Introduction
As per contract requirement, calculation need to be done to show/verify that the earthing
grid design is safe for the worst earth faults to remote earth. This calculation is based on
guidelines provided by IEEE Std. 80 (2000) and IEC 479-1.
Input Data
a) Soil Resistivity : 27.03 m average OF Test 1 & Test 2.
(See grounding system resistance test report July 13, 2012, Refer to Annex A)
b) Symetrical fault level (line-ground) for solid grounded system neutral at 230kV side :
3 ( KVL / 1.732 )
If =
3 (Rf ) ( R++R-+R0)+j (X++X-+X0)
WHEREIN :
KVL = 230,000 ; LINE VOLTAGE
RF = 0 : FAULT RESISTANCE
Z+ = 1.085 + j 8.792
Z- = 1.149 + j 9.058
Z0 = 0.0474 + j 9.909 }
REFER TO ANNEX B
3 ( 230,000 / 1.732 )
If =
3 (0) + (1.085 + 1.149 + 0.0474 ) + j (8.792+9.058 +9.909)
If = 14.34 kA
d) Fault duration ; ts = tc = tf = 1 s ;
We assume duration of 1 s.
g) Total length main horizontal grid using hard drawn Cu Conductor 125 mm : 700m.
g) Substation surface material is gravel crushed rock graded stone thickness :200mm.
h) Substation surface material is gravel crushed rock graded stone Resistivity is 4000 .m.
Refer to Annex D - Table 7.
i) Earthing grid Bare Cu condcutor 125 mm and other data are specified by client's
and NGCP Standard Specification GRD-1.
A. CABLE SIZING :
WHEREIN :
I = If = 14.34 kA
Kf = 11.78 ; Refer to Annex C ( Table 2), the constant for the material at various fusing tempera
or limited conductor temperature at ambient temperature of 40 deg.C.
tc = Duration of fault current for sizing of conductor in seconds = 1s
WHEREIN:
-Soil Resistivity = 27.03
s-Gravel resistivity, 4000 m
hs-Thickness of surface material (gravel) 0.200
Cs = 1-(0.09x(1-/s)/(2hs+0.09))
= 1-(0.09x(1-27.03/4000)/(2x0.2+0.09))
= 1-((0.09x0.9932)/(0.49)
= 1-(0.0894/0.49)
Cs = 0.8176
WHEREIN :
- Soil Resistivity = 27.03 m
LT - Ground grid Cu conductor length, 700m
A - Total area covered by grid = 1726m
h - conductor burial depth = 0.6m
Rg = [(1/LT)+(1/20 x A) x (1+(1/(1+h20/A)]
= 27.03 x [(1/700)+(1/20 x 1726.04) x (1+(1/(1+0.620/1726.04)]
= 27.03 x [0.00142+0.00538x(1+0.939)]
= 27.03 x 0.01185= 0.320
Rg = 0.320
IG = Ig x Df
WHEREIN :
Ig- symetrical grid current = 14.34kA
Df - decrement factor
GPR = IG x Rg
= 18,355.20 x 0.320 IG-maximum grid current, 18,355.20 A
GPR= 5,873.66 V Rg-earthing grid resistance, 0.320
GPR exceed the safe value of touch voltage Etouch value , further design evaluation is necessary.
WHEREIN :
- Soil Resistivity = 27.03 m
IG = 18,355.20 A
WHEREIN :
n = na + nb + nc + nd
2 X 700
= =7.910
177
nc = nd = 1
Kii = 1 ; for grids with ground rods ( i.e. refer to IEEE Standard Annex G )
= = 1.265
Lc + LR =
LM =
WHEREIN :
LC Total Length of Grid Conductor = 700 m
Lr Length of Ground Rod at each location = 3m
LR Total Length of Ground Rods = 3 * 18 = 54
LM Effective Length of Lc + LR for Mesh Voltage,
LM = 786.487
Em = 893.74 V
Em = 893.74 V
Ks = 0.342
Es = 550.437 V
Approved by:
George T. Sulit Revision No.
Professional Electrical Engineer
PRC NO. 2188 Validity 2013 ,PTR No: 1389330 Date 2/28/12Effectivity Date:
AMII-C-001
November 11,2013
2
onstant for the material at various fusing temperature
Ratio @ Fault Location X/R : 12.17
ue , further design evaluation is necessary.
Lower than the tolerable Touch Voltage
s vs 927.18 Volts )
11-Nov-13