maximum Engine H20 Temperature - C (F).. .. 93 (200)
Minimum Engine H20 Temperature - C (F).. 71 (160)

Electric System - DC
System Voltage (Nominal) . 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal) 12 24
Qty. per Battery Bank1 2
SAE size per J537 4D-640 4D-640
CCA @ -18C (0F)640 640
Reserve Capacity - Minutes . 285 285
Battery Cable Circuit*, Max Resistance - ohm..... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 m. Circuit* Length . 00 00
121 - 160 m. Circuit* Length . 000 000
161 - 200 m. Circuit* Length . 0000 0000
Charging Alternator Output - Amp.. 40 40
Starter Cranking Amps - @ 15C (60F)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE__________________________________________________________
Fire Protection Products

JU6H-UF58
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1470 1760


Exhaust Flow - m3/min. (ft.3/min).. 19 (685) 26 (924)
Exhaust Temperature - C (F) .. 649 (1200) 607 (1124)
Maximum Allowable Back Pressure - kPa (in. H20) 7.4 (30)
Minimum Exhaust Pipe Dia. - mm** (in.).. 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr). 35 (9) 41 (10.7)
Fuel Return - L/hr. (gal./hr)
Total Supply Fuel Flow - L/hr. (gal./hr)
Fuel Pressure - kPa (lb./in.2) 21-28 (3-4)
Minimum Line Size - Supply - mm. (in.)...... 12.7 (.50) Sch. 40 - Black Iron
Minimum Line Size - Return - mm. (in.).....9.5 (.375) Sch. 40 - Black Iron
Maximum Allowable Fuel Pump Suction
With Clean Filter - mH 20 (in. H20) 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - m(ft) 1.4 (4.5)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P 115 (+5%, -10%)
Optional Voltage - AC, 1P 230 (+5%, -10%)

Induction Air System


Air Cleaner Type..Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20) 2.6 (10.5) 2.8 (11.4)
Clean Air Cleaner - kPa (in. H20) 0.1 (0.5) 0.3 (1.4)
Engine Air Flow -m3/min. (ft.3/min.). 6.0 (213) 8.9 (314)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2) 276-414 (40-60)
In Pan Oil Temperature - C (F).. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.). 19 (20)
Low - L (qt.) 17 (18)
Total Oil Capacity with Filter - L (qt.) 19.5 (21)

Performance
BMEP - kPa (lb./in.2 ) 1406 (204) 1365 (198)
Piston Speed -m./min. (ft./min.) 378 (1240) 447 (1467)
Mechanical Noise - dB(A) @ 1m.......... C131486
Power Curve C131307
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131593 rev C
ACH 06DEC06
CLARKE
Fire Protection Products
JU6H-UF60 & JU6H-UF62
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.......John Deere Co.
Ignition Type...
....Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... Raw Water
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1693 (766)

Cooling System 1760 2100 2350 2600


Engine H2O Heat -Btu/sec.(kW).....
. 78 (82) 93 (98) 101 (106) 118 (124)
Engine Radiated Heat - Btu/sec.(kW).
.. 46 (48) 54 (57) 54 (57) 54 (57)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 17 (64) 20 (76) 23 (87) 25 (95)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 18 (68) 21 (79) 25 (97) 26 (98)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250
*Positive and Negative Cables Combined Length

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE___________________________________________________________
Fire Protection Products

JU6H-UF60 & JU6H-UF62


INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - ft.3/min. (m3/min.).. 952 (27) 1227 (35) 1345 (38) 1484 (42)
Exhaust Temperature - F (C)... 988 (531) 909 (487) 883 (473) 898 (481)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**.. 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.) 10 (37.9) 10.3 (39.0) 11.2 (42.4) 12.7 (48.0)
Fuel Return - gal./hr. (L/hr.) 5.4 (20.4 ) 5.8 (22.0) 7.0 (26.5) 8.6 (32.6)
Total Supply Fuel Flow - gal./hr. (L/hr.) 15.4 (58.3) 16.1 (60.9) 18.2 (68.9) 21.3 (80.6)
Fuel Pressure - lb./in.2 (kPa). 4-6 (28-41)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft. (m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal) 1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type..Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.). 354 (10.0) 494 (14.0) 538 (15.2) 587 (16.6)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***.. 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa). 40-60 (276-414)
In Pan Oil Temperature - F (C)220-245 (104-118)
Oil Pan Capacity - High - qt. (L).. 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L)... 21 (19.5)

Performance
BMEP - lb./in.2 (kPa)..217 (1496) 218 (1503) 195 (1344) 176 (1213)
Piston Speed - ft./min. (m/min.)...1467 (447) 1750 (533) 1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m........... C13916 (UF60)
Power Curve.. C13481(UF60) & C13496(UF62)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77 o F (25C)

C13509 revN
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF60 & JU6H-UF62
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type...................... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in.).......... 106(4.19) x 127(5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............ 17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration..............Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Charge Air Cooling Type... Raw Water
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........Open
Installation Drawing..........D-538

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 82 (78) 98 (93) 106 (101) 124 (118)
Engine Radiated Heat - kW (Btu/sec)......... 48 (46) 57 (54) 57 (54) 57 (54)
Heat Exchanger Minimium Flow
53 (14)
15C (60F) Raw H2O - L/min. (gal/min.)...... 72 (19) 72 (19) 83 (22)
57 (15)
35C (95F) Raw H2O - L/min. (gal/min.)...... 83 (22) 83 (22) 95 (25)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).(Standard Plumbing).............. 4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Optional: U051148 High Pressure Plumbing:
Maximum Inlet Pressure bar (psi) (High Pressure Plumbing).. 4 (60)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F)............. 91 (196)
Engine Coolant Capacity - L (qt.)..........14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal).........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF60 & JU6H-UF62
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........... 27.0 (952) 35.0 (1227) 38.0 (1345) 42.0 (1484)
Exhaust Temperature - C (F).............531 (988) 487 (909) 473 (883) 481 (898)
Maximum Allowable Back Pressure - kPa (in. H20)...7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............37.9 (10) 39.0 (10.3) 42.4 (11.2) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.).......... 20.4 (5.4) 22.0 (5.8 ) 26.5 (7.0) 32.6 (8.6)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 58.3 (15.4) 61.0 (16.1) 68.9 (18.2) 80.6 (21.3)
Fuel Pressure - kPa (lb./in.2)............. 28-41 (4-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).... 1.4 (4.5)
Fuel Filter Micron Size...............5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)............
3 (12)
1.5 (6)
Clean Air Cleaner - kPa (in. H20)...........
Engine Air Flow - m3/min. (ft.3/min.)........ 10.0 (354) 14.0 (494) 15.2 (538) 16.6 (587)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....... 276-414 (40-60)
In Pan Oil Temperature - C (F).......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.).........19 (20)
Low - L (qt.)....
17 (18)
Total Oil Capacity with Filter - L (qt.)....
19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............15.2 (217) 15.3 (218) 13.7 (195) 12.4 (176)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve................ C131961 (UF60) & C131962 (UF62)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131223 revG
16AUG07 DSP
CLARKE
Fire Protection Products
JU6H-UF68
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.....John Deere Co.
Ignition Type....
. Compression (Diesel)
Number of Cylinders.. 6
Bore and Stroke - in.(mm)...4.19(106) x 5.00(127)
3
Displacement - in. (L)......415(6.8)
Compression Ratio....17.0:1
Valves per cylinder - Intake....
1
Exhaust...1
Combustion System..Direct Injection
Engine Type.... In-Line, 4 Stroke Cycle
Aspiration....Turbocharged
Firing Order (CW Rotation)... 1-5-3-6-2-4
Charge Air Cooling Type... Raw Water
Rotation (Viewed from Front) - Clockwise.
. Standard
Counter-Clockwise..
.. Not Available
Engine Crankcase Vent System..
. Open
Installation Drawing. D-536
Weight - lb (kg) 1693 (766)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW).....
. 65 (69) 78 (82)
Engine Radiated Heat - Btu/sec.(kW).
.. 40 (42) 46 (48)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...
.. 14 (55) 17 (64)
95F (35C) Raw H2O - gal/min. (L/min.)...
.. 15 (58) 18 (68)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...
. 4 (60) (400)
Flow - gal./min (L/min.)..
. 40 (151)
Thermostat, Start to Open - F (C)...
. 187 (86)
Fully Opened - F (C)...
. 196 (91)
Engine Coolant Capacity - qt. (L)....
. 20 (19)
Coolant Pressure Cap - lb./in.2(kPa)...
.. 10 (69)
Maximum Engine H20 Temperature - F (C)....
.. 200 (93)
Minimum Engine H20 Temperature - F (C).....
.. 160 (71)

Electric System - DC
System Voltage (Nominal)....
. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)... 12 24
Qty. per Battery Bank 1 2
SAE size per J537.... 4D-640 4D-640
CCA @ 0F (-18C)..... 640 640
Reserve Capacity - Minutes.....
. 285 285
Battery Cable Circuit*, Max Resistance - ohm........
.. 0.0012 0.0012
Battery Cable Minimum Size
0 -120 in. Circuit* Length. 00 00
121 - 160 in. Circuit* Length.... 000 000
161 - 200 in. Circuit* Length.... 0000 0000
Charging Alternator Output - Amp.......
.. 40 40
Starter Cranking Amps - @ 60F (15C)... .. 440 250

*Positive and Negative Cables Combined Length


NOTE: This engine is Intendend For Indoor Installatin Or In A Weatherproof Enclosure. (Continued)
CLARKE___________________________________________________________
Fire Protection Products

JU6H-UF68
INSTALLATION & OPERATION DATA (Continued)
USA Production

Exhaust System 1470 1760


Exhaust Flow - ft.3/min. (m3/min.)... 717 (20) 952 (27)
Exhaust Temperature - F (C)... 1055 (569) 988 (531)
Maximum Allowable Back Pressure - in. H20 (kPa).. 30 (7.4)
Minimum Exhaust Pipe Dia. - in. (mm)**... 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.). 9.7 (36.7) 10.3 (39.0)
Fuel Return - gal./hr. (L/hr.). 5.2 (19.7) 5.6 (21.2)
Total Supply Fuel Flow - gal./hr (L/hr.) 14.9 (56.4) 15.9 (60.2)
Fuel Pressure - lb./in.2 (kPa)... 4-6 (28-41)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (0.33)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H 20 (mH20) 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft. (m) 4.5 (1.4)
Fuel Filter Micron Size 5

Heater System
Jacket Water Heater
Wattage (Nominal)1500
Voltage - AC, 1P115 (+5%, -10%)
Optional Voltage - AC, 1P...230 (+5%, -10%)

Induction Air System


Air Cleaner Type..Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa) 12 (3)
Clean Air Cleaner - in. H20 (kPa) 6 (1.5)
Engine Air Flow - ft.3/min. (m3/min.)... 234.6 (6.6) 354 (10.0)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***... 130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).40-60 (276-414)
In Pan Oil Temperature - F (C) 220-245 (104-118)
Oil Pan Capacity - High - qt. (L).. 20 (19)
Low - qt. (L) 18 (17)
Total Oil Capacity with Filter - qt. (L)... 21 (19.5)

Performance
BMEP - lb./in.2 (kPa).. 216 (1490) 217 (1496)
Piston Speed - ft./min. (m/min.)... 1240 (378) 1467 (447)
Mechanical Noise - dB(A) @ 1m........... C131485
Power Curve.. C131308
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77 o F (25C)

C131387 revJ
25 FEB08 DSP
CLARKE
Fire Protection Products
JU6H-UF84
INSTALLATION & OPERATION DATA
USA Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - in. (mm)..........4.19 (106) x 5.00 (127)
Displacement - in.3 (L).......... 415 (6.8)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-536
Weight - lb (kg)..... 1693 (766)

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW).......... 95 (100) 113 (119) 123 (130) 140 (148)
Engine Radiated Heat - Btu/sec (kW)......... 54.9 (57.9) 56.2 (59.2) 58.6 (61.8) 62.2 (65.6)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)......
12 (45) 13 (50) 14 (53) 18 (69)
95F (35C) Raw H2O - gal/min. (L/min.)......
13 (50) 16 (61) 17 (63) 20 (76)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
4 (60) (400)
Flow - gal./min (L/min.).............. 40 (151)
Thermostat, Start to Open - F (C).........
187 (86)
Fully Opened - F (C).............
196 (91)
Engine Coolant Capacity - qt. (L).......... 15 (14)
2
Coolant Pressure Cap - lb./in. (kPa).......10 (69)
Maximum Engine H20 Temperature - F (C)...... 200 (93)
160 (71)
Minimum Engine H20 Temperature - F (C).....

Electric System - DC
System Voltage (Nominal)......... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18F (0C).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF84
INSTALLATION & OPERATION DATA (Continued)
USA Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - ft. /min. (m /min.)...........
1398 (39.6) 1588 (45.0) 1773 (50.2) 1952 (55.3)
Exhaust Temperature - F(C)............. 914 (490) 918 (492) 965 (518) 1032 (556)
Maximum Allowable Back Pressure - in. H20 (kPa)... 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**......... 5 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)............ 11.1 (42.0) 12.1 (45.8) 13.3 (50.3) 14.8 (56.0)
Fuel Return - gal./hr. (L/hr.).......... 6.8 (25.7) 7.5 (28.4) 8.2 (31.0) 8.6 (32.6)
Total Supply Fuel Flow - gal./hr. (L/hr.).......... 17.9 (67.7) 19.6 (74.2) 21.5 (81.3) 23.4 (88.6)
Fuel Pressure - lb.in2 (kPa)......... 3-6 (21-41)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.).................375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)........ 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft.(m)... 4.5 (1.4)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)...
12 (3)
Clean Air Cleaner - in. H20 (kPa).
6 (1.5)
Engine Air Flow - ft.3/min. (m 3/min.)........ 558 (15.8) 627 (17.8) 678 (19.2) 718 (20.3)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***..
130 (54)

Lubrication System
2
Oil Pressure - normal - lb./in. (kPa).
35-50 (241-345)
In Pan Oil Temperature - F (C)...
220-245 (104-118)
Oil Pan Capacity - High - qt. (L)..
8 (7.5)
Low - qt. (L).
7 (6.5)
Total Oil Capacity with Filter - qt. (L).
9 (8.5)

Performance
BMEP - lb./in. 2 (kPa).............
198 (1365) 182 (1255) 177 (1220) 175 (1206)
Piston Speed - ft./min. (m/min.)..........
1958 (597) 2167 (661) 2333 (711) 2500 (762)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131096

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131278 revE
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-UF84
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 57.9 (54.9) 59.2 (56.2) 61.8 (58.6) 65.6 (62.2)
Heat Exchanger Minimium Flow
45 (12)
15C (60F) Raw H2O - L/min. (gal/min.)...... 50 (13) 53 (14) 69 (18)
35C (95F) Raw H2O - L/min. (gal/min.)......
50 (13) 61 (16) 63 (17) 76 (20)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).(Standard Plumbing)........ 4 (60) (400)
Flow - L/min. (gal./min)........... 100 (26)
Optional: U051148 High Pressure Plumbing:
Maximum Inlet Pressure bar (psi) (High Pressure Plumbing)4 (60)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F)............. 91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-UF84
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
39.6 (1398) 45.0 (1588) 50.2 (1773) 55.3 (1952)
Exhaust Temperature - C (F)............. 490 (914) 492 (918) 518 (965) 556 (1032)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 42.0 (11.1) 45.8 (12.1) 50.3 (13.3) 56.0 (14.8)
Fuel Return - L/hr. (gal./hr.).......... 25.7 (6.8) 28.4 (7.5) 31.0 (8.2) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.).......... 67.7 (17.9) 74.2 (19.6) 81.3 (21.5) 88.6 (23.4)
Fuel Pressure - kPa (lb./in.2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............. 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 15.8 (558) 17.8 (627) 19.2 (678) 20.3 (718)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2).............
1365 (198) 1255 (182) 1220 (177) 1206 (175)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131965

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131279 reve
16AUG07 DSP
CLARKE
Fire Protection Products
JW6H-UF38
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type............... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)........... 4.56 (116) x 5.06 (129)
3
Displacement - in. (L)............... 496 (8.1)
Compression Ratio............. 16.5:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration................ Turbocharged
Firing Order (CW Rotation)..............1-5-3-6-2-4
Charge Air Cooling Type............. Jacket Water Cooled
Rotation (Viewed from Front) - Clockwise.........
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System........... Open
Installation Drawing............ D-495
Weight - lb (kg).......
2012 (910)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW)........... 96 (101) 90 (95)
Engine Radiated Heat - Btu/sec.(kW)............
24 (25) 27 (28)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..........
11 (41) 13 (51)
95F (35C) Raw H2O - gal/min. (L/min.)..........
18 (68) 21 (81)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.)............. 80 (302)
Thermostat, Start to Open - F (C)......... 180 (82)
Fully Opened - F (C)...........
202 (94)
Engine Coolant Capacity - qt. (L)........... 22 (21)
Coolant Pressure Cap - lb./in.2(kPa)...........
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)...........
160 (71)

Electric System - DC
System Voltage (Nominal)........... 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes..........430 430
Battery Cable Circuit*, Max Resistance - ohm............ 0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF38
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1470 1760
Exhaust Flow - ft.3/min. (m3/min.)..........
1073 (30) 1351 (38)
Exhaust Temperature - F (C)........... 982 (528) 832 (445)
Maximum Allowable Back Pressure - in. H20 (kPa).........
19 (4.7) 26 (6.6)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
5.0 (127) 5.0 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 13.0 (49.2) 14.0 (53.0)
Fuel Return - gal./hr. (L/hr.)......... 63.0 (238.5) 62.0 (234.7)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.0 (287.7) 76.0 (287.7)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
14 (3.5)
Dirty Air Cleaner - in. H20 (kPa)..............
7 (1.7)
Clean Air Cleaner - in. H20 (kPa)............
Engine Air Flow - ft.3/min. (m3/min.)..............
400 (11) 562 (16)
130 (54)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 235 (1618) 228 (1572)
Piston Speed - ft./min. (m/min.)............
1240 (378) 1484 (452)
Mechanical Noise - dB(A) @ 1M. C131484
Power Curve............... C131309

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131386 rev D
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF30 (JDFP-06WA)
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type............... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)........... 4.56 (116) x 5.06 (129)
3
Displacement - in. (L)............... 496 (8.1)
Compression Ratio............. 16.5:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration................ Turbocharged
Firing Order (CW Rotation)..............1-5-3-6-2-4
Charge Air Cooling Type............. Jacket Water Cooled
Rotation (Viewed from Front) - Clockwise.........
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System........... Open
Installation Drawing............ D-495
Weight - lb (kg).......
2012 (910)

Cooling System 1470 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW)........... 104 (110) 112 (118) 117 (123) 113 (119)
Engine Radiated Heat - Btu/sec.(kW)............
24 (25) 28 (30) 29 (31) 29 (31)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)..........
11 (42) 14 (53) 16 (61) 21 (79)
95F (35C) Raw H2O - gal/min. (L/min.)..........
18 (68) 22 (83) 25 (95) 31 (117)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.)............. 80 (302)
Thermostat, Start to Open - F (C)......... 180 (82)
Fully Opened - F (C)...........
202 (94)
Engine Coolant Capacity - qt. (L)........... 22 (21)
Coolant Pressure Cap - lb./in.2(kPa)...........
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)...........
160 (71)

Electric System - DC
System Voltage (Nominal)........... 12 (Standard) 24 (Optinoal)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes..........430 430
Battery Cable Circuit*, Max Resistance - ohm............ 0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 60F (15C)......... 495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF30 (JDFP-06WA)
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1470 1760 2100 2350
Exhaust Flow - ft.3/min. (m3/min.)..........
1107 (31) 1404 (40) 1644 (47) 1908 (54)
Exhaust Temperature - F (C)........... 990 (518) 840 (435) 750 (385) 737 (392)
19 (4.7) 26 (6.6)
Maximum Allowable Back Pressure - in. H20 (kPa)......... 28 (7.1) 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
5.0 (127) 5.0 (127) 5.0 (127) 5.0 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 13.0 (49.2) 14.0 (53.0) 15.0 (56.8) 16.0 (60.6)
Fuel Return - gal./hr. (L/hr.)......... 63.0 (238.5) 62.0 (234.7) 61.0 (230.9) 60.0 (227.1)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.0 (287.7) 76.0 (287.7) 76.0 (287.7) 76.0 (287.7)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
115 (+5%, -10%)
Optional Voltage - AC, 1P.................
Lube Oil Heater Wattage
150
(Required Option When Ambient is Below 40F (4C)...

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
14 (3.5)
Dirty Air Cleaner - in. H20 (kPa)..............
Clean Air Cleaner - in. H20 (kPa)............
7 (1.7)
Engine Air Flow - ft.3/min. (m3/min.)..............
410 (12) 580 (16) 730 (21) 856 (24)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L)..........32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 239 (1648) 240 (1655) 209 (1441) 187 (1289)
Piston Speed - ft./min. (m/min.)............
1240 (378) 1484 (452) 1771 (540) 1982 (604)
Mechanical Noise - dB(A) @ 1M. C13917
Power Curve............... CDDA - W064 - 01

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13426 revH
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF30
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type............... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in)........... 116 (4.56) x 129 (5.06)
Displacement - L (in.3 )...............
8.1 (496)
Compression Ratio............. 16.5:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration................ Turbocharged
Firing Order (CW Rotation)..............1-5-3-6-2-4
Charge Air Cooling Type............. Jacket Water Cooled
Rotation (Viewed from Front) - Clockwise.........
Standard
Counter-Clockwise.............
Not Available
Engine Crankcase Vent System........... Open
Installation Drawing............ D-495

Cooling System 1470 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 110 (104) 118 (112) 123 (117) 119 (113)
Engine Radiated Heat - kW (Btu/sec)......... 25 (24) 30 (28) 31 (29) 31 (29)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
42 (11) 53 (14) 61 (16) 79 (21)
68 (18)
35C (95F) Raw H2O - L/min. (gal/min.)...... 83 (22) 95 (25) 117 (31)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)......... 4 (60) (400)
Flow - L/min. (gal./min)........... 302 (80)
Thermostat, Start to Open - C (F).........82 (180)
94 (202)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.)..........21 (22)
Coolant Pressure Cap - kPa (lb./in.2)....... 69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........... 12
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12
Qty. per Battery Bank............ 1
SAE size per J537.............. 8D-900
CCA @ 0F (-18C).............. 900
Reserve Capacity - Minutes..........430
Battery Cable Circuit*, Max Resistance - ohm............ 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00
121 - 160 in. Circuit* Length............. 000
161 - 200 in. Circuit* Length............. 0000
Charging Alternator Output - Amp.......... 40
Starter Cranking Amps - @ 60F (15C)......... 495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF30
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1470 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)...........
31 (1107) 40 (1404) 47 (1644) 54 (1908)
Exhaust Temperature - C (F).............518 (990) 435 (840) 385 (750) 392 (737)
4.7 (19)
Maximum Allowable Back Pressure - kPa (in. H20)... 6.6 (26) 7.1 (28) 7.5 (30)
127 (5.0)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 49.2 (13.0) 53.0 (14.0) 56.8 (15.0) 61.6 (16.0)
Fuel Return - L/hr. (gal./hr.).......... 238.5 (63.0) 234.7 (62.0) 230.9 (61.0) 227.1 (60.0)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 287.7 (76.0) 287.7 (76.0) 287.7 (76.0) 288.7 (76.0)
2
Fuel Pressure - kPa (lb./in. )................ 172-241 (25-35 )
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 2.7 (9)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
115 (+5%, -10%)
Optional Voltage - AC, 1P.................
Lube Oil Heater Wattage
150
(Required Option When Ambient is Below 4C (40F)...

Induction Air System


Air Cleaner Type.......... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).............
3.5 (14)
Clean Air Cleaner - kPa (in. H20)............
1.7 (7)
Engine Air Flow - m3/min. (ft.3/min.)........ 12 (410) 16 (580) 21 (730) 24 (856)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )........
207-379 (30-55)
In Pan Oil Temperature - C (F)..........
88-104 (190-220)
Oil Pan Capacity - High - L (qt.)......... 30 (32)
Total Oil Capacity with Filter - L (qt.)....
32 (34)

Performance
2 2
BMEP - kg/cm (lb./in. ).............
1648 (239) 1655 (240) 1441 (209) 1289 (187)
378 (1240) 452 (1484) 540 (1771) 604 (1982)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve................ C131966

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C132031 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JW6H-UF48
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
Displacement - in.3 (L)...............
496 (8.1)
Compression Ratio............. 16.5:1
Valves per cylinder - Intake..............
1
1
Exhaust..............
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
1-5-3-6-2-4
Firing Order (CW Rotation)..............
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)....................
2003 (906)

Cooling System 1470 1760


Engine H2O Heat -Btu/sec.(kW)..............
147 (155) 154 (162)
Engine Radiated Heat - Btu/sec.(kW)............
26 (27) 30 (32)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
12 (45) 15 (57)
19 (72) 23 (87)
95F (35C) Raw H2O - gal/min. (L/min.).............
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
23 (22)
Engine Coolant Capacity - qt. (L)..............
2
10 (69)
Coolant Pressure Cap - lb./in. (kPa)..............
200 (93)
Maximum Engine H20 Temperature - F (C)..............
160 (71)
Minimum Engine H20 Temperature - F (C)..............

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................ 430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................40 40
Starter Cranking Amps - @ 60F (15C)...............495 326
*Positive and Negative Cables Combined Length
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. Continued
CLARKE
Fire Protection Products
JW6H-UF48
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1470 1760
Exhaust Flow - ft.3/min. (m3/min.)..........1276 (36) 1506 (43)
Exhaust Temperature - F (C)........... 1030 (540) 855 (443)
Maximum Allowable Back Pressure - in. H20 (kPa).........
19 (4.7) 26 (6.6)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
5.0 (127) 5.0 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 13.0 (49.2) 13.5 (51.1)
Fuel Return - gal./hr. (L/hr.)......... 63.0 (238.5) 62.5 (236.6)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.0 (287.7) 76.0 (287.7)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
14 (3.5)
Dirty Air Cleaner - in. H20 (kPa)..............
7 (1.7)
Clean Air Cleaner - in. H20 (kPa)............
Engine Air Flow - ft.3/min. (m3/min.)..............
460 (13) 615 (17)
130 (54)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 261 (1800) 263 (1813)
Piston Speed - ft./min. (m/min.)............
1240 (378) 1484 (452)
Mechanical Noise - dB(A) @ 1M. C131483
Power Curve............... C131310

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131385 rev C
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF40 (JDFP-06WR)
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
Displacement - in.3 (L)...............
496 (8.1)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
1
Exhaust..............
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
1-5-3-6-2-4
Firing Order (CW Rotation)..............
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)................
2003 (906)

Cooling System 1470 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW)..............
147 (155) 154 (162) 162 (171) 156 (164)
Engine Radiated Heat - Btu/sec.(kW)............
26 (27) 30 (32) 32 (34) 32 (34)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
12 (45) 15 (57) 17 (64) 21 (79)
19 (72) 23 (87)
95F (35C) Raw H2O - gal/min. (L/min.)............. 29 (110) 31 (117)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
23 (22)
Engine Coolant Capacity - qt. (L)..............
2
10 (69)
Coolant Pressure Cap - lb./in. (kPa)..............
200 (93)
Maximum Engine H20 Temperature - F (C)..............
160 (71)
Minimum Engine H20 Temperature - F (C)..............

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................ 430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................40 40
Starter Cranking Amps - @ 60F (15C)...............495 326
*Positive and Negative Cables Combined Length
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. Continued
CLARKE
Fire Protection Products
JW6H-UF40 (JDFP-06WR)
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1470 1760 2100 2350
Exhaust Flow - ft.3/min. (m3/min.)..........1276 (36) 1506 (43) 1740 (49) 2058 (58)
Exhaust Temperature - F (C)........... 1030 (540) 855 (443) 770 (396) 738 (392)
19 (4.7) 26 (6.6)
Maximum Allowable Back Pressure - in. H20 (kPa)......... 28 (7.1) 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
5.0 (127) 5.0 (127) 5.0 (127) 5.0 (127)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 13.0 (49.2) 13.5 (51.1) 14.0 (53.0) 14.5 (54.9)
Fuel Return - gal./hr. (L/hr.)......... 63.0 (238.5) 62.5 (236.6) 62.0 (234.7) 61.5 (232.8)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.0 (287.7) 76.0 (287.7) 76.0 (287.7) 76.0 (287.7)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
115 (+5%, -10%)
Optional Voltage - AC, 1P.................
Lube Oil Heater Wattage
150
(Required Option When Ambient is Below 40F (4C)...

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
14 (3.5)
Dirty Air Cleaner - in. H20 (kPa)..............
Clean Air Cleaner - in. H20 (kPa)............
7 (1.7)
Engine Air Flow - ft.3/min. (m3/min.)..............
460 (13) 615 (17) 760 (22) 923 (26)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 261 (1800) 263 (1813) 228 (1572) 204 (1406)
Piston Speed - ft./min. (m/min.)............
1240 (378) 1484 (452) 1771 (540) 1982 (604)
Mechanical Noise - dB(A) @ 1M. C13918
Power Curve............... CDDA - W064 - 02

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13427 revH
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF40 (JDFP-06WR)
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in)........... 116 (4.56) x 129 (5.06)
3
8.1 (496)
Displacement - L (in. )...............
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
1
Exhaust..............
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
1-5-3-6-2-4
Firing Order (CW Rotation)..............
Raw Water Cooled
Charge Air Cooling Type.............
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Open
Engine Crankcase Vent System..............
Installation Drawing............ D-495

Cooling System 1470 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 155 (147) 162 (154) 171 (162) 164 (156)
Engine Radiated Heat - kW (Btu/sec)......... 27 (26) 32 (30) 34 (32) 34 (32)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
45 (12) 57 (15) 64 (17) 79 (21)
72 (19)
35C (95F) Raw H2O - L/min. (gal/min.)...... 87 (23) 110 (29) 117 (31)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).(Standard Plumbing)........
4 (60) (400)
Flow - L/min. (gal./min)........... 302 (80)
Optional: U051147 High Pressure Plumbing:
Maximum Inlet Pressure bar (psi) (High Pressure Plumbing)...
4 (60)
Thermostat, Start to Open - C (F)......... 82 (180)
Fully Opened - C (F)............. 94 (202)
Engine Coolant Capacity - L (qt.).......... 22 (23)
Coolant Pressure Cap - kPa (lb./in.2)....... 69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal).............. 12
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12
Qty. per Battery Bank............ 1
SAE size per J537.............. 8D-900
CCA @ 0F (-18C).............. 900
430
Reserve Capacity - Minutes................
0.0017
Battery Cable Circuit*, Max Resistance - ohm..................
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00
121 - 160 in. Circuit* Length............. 000
161 - 200 in. Circuit* Length............. 0000
40
Charging Alternator Output - Amp................
495
Starter Cranking Amps - @ 60F (15C)...............
*Positive and Negative Cables Combined Length
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. Continued
CLARKE
Fire Protection Products
JW6H-UF40 (JDFP-06WR)
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1470 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)...........
36 (1276) 43 (1506) 49 (1740) 58 (2058)
Exhaust Temperature - C (F).............540 (1030) 443 (855) 396 (770) 392 (738)
Maximum Allowable Back Pressure - kPa (in. H20)...4.7 (19) 6.6 (26) 7.1 (28) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
127 (5.0)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 49.2 (13.0) 51.1 (13.5) 53.0 (14.0) 54.9 (14.5)
Fuel Return - L/hr. (gal./hr.).......... 238.5 (63.0) 236.6 (62.5) 234.7 (62.0) 232.8 (61.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 287.7 (76.0) 287.7 (76.0) 287.7 (76.0) 287.7 (76.0)
Fuel Pressure - kPa (lb./in.2)................. 172-241 (25-35)
Minimum Line Size - Supply - (in.)............ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 2.7 (9)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater............ Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P..............
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)............
150

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
3.5 (14)
Dirty Air Cleaner - kPa (in. H20)...........
1.7 (7)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)........ 13 (460) 17 (615) 22 (760) 26 (923)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 207-379 (30-55)
In Pan Oil Temperature - C (F)........ 88-104 (190-220)
Oil Pan Capacity - High - L (qt.)....... 30 (32)
Total Oil Capacity with Filter - L (qt.).. 32 (34)
Performance
BMEP - kg/cm2 (lb./in.2).............1800 (261) 1813 (263) 1572 (228) 1406 (204)
Piston Speed - m/min. (ft./min.)..........
378 (1240) 452 (1484) 540 (1771) 604 (1982)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131967

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C132032 revC
16AUG07 DSP
CLARKE
Fire Protection Products
JW6H-UF58
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
3
Displacement - in. (L)...............496 (8.1)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)..............
1-5-3-6-2-4
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)..............
2053 (929)

Cooling System 1760


Engine H2O Heat -Btu/sec.(kW)..............
131 (138)
Engine Radiated Heat - Btu/sec.(kW)............
32 (34)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
35 (132)
95F (35C) Raw H2O - gal/min. (L/min.).............
39 (146)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
Engine Coolant Capacity - qt. (L)..............
23 (22)
Coolant Pressure Cap - lb./in.2(kPa)..............
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)..............
160 (71)

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................
430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................
40 40
Starter Cranking Amps - @ 60F (15C)...............
495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF58
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760
Exhaust Flow - ft.3/min. (m3/min.)..........
1642 (46)
Exhaust Temperature - F (C)........... 866 (463)
Maximum Allowable Back Pressure - in. H20 (kPa).........
26 (6.6)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
6 (152)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 14.0 (53.0)
Fuel Return - gal./hr. (L/hr.)......... 62.5 (236.6)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.5 (289.6)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
14 (3.5)
Dirty Air Cleaner - in. H20 (kPa)..............
7 (1.7)
Clean Air Cleaner - in. H20 (kPa)............
Engine Air Flow - ft.3/min. (m3/min.)..............
692 (20)
130 (54)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 272 (1877)
Piston Speed - ft./min. (m/min.)............
1484 (452)
Mechanical Noise - dB(A) @ 1M. C13919
Power Curve............... C13542

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131384 rev D
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF50
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
3
Displacement - in. (L)...............496 (8.1)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)..............
1-5-3-6-2-4
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)........ 2053 (929)

Cooling System 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW)..............
131 (138) 170 (179) 196 (207)
Engine Radiated Heat - Btu/sec.(kW)............
32 (34) 36 (38) 37 (39)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
35 (132) 42 (159) 44 (167)
95F (35C) Raw H2O - gal/min. (L/min.).............
39 (146) 45 (170) 47 (178)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
Engine Coolant Capacity - qt. (L)..............
23 (22)
Coolant Pressure Cap - lb./in.2(kPa)..............
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)..............
160 (71)

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................
430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................
40 40
Starter Cranking Amps - @ 60F (15C)...............
495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF50
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
Exhaust Flow - ft.3/min. (m3/min.)..........
1642 (46) 2066 (59) 2345 (66)
Exhaust Temperature - F (C)........... 866 (463) 788 (420) 806 (430)
26 (6.6) 28 (7.1)
Maximum Allowable Back Pressure - in. H20 (kPa)......... 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
6 (152)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 14.0 (53.0) 16.0 (60.6) 17.0 (64.4)
Fuel Return - gal./hr. (L/hr.)......... 62.5 (236.6)62.0 (234.7) 61.5 (232.8)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 76.5 (289.6)78.0 (295.3) 78.5 (297.2)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)..............
14 (3.5)
Clean Air Cleaner - in. H20 (kPa)............
7 (1.7)
Engine Air Flow - ft.3/min. (m3/min.)..............
692 (20) 881 (25) 992 (28)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 272 (1877) 259 (1782) 238 (1640)
Piston Speed - ft./min. (m/min.)............
1484 (452) 1771 (540) 1982 (604)
Mechanical Noise - dB(A) @ 1M. C13919
Power Curve............... C13542

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13613 revG
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF50
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in)........... 116 (4.56) x 129 (5.06)
Displacement - L (in.3 )............... 8.1 (496)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............Turbocharged
Firing Order (CW Rotation)..............1-5-3-6-2-4
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Counter-Clockwise.............
Not Available
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495

Cooling System 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 138 (131) 179 (170) 207 (196)
Engine Radiated Heat - kW (Btu/sec)......... 34 (32) 38 (36) 39 (37)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
132 (35) 159 (42) 167 (44)
146 (39)
35C (95F) Raw H2O - L/min. (gal/min.)...... 170 (45) 178 (47)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).(Standard Plumbing).......... 4 (60) (400)
Flow - L/min. (gal./min)........... 302 (80)
Optional: U051148 High Pressure Plumbing:
Maximum Inlet Pressure bar (psi) (High Pressure Plumbing)..
4 (60)
Thermostat, Start to Open - C (F)......... 82 (180)
Fully Opened - C (F)............. 94 (202)
Engine Coolant Capacity - L (qt.).......... 22 (23)
Coolant Pressure Cap - kPa (lb./in.2)....... 69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal).............. 12
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12
Qty. per Battery Bank............ 1
SAE size per J537.............. 8D-900
CCA @ 0F (-18C).............. 900
Reserve Capacity - Minutes................
430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00
121 - 160 in. Circuit* Length............. 000
161 - 200 in. Circuit* Length............. 0000
Charging Alternator Output - Amp................
40
Starter Cranking Amps - @ 60F (15C)...............
495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF50
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1760 2100 2350
Exhaust Flow - m3/min. (ft.3/min.)...........
46 (1642) 59 (2066) 66 (2345)
Exhaust Temperature - C (F).............463 (866) 420 (788) 430 (806)
6.6 (26)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.1 (28) 7.5 (30)
6 (152)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 53.0 (14.0) 60.6 (16.0) 64.4 (17.0)
Fuel Return - L/hr. (gal./hr.).......... 236.6 (62.5) 234.7 (62.0) 232.8 (61.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 289.6 (76.5) 295.3 (78.0) 297.2 (78.5)
Fuel Pressure - kPa (lb./in.2).............. 172-241 (25-35)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 2.7 (9)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater............Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
115 (+5%, -10%)
Optional Voltage - AC, 1P..............
Lube Oil Heater Wattage
150
(Required Option When Ambient is Below 40F (4C)............

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3.5 (14)
Clean Air Cleaner - kPa (in. H20)..........
1.7 (7)
Engine Air Flow - m3/min. (ft.3/min.)........ 20 (692)
54(130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 207-379 (30-55)
In Pan Oil Temperature - C (F)........ 88-104 (190-220)
Oil Pan Capacity - High - L (qt.)....... 30 (32)
Total Oil Capacity with Filter - L (qt.).. 32 (34)
Performance
2 2
BMEP - kg/cm (lb./in. ).............1877 (272) 1782 (259) 1640 (238)
452 (1484) 540 (1771) 604 (1982)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131968

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C132033 revD
16AUG07 DSP
CLARKE
Fire Protection Products
JW6H-UFH8
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
3
Displacement - in. (L)...............496 (8.1)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)..............
1-5-3-6-2-4
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)..........2053 (929)

Cooling System 1760


Engine H2O Heat -Btu/sec.(kW)..............
145 (153)
Engine Radiated Heat - Btu/sec.(kW)............
35 (37)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
38 (144)
95F (35C) Raw H2O - gal/min. (L/min.).............
42 (158)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
Engine Coolant Capacity - qt. (L)..............
23 (22)
Coolant Pressure Cap - lb./in.2(kPa)..............
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)..............
160 (71)

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................
430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................
40 40
Starter Cranking Amps - @ 60F (15C)...............
495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UFH8
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760
Exhaust Flow - ft.3/min. (m3/min.)..........
1805 (51)
Exhaust Temperature - F (C)........... 884 (473)
26 (6.6)
Maximum Allowable Back Pressure - in. H20 (kPa).........
Minimum Exhaust Pipe Dia. - in. (mm)**..............
6 (152)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 15.2 (57.5)
Fuel Return - gal./hr. (L/hr.)......... 62.5 (236.6)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 77.7 (294.1)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)..............
14 (3.5)
Clean Air Cleaner - in. H20 (kPa)............
7 (1.7)
Engine Air Flow - ft.3/min. (m3/min.)..............
736 (21)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 300 (2064)
Piston Speed - ft./min. (m/min.)............
1484 (452)
Mechanical Noise - dB(A) @ 1M. Consult Factory
Power Curve............... C132065

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C132024 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF60
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.............. John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - in.(mm)..............
4.56 (116) x 5.06 (129)
3
Displacement - in. (L)...............496 (8.1)
Compression Ratio............. 15.7:1
Valves per cylinder - Intake..............
1
Exhaust..............
1
Combustion System............. Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)..............
1-5-3-6-2-4
Charge Air Cooling Type............. Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Not Available
Counter-Clockwise.............
Engine Crankcase Vent System..............
Open
Installation Drawing............ D-495
Weight - lb (kg)............2053 (929)

Cooling System 1760 2100 2350


Engine H2O Heat -Btu/sec.(kW)..............
159 (168) 197 (208) 206 (217)
Engine Radiated Heat - Btu/sec.(kW)............
38 (40) 40 (42) 38 (40)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.).............
41 (155) 44 (167) 44 (167)
95F (35C) Raw H2O - gal/min. (L/min.).............
45 (170) 47 (178) 47 (178)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).......... 4 (60) (400)
Flow - gal./min (L/min.).............
80 (302)
Thermostat, Start to Open - F (C)............
180 (82)
Fully Opened - F (C)..............
202 (94)
Engine Coolant Capacity - qt. (L)..............
23 (22)
Coolant Pressure Cap - lb./in.2(kPa)..............
10 (69)
Maximum Engine H20 Temperature - F (C)..............
200 (93)
Minimum Engine H20 Temperature - F (C)..............
160 (71)

Electric System - DC
System Voltage (Nominal).............. 12 (Standard) 24 (Optional)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).............. 12 24
Qty. per Battery Bank............ 1 1
SAE size per J537.............. 8D-900 8D-900
CCA @ 0F (-18C).............. 900 900
Reserve Capacity - Minutes................
430 430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017 0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length............ 00 00
121 - 160 in. Circuit* Length............. 000 000
161 - 200 in. Circuit* Length............. 0000 0000
Charging Alternator Output - Amp................
40 40
Starter Cranking Amps - @ 60F (15C)...............
495 326
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF60
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
Exhaust Flow - ft.3/min. (m3/min.)..........
1968 (56) 2297 (65) 2418 (68)
Exhaust Temperature - F (C)........... 902 (483) 853 (456) 813 (434)
26 (6.6) 28 (7.1)
Maximum Allowable Back Pressure - in. H20 (kPa)......... 30 (7.5)
Minimum Exhaust Pipe Dia. - in. (mm)**..............
6 (152)

Fuel System
Fuel Consumption - gal./hr. (L/hr.)......... 16.5 (62.5) 17.5 (66.2) 17.5 (66.2)
Fuel Return - gal./hr. (L/hr.)......... 62.5 (236.6)62.0 (234.7) 61.5 (232.8)
Total Supply Fuel Flow - gal./hr. (L/hr.)......... 79.0 (299.1)79.5 (300.9) 79.0 (299.0)
Fuel Pressure - lb./in.2 (kPa)........... 25-35 (172-241)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.848 (0.33)
Minimum Line Size - Return - (in.)................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm)..................
.675 (0.26)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m) 9 (2.7)
Fuel Filter Micron Size............ 5

Heater System
Jacket Water Heater............... Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
Optional Voltage - AC, 1P.................
115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)...
150

Induction Air System


Air Cleaner Type............... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa)..............
14 (3.5)
Clean Air Cleaner - in. H20 (kPa)............
7 (1.7)
Engine Air Flow - ft.3/min. (m3/min.)..............
780 (22) 939 (27) 1020 (29)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***....
130 (54)

Lubrication System
Oil Pressure - normal - lb./in.2 (kPa).........
30-55 (207-379)
In Pan Oil Temperature - F (C)........... 190-220 (88-104)
Oil Pan Capacity - High - qt. (L).......... 32 (30)
Total Oil Capacity with Filter - qt. (L).........
34 (32)

Performance
BMEP - lb./in.2 (kPa)............ 327 (2252) 285 (1966) 245 (1687)
Piston Speed - ft./min. (m/min.)............
1484 (452) 1771 (540) 1982 (604)
Mechanical Noise - dB(A) @ 1M. C13920
Power Curve............... C13543

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13614 revF
DSP 30AUG07
CLARKE
Fire Protection Products
JW6H-UF60
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....................
John Deere Co.
Ignition Type........................
Compression (Diesel)
Number of Cylinders...................
6
Bore and Stroke - mm (in)...................
116 (4.56) x 129 (5.06)
Displacement - L (in.3 ).....................
8.1 (496)
Compression Ratio...................
15.7:1
Valves per cylinder - Intake................
1
Exhaust................
1
Combustion System...................
Direct Injection
Engine Type......................
In-Line, 4 Stroke Cycle
Aspiration.......................
Turbocharged
Firing Order (CW Rotation)..................
1-5-3-6-2-4
Charge Air Cooling Type.................
Raw Water Cooled
Rotation (Viewed from Front) - Clockwise............
Standard
Counter-Clockwise.............
Not Available
Engine Crankcase Vent System..............
Open
Installation Drawing..................
D-495

Cooling System 1760 2100 2350


Engine H2O Heat - kW (Btu/sec)..................
168 (159) 208 (197) 217 (206)
40 (38)
Engine Radiated Heat - kW (Btu/sec).................42 (40) 40 (38)
Heat Exchanger Minimium Flow
155(41)
15C (60F) Raw H2O - L/min. (gal/min.)..........167 (44) 167 (44)
170 (45) 178 (47)
35C (95F) Raw H2O - L/min. (gal/min.).......... 178 (47)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).(Standard Plumbing)..............
4 (60) (400)
Flow - L/min. (gal./min).................302 (80)
Optional: U051148 High Pressure Plumbing:
Maximum Inlet Pressure bar (psi) (High Pressure Plumbing)........
4 (60)
Thermostat, Start to Open - C (F)........... 82 (180)
Fully Opened - C (F)...............94 (202)
Engine Coolant Capacity - L (qt.)................ 22 (23)
2
Coolant Pressure Cap - kPa (lb./in. )............. 69 (10)
Maximum Engine H20 Temperature - C (F)............ 93 (200)
Minimum Engine H20 Temperature - C (F)...........
71 (160)

Electric System - DC
System Voltage (Nominal).............. 12
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal).................. 12
1
Qty. per Battery Bank...............
SAE size per J537.................8D-900
CCA @ 0F (-18C).................900
Reserve Capacity - Minutes.............430
Battery Cable Circuit*, Max Resistance - ohm..................
0.0017
Battery Cable Minimum Size
0 -120 in. Circuit* Length...............
00
121 - 160 in. Circuit* Length................
000
161 - 200 in. Circuit* Length................
0000
Charging Alternator Output - Amp...................
40
Starter Cranking Amps - @ 60F (15C)..................
495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-UF60
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1760 2100 2350
Exhaust Flow - m3/min. (ft.3/min.)...........
56 (1968) 65 (2297) 68 (2418)
Exhaust Temperature - C (F).............483 (908) 456 (853) 434 (813)
6.6 (26)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.1 (28) 7.5 (30)
152 (6)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 62.5 (16.5) 66.2 (17.5) 66.2 (17.5)
Fuel Return - L/hr. (gal./hr.).......... 236.6 (62.5) 234.7 (62.0) 232.8 (61.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......... 299.1 (79.0) 300.9 (79.5) 299.0 (79.0)
2
Fuel Pressure - kPa (lb./in. )............... 172-241 (25-35)
Minimum Line Size - Supply - (in.)............ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.033 (.848)
Minimum Line Size - Return - (in.)............ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)..................
.026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 2.7 (9)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater............Standard
Wattage (Nominal).............. 2500
Voltage - AC, 1P.............. 230 (+5%, -10%)
115 (+5%, -10%)
Optional Voltage - AC, 1P..............
Lube Oil Heater Wattage
150
(Required Option When Ambient is Below 40F (4C)............

Induction Air System


Air Cleaner Type............ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3.5 (14)
Clean Air Cleaner - kPa (in. H20)..........
1.7 (7)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 22 (780) 27 (939) 29 (1020)
54(130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 207-379 (30-55)
In Pan Oil Temperature - C (F)........ 88-104 (190-220)
Oil Pan Capacity - High - L (qt.)....... 30 (32)
Total Oil Capacity with Filter - L (qt.)....
32 (34)

Performance
2 2
BMEP - kg/cm (lb./in. ).............
2252 (327) 1966 (285) 1687 (245)
452 (1484) 540 (1771) 604 (1982)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve................ C131969

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C132034 rev C
16AUG07 DSP
CLARKE
Fire Protection Products
JU4H-NL14
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 32 (30) 34 (32) 36 (34) 38 (36)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 6 (6) 7 (7) 8 (8) 8 (8)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 13 (12) 14 (13) 17 (16) 17 (16)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL14
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)........ 13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F).......... 584 (1083) 568 (1055) 556 (1033) 543 (1010)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr.)....... 11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)
Fuel Return - L/hr. (gal./hr.)....... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2)
Fuel Pressure - kPa (lb./in. 2)......21-41 (3-6)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)..... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).. 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type.....Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).... 241-345 (35-50)
In Pan Oil Temperature - C (F)....... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............ 462 (67) 448 (65) 437 (63) 426 (62)
Piston Speed - m/min. (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m.......... Consult Factory
Power Curve.............. C131088

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131253 revG
11FEB08 DSP
CLARKE
Fire Protection Products
JU4H-NL20 & JU4H-NL22
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-525

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 7 (7) 8 (8) 8 (8) 8 (8)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 14 (13) 16 (15) 17 (16) 18 (17)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 15 (4) 23 (6) 30 (8) 38 (10)
35C (95F) Raw H2O - L/min. (gal/min.).... 23 (6) 30 (8) 38 (10) 45 (12)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL20 & JU4H-NL22
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)......... 11.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)
Exhaust Temperature - C (F)...........549 (1021) 547 (1016) 580 (1076) 591 (1095)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 14.4 (3.8) 20.1 (5.3) 21.2 (5.6) 22.0 (5.8)
Fuel Return - L/hr. (gal./hr.)....... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr. (gal./hr.)....... 44.3 (11.7) 52.3 (13.8) 55.3 (14.6) 58.0 (15.3)
Fuel Pressure - kPa (lb./in.2).......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20).......0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size........... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........241-345 (35-50)
In Pan Oil Temperature - C (F)............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.).............7.5 (8)
Low - L (qt.)... 6.5 (7)
Total Oil Capacity with Filter - L (qt.)........8.5 (9)

Performance
BMEP - kPa (lb./in.2)............ 675 (98) 634 (92) 607 (88) 573 (83)
Piston Speed - m/min. (ft./min.)......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............. Consult Factory
Power Curve.............. C13774 (NL20) & C13775 (NL22)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C13735 revJ
11FEB08 DSP
CLARKE
Fire Protection Products
JU4H-NL24
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - Btu/sec (kW)........ 40 (42) 42 (44) 44 (46) 45 (47)
Engine Radiated Heat (With Blanket) - Btu/sec (kW).... 8 (8) 8 (8) 9 (9) 9 (9)
Engine Radiated Heat (Without Blanket) - Btu/sec (kW). 17 (16) 18 (17) 19 (18) 20 (19)
Heat Exchanger Minimum Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL24
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........ 13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F)......... 580 (1076) 591 (1095) 599 (1110) 607 (1125)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr.)....... 21.2 (5.6) 22.0 (5.8) 22.7 (6.0) 23.5 (6.2)
Fuel Return - L/hr. (gal./hr.).... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.)....... 55.3 (14.6) 58.0 (15.3) 60.2 (15.9) 62.5 (16.5)
2
Fuel Pressure - kPa (lb./in. )..........21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P.........

Induction Air System


Air Cleaner Type..........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )........241-345 (35-50)
In Pan Oil Temperature - C (F)...........104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.)... 8.5 (9)

Performance
BMEP - kPa (lb./in. 2)............ 608 (88) 573 (83) 545 (79) 517 (75)
Piston Speed - m/min. (ft./min.)....... 597 (1958) 661 (2167) 711 (2334) 762 (2501)
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve.............. C131089

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131254 revG
11FEB08 DSP
CLARKE
Fire Protection Products
JU4H-NL34
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 42 (40) 44 (42) 54 (51) 61 (58)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 9 (9) 9(9) 11 (10) 13 (12)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 20 (19) 20 (19) 25 (24) 28 (27)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 25 (7) 25 (7) 32 (9) 33 (9)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 38 (10) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/min. (gal./min)......... 100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2)......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL34
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........17.1 (602) 17.9 (631) 22.3 (788) 25.8 (910)
Exhaust Temperature - C (F)......... 519 (966) 483 (901) 511 (952) 509 (949)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.).......17.0 (4.5) 29.5 (7.8) 34.4 (9.1) 32.6 (8.6)
Fuel Return - L/hr. (gal./hr.)....... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.).......51.1 (13.5) 65.5 (17.3) 71.9 (19.0) 71.6 (18.9)
Fuel Pressure - kPa (lb./in. 2)...... 21-41 (3-6)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........6.6 (231.6) 7.2 (255) 8.6 (305.2) 10.0 (352.9)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in. 2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............ 710 (103) 641 (93) 724 (105) 745 (108)
Piston Speed - m/min (ft./min.)....... 597 (1958) 660 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve............ C131090

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131255 revF
11FEB08 DSP
CLARKE
Fire Protection Products
JU4H-NL50 & JU4H-NL52
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-525

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 12 (11) 15 (14) 14 (13) 14 (13)
Engine Radiated Heat (Without Blanket)- kW (Btu/sec). 26 (25) 31 (29) 30 (28) 30 (28)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 38 (10) 45 (12)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL50 & JU4H-NL52
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........ 16.0 (554) 20.0 (698) 21.0 (752) 24.0 (839)
Exhaust Temperature - C (F)........... 598 (1108) 580 (1076) 537 (998) 519 (966)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 14.4 (3.8) 17.0 (4.5) 18.5 (4.9) 29.9 (7.9)
Fuel Return - L/hr. (gal./hr.)....... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.)....... 44.3 (11.7) 49.2 (13.0) 52.6 (13.9) 65.9 (17.4)
Fuel Pressure - kPa (lb./in.2)...........21-41 (3-6)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)........... .033 (.848)
Minimum Line Size - Return - (in.)...... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)........... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20).......0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P.........

Induction Air System


Air Cleaner Type....... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 5.4 (190) 6.9 (244) 7.8 (277) 8.9 (316)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).....241-345 (35-50)
In Pan Oil Temperature - C (F).......104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......8 (7.5)
Low - L (qt.)7 (6.5)
Total Oil Capacity with Filter - L (qt.)..9 (8.5)

Performance
BMEP - kPa (lb./in.2)............1241 (180) 1228 (178) 1076 (156) 973 (141)
Piston Speed - m/min. (ft./min.)....... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m.......... Consult Factory
Power Curve.............. C13776 (NL50) & C13777 (NL52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C13738 revJ
11FEB08 DSP
CLARKE
Fire Protection Products
JU4H-NL54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 60 (57) 73 (69) 80 (76) 86 (82)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 14 (13) 16 (15) 16 (15) 16 (15)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 29 (28) 33 (31) 35 (33) 35 (33)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 27 (7) 25 (7) 31 (8) 34 (9)
35C (95F) Raw H2O - L/min. (gal/min.).... 30 (8) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-NL54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)........ 21.8 (768) 26.4 (934) 30.0 (1061) 33.8 (1193)
Exhaust Temperature - C (F)......... 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 27.3 (7.2) 39.0 (10.3) 37.9 (10.0) 41.6 (11.0)
Fuel Return - L/hr. (gal./hr.)....... 34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.)....... 61.4 (16.2) 75.0 (19.8) 75.4 (19.9) 80.6 (21.3)
Fuel Pressure - kPa (lb./in. 2)............ 21-41 (3-6)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)....... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type.......Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in. 2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......... 7.5 (8)
Low - L (qt.)... 6.5 (7)
Total Oil Capacity with Filter - L (qt.).... 8.5 (9)

Performance
2
BMEP - kPA (lb./in. )............1034 (150) 1068 (155) 1034 (150) 958 (139)
Piston Speed - m/min (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve.............. C131092

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131257 revH
11FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL09 & JU4R-NL11
INSTALLATION & OPERATION DATA (Continued)
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders............. 4
Bore and Stroke - mm (in.).......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio........... 17.0:1
Valves per cylinder - Intake........... 1
Exhaust........... 1
Combustion System.......... Direct Injection
Engine Type............Rotary, 4 Stroke Cycle
Aspiration.............Naturally Aspirated
Firing Order (CW Rotation)......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise.......Standard
Counter-Clockwise..... Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.........D-525

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)....... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat (With Blanket) - kW (Btu/sec)... 4 (4) 5 (5) 6 (6) 6 (6)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec).. 9 (8) 12 (11) 12 (11) 13 (12)
Radiator Minimum Ventilation Flow - m/min. (ft./min.). 109 (3839) 130 (4607) 144 (5092) 135 (4777)
Thermostat, Start to Open - C (F)..... 86 (187)
Fully Opened - C (F)......... 91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
Coolant Pressure Cap - kPa (lb./in.2)........ 69 (10)
Maximum Engine H20 Temperature - C (F)....... 93 (200)
Minimum Engine H20 Temperature - C (F)........... 71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)........... 12 24
Qty. per Battery Bank......... 1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........285 285
Battery Cable Circuit*, Max Resistance - ohm......... 0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length........ 00 00
121 - 160 m Circuit* Length..........000 000
161 - 200 m Circuit* Length..........0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL09 & JU4R-NL11
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........ 11.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)
Exhaust Temperature - C (F).......... 418 (784) 504 (938) 583 (1082) 573 (1063)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 8.3 (2.2) 10.6 (2.8) 11.7 (3.1) 12.9 (3.4)
Fuel Return - L/hr. (gal./hr.)...... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.).......38.2 (10.1) 42.8 (11.3) 45.8 (12.1) 48.9 (12.9)
Fuel Pressure - kPa (lb./in.2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPa (lb./in.2)............ 766 (111) 761 (111) 697 (101) 645 (93)
Piston Speed - m/min. (ft./min.)......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve.............. C131983 (NL09) & C131984 (NL11)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132009 revD
11FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL13
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 32 (30) 34 (32) 36 (34) 38 (36)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 8 (8) 8 (8)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 16 (15) 16 (15)
Radiator Minimum Ventilation Flow - m3/min.(ft3/min.) 122 (4303) 135 (4777) 145 (5110) 154 (5426)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 15 (16)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL13
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)........ 16 (581) 18 (630)
Exhaust Temperature - C (F)......... 565 (1049) 557 (1034)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr)....... 13.6 (3.6) 14.8 (3.9)
Fuel Return - L/hr. (gal./hr.)....... 37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal/hr.).......51.1 (13.5) 53.8 (14.2)
Fuel Pressure - kPa (lb./in. 2)..... 21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type..... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
2
BMEP - kPA (lb./in. )............ 459 (67) 445 (65)
Piston Speed - m/min. (ft./min.).......711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve............ C131985

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132010 revD
15FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL19 & JU4R-NL21
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-525

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)....... 20 (19) 30 (28) 42 (40) 44 (42)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).. 7 (7) 7 (7) 8 (8) 8 (8)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec).. 14 (13) 15 (14) 16 (15) 17 (16)
Radiator Minimum Ventilation Flow m3/min.(ft3/min.). 109 (3839) 130 (4607) 144 (5092) 135 (4777)
Thermostat, Start to Open - C (F)..... 86 (187)
Fully Opened - C (F)......... 91 (196)
Engine Coolant Capacity - L (qt.).......... 15 (16)
Coolant Pressure Cap - kPa (lb./in.2)........ 69 (10)
Maximum Engine H20 Temperature - C (F).......93 (200)
Minimum Engine H20 Temperature - C (F)........... 71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL19 & JU4R-NL21
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........ 11.0 (379) 12.0 (415) 13.0 (469) 15.0 (531)
Exhaust Temperature - C (F).......... 547 (1017) 546 (1015) 583 (1081) 598 (1108)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 14.4 (3.8) 20.1 (5.3) 21.2 (5.6) 22.0 (5.8)
Fuel Return - L/hr. (gal./hr.)..... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr. (gal./hr.)........ 44.3 (11.7) 52.3 (13.8) 55.3 (14.6) 58.0 (15.3)
Fuel Pressure - kPa (lb./in.2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 4.0 (140) 4.4 (155) 4.7 (166) 5.3 (186)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPa (lb./in.2)............ 656 (95) 621 (90) 567 (82) 549 (80)
Piston Speed - m/min. (ft./min.)......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve.............. C131986 (NL19) & C131987 (NL21)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132011 revD
11FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL23
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Naturally Aspirated
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-545

Cooling System - Radiator 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 42 (40) 44 (42) 46 (44) 47 (45)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 9 (9) 9 (9)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 18 (17) 19 (18)
Radiator Minimum Ventilation Flow - m3/min.(ft3/min.) 122 (4303) 135 (4777) 145 (5110) 154 (5426)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 15 (16)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL23
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........ 16 (581) 18 (630)
Exhaust Temperature - C (F)......... 608 (1126) 620 (1148)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 76 (3)

Fuel System
Fuel Consumption - L/hr. (gal.hr.)....... 22.7 (6.0) 23.5 (6.2)
Fuel Return - L/hr. (gal./hr.).....37.5 (9.9) 39.0 (10.3)
Total Supply Fuel Flow - L/hr. (gal./hr.)...... 60.2 (15.9) 62.5 (16.5)
Fuel Pressure - kPa (lb./in. 2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P.........

Induction Air System


Air Cleaner Type..... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )....... 241-345 (35-50)
In Pan Oil Temperature - C (F)........104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........ 7.5 (8)
Low - L (qt.).. 6.5 (7)
Total Oil Capacity with Filter - L (qt.).... 8.5 (9)

Performance
BMEP - kPa (lb./in. 2)............ 528 (77) 487 (71)
Piston Speed - m/min. (ft./min.)....... 711 (2334) 762 (2501)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve.............. C131988

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132012 revD
15FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL40
INSTALLATION & OPERATION DATA
UK Production

Basic Engine Description


Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.).........106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio..........17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........Open
Installation Drawing......... D-525

Cooling System - Radiator 1760 2100 2350


Engine H2O Heat - kW (Btu/sec.). 42 (40) 50 (47) 50 (47)
Engine Radiated Heat (With Blanket) - kW (Btu/sec.) .. 11 (10) 12 (11) 12 (11)
Engine Radiated Heat (Without Blanket) - kW (Btu/se.. 22 (21) 25 (24) 25 (24)
Radiator Minimum Ventilation Flow m 3/min.(ft 3/min.) 260 (9190) 310 (10944) 348 (12277)
Thermostat, Start to Open - C (F). 86 (187)
Fully Opened - C (F). 91 (196)
Engine Coolant Capacity - L (qt.).. . 17 (18)
Coolant Pressure Cap - kPa (lb./in.2) .. 69 (10)
Maximum Engine H 20 Temperature - C (F).. .. 93 (200)
Minimum Engine H 20 Temperature - C (F).. 71 (160)

Electric System - DC
System Voltage (Nominal)........ 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537........... 4D-640 4D-640
CCA @ -18C (0F)...........640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length.......00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp....... 40 40
Starter Cranking Amps - @ 15C (60F)....... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL40
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350


Exhaust Flow - m3/min. (ft.3/min.)........ 12.0 (435) 15.0 (531) 17.0 (588)
Exhaust Temperature - C (F)........... 582 (1080) 567 (1053) 553 (1028)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 11.4 (3.0) 12.1 (3.2) 11.7 (3.1)
Fuel Return - L/hr. (gal./hr.)..... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0)
Total Supply Fuel Flow - L/hr. (gal./hr.)....... 41.3 (10.9) 44.3 (11.7) 45.8 (12.1)
Fuel Pressure - kPa (lb./in.2)........... 21-41 (3-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 4.8 (170) 6.1 (214) 7.0 (246)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........241-345 (35-50)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......... 7.5 (8)
Low - L (qt.).... 6.5 (7)
Total Oil Capacity with Filter - L (qt.).... 8.5 (9)

Performance
BMEP - kPa (lb./in.2)............1059 (154) 995 (144) 898 (130)
Piston Speed - m/min. (ft./min.).........447 (1467) 533 (1750) 597 (1958)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve.............. C131989

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132013 revD
15FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL49 & JU4R-NL51
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-525

Cooling System - Radiator 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec.)... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat (With Blanket) - kW (Btu/sec.) 12 (11) 14 (13) 13 (12) 13 (12)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec.) 25 (24) 29 (28) 28 (27) 28 (27)
3 3
Radiator Minimum Ventilation Flow - m /min. (ft /min.)260 (9190) 310 (10944) 348 (12277) 320 (11316)
Thermostat, Start to Open - C (F)86 (187)
Fully Opened - C (F)91 (196)
Engine Coolant Capacity - L (qt.).. 17 (18)
Coolant Pressure Cap - kPa (lb./in.2). 69 (10)
Maximum Engine H20 Temperature - C (F).. 93 (200)
Minimum Engine H20 Temperature - C (F)... 160 (71)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL49 & JU4R-NL51
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........ 16.0 (554) 20.0 (698) 21.0 (752) 24.0 (839)
Exhaust Temperature - C (F).......... 594 (1102) 576 (1069) 545 (1013) 530 (987)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 14.4 (3.8) 17.0 (4.5) 18.5 (4.9) 29.9 (7.9)
Fuel Return - L/hr. (gal./hr.)..... 29.9 (7.9) 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr (gal./hr.)...... 44.3 (11.7) 49.2 (13.0) 52.6 (13.9) 65.9 (17.4)
Fuel Pressure - kPa (lb./in.2)............. 21-41 (3-6)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)........ .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type.....Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)......... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 5.4 (190) 6.9 (244) 7.8 (277) 8.9 (316)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPa (lb./in.2)............ 1204 (175) 1159 (168) 992 (144) 834 (121)
Piston Speed - m/min. (ft./min.)......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve.............. C131990 (NL) & C131991 (NL51)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132014 revD
15FEB08 DSP
CLARKE
Fire Protection Products
JU4R-NL53
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.).........106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........4.5 (275)
Compression Ratio..........17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........Open
Installation Drawing......... D-545

Cooling System - Radiator 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 60 (57) 73 (69)
Engine Radiated Heat (with blanket) - kW (Btu/sec).... 15 (14) 15 (14)
Engine Radiated Heat (without blanket) - kW (Btu/sec). 32 (30) 32 (30)
3 3
Radiator Minimum Ventilation Flow - m /min. (ft /min.) 291 (10259) 320 (11315)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 17 (18)
Coolant Pressure Cap - kPa (lb./in.2)...... 69 (10)
Maximum Engine H 20 Temperature - C (F)......93 (200)
Minimum Engine H 20 Temperature - C (F)..... 71 (160)

Electric System - DC
System Voltage (Nominal)........ 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537........... 4D-640 4D-640
CCA @ -18C (0F)...........640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length.......00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp....... 40 40
Starter Cranking Amps - @ 15C (60F)....... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4R-NL53
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600
3 3
Exhaust Flow - m /min. (ft. /min.)........21.8 (768) 26.4 (934)
Exhaust Temperature - C (F).........607 (1125) 597 (1107)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 28.7 (7.4) 39.0 (10.3)
Fuel Return - L/hr. (gal./hr.).... 34.0 (8.0) 36.0 (9.5)
Total Supply Fuel Flow - L/hr. (gal./hr.). 62.7 (15.4) 75.0 (19.8)
Fuel Pressure - kPa (lb./in. 2)......... 21-41 (3-6)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)..... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 2.5 (10)
Clean Air Cleaner - kPa (in. H20)....... 1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 7.3 (259) 8.9 (315)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in. 2)...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
2
BMEP - kPA (lb./in. )............ 957 (139) 869 (126)
Piston Speed - m/min. (ft./min.)....... 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve............. C131992

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132015 revD
DSP 25FEB08
CLARKE
Fire Protection Products
JU6H-NL30 & JU6H-NL32
INSTALLATION & OPERATION DATA
UK Production

Basic Engine Description


Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-526

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 63 (60) 73 (69) 75 (71) 86 (82)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 16 (15) 18 (17) 18 (17) 18 (17)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 33 (31) 38 (36) 38 (36) 38 (36)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 45 (12) 53 (14) 61 (16) 68 (18)
35C (95F) Raw H2O - L/min. (gal/min.).... 57 (15) 64 (17) 72 (19) 79 (21)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL30 & JU6H-NL32
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)........ 21.0 (755) 27.0 (953) 30.0 (1055) 35.0 (1236)
Exhaust Temperature - C (F)........... 551 (1023) 515 (959) 473 (884) 467 (872)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 34.8 (9.2) 40.5 (10.7) 42.4 (11.2) 42.0 (11.1)
Fuel Return - L/hr. (gal./hr.)..... 18.9 (5.0) 22.7 (6.0) 25.7 (6.8) 28.4 (7.5)
Total Supply Fuel Flow - L/hr. (gal./hr.)... 53.7 (14.2) 63.2 (16.7) 68.1 (18.0) 70.4 (18.6)
Fuel Pressure - kPa (lb./in.2)..............21-28 (3-4)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)....... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P......... 230 (+5%, -10%)

Induction Air System


Air Cleaner Type......Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 3 (12)
Clean Air Cleaner - kPa (in. H20)......... 1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 7.8 (275) 10.2 (361) 11.9 (422) 14.1 (498)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....... 276-414 (40-60)
In Pan Oil Temperature - C (F)......... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......... 19 (20)
Low - L (qt.). 17 (18)
Total Oil Capacity with Filter - L (qt.).... 19.5 (21.0)

Performance
BMEP - kPa (lb./in.2)............1048 (152) 1000 (145) 896 (130) 807 (117)
Piston Speed - m/min. (ft./min.).........447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m............ Consult Factory
Power Curve.............. C13782 (NL30) & C13783 (NL32)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C13739 revJ
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL34
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 79 (75) 86 (82) 95 (90) 123 (117)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 18 (17) 18 (17) 18 (17) 20 (19)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 38 (36) 38 (36) 38 (36) 42 (40)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 26 (7) 49 (13) 23 (6) 58 (15)
35C (95F) Raw H2O - L/min. (gal/min.).... 49 (13) 54 (14) 61 (16) 65 (17)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2)......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL34
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........ 30.6 (1081) 35.2 (1243) 38.7 (1365) 45.7 (1614)
Exhaust Temperature - C (F)......... 527 (980) 511 (951) 507 (944) 530 (986)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 31.4 (8.3) 45.0 (11.9) 37.5 (9.9) 40.9 (10.8)
Fuel Return - L/hr. (gal./hr.)..... 25.7 (6.8) 28.4 (7.5) 30.7 (8.1) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.)... 57.1 (15.1) 73.4 (19.4) 68.2 (18.0) 73.5 (19.4)
Fuel Pressure - kPa (lb./in. 2)...... 21-41 (3-6)
Minimum Line Size - Supply - (in.)........... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type......Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 3 (12)
Clean Air Cleaner - kPa (in. H20)....... 1.5 (6)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 11.7 (412.9) 13.7 (483.6) 15.1 (533.4) 17.1 (605.1)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).... 241-345 (35-50)
In Pan Oil Temperature - C (F)....... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)...... 7.5 (8)
Low - L (qt.)... 6.5 (7)
Total Oil Capacity with Filter - L (qt.).... 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............ 896 (130) 807 (117) 752 (109) 772 (112)
Piston Speed - m/min. (ft./min.)........ 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m......... Consult Factory
Power Curve.............. C131094

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131259 revG
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL50 & JU6H-NL52
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-526

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 83 (79) 95 (90) 106 (101) 101 (96)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 21 (20) 24 (23) 24 (23) 24 (23)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 44 (42) 50 (47) 50 (47) 50 (47)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 61 (16) 72 (19) 83 (22) 95 (25)
35C (95F) Raw H2O - L/min. (gal/min.).... 72 (19) 83 (22) 95 (25) 106 (28)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL50 & JU6H-NL52
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)......... 26.0 (924) 34.0 (1204) 38.0 (1359) 42.0 (1496)
Exhaust Temperature - C (F)...........607 (1124) 557 (1034) 525 (977) 512 (953)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 40.5 (10.7) 46.6 (12.3) 48.8 (12.9) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.)...... 22.0 (5.8) 26.1 (6.9) 29.9 (7.9) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.)......62.5 (16.5) 72.7 (19.2) 78.7 (20.8) 70.6 (21.3)
Fuel Pressure - kPa (lb./in.2)............. 21-28 (3-4)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)............ .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size........... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type.... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 3 (12)
Clean Air Cleaner - kPa (in. H20)......... 1.5 (6)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 8.9 (314) 12.3 (433) 14.4 (508) 16.1 (568)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........ 276-414 (40-60)
In Pan Oil Temperature - C (F)...........104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........... 19 (20)
Low - L (qt.).. 17 (18)
Total Oil Capacity with Filter - L (qt.)......19.5 (21.0)

Performance
BMEP - kPa (lb./in.2)............ 1365 (198) 1317 (191) 1179 (171) 1062 (154)
Piston Speed - m/min. (ft./min.)......... 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m........................................... Consult Factory
Power Curve.............. C13778 (NL50) & C13779 (NL52)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C13742 revJ
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
3
Displacement - L (in. )..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 24 (23) 24 (23) 24 (23) 24 (23)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 50 (47) 52 (49) 52 (49) 52 (49)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 42 (11) 49 (13)
35C (95F) Raw H2O - L/min. (gal/min.).... 53 (14) 61 (16) 64 (17) 72 (19)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa) 14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........36.6 (1291) 42.3 (1493) 46.2 (1631) 50.9 (1796)
Exhaust Temperature - C (F).......... 552 (1026) 548 (1019) 548 (1018) 569 (1057)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.).......37.9 (10.0) 43.2 (11.4) 45.1 (11.9) 46.9 (12.4)
Fuel Return - L/hr. (gal./hr.)...25.7 (6.8) 28.4 (7.5) 31.0 (8.2) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.).... 63.6 (16.8) 71.6 (18.9) 76.1 (20.1) 79.5 (21.0)
Fuel Pressure - kPa (lb./in. 2).. 21-41 (3-6)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)..... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20).......... 3 (12)
Clean Air Cleaner - kPa (in. H20)........ 1.5 (6)
Engine Air Flow - m 3/min. (ft. 3/min.)........13.5 (476) 15.7 (555) 17.1 (605) 18.3 (648)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).... 241-345 (35-50)
In Pan Oil Temperature - C (F)....... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)..... 7.5 (8)
Low - L (qt.)... 6.5 (7)
Total Oil Capacity with Filter - L (qt.).... 8.5 (9)

Performance
BMEP - kPa (lb./in. 2)............ 1158 (168) 1073 (156) 993 (144) 924 (134)
Piston Speed - m/min. (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m....... Consult Factory
Power Curve.............. C131095

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131260 revH
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL60 & JU6H-NL62
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in. 3)..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust........... 1
Combustion System..........Direct Injection
Engine Type............In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)......... 1-5-3-6-2-4
Charge Air Cooling Type. Raw Water
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-526

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec)........ 82 (78) 98 (93) 106 (101) 124 (118)
Engine Radiated Heat (With Blanket)- kW (Btu/sec).... 22 (21) 27 (26) 27 (26) 27 (26)
Engine Radiated Heat (Without Blanket)- kW (Btu/sec). 48 (46) 57 (54) 57 (54) 57 (54)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 53 (14) 72 (19) 72 (19) 83 (22)
35C (95F) Raw H2O - L/min. (gal/min.).... 57 (15) 83 (22) 83 (22) 95 (25)
Heat Exchanger Maximum Cooling H2O
2
Max. Inlet Pressure - bar (lb./in. )(kPa)(Standard Plumbing) 5 (72.5) (500)
Optional: U051146 High Pressure Plumbing
Max. Inlet Pressure - bar (lb./in.2) (High Pressure Plumbing).....14 (203)
Flow - L/min (gal./min.)......... 100 (26)
Thermostat, Start to Open - C (F)...... 86 (187)
Fully Opened - C (F)...... 91 (196)
Engine Coolant Capacity - L (qt.).........14 (15)
2
Coolant Pressure Cap - kPa (lb./in. )......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H 20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL60 & JU6H-NL62
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)......... 27.0 (952) 35.0 (1227) 38.0 (1345) 42.0 (1484)
Exhaust Temperature - C (F)...........531 (988) 487 (909) 473 (883) 481 (898)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.4 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 37.9 (10.0) 39.0 (10.3) 42.4 (11.2) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.)....... 20.4 (5.4) 22.0 (5.8) 26.5 (7.0) 33.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.).....58.3 (15.4) 61.0 (16.1) 68.9 (18.2) 71.6 (21.3)
Fuel Pressure - kPa (lb./in.2)...........28-41 (4-6)
Minimum Line Size - Supply - (in.).......... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)........... .033 (.848)
Minimum Line Size - Return - (in.)........... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.)........... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P.........

Induction Air System


Air Cleaner Type..... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 3 (12)
Clean Air Cleaner - kPa (in. H20)......... 1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 10.0 (354) 14.0 (494) 15.2 (538) 16.6 (587)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)..........276-414 (40-60)
In Pan Oil Temperature - C (F)...........104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........... 19 (20)
Low - L (qt.)........ 17 (18)
Total Oil Capacity with Filter - L (qt.)......19.5 (21.0)

Performance
BMEP - kPa (lb./in.2)............1496 (217) 1503 (218) 1345 (195) 1214 (176)
Piston Speed - m/min. (ft./min.).........447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m......... Consult Factory
Power Curve.............. C13780 (NL60) & C13781 (NL62)

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C13743 revJ
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL74
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat (With Blanket) - kW (Btu/sec).... 27 (26) 28 (27) 29 (28) 31 (29)
Engine Radiated Heat (Without Blanket) - kW (Btu/sec). 58 (55) 59 (56) 62 (59) 66 (63)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 45 (12) 50 (13) 53 (14) 69 (18)
35C (95F) Raw H2O - L/min. (gal/min.).... 50 (13) 61 (16) 63 (17) 76 (20)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)(Standard Plumbing) 5 (72.5) (500)
Optional: U051146 High Pressure Plumbing
Max. Inlet Pressure - bar (lb./in.2).(High Pressure Plumbing )... 14 (203)
Flow - L/min (gal./min.)......... 100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2)......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL74
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........ 39.6 (1398) 45.0 (1588) 50.2 (1773) 55.3 (1952)
Exhaust Temperature - C (F)......... 490 (914) 492 (918) 518 (965) 556 (1032)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 34.4 (9.1) 37.6 (9.9) 41.3 (10.9) 45.9 (12.1)
Fuel Return - L/hr. (gal./hr.)... 21.1 (5.6) 23.2 (6.1) 25.6 (6.8) 26.7 (7.1)
Total Supply Fuel Flow - L/hr. (gal./hr.)... 55.5 (14.7) 60.8 (16.0) 66.9 (17.7) 72.6 (19.2)
Fuel Pressure - kPa (lb./in. 2)...... 21-41 (3-6)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)....... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.). 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type...Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20)......... 3 (12)
Clean Air Cleaner - kPa (in. H20)....... 1.5 (6)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 15.8 (558) 17.8 (627) 19.2 (678) 20.3 (718)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. ).241-345 (35-50)
In Pan Oil Temperature - C (F)...... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)..... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.)..... 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............1365 (198) 1255 (182) 1220 (177) 1206 (175)
Piston Speed - m/min. (ft./min.)........ 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m......... Consult Factory
Power Curve.............. C131096

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131383 revH
15FEB08 DSP
CLARKE
Fire Protection Products
JU6H-NL84
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)......... 106 (4.19) x 127 (5.0)
Displacement - L (in.3)..........6.8 (415)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-538

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec)........ 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat (With blanket) - kW (Btu/sec).... 27 (25) 28 (27) 29 (28) 31 (29)
Engine Radiated Heat (Without blanket) - kW (Btu/sec). 58 (55) 59 (56) 62 (59) 66 (63)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 45 (12) 50 (13) 53 (14) 69 (18)
35C (95F) Raw H2O - L/min. (gal/min.).... 50 (13) 61 (16) 63 (17) 76 (20)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)(Standard Plumbing) 5 (72.5) (500)
Optional: U051146 High Pressure Plumbing
Max. Inlet Pressure - bar (lb./in.2)(High Pressure Plumbing ).... 14 (203)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2)......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12 24
Qty. per Battery Bank.........1 2
SAE size per J537...........4D-640 4D-640
CCA @ -18C (0F)........... 640 640
Reserve Capacity - Minutes........ 285 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00 00
121 - 160 m Circuit* Length.......... 000 000
161 - 200 m Circuit* Length.......... 0000 0000
Charging Alternator Output - Amp.......40 40
Starter Cranking Amps - @ 15C (60F).......380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-NL84
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m 3/min. (ft. 3/min.)........39.6 (1398) 45.0 (1588) 50.2 (1773) 55.3 (1952)
Exhaust Temperature - C (F).......... 490 (914) 492 (918) 518 (965) 556 (1032)
Maximum Allowable Back Pressure - kPa (in. H 20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.).......42.0 (11.1) 45.8 (12.1) 50.3 (13.3) 56.0 (14.8)
Fuel Return - L/hr. (gal./hr.)...25.7 (6.8) 28.4 (7.5) 31.0 (8.2) 32.6 (8.6)
Total Supply Fuel Flow - L/hr. (gal./hr.)...67.7 (17.9) 74.2 (19.6) 81.3 (21.5) 88.6 (23.4)
2
Fuel Pressure - kPa (lb./in. ).21-41 (3-6)
Minimum Line Size - Supply - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)....... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).. 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)............ 1500
Voltage - AC, 1P............ 115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20).......... 3 (12)
Clean Air Cleaner - kPa (in. H20)........ 1.5 (6)
Engine Air Flow - m 3/min. (ft. 3/min.)........15.8 (558) 17.8 (627) 19.2 (678) 20.3 (718)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...241-345 (35-50)
In Pan Oil Temperature - C (F)......104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......... 7.5 (8)
Low - L (qt.).. 6.5 (7)
Total Oil Capacity with Filter - L (qt.). 8.5 (9)

Performance
BMEP - kPA (lb./in. 2)............1365 (198) 1255 (182) 1220 (177) 1206 (175)
Piston Speed - m/min. (ft./min.)......... 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m........ Consult Factory
Power Curve.............. C131096

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131261 revH
25FEB08 DSP
CLARKE
Fire Protection Products
JW6H-NL30
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer. John Deere Co.
Ignition Type............. Compression (Diesel)
Number of Cylinders........... 6
Bore and Stroke - mm (in.)........... 116 (4.56) x 129 (5.06)
Displacement - L (in. 3)............ 8.1 (496)
Compression Ratio.......... 16.5:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System........... Direct Injection
Engine Type............. In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)........... 1-5-3-6-2-4
Charge Air Cooling Type..........Jacket Water Cooled
Rotation (Viewed from Front) - Clockwise.......Standard
Counter-Clockwise.....
Not Available
Engine Crankcase Vent System.........Open
Installation Drawing......... UD-119

Cooling System 1470 1760 2100 2350


Engine H 2O Heat -kW (Btu/sec.)......... 110 (104) 118 (112) 123 (117) 119 (113)
Engine Radiated Heat (With Blanket) - Kw (Btu/sec.)... 25 (24) 30 (28) 31 (29) 31 (29)
Engine Radiated Heat (Without Blanket) - Kw (Btu/sec.). 52 (49) 63 (60) 66 (63) 66 (63)
Heat Exchanger Minimium Flow
60F (15C) Raw H 2O - L/Min. (gal/min.)..... 42 (11) 53 (14) 61 (16) 79 (21)
95F (35C) Raw H 2O - L/Min. (gal/min.)..... 68 (18) 83 (22) 95 (25) 117 (31)
Heat Exchanger Maximum Cooling H 2O
Max. Inlet Pressure - bar (lb./in. 2)(kPa)14 (203) (1400)
Flow - L/Min. (Gal./min.)........302 (80)
Thermostat, Start to Open - C (F)......82 (180)
Fully Opened - C(F)........ 94 (202)
Engine Coolant Capacity - L (qt.)......... 21 (22)
Coolant Pressure Cap - kPa (lb./in. 2)...... 69 (10)
Maximum Engine H 20 Temperature - C (F)...... 93 (200)
Minimum Engine H 20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)......... 12
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12
Qty. per Battery Bank.........1
SAE size per J537...........8D-900
CCA @ -18C (0F)...........900
Reserve Capacity - Minutes........ 430
Battery Cable Circuit*, Max Resistance - ohm..........0.0017
Battery Cable Minimum Size
0 -120 m Circuit* Length......... 00
121 - 160 m Circuit* Length..........000
161 - 200 m Circuit* Length..........0000
Charging Alternator Output - Amp.......40
Starter Cranking Amps - @ 15C (60C).......495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-NL30
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1470 1760 2100 2350
Exhaust Flow - m 3/min. (ft. 3/min.)........31 (1107) 40 (1404) 47 (1644) 54 (1908)
Exhaust Temperature - C (F)......... 518 (990) 435 (840) 385 (750) 392 (737)
Maximum Allowable Back Pressure - kPa (in. H 20)... 4.7 (19) 6.6 (26) 7.1 (28) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5.0) 127 (5.0) 127 (5.0) 127 (5.0)

Fuel System
Fuel Consumption - L/hr (gal./hr.)....... 49.2 (13) 53.0 (14.0) 56.8 (15.0) 60.6 (16.0)
Fuel Return - L/hr. (gal./hr.).... 238.5 (63) 234.9 (62.0) 230.9 (61.0) 227.1 (60.0)
Total Supply Fuel Flow - L/hr. (gal./hr.).... 287.7 (76) 287.9 (76.0) 287.7 (76.3) 287.7 (76.0)
Fuel Pressure - kPa (lb./in. 2)...... 172-241 (25-35)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in).......... .033 (.848)
Minimum Line Size - Return - (in.)... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. m H 20 (in. H 20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 2.7 (9)
Fuel Filter Micron Size.......... 5

Heater System
Jacket Water Heater............Standard
Wattage (Nominal)............ 2500
Voltage - AC, 1P............230 (+5%, -10%)
Optional Voltage - AC, 1P.........115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C) 150

Induction Air System


Air Cleaner Type..... Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).......... 3.5 (14)
Clean Air Cleaner - Kpa (in. H20)....... 1.7 (7)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 12 (410) 16 (580) 21 (730) 24 (856)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in. 2)...... 207-379 (30-55)
In Pan Oil Temperature - C (F).........88-104 (190-220)
Oil Pan Capacity - High - L (qt.)........ 30 (32)
Total Oil Capacity with Filter - L (qt.)...... 32 (34)

Performance
BMEP -kPa (lb./in. 2)..........1648 (239) 1655 (240) 1441 (209) 1289 (187)
Piston Speed - m/min. (ft./min.)......... 378 (1240) 452 (1484) 540 (1771) 604 (1982)
Mechanical Noise - dB(A) @ 1M... C13917
Power Curve............ CDDA - W064 - 01

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13997 Rev F
11FEB08 DSP
CLARKE
Fire Protection Products
JW6H-NL40
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer............ John Deere Co.
Ignition Type.............. Compression (Diesel)
Number of Cylinders............6
Bore and Stroke - mm (in.)........... 116 (4.56) x 129 (5.06)
Displacement - L (in.3)............ 8.1 (496)
Compression Ratio............ 15.7:1
Valves per cylinder - Intake........... 1
Exhaust........... 1
Combustion System............Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)........... 1-5-3-6-2-4
Charge Air Cooling Type........... Raw Water Cooled
Rotation (Viewed from Front) - Clockwise........ Standard
Counter-Clockwise......Not Available
Engine Crankcase Vent System.......... Open
Installation Drawing........... UD-119

Cooling System 1470 1760 2100 2350


Engine H2O Heat -kW (Btu/sec.)......... 155 (147) 162 (154) 171 (162) 164 (156)
Engine Radiated Heat (With Blanket) - Kw (Btu/sec.)... 27 (26) 32 (30) 34 (32) 34 (32)
Engine Radiated Heat (Without Blanket) - Kw (Btu/sec.). 57 (54) 69 (65) 72 (68) 72 (68)
Heat Exchanger Minimium Flow
60F (15C) Raw H 2O - L/Min. (gal/min.)..... 45 (12) 57 (15) 64 (17) 79 (21)
95F (35C) Raw H 2O - L/Min. (gal/min.)..... 72 (19) 87 (23) 110 (29) 117 (31)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)(Standard Plumbing) 5 (72.5) (500)
Optional: U051147 High Pressure Plumbing
Max. Inlet Pressure - bar (lb./in.2)(High Pressure Plumbing).....
14 (203)
Flow - L/min (Gal./min.).......... 302 (80)
Thermostat, Start to Open - C (F)...... 82 (180)
Fully Opened - C (F)........94 (202)
Engine Coolant Capacity - L (qt.)......... 22 (23)
Coolant Pressure Cap - kPa (lb./in.2)...... 69 (10)
Maximum Engine H20 Temperature - C (F)........ 93 (200)
Minimum Engine H20 Temperature - C (F)...... 71 (160)

Electric System - DC
System Voltage (Nominal).........12
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)............ 12
Qty. per Battery Bank.......... 1
SAE size per J537........... 8D-900
CCA @ -18C (0F)...........900
Reserve Capacity - Minutes.......... 430
Battery Cable Circuit*, Max Resistance - ohm.......... 0.0017
Battery Cable Minimum Size
0 -120 m Circuit* Length.........00
121 - 160 m Circuit* Length..........000
161 - 200 m Circuit* Length..........0000
Charging Alternator Output - Amp....... 40
Starter Cranking Amps - @ 15C (60C)........ 495
*Positive and Negative Cables Combined Length
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. Continued
CLARKE
Fire Protection Products
JW6H-NL40
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1470 1760 2100 2350
Exhaust Flow - m 3/min. (ft. 3/min.)........ 36 (1276) 43 (1506) 49 (1740) 58 (2058)
Exhaust Temperature - C (F)......... 540 (1030) 443 (855) 396 (770) 392 (738)
Maximum Allowable Back Pressure - kPa (in. H 20)... 4.7 (19.0) 6.6 (26.0) 7.1 (28.0) 7.5 (30.0)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 127 (5.0) 127 (5.0) 127 (5.0) 127 (5.0)

Fuel System
Fuel Consumption - L/hr. (Gal./hr.)........ 49 (13) 51 (13.5) 53 (14) 55 (14.5)
Fuel Return - L/hr. (Gal./hr.).... 238 (63) 237 (62.5) 235 (62) 233 (61.5)
Total Supply Fuel Flow - L/hr. (Gal./hr.).... 287 (76) 288 (76) 288 (76) 288 (76)
Fuel Pressure - lb./in. 2 (kPa)...... 172-241 (25-35)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H 20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - m (ft.)..... 2.7 (9)
Fuel Filter Micron Size........... 5

Heater System
Jacket Water Heater............ Standard
Wattage (Nominal).............2500
Voltage - AC, 1P.............230 (+5%, -10%)
Optional Voltage - AC, 1P.......... 115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C) 150

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20).......... 3.2 (14)
Clean Air Cleaner - kPa (in. H20)........ 1.7 (7)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 13 (460) 17 (615) 22 (760) 26 (923)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***... 54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in. 2)........ 207-379 (30-55)
In Pan Oil Temperature - C (F).......... 88-104 (190-220)
Oil Pan Capacity - High - L (qt.)......... 30 (32)
Total Oil Capacity with Filter - L (qt.)........ 32 (34)

Performance
BMEP - kPa (lb./in. 2)........... 1800 (261) 1813 (263) 1572 (228) 1406 (204)
Piston Speed - m/min. (ft./min.)........ 378 (1240) 452 (1484) 540 (1771) 604 (1982)
Mechanical Noise - dB(A) @ 1M... C13918
Power Curve............ CDDA - W064 - 02
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13998 Rev G
15FEB08 DSP
CLARKE
Fire Protection Products
JW6H-NL50
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer...........John Deere Co.
Ignition Type..............Compression (Diesel)
Number of Cylinders............6
Bore and Stroke - mm (in.)........... 116 (4.56) x 129 (5.06)
Displacement - L (in. 3)............8.1 (496)
Compression Ratio............ 15.7:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System............Direct Injection
Engine Type.............In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)........... 1-5-3-6-2-4
Charge Air Cooling Type.......... Raw Water Cooled
Rotation (Viewed from Front) - Clockwise........ Standard
Counter-Clockwise...... Not Available
Engine Crankcase Vent System.......... Open
Installation Drawing........... UD-119

Cooling System 1760 2100 2350


Engine H2O Heat -kW (Btu/sec.)......... 138 (131) 179 (170) 207 (196)
Engine Radiated Heat (With Blanket)- Kw (Btu/sec.)... 34 (32) 38 (36) 39 (37)
Engine Radiated Heat (Without Blanket)- Kw (Btu/sec.). 72 (68) 81 (77) 84 (80)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - L/Min. (gal/min.)..... 132 (35) 159 (42) 167 (44)
95F (35C) Raw H2O - L/Min. (gal/min.)..... 146 (39) 170 (45) 178 (47)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in. 2)(kPa)(Standard Plumbing) 5 (72.5) (500)
Optional: U051148 High Pressure Plumbing
Max. Inlet Pressure - bar (lb./in.2) (High Pressure Plumbing)..... 14 (203)
Flow - L/min (gal./min.).........302 (80)
Thermostat, Start to Open - C (F)......82 (180)
Fully Opened - C (F)........ 94 (202)
Engine Coolant Capacity - L (qt.)......... 22 (23)
Coolant Pressure Cap - kPa (lb./in. 2)...... 69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
71 (160)
Minimum Engine H 20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12
Qty. per Battery Bank.........1
SAE size per J537........... 8D-900
CCA @ -18C (0F)...........900
Reserve Capacity - Minutes........ 430
Battery Cable Circuit*, Max Resistance - ohm.......... 0.0017
Battery Cable Minimum Size
0 -120 m Circuit* Length......... 00
121 - 160 m Circuit* Length..........000
161 - 200 m Circuit* Length..........0000
Charging Alternator Output - Amp....... 40
Starter Cranking Amps - @ 15C (60C).......495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-NL50
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1760 2100 2350
Exhaust Flow - m 3/min. (ft. 3/min.)........ 46 (1642) 59 (2066) 66 (2345)
Exhaust Temperature - C (F)......... 463 (866) 420 (788) 403 (806)
Maximum Allowable Back Pressure - kPa (in. H 20)... 6.6 (26) 7.1 (28) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 152 (6)

Fuel System
Fuel Consumption - L/hr. (Gal./hr.)........ 53 (14) 61 (16) 64 (17)
Fuel Return - L/hr. (Gal./hr.).... 237 (62.5) 234 (62) 233 (61.5)
Total Supply Fuel Flow - L/hr. (Gal./hr.)....290 (76.5) 295 (78) 297 (78.5)
Fuel Pressure - lb./in.2 (kPa)......172-241 (25-35)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H 20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - m (ft.).... 2.7 (9)
Fuel Filter Micron Size........... 5

Heater System
Jacket Water Heater............ Standard
Wattage (Nominal)............. 2500
Voltage - AC, 1P............. 230 (+5%, -10%)
Optional Voltage - AC, 1P..........115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)150

Induction Air System


Air Cleaner Type........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H 20).......... 3.5 (14)
Clean Air Cleaner - kPa (in. H20)........ 1.7 (7)
Engine Air Flow - m 3/min. (ft. 3/min.)........ 20 (692) 25 (881) 28 (992)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 207-379 (30-55)
In Pan Oil Temperature - C (F)..........88-104 (190-220)
Oil Pan Capacity - High - L (qt.)......... 30 (32)
Total Oil Capacity with Filter - L (qt.)...... 32 (34)

Performance
2
BMEP - kPa (lb./in. )...........1877 (272) 1782 (259 1640 (238)
Piston Speed - m/min. (ft./min.)........452 (1484) 540 (1771) 604 (1982)
Mechanical Noise - dB(A) @ 1M... C13919
Power Curve............ C13542

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C13999 Rev G
15FEB08 DSP
CLARKE
Fire Protection Products
JW6H-NL60
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer...........John Deere Co.
Ignition Type..............Compression (Diesel)
Number of Cylinders............6
Bore and Stroke - mm (in.)........... 116 (4.56) x 129 (5.06)
3
Displacement - L (in. )............8.1 (496)
Compression Ratio............ 15.7:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System............Direct Injection
Engine Type.............In-Line, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation)........... 1-5-3-6-2-4
Charge Air Cooling Type.......... Raw Water Cooled
Rotation (Viewed from Front) - Clockwise........ Standard
Counter-Clockwise...... Not Available
Engine Crankcase Vent System.......... Open
Installation Drawing........... UD-119

Cooling System 1470 1760 2100 2350


Engine H2O Heat -kW (Btu/sec.).........152 (161) 159 (168) 197 (208) 206 (217)
Engine Radiated Heat (With Blanket) - Kw (Btu/sec.)... 40 (38) 42 (40) 40 (38)
Engine Radiated Heat (Without Blanket) - Kw (Btu/sec.). 86 (82) 90 (85) 86 (82)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - L/Min. (gal/min.)..... 123 (32) 155 (41) 167 (44) 167 (44)
95F (35C) Raw H2O - L/Min. (gal/min.)..... 141 (37) 170 (45) 178 (47) 178 (47)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in. 2)(kPa)(Standard Plumbing) 5 (72.5 ) (500)
Optional: U051148 High Pressure Plumbing
14 (203)
Max. Inlet Pressure - bar (lb./in.2) (High Pressure Plumbing).....
Flow - L/min (gal./min.).........302 (80)
Thermostat, Start to Open - C (F)......82 (180)
Fully Opened - C (F)........ 94 (202)
Engine Coolant Capacity - L (qt.)......... 22 (23)
Coolant Pressure Cap - kPa (lb./in. 2)...... 69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
71 (160)
Minimum Engine H 20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12
Qty. per Battery Bank.........1
SAE size per J537........... 8D-900
CCA @ -18C (0F)...........900
Reserve Capacity - Minutes........ 430
Battery Cable Circuit*, Max Resistance - ohm.......... 0.0017
Battery Cable Minimum Size
0 -120 m Circuit* Length......... 00
121 - 160 m Circuit* Length..........000
161 - 200 m Circuit* Length..........0000
Charging Alternator Output - Amp....... 40
Starter Cranking Amps - @ 15C (60C).......495
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JW6H-NL60
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 1470 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)........ 47 (1653) 56 (1968) 65 (2297) 68 (2418)
Exhaust Temperature - C (F).........589 (1100) 483 (902) 456 (853) 434 (813)
Maximum Allowable Back Pressure - kPa (in. H20)... 4.7 (19) 6.6 (26) 7.1 (28) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 152 (6) 152 (6) 152 (6) 152 (6)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)........ 60 (16) 62 (16.5) 66 (17.5) 66 (17.5)
Fuel Return - L/hr. (gal./hr.).... 239 (63) 237 (62.5) 235 (62) 233 (61.5)
Total Supply Fuel Flow - L/hr. (gal./hr.).... 299 (79) 299 (79) 301 (79.5) 299 (79)
2
Fuel Pressure - lb./in. (kPa)......25-35 (172-241)
Minimum Line Size - Supply - (in.)...... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
Minimum Line Size - Return - (in.)... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - m (ft.).... 2.7 (9)
Fuel Filter Micron Size........... 5

Heater System
Jacket Water Heater............Standard
Wattage (Nominal).............2500
Voltage - AC, 1P.............230 (+5%, -10%)
Optional Voltage - AC, 1P..........115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C)
150 150

Induction Air System


Air Cleaner Type........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20).......... 3.5 (14)
Clean Air Cleaner - kPa (in. H20)........ 1.7 (7)
Engine Air Flow - m3/min. (ft.3/min.)........ 17 (600) 22 (780) 27 (939) 29 (1020)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 207-379 (30-55)
In Pan Oil Temperature - C (F)..........88-104 (190-220)
Oil Pan Capacity - High - L (qt.)......... 30 (32)
Total Oil Capacity with Filter - L (qt.)...... 32 (34)

Performance
BMEP - kPa (lb./in.2)...........2229 (324) 2252 (327) 1966 (285) 1687 (245)
Piston Speed - m/min. (ft./min.)........378 (1240) 452 (1484) 540 (1771) 604 (1982)
Mechanical Noise - dB(A) @ 1M... C13920
Power Curve............ C13543
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)

C131000 RevH
15FEB08 DSP
CLARKE
Fire Protection Products
JU4H-LP20
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 275 (4.5)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-124

Cooling System - 3 Pass 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 20 (19) 30 (28) 42 (40)
Engine Radiated Heat - kW (Btu/sec)......... 14.0 (13.0) 16.0 (15.0) 17.0 (16.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
15 (4) 23 (6) 30 (8)
35C (95F) Raw H2O - L/min. (gal/min.)......
23 (6) 30 (8) 38 (10)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).............
10 (145) (1000)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-LP20
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)...........
11.0 (379) 12.0 (415) 13.0 (469)
Exhaust Temperature - C (F)............. 549 (1021) 547 (1016) 580 (1076)
7.5 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
76 (3)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 14.4 (3.8) 20.1 (5.3) 21.2 (5.6)
30.0 (7.9) 32.2 (8.5) 34.1 (9.0)
Fuel Return - L/hr. (gal./hr.)............
44.4 (11.7) 52.3 (13.8) 55.3 (14.6)
Total Supply Fuel Flow - L/hr (gal./hr.)............
2
21-41 (3-6)
Fuel Pressure - kPa (lb./in. )..............
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)...... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 4.0 (140) 4.4 (155) 4.7 (166)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)............
241-345 (35-50)
In Pan Oil Temperature - C (F).............
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......v...
7.5 (8)
Low - L (qt.)......
6.5 (7)
Total Oil Capacity with Filter - L (qt.)........
8.5 (9)

Performance
BMEP - kg/cm2 (lb./in. 2).............
6.9 (98) 6.5 (92) 6.1 (88)
447 (1467) 533 (1750) 597 (1958)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131006

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131244 revC
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-LP24
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Naturally Aspirated
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-124

Cooling System - 3 Pass 2350 2600 2800 2960


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 44 (42) 46 (44) 47 (45)
Engine Radiated Heat - kW (Btu/sec)......... 17 (16) 18 (17) 19 (18) 20 (19)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 37 (10) 40 (11)
35C (95F) Raw H2O - L/min. (gal/min.)......
38 (10) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
10 (145) (1000)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-LP24
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 2350 2600 2800 2960
3 3
Exhaust Flow - m /min. (ft. /min.)...........
13 (469) 15 (531) 16 (581) 18 (630)
Exhaust Temperature - C (F).............580 (1076) 591 (1095) 599 (1110) 607 (1125)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
76 (3.0)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 21.2 (5.6) 22.0 (5.8) 22.6 (6.0) 23.3 (6.2)
Fuel Return - L/hr. (gal./hr.)............
34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
55.3 (14.6) 58.0 (15.3) 60.1 (15.9) 62.3 (16.5)
Total Supply Fuel Flow - L/hr (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )............
241-345 (35-50)
In Pan Oil Temperature - C (F).............
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).............
7.5 (8)
Low - L (qt.)......
6.5 (7)
Total Oil Capacity with Filter - L (qt.)........
8.5 (9)

Performance
BMEP - kPa (lb./in. 2).............
608 (88) 573 (83) 545 (79) 517 (75)
Piston Speed - ft./min. (m/min.)..........
597 (1958) 661 (2167) 711 (2334) 762 (2501)
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131089

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131252 revC
ACH 30AUG07
CLARKE
Fire Protection Products
JU4H-LP50 (14 Bar Cooling System)
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type.....................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)......... 4.19(106) x 5.00(127)
3
Displacement - L (in. )..........4.5 (275)
Compression Ratio.......... 17.0:1
Valves per cylinder - Intake...........1
Exhaust...........1
Combustion System..........Direct Injection
Engine Type............ Rotary, 4 Stroke Cycle
Aspiration............. Turbocharged
Firing Order (CW Rotation).........1-3-4-2
Rotation (Viewed from Front) - Clockwise....... Standard
Counter-Clockwise.....Not Available
Engine Crankcase Vent System........ Open
Installation Drawing......... D-124

Cooling System - 3 Pass 1760 2100 2350


Engine H2O Heat - kW (Btu/sec)........ 42 (40) 50 (47) 50 (47)
Engine Radiated Heat - kW (Btu/sec)....... 26.0 (25.0) 31.0 (29.0) 30.0 (28.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.).... 30 (8) 34 (9) 38 (10)
35C (95F) Raw H2O - L/min. (gal/min.).... 38 (10) 42 (11) 45 (12)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)........... 14 (203) (1400)
Flow - L/min. (gal./min)......... 100 (26)
Thermostat, Start to Open - C (F)......86 (187)
Fully Opened - C (F)......91 (196)
Engine Coolant Capacity - L (qt.)......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2)......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....71 (160)

Electric System - DC
System Voltage (Nominal)........12
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)...........12
Qty. per Battery Bank.........1
SAE size per J537...........4D-640
CCA @ -18C (0F)........... 640
Reserve Capacity - Minutes........ 285
Battery Cable Circuit*, Max Resistance - ohm.........0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length....... 00
121 - 160 m Circuit* Length.......... 000
161 - 200 m Circuit* Length.......... 0000
Charging Alternator Output - Amp.......40
Starter Cranking Amps - @ 15C (60F).......380
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-LP50 (14 Bar Cooling System)
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)........16.0 (554) 20.0 (698) 21.0 (752)
Exhaust Temperature - C (F)........ 598 (1108) 580 (1076) 537 (998)
Maximum Allowable Back Pressure - kPa (in. H20)... 30 (7.4)
Minimum Exhaust Pipe Dia. - mm (in.)**........ 102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)....... 14.4 (3.8) 17.0 (4.5) 18.5 (4.9)
Fuel Return - L/hr. (gal./hr)....... 30.0 (7.9) 32.2 (8.5) 34.1 (9.0)
Total Supply Fuel Flow - L/hr (gal./hr.)....... 44.4 (11.7) 49.2 (13.0) 52.6 (13.9)
2
Fuel Pressure - kPa (lb./in. ).............. 21-41 (3-6)
Minimum Line Size - Supply - mm (in.)**.......50 Sch. 40 - Black
Minimum Line Size - Return - mm (in.)**......37 Sch. 40 - Black
Maximum Allowable Fuel Pump Suction
With Clean Filter - mH20 (in. H20)....... 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m(ft)... 1.4 (4.5)
Fuel Filter Micron Size.......... 2

Heater System
Jacket Water Heater
Wattage (Nominal)........... 1500
Voltage - AC, 1P............115 (+5%, -10%)
Optional Voltage - AC, 1P.........230 (+5%, -10%)

Induction Air System


Air Cleaner Type........ Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - mm H20 (in. H20)........ 5 (127)
Clean Air Cleaner - mm H20 (in. H20)...... 1 (25)
Engine Air Flow - m3/min. (ft.3/min.)........ 5.4 (190) 6.9 (244) 7.8 (277)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***. 54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt)....... 8 (7.5)
Low - L (qt.) 7 (6.5)
Total Oil Capacity with Filter - L (qt.).. 9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2).......... 12.7 (180) 12.5 (178) 11.0 (156)
Piston Speed - m/min. (ft/min.).......447 (1467) 533 (1750) 597 (1958)
Mechanical Noise - dB(A) @ 1m........... Consult Factory
Power Curve............ C131008

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131245 revA
MJD Jan05
CLARKE
Fire Protection Products
JU4H-LP54
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-124

Cooling System - 3 Pass 2350 2600 2800 2960


Engine H2O Heat - kW (Btu/sec).......... 60 (57) 73 (69) 80 (76) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 29.1 (27.6) 33.3 (31.6) 34.6 (32.8) 34.6 (32.8)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
27 (7) 25 (7) 31 (8) 34 (9)
35C (95F) Raw H2O - L/min. (gal/min.)......
30 (8) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..............
10 (145) (1000)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-LP54
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 2350 2600 2800 2960
3 3
Exhaust Flow - m /min. (ft. /min.)...........
21.8 (768) 26.4 (934) 30.0 (1061) 33.8 (1193)
Exhaust Temperature - C (F)............. 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
102 (4.0)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 27.3 (7.2) 39.0 (10.3) 37.9 (10.0) 41.6 (11.0)
34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Fuel Return - L/hr. (gal./hr.)............
61.4 (16.2) 75.0 (19.8) 75.4 (19.9) 80.6 (21.3)
Total Supply Fuel Flow - L/hr (gal./hr.)............
2
21-41 (3-6)
Fuel Pressure - kPa (lb./in. )..............
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type.............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )............
241-345 (35-50)
In Pan Oil Temperature - C (F).............
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).............
7.5 (8)
Low - L (qt.)......
6.5 (7)
Total Oil Capacity with Filter - L (qt.)........
8.5 (9)

Performance
2 2
BMEP - kg/cm (lb./in. ).............
150 (10.5) 155 (10.9) 150 (10.5) 139 (9.8)
Piston Speed - m/min. (ft./min.)..........
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131092

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131249 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-LP50
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-125

Cooling System - 3 Pass 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 83 (79) 95 (90) 106 (101)
Engine Radiated Heat - kW (Btu/sec)......... 59.0 (56.0) 67.0 (64.0) 67.0 (64.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
61 (16) 72 (19) 83 (22)
35C (95F) Raw H2O - L/min. (gal/min.)......
72 (19) 83 (22) 95 (25)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa).............
10 (145) (1000)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-LP50
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)...........
26.0 (924) 34.0 (1204) 38.0 (1359)
Exhaust Temperature - C (F).............607 (1124) 557 (1034) 525 (977)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 41.0 (10.8) 47.0 (12.4) 49.0 (12.9)
25.1 (6.6) 28.8 (7.6)
Fuel Return - L/hr. (gal./hr.)............ 30.0 (7.9)
66.1 (17.4) 75.8 (20.0) 79.0 (20.8)
Total Supply Fuel Flow - L/hr (gal./hr.)............
2
21-28 (3-4)
Fuel Pressure - kPa (lb./in. )..............
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type......................
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
3 (12)
Dirty Air Cleaner - kPa (in. H20)...........
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 8.9 (314) 12.3 (433) 14.4 (508)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)....................
276-414 (40-60)
In Pan Oil Temperature - C (F)......................
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).....................
19 (20)
Low - L (qt.)..............
17 (18)
Total Oil Capacity with Filter - L (qt.)................
19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in. 2).............
198 (13.9) 191 (13.4) 171 (12.0)
Piston Speed - m/min. (ft./min.)..........
447 (1467) 533 (1750) 597 (1958)
Mechanical Noise - dB(A) @ 1m.........................
Consult Factory
Power Curve................ C131012

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131246 revC
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-LP54
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-125

Cooling System - 3 Pass 2350 2600 2800 2960


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 50.2 (47.6) 51.5 (48.9) 51.5 (48.9) 51.5 (48.9)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 42 (11) 49 (13)
35C (95F) Raw H2O - L/min. (gal/min.)......
53 (14) 61 (16) 64 (17) 72 (19)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..............
10 (145) (1000)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-LP54
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 2350 2600 2800 2960
3 3
Exhaust Flow - m /min. (ft. /min.)...........
36.6 (1291) 42.3 (1493) 46.2 (1631) 50.9 (1796)
Exhaust Temperature - C (F).............552 (1026) 548 (1019) 548 (1018) 569 (1057)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 37.9 (10.0) 43.2 (11.4) 45.0 (11.9) 46.9 (12.4)
Fuel Return - L/hr. (gal./hr.)............
25.7 (6.8) 28.3 (7.5) 31.2 (8.2) 32.6 (8.6)
63.6 (16.8) 71.5 (18.9) 76.2 (20.1) 79.5 (21.0)
Total Supply Fuel Flow - L/hr (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type......................
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 13.5 (476) 15.7 (555) 17.1 (605) 18.3 (648)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...........................
241-345 (35-50)
In Pan Oil Temperature - C (F)......................
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).....................
7.5 (8)
Low - L (qt.)................
6.5 (7)
Total Oil Capacity with Filter - L (qt.)................
8.5 (9)

Performance
BMEP - kg/cm2 (lb./in. 2).............171 (12.0) 159 (11.2) 148 (10.4) 138 (9.7))
Piston Speed - m/min. (ft./min.)..........597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m.........................
Consult Factory
Power Curve................ C131095

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131251 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-LP60
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Charge Air Cooling Type...Raw Water
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-125

Cooling System - 3 Pass 1760 2100 2350


Engine H2O Heat - kW (Btu/sec).......... 82 (78) 98 (93) 106 (101)
Engine Radiated Heat - kW (Btu/sec)......... 64.0 (61) 77.0 (73) 77.0 (73)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
53 (14) 72 (19) 72 (19)
35C (95F) Raw H2O - L/min. (gal/min.)......
57 (15) 83 (22) 83 (22)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
5 (72.5) (500)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-LP60
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 1760 2100 2350
3 3
Exhaust Flow - m /min. (ft. /min.)...........
27.0 (952) 35.0 (1227) 38.0 (1345)
Exhaust Temperature - C (F)............. 531 (988) 487 (909) 473 (883)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 38.0 (10.0) 39.0 (10.3) 42.0 (11.1)
23.3 (6.2) 23.9 (6.3) 25.7 (6.8)
Fuel Return - L/hr. (gal./hr.)............
61.3 (16.2) 62.9 (16.6) 67.7 (17.9)
Total Supply Fuel Flow - L/hr (gal./hr.)............
2
28-41 (4-6)
Fuel Pressure - kPa (lb./in. )..............
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type........................
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
3 3
Engine Air Flow - m /min. (ft. /min.)........ 10.0 (354) 14.0 (494) 15.2 (538)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..54 (130)

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)..................
276-414 (40-60)
In Pan Oil Temperature - C (F)........................
104-118 (220-245)
Oil Pan Capacity - High - L (qt.)......................
19 (20)
Low - L (qt.).................
17 (18)
Total Oil Capacity with Filter - L (qt.)..................
19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in. 2)............. 217 (15.2) 218 (15.3) 195 (13.7)
Piston Speed - m/min. (ft./min.).......... 447 (1467) 533 (1750) 597 (1958)
Mechanical Noise - dB(A) @ 1m.........................
Consult Factory
Power Curve................ C131010

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131247 revC
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-LP84
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... D-125

Cooling System - 3 Pass 2350 2600 2800 2960


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 57.9 (54.9) 59.2 (56.2) 61.8 (58.6) 65.6 (62.2)
Heat Exchanger Minimium Flow
45 (12)
15C (60F) Raw H2O - L/min. (gal/min.)...... 50 (13) 53 (14) 69 (18)
50 (13)
35C (95F) Raw H2O - L/min. (gal/min.)...... 61 (16) 63 (17) 76 (20)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)........... 5 (72.5) (500)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-LP84
INSTALLATION & OPERATION DATA (Continued)
Exhaust System 2350 2600 2800 2960
3 3
Exhaust Flow - m /min. (ft. /min.)...........
39.6 (1398) 45.0 (1588) 50.2 (1773) 55.3 (1952)
Exhaust Temperature - C (F).............490 (914) 492 (918) 518 (965) 556 (1032)
Maximum Allowable Back Pressure - kPa (in. H20)...
7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........
127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 42.0 (11.1) 45.8 (12.1) 50.3 (13.3) 56.0 (14.8)
Fuel Return - L/hr. (gal./hr.)............
25.7 (6.8) 28.3 (7.5) 31.2 (8.2) 32.6 (8.6)
67.7 (17.9) 74.1 (19.6) 81.5 (21.5) 88.6 (23.4)
Total Supply Fuel Flow - L/hr (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type......................
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 15.8 (558) 17.8 (627) 19.2 (678) 20.3 (718)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )....................
241-345 (35-50)
In Pan Oil Temperature - C (F)......................
104-118 (220-245)
Oil Pan Capacity - High - L (qt.).....................
7.5 (8)
Low - L (qt.)..............
6.5 (7)
Total Oil Capacity with Filter - L (qt.)................
8.5 (9)

Performance
BMEP - kg/cm2 (lb./in. 2).............
198 (13.9) 182 (12.8) 177 (12.4) 175 (12.3))
Piston Speed - m/min. (ft./min.)..........
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m.........................
Consult Factory
Power Curve................ C131096

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131248 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-AP50
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........4.19(106) x 5.00(127)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-131

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 42 (40) 50 (47) 50 (47) 56 (53)
Engine Radiated Heat - kW (Btu/sec)......... 26.0 (25.0) 31.0 (29.0) 30.0 (28.0) 30.0 (28.0)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 38 (10) 45 (12)
35C (95F) Raw H2O - L/min. (gal/min.)......
38 (10) 42 (11) 45 (12) 53 (14)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)........... 14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-AP50
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........16.0 (554) 20.0 (698) 21.0 (752) 24.0 (839)
Exhaust Temperature - C (F)............. 598 (1108) 580 (1076) 537 (998) 519 (966)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
102 (4)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 14.4 (3.8) 17.0 (4.5) 18.5 (4.9) 29.9 (7.9)
30.0 (7.9)
Fuel Return - L/hr. (gal./hr.)............. 32.2 (8.5) 34.1 (9.0) 36.0 (9.5)
44.4 (11.7) 49.2 (13.0) 52.6 (13.9) 65.9 (17.4)
Total Supply Fuel Flow - L/hr (gal./hr.).............
Fuel Pressure - kPa (lb./in.2)....................
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)....... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 2.5 (10)
1.2 (5)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)........5.4 (190) 6.9 (244) 7.8 (277) 8.9 (316)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).............. 241-345 (35-50)
In Pan Oil Temperature - C (F)............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)........... 8 (7.5)
Low - L (qt.).......... 7 (6.5)
Total Oil Capacity with Filter - L (qt.)........ 9 (8.5)

Performance
BMEP - kg/cm2 (lb./in.2).............
12.7 (180) 12.5 (178) 11.0 (156) 9.9 (141)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.................
Consult Factory
Power Curve................ C131128

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132129 revB
DSP 30AUG07
CLARKE
Fire Protection Products
JU4H-AP54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............4
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 4.5 (275)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. Rotary, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-3-4-2
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-131

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 60 (57) 73 (69) 80 (76) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 29.1 (27.6) 33.3 (31.6) 34.6 (32.8) 34.6 (32.8)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
27 (7) 25 (7) 31 (8) 34 (9)
35C (95F) Raw H2O - L/min. (gal/min.)......
30 (8) 42 (11) 45 (12) 48 (13)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)...........
14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU4H-AP54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
21.8 (768) 26.4 (934) 30.0 (1061) 33.8 (1193)
Exhaust Temperature - C (F)............. 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in. H20)...7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**.........102 (4)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 27.3 (7.2) 39.0 (10.3) 37.9 (10.0) 41.6 (11.0)
34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
Fuel Return - L/hr. (gal./hr.)............
61.4 (16.2) 75.0 (19.8) 75.4 (19.9) 80.6 (21.3)
Total Supply Fuel Flow - L/hr. (gal./hr.)............
2
21-41 (3-6)
Fuel Pressure - kPa (lb./in. )..............
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
2.5 (10)
Clean Air Cleaner - kPa (in. H20)..........
1.2 (5)
Engine Air Flow - m3/min. (ft.3/min.)........ 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
2
BMEP - kPA (lb./in. ).............
1034 (150) 1068 (155) 1034 (150) 958 (139)
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Piston Speed - m/min (ft./min.)..........
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................. C131179

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131284 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP30
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-132

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 63 (60) 73 (69) 75 (71) 86 (82)
Engine Radiated Heat - kW (Btu/sec)......... 33 (31) 38 (36) 38 (36) 38 (36)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
45 (12) 53 (14) 61 (16) 68 (18)
57 (15)
35C (95F) Raw H2O - L/min. (gal/min.)...... 64 (17) 72 (19) 79 (21)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP30
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........
21.0 (755) 27.0 (953) 30.0 (1055) 35.0 (1236)
Exhaust Temperature - C (F)............. 551 (1023) 515 (959) 473 (884) 467 (872)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
127 (5)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 35.0 (9.2) 41.0 (10.8) 42.0 (11.1) 42.0 (11.1)
19.0 (5.0) 23.0 (6.1)
Fuel Return - L/hr. (gal./hr.)............. 26.0 (6.9) 28.0 (7.4)
54.0 (14.2) 64.0 (16.9) 68.0 (18.0) 70.0 (18.5)
Total Supply Fuel Flow - L/hr (gal./hr.).............
Fuel Pressure - kPa (lb./in.2)....................
21-28 (3-4)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........3 (12)
1.5 (6)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)........ 7.8 (275) 10.2 (361) 11.9 (422) 14.1 (498)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)........... 276-414 (40-60)
In Pan Oil Temperature - C (F)............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.).......... 19 (20)
Low - L (qt.).. 17 (18)
Total Oil Capacity with Filter - L (qt.)...... 19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............
10.7 (152) 10.2 (145) 9.1 (130) 8.2 (117)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.................
Consult Factory
Power Curve................ C131129

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132130 revB
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP34
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-132

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 79 (75) 86 (82) 95 (90) 123 (117)
Engine Radiated Heat - kW (Btu/sec)......... 38.1 (36.1) 38.1 (36.1) 38.1 (36.1) 41.9 (39.7)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
26 (7) 49 (13) 23 (6) 58 (15)
49 (13)
35C (95F) Raw H2O - L/min. (gal/min.)...... 54 (14) 61 (16) 65 (17)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
91 (196)
Fully Opened - C (F).............
Engine Coolant Capacity - L (qt.).......... 14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 0
121 - 160 m Circuit* Length............. 000 0
161 - 200 m Circuit* Length............. 0000 0
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP34
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
30.6 (1081) 35.2 (1243) 38.7 (1365) 45.7 (1614)
Exhaust Temperature - C (F)............. 527 (980) 511 (951) 507 (944) 530 (986)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 31.4 (8.3) 45.0 (11.9) 37.5 (9.9) 40.9 (10.8)
Fuel Return - L/hr. (gal./hr.)............
25.7 (6.8) 28.4 (7.5) 30.7 (8.1) 32.6 (8.6)
57.2 (15.1) 73.4 (19.4) 68.2 (18.0) 73.5 (19.4)
Total Supply Fuel Flow - L/hr. (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 11.7 (412.9) 13.7 (483.6) 15.1 (533.4) 17.1 (605.1)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2).............
896 (130) 807 (117) 752 (109) 772 (112)
Piston Speed - m/min (ft./min.)..........
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131180

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131286 revC
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP50
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type...................... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in.).......... 4.19(106) x 5.00(127)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-132

Cooling System - 3 Pass 1470 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 73 (69) 83 (79) 95 (90) 106 (101) 101 (96)
Engine Radiated Heat - kW (Btu/sec)......... 31 (33) 42 (44) 47 (50) 47 (50) 47 (50)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
52 (14) 61 (16) 72 (19) 83 (22) 95 (25)
35C (95F) Raw H2O - L/min. (gal/min.)......
63 (17) 72 (19) 83 (22) 95 (25) 106 (28)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)............
14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.)..........14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal).........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 - 3.0 m Circuit* Length............ 00 00
3.1 - 4.0 m Circuit* Length............. 000 000
4.1 - 5.0 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP50
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1470 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........
19.4 (685) 26.0 (924) 34.0 (1204) 38.0 (1359) 42.0 (1496)
650 (1201)
Exhaust Temperature - C (F)............. 607 (1124) 557 (1034) 525 (977) 512 (953)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
127 (5)
Minimum Exhaust Pipe Dia. - mm (in.)**.........

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 35.3 (9.3) 41.0 (10.8) 47.0 (12.4) 49.0 (12.9) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.)..............
Total Supply Fuel Flow - L/hr (gal./hr.)................
Fuel Pressure - kPa (lb./in.2)....................
21-28 (3-4)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
Optional Voltage - AC, 1P..........
230 (+5%, -10%)

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
1.5 (6)
Clean Air Cleaner - kPa (in. H20)..........
Engine Air Flow - m3/min. (ft.3/min.)........ 6.0 (213) 8.9 (314) 12.3 (433) 14.4 (508) 16.1 (568)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2)...... 276-414 (40-60)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 19 (20)
Low - L (qt.) 17 (18)
Total Oil Capacity with Filter - L (qt.).. 19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............
14.3 (204) 13.9 (198) 13.4 (191) 12.0 (171) 10.8 (154)
Piston Speed - m/min. (ft./min.)..........
374 (1226) 447 (1467) 533 (1750) 597 (1958) 661 (2167)
Mechanical Noise - dB(A) @ 1m.................
Consult Factory
Power Curve................ C131130

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 4.5 meters of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132131 revB
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP54
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
3
Displacement - L (in. ).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-132

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 50.2 (47.6) 51.5 (48.9) 51.5 (48.9) 51.5 (48.9)
Heat Exchanger Minimium Flow
15C (60F) Raw H2O - L/min. (gal/min.)......
30 (8) 34 (9) 42 (11) 49 (13)
35C (95F) Raw H2O - L/min. (gal/min.)......
53 (14) 61 (16) 64 (17) 72 (19)
Heat Exchanger Maximum Cooling H2O
Inlet Pressure - bar (lb./in.2) (kPa)..........
14 (203) (1400)
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F).........
86 (187)
Fully Opened - C (F).............
91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 0
121 - 160 m Circuit* Length............. 000 0
161 - 200 m Circuit* Length............. 0000 0
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP54
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
36.6 (1291) 42.3 (1493) 46.2 (1631) 50.9 (1796)
Exhaust Temperature - C (F)............. 552 (1026) 548 (1019) 548 (1018) 569 (1057)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 37.9 (10.0) 43.2 (11.4) 45.0 (11.9) 46.9 (12.4)
Fuel Return - L/hr. (gal./hr.)............
25.7 (6.8) 28.3 (7.5) 31.2 (8.2) 32.6 (8.6)
63.6 (16.8) 71.4 (18.9) 76.2 (20.1) 79.6 (21.0)
Total Supply Fuel Flow - L/hr (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 13.5 (476) 15.7 (555) 17.1 (605) 18.3 (648)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPa (lb./in. 2).............
1158 (168) 1073 (156) 993 (144) 924 (134)
Piston Speed - m/min. (ft./min.)..........
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131181

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131287 revD
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP60
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer....John Deere Co.
Ignition Type...................... Compression (Diesel)
Number of Cylinders............. 6
Bore and Stroke - mm (in.).......... 106(4.19) x 127(5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............ 17.0:1
Valves per cylinder - Intake............
1
1
Exhaust............
Combustion System............Direct Injection
Engine Type..............In-Line, 4 Stroke Cycle
Aspiration..............Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Charge Air Cooling Type... Raw Water
Rotation (Viewed from Front) - Clockwise........
Standard
Not Available
Counter-Clockwise..............
Engine Crankcase Vent System........Open
Installation Drawing..........UD-132

Cooling System - 3 Pass 1760 2100 2350 2600


Engine H2O Heat - kW (Btu/sec).......... 82 (78) 98 (93) 106 (101) 124 (118)
Engine Radiated Heat - kW (Btu/sec)......... 48 (46) 57 (54) 57 (54) 57 (54)
Heat Exchanger Minimium Flow
53 (14)
15C (60F) Raw H2O - L/min. (gal/min.)...... 72 (19) 72 (19) 83 (22)
35C (95F) Raw H2O - L/min. (gal/min.)......
57 (15) 83 (22) 83 (22) 95 (25)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)(Standard Plumbing)
5 (72.5) (500)
Optional: U051148 High Pressure Plumbing:
14 (203)
Max. Inlet Pressure - bar (lb./in.2)(High Pressure Plumbing)......
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F)............. 91 (196)
Engine Coolant Capacity - L (qt.)..........14 (15)
Coolant Pressure Cap - kPa (lb./in.2).......69 (10)
Maximum Engine H20 Temperature - C (F)......93 (200)
Minimum Engine H20 Temperature - C (F).....
71 (160)

Electric System - DC
System Voltage (Nominal).........12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 440 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP60
INSTALLATION & OPERATION DATA (Continued)
UK Production

Exhaust System 1760 2100 2350 2600


Exhaust Flow - m3/min. (ft.3/min.)...........27.0 (952) 35.0 (1227) 38.0 (1345) 42.0 (1484)
Exhaust Temperature - C (F).............531 (988) 487 (909) 473 (883) 481 (898)
7.4 (30)
Maximum Allowable Back Pressure - kPa (in. H20)...
Minimum Exhaust Pipe Dia. - mm (in.)**......... (5)
127

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 38.0 (10.0) 39.0 (10.3) 42.0 (11.1) 48.0 (12.7)
Fuel Return - L/hr. (gal./hr.).............
Total Supply Fuel Flow - L/hr (gal./hr.).............
Fuel Pressure - kPa (lb./in.2)....................
28-41 (4-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.)...........375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.).......... 1.4 (4.5)
Fuel Filter Micron Size............... 5

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
115 (+5%, -10%)
Voltage - AC, 1P.............
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)........... 3 (12)
Clean Air Cleaner - kPa (in. H20)..........1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........10.0 (354) 14.0 (494) 15.2 (538) 16.6 (587)
54 (130)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..

Lubrication System
Oil Pressure - normal - kPa (lb./in.2).................... 276-414 (40-60)
In Pan Oil Temperature - C (F).............. 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)............ 19 (20)
Low - L (qt.).... 17 (18)
Total Oil Capacity with Filter - L (qt.)........ 19.5 (21.0)

Performance
BMEP - kg/cm2 (lb./in.2).............
15.2 (217) 15.3 (218) 13.7 (195) 12.4 (176)
447 (1467) 533 (1750) 597 (1958) 661 (2167)
Piston Speed - m/min. (ft./min.)..........
Mechanical Noise - dB(A) @ 1m.................
Consult Factory
Power Curve................ C131131

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C132132 revB
DSP 30AUG07
CLARKE
Fire Protection Products
JU6H-AP84
INSTALLATION & OPERATION DATA
UK Production
Basic Engine Description
Engine Manufacturer.... John Deere Co.
Ignition Type......................Compression (Diesel)
Number of Cylinders.............6
Bore and Stroke - mm (in.)..........106 (4.19) x 127 (5.00)
Displacement - L (in.3).......... 6.8 (415)
Compression Ratio............17.0:1
Valves per cylinder - Intake............
1
Exhaust............
1
Combustion System............ Direct Injection
Engine Type.............. In-Line, 4 Stroke Cycle
Aspiration.............. Turbocharged
Firing Order (CW Rotation).......... 1-5-3-6-2-4
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise..............
Not Available
Engine Crankcase Vent System........ Open
Installation Drawing.......... UD-132

Cooling System - 3 Pass 2350 2600 2800 3000


Engine H2O Heat - kW (Btu/sec).......... 100 (95) 119 (113) 130 (123) 148 (140)
Engine Radiated Heat - kW (Btu/sec)......... 57.9 (54.9) 59.2 (56.2) 61.8 (58.6) 65.6 (62.2)
Heat Exchanger Minimium Flow
45 (12)
15C (60F) Raw H2O - L/min. (gal/min.)...... 50 (13) 53 (14) 69 (18)
50 (13)
35C (95F) Raw H2O - L/min. (gal/min.)...... 61 (16) 63 (17) 76 (20)
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)(Standard Plumbing)
5 (72.5) (500)
Optional: U051146 High Pressure Plumbing
14 (203)
Max. Inlet Pressure - bar (lb./in.2)(High Pressure Plumbing)......
Flow - L/min. (gal./min)........... 100 (26)
Thermostat, Start to Open - C (F)......... 86 (187)
Fully Opened - C (F)............. 91 (196)
Engine Coolant Capacity - L (qt.).......... 14 (15)
2
Coolant Pressure Cap - kPa (lb./in. ).......69 (10)
Maximum Engine H20 Temperature - C (F)...... 93 (200)
71 (160)
Minimum Engine H20 Temperature - C (F).....

Electric System - DC
System Voltage (Nominal)......... 12 24
Battery Capacity for Ambients Above 0C (32F)
Voltage (Nominal)................ 12 24
Qty. per Battery Bank.......... 1 2
SAE size per J537............ 4D-640 4D-640
CCA @ -18C (0F).............. 640 640
Reserve Capacity - Minutes............ 285 285
Battery Cable Circuit*, Max Resistance - ohm...........0.0012 0.0012
Battery Cable Minimum Size
0 -120 m Circuit* Length............ 00 00
121 - 160 m Circuit* Length............. 000 000
161 - 200 m Circuit* Length............. 0000 0000
Charging Alternator Output - Amp.......... 40 40
Starter Cranking Amps - @ 15C (60F)......... 380 250
*Positive and Negative Cables Combined Length

NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
CLARKE
Fire Protection Products
JU6H-AP84
INSTALLATION & OPERATION DATA (Continued)
UK Production
Exhaust System 2350 2600 2800 3000
3 3
Exhaust Flow - m /min. (ft. /min.)...........
39.6 (1398) 45.0 (1588) 50.2 (1773) 55.3 (1952)
Exhaust Temperature - C (F)............. 490 (914) 492 (918) 518 (965) 556 (1032)
Maximum Allowable Back Pressure - kPa (in. H20)... 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in.)**......... 127 (5)

Fuel System
Fuel Consumption - L/hr. (gal./hr.)............ 42.0 (11.1) 45.8 (12.1) 50.3 (13.3) 56.0 (14.8)
Fuel Return - L/hr. (gal./hr.)............
25.7 (6.8) 28.3 (7.5) 31.2 (8.2) 32.6 (8.6)
67.8 (17.9) 74.1 (19.6) 81.5 (21.5) 88.6 (23.4)
Total Supply Fuel Flow - L/hr. (gal./hr.)............
Fuel Pressure - kPa (lb./in.2)..............
21-41 (3-6)
Minimum Line Size - Supply - (in.)....... .50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .033 (.848)
Minimum Line Size - Return - (in.).......... .375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).............. .026 (.675)
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H20 (in. H20)........ 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)... 1.4 (4.5)
Fuel Filter Micron Size............... 2

Heater System
Jacket Water Heater
Wattage (Nominal)..............
1500
Voltage - AC, 1P.............
115 (+5%, -10%)
230 (+5%, -10%)
Optional Voltage - AC, 1P..........

Induction Air System


Air Cleaner Type..............
Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in. H20)...........
3 (12)
Clean Air Cleaner - kPa (in. H20)..........
1.5 (6)
Engine Air Flow - m3/min. (ft.3/min.)........ 15.8 (558) 17.8 (627) 19.2 (678) 20.3 (718)
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***..
54 (130)

Lubrication System
2
Oil Pressure - normal - kPa (lb./in. )...... 241-345 (35-50)
In Pan Oil Temperature - C (F)........ 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)

Performance
BMEP - kPA (lb./in. 2).............
1365 (198) 1255 (182) 1220 (177) 1206 (175)
Piston Speed - m/min (ft./min.)..........
597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m................
Consult Factory
Power Curve................ C131182

** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greater than one half the max. allowable back pressure.)

*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)

C131288 revD
DSP 30AUG07
Clarke Cooling Loop Piping Detail C13977 Dtail des tubulures de la boucle de refroidissement Clarke C13977
English to French-Canadian Translator Traducteur Anglais>Franais canadien

English Text Texte en franais canadien

NFPA-20 Cooling Loop Piping Detail Dtail des tubulures de la boucle de refroidissement NFPA-20
NOTES: REMARQUES :
1) PIPING ARRANGEMENT PER NFPA-20 1) AGENCEMENT DES TUBULURES SELON NFPA-20
2) PIPING BY OTHERS 2) TUBULURES PAR DAUTRES
3) DISCHARGE PIPING FROM HEAT 3) LA TUBULURE DE DCHARGE DEPUIS LA SORTIE DE
EXCHANGER OUTLET IS ONE PIPE SIZE LCHANGEUR DE CHALEUR EST UNE TAILLE DE
LARGER THAN THE INLET PIPING TO THE TUYAU PLUS GRANDE QUE LA TUBULURE DENTRE
HEAT EXCHANGER. DE LCHANGEUR DE CHALEUR.
COOLING LOOP WATER DIRECTION OF FLOW EAU DE LA BOUCLE DE REFROIDISSEMENT SENS DE
LCOULEMENT
PUMP DISCHARGE CONNECTION BRANCHEMENT DE LA POMPE DE DCHARGE
COOLING LOOP (BY CLARKE) BOUCLE DE REFROIDISSEMENT (PAR CLARKE)
ENGINE COOLING WATER PIPED TO DRAIN EAU DE REFROIDISSEMENT DU MOTEUR ACHEMINE
VERS LA VIDANGE
ENGINE MOTEUR
GUARD CAPOT DE PROTECTION
COUPLING RACCORD
PUMP POMPE
INLET ENTRE
ENGINE HEAT EXCHANGER CHANGEUR DE CHALEUR DU MOTEUR
OUTLET SORTIE
VIEW A-A VUE A-A
BY-PASS LINE CONDUITE DE DRIVATION
UNION UNION
PRESSURE REGULATOR RGULATEUR DE PRESSION
GAUGE MANOMTRE
BALL VALVE VANNE BOISSEAU SPHRIQUE
WYE STRAINER FILTRE 45
SHUT-OFF VALVE VANNE DARRT
12V OR 24V SOLENOID VALVE LECTROVANNE EN 12V OU 24V
STANDARD COOLING LOOP BOUCLE DE REFROIDISSEMENT STANDARD

C131052 revA
Clarke Wiring Diagram C07575 Diagrama de Cableado C07575 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol

WIRING DIAGRAM, F.P. ENGINE DIAGRAMA DE CABLEADO, MOTOR F.P.


w/ELECTRIC GAUGES & DUAL STARTERS CON/INDICADORES ELCTRICOS & ARRANCADORES
NEGATIVE GROUND, 12 OR 24V DC DUALES, TIERRA NEGATIVA, 12 O 24V DC

LEGEND LEYENDA
AB ALTERNATOR BRIDGE AB - PUENTE DE ALTERNADOR
AL ALTERNATOR AL - ALTERNADOR
AM AUTOMATIC MODE POSITION AM - POSICIN DE MODO AUTOMTICO
B1 BATTERY #1 B1 - BATERA # 1
B2 BATTERY #2 B2 - BATERA # 2
BB - BATTERY BRIDGE BB - PUENTE DE BATERA
BI BATTERY ISOLATOR B1 - AISLANTE DE BATERA
C1 CRANK (MANUAL) SWITCH-BATT #1 C1 - INTERRUPTOR DE ARRANQUE (MANUAL) BAT # 1
C2 CRANK (MANUAL) SWITCH-BATT #2 C2 - INTERRUPTOR DE ARRANQUE (MANUAL) BAT # 2
CB COOLANT BRIDGE CB - PUENTE REFRIGERANTE
DR DROPPING RESISTOR (24V ONLY) DR - RESISTOR DE CADA (SLO 24V)
GS GOVERNOR SOLENOID GS - SOLENOIDE DE GOBERNADOR
MM MANUAL MODE POSITION MM - POSICIN DE MODO MANUAL
MP MAGNETIC PICK-UP MP - PICK-UP MAGNTICO
MS MODE SELECTOR MS - SELECTOR DE MODO
OP OIL PRESSURE 20# OP - PRESIN DE ACEITE #20
OS OVERSPEED RESET N.C. OS - RESTABLECIMIENTO DE SOBREVELOCIDAD N.C.
OV OVERSPEED VERIFY @67% OV - VERIFICACIN DE SOBREVELOCIDAD @67%
PG PRESSURE GAUGE (LUBE) PG - MANMETRO (LUBRICACIN)
PS PRESSURE SENDER (LUBE) R1- REMOT #1 (DE GIRO)
R1 RELAY #1 (CRANKING) R2 - REMOT #2 (DE GIRO)
R2 RELAY #2 (CRANKING) PS - TRANSMISOR DE PRESIN (LUBRICACIN)
R3 REMOTE RUN RELAY N.O. R3 - RELEVADOR DE OPERACIN REMOTA N.O.
S1 STARTER #1 S1 - ARRANCADOR # 1
S2 STARTER #2 S2 - ARRANCADOR # 2
SI STARTER ISOLATOR SI - AISLANTE DE ARRANCADOR
SW#1 CRANK TERMINATE SW#1 - TERMINACIN
SW#2 OVERSPEED SW#2 - SOBREVELOCIDAD
TG TEMPERATURE GAUGE (WATER) TG - INDICADOR DE TEMPERATURA (AGUA)
TH TACHOMETER HOURMETER TH - TACMETRO - HORMETRO
TS TEMPERATURE SENDER (WATER) TS - TRANSMISOR DE TEMPERATURA (AGUA)
V1 VOLTMETER / BATT #1 V1 - VOLTMETRO / BAT # 1
V2 VOLTMETER / BATT #2 V2 - VOLTMETRO / BAT # 2
WL WARNING LAMP CONTROLS NOT IN AUTOMATIC WL - LUZ DE ADVERTENCIA DE "LOS CONTROLES NO
POSITION SE ENCUENTRAN EN POSICIN AUTOMTICA"
WS WATER SOLENOID VALVE WS - VLVULA SOLENOIDE DE AGUA
WT WATER TEMPERATURE N.O. SW WT - INTERRUPTOR NORMALMENTE CERRADO DE
TEMPERATURA DE AGUA

COLOR CODE CDIGO DE COLOR


A WHITE A - BLANCO
B RED B - ROJO
C ORANGE C - NARANJA
D YELLOW D - AMARILLO
E GREEN E - VERDE
F GREEN F - VERDE
G BLUE G - AZUL
I PINK I - ROSA
J BLACK J - NEGRO
K BROWN K - CAF
L GRAY L.- GRIS
M - PURPLE M - MORADO
Clarke Wiring Diagram C07575 Diagrama de Cableado C07575 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol

Notes: Notas:
1. BROKEN LINE (---) SYMBOLS INDICATE 1. LOS SMBOLOS CON LNEA PUNTEADA (---) INDICAN QUE
COMPONENTS NOT SUPPLIED BY CLARKE. LOS COMPONENTES NO SON SUMINISTRADOS POR
2. REFER TO ENGINE MODEL INSTALLATION DATA CLARKE.
SHEET FOR SPECIFIC BATTERY AND CABLE 2. CONSULTE LA HOJA DE DATOS DE INSTALACIN DE
SIZE REQUIREMENTS. MODELO DE MOTOR SOBRE LOS REQUISITOS
3. 12 VOLT SYSTEM DOES NOT INCLUDE THE TWO ESPECFICOS DE LA BATERA Y TAMAO DE CABLES.
(DR) DROPPING RESISTORS. RED WIRES (B) 3. EL SISTEMA DE 12 VOLTS NO INCLUYE LOS DOS
CONNECT DIRECTLY TO PG & TG RESISTORES DE CADA (DR). LOS CABLES ROJOS (B)
CONECTADOS DIRECTAMENTE A PG Y TG
RESPECTIVELY. RESPECTIVAMENTE
4. SOME MODESL HAVE A STARTER THAT IS 4. ALGUNOS MODELOS CUENTAN CON UN ARRANCADOR
INTERNALLY GROUNDED; FOR THOSE THE QUE EST INTERNAMENTE ATERRIZADO; PARA SOS EL
BATTERY NEGATIVE CABLE (GRD) SHOULD BE CABLE NEGATIVO DE BATERA (GRD) DEBER
ATTACHED TO THE ENGINE BLOCK (ALL PAINT CONECTARSE CON EL MONOBLOQUE DEL MOTOR (SE
SHOULD BE REMOVED TO BARE METAL). DEBER REMOVER TODA LA PINTURA PARA QUE EL
5. JDFP ONLY ALL OTHER HAVE INTERNAL METAL QUEDE SIN RECUBRIMIENTO.
GROUND. 5. SLO JDFP - TODOS LOS OTROS CUENTAN CON TIERRA
6. IK6 TURBOCHARGED MODEL ENGINES ONLY. INTERNA
7. WIRE E25 IS NOT USED ON IK6 NATURALLY 6. SLO MOTORES DE MODELO TURBOCARGADOS IK6.
ASPIRATED ENGINES. 7. EL CABLE E25 NO SE UTILIZA EN MOTORES DE
ASPIRACIN NATURAL IK6.

Texto Adicional:
Additional Text:
INTERCONEXIN DE TERMINALES AL CONTROLADOR
INTER-CONNECT TERMINALS TO CONTROLLER
BY OTHERS POR OTROS
POR CLARKE
BY CLARKE
PARA "WS" CUANDO EL CIRCUITO DE ENFRIAMIENTO
FOR WS WHEN COOLING LOOP IS SUPPLIED BY
ES SUMINISTRADO POR DIAGRAMA DE REFERENCIA
CLARKE REF. DRAWING C07606
CLARKE C07606
OVERSPEED SWITCH
INTERRUPTOR DE SOBREVELOCIDAD
TACH
TACMETRO
SIGNAL INPUT
TEST ENTRADA DE SEAL
SEE NOTE #4 PRUEBA
CONSULTE LA NOTA #4
SEE NOTE #6
CONSULTE LA NOTA #6
SEE NOTE #7
SEE NOTE #5 CONSULTE LA NOTA #7
24 VOLT SYSTEM SHOWN CONSULTE LA NOTA #5
SE MUESTRA SISTEMA DE 24 VOLT
INSTRUMENT PANEL
PANEL DE INSTRUMENTOS
ENGINE
MOTOR
12V BATTERY DETAIL
DETALLE DE BATERA DE 12 V

C13995 rev A
Clarke Wiring Diagram C07575 Schma de cblage Clarke C07575
English to French-Canadian Translator Traducteur Anglais>Franais canadien

English Text Texte en franais canadien

WIRING DIAGRAM, F.P. ENGINE SCHMA DE CBLAGE, MOTEUR F.P. AVEC INDICATEURS
W/ELECTRIC GAUGES & DUAL STARTERS LECTRIQUES ET DMARREURS DOUBLES
NEGATIVE GRD. 12 OR 24VDC NGATIF LA MASSE 12 OU 24V c.c.

FOR CLARKE US ENGINES BUILT BEGINNING POUR MOTEURS AMRICAINS CLARKE CONSTRUITS
FEBRUARY 2003 PARTIR DE FVRIER 2003

LEGEND LGENDE
AB ALTERNATOR BRIDGE AB PONT DALTERNATEUR
AL ALTERNATOR AL ALTERNATEUR
AM AUTOMATIC MODE POSITION AM POSITION DE MODE AUTOMATIQUE
B1 BATTERY #1 B1 BATTERIE N 1
B2 BATTERY #2 B2 BATTERIE N 2
BB - BATTERY BRIDGE BB PONT DE BATTERIE
BI BATTERY ISOLATOR BI ISOLATEUR DE BATTERIE
C1 CRANK (MANUAL) SWITCH-BATT #1 C1 COMMUTATEUR LANCEMENT (MANUEL) BATTERIE N 1
C2 CRANK (MANUAL) SWITCH-BATT #2 C2 COMMUTATEUR LANCEMENT (MANUEL) BATTERIE N 2
CB COOLANT BRIDGE CB PONT DE LIQUIDE DE REFROIDISSEMENT
DR DROPPING RESISTOR (24V ONLY) DR RSISTANCE SHUNT (24V UNIQUEMENT)
GS GOVERNOR SOLENOID GS SOLENODE DE RGULATEUR
MM MANUAL MODE POSITION MM POSITION DE MODE MANUEL
MP MAGNETIC PICK-UP MP CAPTEUR LECTROMAGNTIQUE
MS MODE SELECTOR MS SLECTEUR DE MODE
OP OIL PRESSURE 20# OP PRESSION DHUILE 20 LIVRES
OS OVERSPEED RESET N.C. OS REMISE ZRO EN CAS DE SURVITESSE N.C.
OV OVERSPEED VERIFY @67% OV VRIFICATION DE SURVITESSE 67%
PG PRESSURE GAUGE (LUBE) PG MANOMTRE (LUBRIFICATION)
R1 RELAY #1 (CRANKING) R1 RELAIS N 1 (LANCEMENT)
R2 RELAY #2 (CRANKING) R2 RELAIS N 2 (LANCEMENT)
R3 REMOTE RUN RELAY N.O. R3 RELAIS DE FONCTIONNEMENT DISTANCE N.O.
S1 STARTER #1 S1 DMARREUR N 1
S2 STARER #2 S2 DMARREUR N 2
SI STARTER ISOLATOR SI ISOLATEUR DE DMARREUR
SW#1 CRANK TERMINATE SW#1 FIN DE LANCEMENT
SW#2 OVERSPEED SW#2 SURVITESSE
TG TEMPERATURE GAUGE (WATER) TG THERMOMTRE (EAU)
TH TACHOMETER HOURMETER TH TACHOMTRE COMPTEUR DHEURES
TS TEMPERATURE SENDER (WATER) TS ENVOI DE TEMPRATURE (EAU)
V1 VOLTMETER / BATT #1 V1 VOLTMTRE / BATTERIE N 1
V2 VOLTMETER / BATT #2 V2 VOLTMTRE / BATTERIE N 2
WL WARNING LAMP CONTROLS NOT IN WL TMOIN AVERTISSEUR LES COMMANDES NE
AUTOMATIC POSITION SONT PAS EN POSITION AUTOMATIQUE
WS WATER SOLENOID VALVE WS LECTROVANNE DEAU
(PROVIDED BY OTHERS) (FOURNIE PAR DAUTRES)
WT WATER TEMPERATURE N.O. SW WT COMMUTATEUR DE TEMPRATURE DEAU N.O. SW

COLOR CODE CODE DE COULEURS


A WHITE A BLANC
B RED B ROUGE
C ORANGE C ORANGE
D YELLOW D JAUNE
E GREEN E VERT
F GREEN F VERT
G BLUE G BLEU
I PINK I ROSE
J BLACK J NOIR
K BROWN K MARRON
L GRAY L GRIS
M - PURPLE M - VIOLET

Page 1 sur 2
Clarke Wiring Diagram C07575 Schma de cblage Clarke C07575
English to French-Canadian Translator Traducteur Anglais>Franais canadien

English Text Texte en franais canadien


Notes: Remarques :
1. BROKEN LINE (---) SYMBOLS INDICATE 1. LES LIGNES POINTILLES (---) INDIQUENT DES
COMPONENTS NOT SUPPLIED BY CLARKE. COMPOSANTS QUI NE SONT PAS FOURNIS PAR CLARKE.
2. REFER TO ENGINE MODEL INSTALLATION DATA 2. CONSULTEZ LA FICHE TECHNIQUE DINSTALLATION DU
SHEET FOR SPECIFIC BATTERY AND CABLE SIZE MOTEUR POUR LES EXIGENCES RELATIVES LA
REQUIREMENTS. BATTERIE ET LA TAILLE DES CBLES.
3. 12 VOLT SYSTEM DOES NOT INCLUDE THE TWO 3. LE SYSTME EN 12V NINCLUT PAS LES DEUX
(DR) DROPPING RESISTORS. RED WIRES (B) RSISTANCES SHUNT (DROPPING RESISTOR OU DR).
CONNECT DIRECTLY TO PG & TG RESPECTIVELY. LES FILS ROUGES (B) SONT RELIS DIRECTEMENT PG
ET TG RESPECTIVEMENT.
4. SOME MODELS HAVE A STARTER THAT IS 4. CERTAINS MODLES COMPORTENT UN DMARREUR
INTERNALLY GROUNDED; FOR THOSE THE MIS LA TERRE DE FAON INTERNE ; POUR CES
BATTERY NEGATIVE CABLE (GRD) SHOULD BE DERNIERS, LE CBLE NGATIF DE LA BATTERIE (TERRE)
ATTACHED TO THE ENGINE BLOCK (ALL PAINT DOIT TRE RELI AU BTI DU MOTEUR (LA PEINTURE
SHOULD BE REMOVED TO BARE METAL). DOIT TRE ENLEVE POUR EXPOSER LE MTAL NU).
5. PDFP ONLY ALL OTHER HAVE INTERNAL 5. PDFP UNIQUEMENT TOUS LES AUTRES MODLES
GROUND. COMPORTENT UNE MASSE INTERNE.

Texte supplmentaire :
Additional Text: BORNES DINTERCONNEXION AVEC LE CONTRLEUR
INTER-CONNECT TERMINALS TO CONTROLLER PAR DAUTRES
BY OTHERS PAR CLARKE
BY CLARKE POUR WS LORSQUE LA BOUCLE DE REFROIDISSEMENT
FOR WS WHEN COOLING LOOP IS SUPPLIED BY EST FOURNIE PAR CLARKE, PLAN DE RFRENCE C07606
CLARKE REF. DRAWING C07606 COMMUTATEUR DE SURVITESSE
OVERSPEED SWITCH TACH
TACH ENTRE DU SIGNAL
SIGNAL INPUT TEST
TEST VOIR REMARQUE N 5
SEE NOTE #5 SYSTME EN 24V ILLUSTR
24 VOLT SYSTEM SHOWN TABLEAU DINSTRUMENTS
INSTRUMENT PANEL MOTEUR
ENGINE
DTAIL DE LA BATTERIE DE 12V c.c.
12V DC BATTERY DETAIL

C131060 revA

Page 2 sur 2
This page intentionally left blank
Clarke Wiring Diagram C07602 Clarke Verspannung Diagramm C07602
English to German Translator Englisch zu Deutsch bersetzung

English Text German Text

WIRING DIAGRAM, F.P. ENGINE SCHALTPLAN, F.P. MOTOR


w/ELECTRIC GAUGES MIT ELEKTROMESSGERTEN
NEGATIVE GROUND, 12 OR 24V DC NEGATIVE ERDE, 12 ODER 24 V GLEICHSTROM

LEGEND LEGENDE
AB ALTERNATOR BRIDGE AB ALTERNATORBRCKE
AL ALTERNATOR AL ALTERNATOR
AM AUTOMATIC MODE POSITION AM POSITION AUTOMATIKMODUS
B1 BATTERY #1 B1 BATTERIE #1
B2 BATTERY #2 B2 BATTERIE #2
BB - BATTERY BRIDGE BB BATTERIEBRCKE
BI BATTERY ISOLATOR B1 BATTERIETRENNSCHALTER
C1 CRANK (MANUAL) SWITCH-BATT #1 C1 KURBEL (MANUELL) SCHALTER BATT #1
C2 CRANK (MANUAL) SWITCH-BATT #2 C2 - KURBEL (MANUELL) SCHALTER BATT #2
CB COOLANT BRIDGE CB KHLMITTELBRCKE
DR DROPPING RESISTOR (24V ONLY) DR REDUZIERWIDERSTAND
GS GOVERNOR SOLENOID GS REGLERMAGNET
MM MANUAL MODE POSITION MM POSITION MANUELLER MODUS
MP MAGNETIC PICK-UP MP INDUKTIVER GEBER
MS MODE SELECTOR MS BETRIEBSARTEN-WAHLSCHALTER
OP OIL PRESSURE 20# OP LDRUCK 20#
OS OVERSPEED RESET N.C. OS BERDREHZAHL RESET N.C.
OV OVERSPEED VERIFY @67% OV BERDREHZAHL-BERPRFUNG @ %
PG PRESSURE GAUGE (LUBE) PG MANOMETER (SCHMIERUNG)
PL TURBO PRELUBE SOLENOID PL VORSCHMIERUNGS-TURBOMAGNET
PS PRESSURE SENDER (LUBE) PS DRUCKSENDER (SCHMIERUNG)
R3 REMOTE RUN RELAY N.O. R3 FERNGESTEUERTES RELAIS N.O.
SC1 STARTER CONTACTOR BATT #1 SC1 ANLASSERSCHTZ BATT #1
SC2 STARTER CONTACTOR BATT #2 SC2 ANLASSERSCHTZ BATT #2
SI STARTER ISOLATOR SI ANLASSER-TRENNSCHALTER
ST STARTER ST ANLASSER
SW#1 CRANK TERMINATE SW#1 KURBELENDE
SW#2 OVERSPEED SW#2- BERDREHZAHL
TG TEMPERATURE GAUGE (WATER) TG TEMPERATURMESSGERT (WASSER)
TH TACHOMETER HOURMETER TH TACHOMETER STUNDENZHLER
TS TEMPERATURE SENDER (WATER) TS TEMPERATURSENDER (WASSER)
V1 VOLTMETER / BATT #1 V1 VOLTMETER / BATT#1
V2 VOLTMETER / BATT #2 V2 VOLTMETER / BATT#2
WL WARNING LAMP CONTROLS NOT IN WL WARNLEUCHTE BEDIENELEMENTE NICHT IN
AUTOMATIC POSITION AUTOMATIKPOSITION
WS WATER SOLENOID VALVE WS WASSERMAGNETVENTIL
WT WATER TEMPERATURE N.O. SW WT WASSERTEMPERATUR N.O. SW

COLOR CODE FARBKODE


A WHITE A WEISS
B RED B ROT
C ORANGE C ORANGE
D YELLOW D GELB
E GREEN E GRN
F GREEN F GRN
G BLUE G BLAU
I PINK I ROSA
J BLACK J SCHWARZ
K BROWN K BRAUN
L GRAY L GRAU
M - PURPLE M - PURPUR

Page 1 of 2
Clarke Wiring Diagram C07602 Clarke Verspannung Diagramm C07602
English to German Translator Englisch zu Deutsch bersetzung

English Text German Text


Notes: (SIEHE ANMERKUNGEN)
1. BROKEN LINE (---) SYMBOLS INDICATE 1. UNTERBROCHENE LINIE (---) WEIST AUF
COMPONENTS NOT SUPPLIED BY CLARKE. BAUTEILE HIN, DIE NICHT VON CLARKE
2. REFER TO ENGINE MODEL INSTALLATION GELIEFERT WERDEN.
DATA SHEET FOR SPECIFIC BATTERY AND 2. SIEHE INSTALLATIONSDATENBLATT FR
CABLE SIZE REQUIREMENTS. MOTORMODELL WEGEN SPEZIFISCHER
3. 12 VOLT SYSTEM DOES NOT INCLUDE THE ANFORDERUNGEN AN BATTERIE UND
TWO (DR) DROPPING RESISTORS. RED KABELGRSSE
WIRES (B) CONNECT DIRECTLY TO PG & 3. DAS 12-VOLT-SYSTEM BEINHALTET NICHT
TG RESPECTIVELY. DIE BEIDEN (DR) REDUZIERWIDERSTNDE.
4. SOME MODESL HAVE A STARTER THAT IS ROTE DRHTE (B) WERDEN DIREKT AN PG
INTERNALLY GROUNDED; FOR THOSE THE BZW. TG GEFHRT:
BATTERY NEGATIVE CABLE (GRD) SHOULD 4. EINIGE MODELLE HABEN EINEN ANLASSER
BE ATTACHED TO THE ENGINE BLOCK (ALL DER INTERN GEERDET IST; FR DIESE
PAINT SHOULD BE REMOVED TO BARE SOLLTE DAS BATTERIENEGATIVKABEL
METAL). (ERDE) AM MOTORBLOCK ANGEBRACHT
5. JDFP ONLY ALL OTHER HAVE INTERNAL WERDEN (ALLE FARBE SOLLTE BIS AUF
GROUND. DAS BLANKE BETALL ENTFERNT WERDEN)
6. IK6 TURBOCHARGED MODEL ENGINES 5. NUR JDFP ALLE ANDEREN HABEN
ONLY. INTERNE ERDE
7. WIRE E25 IS NOT USED ON IK6 NATURALLY 6. IK 6 NUR TURBO-MOTORMODELLE
ASPIRATED ENGINES. 7. DRAHT E25 WIRD NICHT AN
SAUGMOTOREN IK6 VERWENDET.
Additional Text: Zustzlicher Text:
INTER-CONNECT TERMINALS TO CONTROLLER KLEMMEN MIT DEM REGLER VERBINDEN
BY OTHERS VON ANDEREN
BY CLARKE VON CLARKE
FOR WS WHEN COOLING LOOP IS SUPPLIED BY FR WS WENN KHLSCHLEIFE VON CLARKE
CLARKE REF. DRAWING C07606 GELIEFERT WIRD SIEHE ZEICHNUNG C07606
OVERSPEED SWITCH BERDREHZAHLSCHALTER
TACH TACHOMETER
SIGNAL INPUT SIGNALEINGANG
TEST TEST
SEE NOTE #4 SIEHE ANMERKUNG #4
SEE NOTE #6 SIEHE ANMERKUNG #6
SEE NOTE #7 SIEHE ANMERKUNG #7
SEE NOTE #5 SIEHE ANMERKUNG #5
24 VOLT SYSTEM SHOWN 24 VOLT-SYSTEM DARGESTELLT
INSTRUMENT PANEL INSTRUMENTENTAFEL
ENGINE MOTOR
12V BATTERY DETAIL 12 V BATTERIEDETAIL

C13969 rev A
Page 2 of 2
Clarke Wiring Diagram C07602 Diagrama de Cableado C07602 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol

WIRING DIAGRAM, F.P. ENGINE DIAGRAMA DE CABLEADO, MOTOR F.P.


w/ELECTRIC GAUGES CON/INDICADORES ELCTRICOS
NEGATIVE GROUND, 12 OR 24V DC TIERRA NEGATIVA, 12 O 24V DC

LEGEND LEYENDA
AB ALTERNATOR BRIDGE AB - PUENTE DE ALTERNADOR
AL ALTERNATOR AL - ALTERNADOR
AM AUTOMATIC MODE POSITION AM - POSICIN DE MODO AUTOMTICO
B1 BATTERY #1 B1 - BATERA # 1
B2 BATTERY #2 B2 - BATERA # 2
BB - BATTERY BRIDGE BB - PUENTE DE BATERA
BI BATTERY ISOLATOR B1 - AISLANTE DE BATERA
C1 CRANK (MANUAL) SWITCH-BATT #1 C1 - INTERRUPTOR DE ARRANQUE (MANUAL) BAT # 1
C2 CRANK (MANUAL) SWITCH-BATT #2 C2 - INTERRUPTOR DE ARRANQUE (MANUAL) BAT # 2
CB COOLANT BRIDGE CB - PUENTE REFRIGERANTE
DR DROPPING RESISTOR (24V ONLY) DR - RESISTOR DE CADA (SLO 24V)
GS GOVERNOR SOLENOID GS - SOLENOIDE DE GOBERNADOR
MM MANUAL MODE POSITION MM - POSICIN DE MODO MANUAL
MP MAGNETIC PICK-UP MP - PICK-UP MAGNTICO
MS MODE SELECTOR MS - SELECTOR DE MODO
OP OIL PRESSURE 20# OP - PRESIN DE ACEITE #20
OS OVERSPEED RESET N.C. OS - RESTABLECIMIENTO DE SOBREVELOCIDAD N.C.
OV OVERSPEED VERIFY @67% OV - VERIFICACIN DE SOBREVELOCIDAD @67%
PG PRESSURE GAUGE (LUBE) PG - MANMETRO (LUBRICACIN)
PL TURBO PRELUBE SOLENOID PL - SOLEOIDE DE PRELUBRICACIN DEL TURBO
PS PRESSURE SENDER (LUBE) PS - TRANSMISOR DE PRESIN (LUBRICACIN)
R3 REMOTE RUN RELAY N.O. R3 - RELEVADOR DE OPERACIN REMOTA N.O.
SC1 STARTER CONTACTOR BATT #1 SC1 - CONTACTOR DE ARRANCADOR BAT # 1
SC2 STARTER CONTACTOR BATT #2 SC2 - CONTACTOR DE ARRANCADOR BAT # 2
SI STARTER ISOLATOR SI - AISLANTE DE ARRANCADOR
ST STARTER ST - ARRANCADOR
SW#1 CRANK TERMINATE SW#1 - TERMINACIN DE GIRO
SW#2 OVERSPEED SW#2 - SOBREVELOCIDAD
TG TEMPERATURE GAUGE (WATER) TG - INDICADOR DE TEMPERATURA (AGUA)
TH TACHOMETER HOURMETER TH - TACMETRO - HORMETRO
TS TEMPERATURE SENDER (WATER) TS - TRANSMISOR DE TEMPERATURA (AGUA)
V1 VOLTMETER / BATT #1 V1 - VOLTMETRO / BAT # 1
V2 VOLTMETER / BATT #2 V2 - VOLTMETRO / BAT # 2
WL WARNING LAMP CONTROLS NOT IN AUTOMATIC WL - LUZ DE ADVERTENCIA DE "LOS CONTROLES NO
POSITION SE ENCUENTRAN EN POSICIN AUTOMTICA"
WS WATER SOLENOID VALVE WS - VLVULA SOLENOIDE DE AGUA
WT WATER TEMPERATURE N.O. SW WT - INTERRUPTOR NORMALMENTE CERRADO DE
TEMPERATURA DE AGUA

COLOR CODE CDIGO DE COLOR


A WHITE A - BLANCO
B RED B - ROJO
C ORANGE C - NARANJA
D YELLOW D - AMARILLO
E GREEN E - VERDE
F GREEN F - VERDE
G BLUE G - AZUL
I PINK I - ROSA
J BLACK J - NEGRO
K BROWN K - CAF
L GRAY L.- GRIS
M - PURPLE M - MORADO
Clarke Wiring Diagram C07602 Diagrama de Cableado C07602 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol

Notes: Notas:
1. BROKEN LINE (---) SYMBOLS INDICATE 1. LOS SMBOLOS CON LNEA PUNTEADA (---) INDICAN QUE
COMPONENTS NOT SUPPLIED BY CLARKE. LOS COMPONENTES NO SON SUMINISTRADOS POR
2. REFER TO ENGINE MODEL INSTALLATION DATA CLARKE.
SHEET FOR SPECIFIC BATTERY AND CABLE 2. CONSULTE LA HOJA DE DATOS DE INSTALACIN DE
SIZE REQUIREMENTS. MODELO DE MOTOR SOBRE LOS REQUISITOS
3. 12 VOLT SYSTEM DOES NOT INCLUDE THE TWO ESPECFICOS DE LA BATERA Y TAMAO DE CABLES.
(DR) DROPPING RESISTORS. RED WIRES (B) 3. EL SISTEMA DE 12 VOLTS NO INCLUYE LOS DOS
CONNECT DIRECTLY TO PG & TG RESISTORES DE CADA (DR). LOS CABLES ROJOS (B)
CONECTADOS DIRECTAMENTE A PG Y TG
RESPECTIVELY. RESPECTIVAMENTE
4. SOME MODESL HAVE A STARTER THAT IS 4. ALGUNOS MODELOS CUENTAN CON UN ARRANCADOR
INTERNALLY GROUNDED; FOR THOSE THE QUE EST INTERNAMENTE ATERRIZADO; PARA SOS EL
BATTERY NEGATIVE CABLE (GRD) SHOULD BE CABLE NEGATIVO DE BATERA (GRD) DEBER
ATTACHED TO THE ENGINE BLOCK (ALL PAINT CONECTARSE CON EL MONOBLOQUE DEL MOTOR (SE
SHOULD BE REMOVED TO BARE METAL). DEBER REMOVER TODA LA PINTURA PARA QUE EL
5. JDFP ONLY ALL OTHER HAVE INTERNAL METAL QUEDE SIN RECUBRIMIENTO.
GROUND. 5. SLO JDFP - TODOS LOS OTROS CUENTAN CON TIERRA
6. IK6 TURBOCHARGED MODEL ENGINES ONLY. INTERNA
7. WIRE E25 IS NOT USED ON IK6 NATURALLY 6. SLO MOTORES DE MODELO TURBOCARGADOS IK6.
ASPIRATED ENGINES. 7. EL CABLE E25 NO SE UTILIZA EN MOTORES DE
ASPIRACIN NATURAL IK6.

Additional Text: Texto Adicional:


INTERCONEXIN DE TERMINALES AL CONTROLADOR
INTER-CONNECT TERMINALS TO CONTROLLER
POR OTROS
BY OTHERS
BY CLARKE POR CLARKE
FOR WS WHEN COOLING LOOP IS SUPPLIED BY PARA "WS" CUANDO EL CIRCUITO DE ENFRIAMIENTO
ES SUMINISTRADO POR DIAGRAMA DE REFERENCIA
CLARKE REF. DRAWING C07606
CLARKE C07606
OVERSPEED SWITCH
TACH INTERRUPTOR DE SOBREVELOCIDAD
TACMETRO
SIGNAL INPUT
ENTRADA DE SEAL
TEST
SEE NOTE #4 PRUEBA
SEE NOTE #6 CONSULTE LA NOTA #4
CONSULTE LA NOTA #6
SEE NOTE #7
CONSULTE LA NOTA #7
SEE NOTE #5
24 VOLT SYSTEM SHOWN CONSULTE LA NOTA #5
INSTRUMENT PANEL SE MUESTRA SISTEMA DE 24 VOLT
PANEL DE INSTRUMENTOS
ENGINE
MOTOR
12V BATTERY DETAIL
DETALLE DE BATERA DE 12 V

C13987 revA
Clarke Wiring Diagram C07602 Schma de cblage Clarke C07602
English to French-Canadian Translator Traducteur Anglais > Franais canadien

English Text Texte en franais canadien

WIRING DIAGRAM, F.P. ENGINE SCHMA DE CBLAGE, MOTEUR F.P.


w/ELECTRIC GAUGES AVEC INDICATEURS LECTRIQUES
NEGATIVE GROUND, 12 OR 24V DC NGATIF LA MASSE, 12 OU 24V c.c.

LEGEND LGENDE
AB ALTERNATOR BRIDGE AB PONT DALTERNATEUR
AL ALTERNATOR AL ALTERNATEUR
AM AUTOMATIC MODE POSITION AM POSITION DE MODE AUTOMATIQUE
B1 BATTERY #1 B1 BATTERIE N 1
B2 BATTERY #2 B2 BATTERIE N 2
BB - BATTERY BRIDGE BB PONT DE BATTERIE
BI BATTERY ISOLATOR BI ISOLATEUR DE BATTERIE
C1 CRANK (MANUAL) SWITCH-BATT #1 C1 COMMUTATEUR LANCEMENT (MANUEL) BATTERIE N1
C2 CRANK (MANUAL) SWITCH-BATT #2 C2 COMMUTATEUR LANCEMENT (MANUEL) BATTERIE N 2
CB COOLANT BRIDGE CB PONT DE LIQUIDE DE REFROIDISSEMENT
DR DROPPING RESISTOR (24V ONLY) DR RSISTANCE SHUNT (24V UNIQUEMENT)
GS GOVERNOR SOLENOID GS SOLENODE DE RGULATEUR
MM MANUAL MODE POSITION MM POSITION DE MODE MANUEL
MP MAGNETIC PICK-UP MP CAPTEUR LECTROMAGNTIQUE
MS MODE SELECTOR MS SLECTEUR DE MODE
OP OIL PRESSURE 20# OP PRESSION DHUILE 20 LIVRES
OS OVERSPEED RESET N.C. OS REMISE ZRO EN CAS DE SURVITESSE N.C.
OV OVERSPEED VERIFY @67% OV VRIFICATION DE LA SURVITESSE 67%
PG PRESSURE GAUGE (LUBE) PG MANOMTRE (LUBRIFICATION)
PL TURBO PRELUBE SOLENOID PL SOLNODE DE PRLUBRIFICATION DU
TURBOCOMPRESSEUR
PS PRESSURE SENDER (LUBE) PS ENVOI DE PRESSION (LUBRIFICATION)
R3 REMOTE RUN RELAY N.O. R3 RELAIS DE FONCTIONNEMENT DISTANCE N.O.
SC1 STARTER CONTACTOR BATT #1 SC1 CONTACTEUR DE DMARREUR BATTERIE N 1
SC2 STARTER CONTACTOR BATT #2 SC2 CONTACTEUR DE DMARREUR BATTERIE N 2
SI STARTER ISOLATOR SI ISOLATEUR DE DMARREUR
ST STARTER ST DMARREUR
SW#1 CRANK TERMINATE SW#1 FIN DE LANCEMENT
SW#2 OVERSPEED SW#2 SURVITESSE
TG TEMPERATURE GAUGE (WATER) TG THERMOMTRE (EAU)
TH TACHOMETER HOURMETER TH TACHOMTRE COMPTEUR DHEURES
TS TEMPERATURE SENDER (WATER) TS ENVOI DE TEMPRATURE (EAU)
V1 VOLTMETER / BATT #1 V1 VOLTMTRE / BATTERIE N 1
V2 VOLTMETER / BATT #2 V2 VOLTMTRE / BATTERIE N 2
WL WARNING LAMP CONTROLS NOT IN WL TMOIN AVERTISSEUR LES COMMANDES
AUTOMATIC POSITION NE SONT PAS EN POSITION AUTOMATIQUE
WS WATER SOLENOID VALVE WS LECTROVANNE DEAU
WT WATER TEMPERATURE N.O. SW WT COMMUTATEUR TEMPRATURE DEAU N.O. SW

COLOR CODE CODE DE COULEURS


A WHITE A BLANC
B RED B ROUGE
C ORANGE C ORANGE
D YELLOW D JAUNE
E GREEN E VERT
F GREEN F VERT
G BLUE G BLEU
I PINK I ROSE
J BLACK J NOIR
K BROWN K MARRON
L GRAY L GRIS
M - PURPLE M VIOLE

Page 1 sur 2
Clarke Wiring Diagram C07602 Schma de cblage Clarke C07602
English to French-Canadian Translator Traducteur Anglais > Franais canadien

English Text Texte en franais canadien

Notes: Remarques :
1. BROKEN LINE (---) SYMBOLS INDICATE 1. LES LIGNES POINTILLES (---) INDIQUENT DES
COMPONENTS NOT SUPPLIED BY CLARKE. COMPOSANTS QUI NE SONT PAS FOURNIS PAR
CLARKE.
2. REFER TO ENGINE MODEL INSTALLATION 2. CONSULTEZ LA FICHE TECHNIQUE DINSTALLATION
DATA SHEET FOR SPECIFIC BATTERY AND DU MOTEUR POUR LES EXIGENCES RELATIVES LA
CABLE SIZE REQUIREMENTS. BATTERIE ET LA TAILLE DES CBLES.
3. 12 VOLT SYSTEM DOES NOT INCLUDE THE 3. LE SYSTME EN 12V NINCLUT PAS LES DEUX
TWO (DR) DROPPING RESISTORS. RED WIRES RSISTANCES SHUNT (DROPPING RESISTOR OU
(B) CONNECT DIRECTLY TO PG & TG DR). LES FILS ROUGES (B) SONT RELIS
RESPECTIVELY. DIRECTEMENT PG ET TG RESPECTIVEMENT.
4. SOME MODELS HAVE A STARTER THAT IS 4. CERTAINS MODLES COMPORTENT UN
INTERNALLY GROUNDED; FOR THOSE THE DMARREUR MIS LA TERRE DE FAON INTERNE ;
BATTERY NEGATIVE CABLE (GRD) SHOULD BE POUR CES DERNIERS, LE CBLE NGATIF DE LA
ATTACHED TO THE ENGINE BLOCK (ALL PAINT BATTERIE (TERRE) DOIT TRE RELI AU BTI DU
SHOULD BE REMOVED TO BARE METAL). MOTEUR (LA PEINTURE DOIT TRE ENLEVE POUR
EXPOSER LE MTAL NU).
5. JDFP ONLY ALL OTHER HAVE INTERNAL 5. JDFP UNIQUEMENT TOUS LES AUTRES MODLES
GROUND. COMPORTENT UNE MASSE INTERNE.
6. IK6 TURBOCHARGED MODEL ENGINES ONLY. 6. MOTEURS IK6 TURBOCOMPRESSEUR UNIQUEMENT.
7. WIRE E25 IS NOT USED ON IK6 NATURALLY 7. LE FIL E25 NEST PAS UTILIS SUR LES MOTEURS
ASPIRATED ENGINES. IK6 ASPIRATION NATURELLE

Additional Text: Texte supplmentaire :


INTER-CONNECT TERMINALS TO CONTROLLER BORNES DINTERCONNEXION AVEC LE CONTRLEUR
BY OTHERS PAR DAUTRES
BY CLARKE PAR CLARKE
FOR WS WHEN COOLING LOOP IS SUPPLIED BY POUR WS LORSQUE LA BOUCLE DE REFROIDISSEMENT
CLARKE REF. DRAWING C07606 EST FOURNIE PAR CLARKE, PLAN DE RFRENCE C07606
OVERSPEED SWITCH COMMUTATEUR DE SURVITESSE
TACH TACH
SIGNAL INPUT ENTRE DU SIGNAL
TEST TEST
SEE NOTE #4 VOIR REMARQUE N 4
SEE NOTE #6 VOIR REMARQUE N 6
SEE NOTE #7 VOIR REMARQUE N 7
SEE NOTE #5 VOIR REMARQUE N 5
24 VOLT SYSTEM SHOWN SYSTME EN 24V ILLUSTR
INSTRUMENT PANEL TABLEAU DINSTRUMENTS
ENGINE MOTEUR

12V BATTERY DETAIL DTAIL DE LA BATTERIE DE 12V

C131062 rev A

Page 2 sur 2
This page intentionally left blank
Clarke Wiring Diagram C07591 Diagrama de Cableado C07591 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol


WIRING DIAGRAM DIAGRAMA DE CABLEADO
J.W. HEATER 115/230VAC CALENTADOR J.W. 115/230VAC
Notes: Notas:
1. VARIFY HEATER VOLTAGE PRIOR TO VERIFIQUE EL VOLTAJE DEL CALENTADOR ANTES DE
CONNECTING TO POWER SOURCE. CONECTAR A LA FUENTE DE POTENCIA.

VAC POWER POTENCIA VAC


SEE NOTE #1 CONSULTE LA NOTA #1
JACKET WATER HEATER WITH VOLTAGE & WATTAGE CALENTADOR DE AGUA DE LA CHAQUETA CON
IDENTIFICATION VOLTAJE E IDENTIFICACIN DE VOLTAJE
THERMOSTAT TERMOSTATO
BLACK NEGRO
GREEN VERDE
HIGH LIMIT THERMOSTAT

C13994 revA
Clarke Wiring Diagram C07591 Schma de cblage Clarke C07591
English to French-Canadian Translator Traducteur Anglais > Franais canadien

English Text Texte en franais canadien

WIRING DIAGRAM SCHMA DE CBLAGE


Jacket Water Heater 120/240VAC-1500 Watts Chauffe-eau radiateur 120/240V c.c. 1500 W

Notes: Remarques :
1. VARIFY HEATER VOLTAGE PRIOR TO 1. VRIFIER LA TENSION DU RADIATEUR AVANT DE
CONNECTING TO POWER SOURCE LE RELIER LALIMENTATION LECTRIQUE

PDFP PDFP
VAC POWER ALIMENTATION EN COURANT ALTERNATIF
SEE NOTE #1 VOIR REMARQUE N 1
BLACK NOIR
GREEN GRD VERT POUR LA TERRE
THERMOSTAT THERMOSTAT
HEATER (w/VOLTAGE IDENTIFICATION) RCHAUFFEUR (AVEC IDENTIFICATION DE LA TENSION)
HIGH LIMIT THERMOSTAT THERMOSTAT DE LIMITE LEVE

C131061 revA

1
This page intentionally left blank
Clarke Verspannung Diagramm C07651 Clarke Verspannung Diagramm C07651
Englisch zu Deutsch bersetzung Englisch zu Deutsch bersetzung

English Text German Text

WIRING DIAGRAM SCHALTPLAN


J.W. HEATER 115/230VAC MANTEL-WASSERERHITZER 115/230VAC

Notes: Anmerkungen:
1. VARIFY HEATER VOLTAGE PRIOR TO 1. ERHITZERSPANNUNG VOR DEM
CONNECTING TO POWER SOURCE, VARIFY ANSCHLUSS AN STROMQUELLE PRFEN,
SUPPLY CIRCUIT HAS ADEQUATE PRFEN, OB VERSORGUNGSSTROMKREIS
AMPERAGE FOR J.W. HEATER AND LUBE DIE RICHTIGE STROMSTRKE FR DEN
OIL HEATER WHEN PROVIDED. MANTELWASSERERHITZER UND
SCHMIERLERHITZER (FALLS GELIEFERT)
2. - - - - WIRING SUPPLIED BY OTHERS 2. SCHALTUNGEN WERDEN VON ANDEREN
GELIEFERT.

DDFP DDFP (?)


JDFP JDFP (?)
VMFP VMFP (?)
ON AN
OFF AUS
VAC POWER VAC LEISTUNG
SEE NOTE #1 SIEHE ANMERKUNG #1
JACKET WATER HEATER WITH VOLTAGE & MANTELWASSERERHITZER MIT SPANNUNGS- UND
WATTAGE IDENTIFICATION WATTLEISTUNGSKENNZEICHNUNG
OPTIONAL OPTIONAL
LUBE OIL HEAER WITH VOLTAGE AND WATTAGE SCHMIERLERHITZER MIT SPANNUNGS- UND
IDENTIFICATION WATTLEISTUNGSKENNZEICHNUNG
THERMOSTAT THERMOSTAT

C13972 revA
Seite 1 von 1
Clarke Wiring Diagram C07651 Diagrama de Cableado C07651 de Clarke
English to Spanish Translator Traductor del Ingls al Espaol

English Text Texto en Espaol


WIRING DIAGRAM DIAGRAMA DE CABLEADO
J.W. HEATER 115/230VAC CALENTADOR J.W. 115/230VAC
Notes: Notas:
1. VARIFY HEATER VOLTAGE PRIOR TO 1. VERIFIQUE EL VOLTAJE DEL CALENTADOR ANTES
CONNECTING TO POWER SOURCE, VARIFY DE CONECTAR A LA FUENTE DE POTENCIA,
SUPPLY CIRCUIT HAS ADEQUATE AMPERAGE VERIFIQUE QUE EL CIRCUITO DE ALIMENTACIN
FOR J.W. HEATER AND LUBE OIL HEATER TENGA EL AMPERAJE ADECUADO PARA EL
WHEN PROVIDED. CALENTADOR J.W. AS COMO EL CALENTADOR DE
ACEITE LUBRICANTE CUANDO SE TENGA
INSTALADO.
2. - - - - WIRING SUPPLIED BY OTHERS
2. ----CABLEADO SUMINISTRADO POR OTROS
DDFP
JDFP DDFP
VMFP JDFP
ON VMFP
OFF ACTIVADO
VAC POWER DESACTIVADO
SEE NOTE #1 POTENCIA VAC
JACKET WATER HEATER WITH VOLTAGE & WATTAGE CONSULTE LA NOTA #1
IDENTIFICATION CALENTADOR DE AGUA DE LA CHAQUETA CON
OPTIONAL VOLTAJE E IDENTIFICACIN DE VOLTAJE
LUBE OIL HEAER WITH VOLTAGE AND WATTAGE OPCIONAL
IDENTIFICATION CALENTADOR DE ACEITE LUBRICANTE CON
THERMOSTAT IDENTIFICACIN DE VOLTAJE Y WATTAJE
TERMOSTATO

C13988 revA
Clarke Wiring Diagram C07651 Schma de cblage Clarke C07651
English to French-Canadian Translator Traducteur Anglais > Franais canadien

English Text Texte en franais canadien

WIRING DIAGRAM SCHMA DE CBLAGE


J.W. HEATER 115/230VAC CHAUFFE-EAU RADIATEUR 115/230V c.a.

Notes: Remarques :
1. VERIFY HEATER VOLTAGE PRIOR TO 1. VRIFIEZ LA TENSION DU RADIATEUR AVANT DE LE
CONNECTING TO POWER SOURCE, VARIFY RELIER LALIMENTATION LECTRIQUE, VRIFIER
SUPPLY CIRCUIT HAS ADEQUATE AMPERAGE QUE LE CIRCUIT DALIMENTATION A UNE CAPACIT
FOR J.W. HEATER AND LUBE OIL HEATER SUFFISANTE POUR LE CHAUFFE-EAU RADIATEUR
WHEN PROVIDED. ET LE RCHAUFFEUR DHUILE DE LUBRIFICATION,
LE CAS CHANT.
2. - - - - WIRING SUPPLIED BY OTHERS 2. - - - - CBLGE FOURNI PAR DAUTRES

DDFP DDFP
JDFP JDFP
VMFP VMFP
ON MARCHE
OFF ARRT
VAC POWER ALIMENTATION EN COURANT ALTERNATIF
SEE NOTE #1 VOIR REMARQUE N 1
JACKET WATER HEATER WITH VOLTAGE & CHAUFFE-EAU RADIATEUR AVEC IDENTIFICATION DE
WATTAGE IDENTIFICATION TENSION ET DE PUISSANCE
OPTIONAL EN OPTION
LUBE OIL HEATER WITH VOLTAGE AND WATTAGE RCHAUFFEUR DHUILE DE LUBRIFICATION AVEC
IDENTIFICATION IDENTIFICATION DE TENSION ET DE PUISSANCE
THERMOSTAT THERMOSTAT

C131053 revA