Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ASHRAE STANDARD
Standard Method of Test
for the Evaluation of
Building Energy Analysis
Computer Programs
See Annex C for approval dates by the ASHRAE Standards Committee, the ASHRAE Board of Directors, and the
American National Standards Institute.
This standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which the
Standards Committee has established a documented program for regular publication of addenda or revisions,
including procedures for timely, documented, consensus action on requests for change to any part of the stan-
dard. The change submittal form, instructions, and deadlines may be obtained in electronic form from the ASHRAE
Web site, http://www.ashrae.org, or in paper form from the Manager of Standards. The latest edition of an ASHRAE
Standard may be purchased from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-
mail: orders@ashrae.org. Fax: 404-321-5478. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723
(for orders in U.S. and Canada).
SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards
Institute (ANSI), of which ASHRAE is a member and which has approved this standard as an ANS, as substantial agreement reached
by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority but not necessarily
unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.
Compliance with this standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public
review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The
Project Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE
members, all must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests
of all Project Committees.
The Manager of Standards of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard,
d. permission to reprint portions of the Standard.
DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available
information and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or
performance of any products, components, or systems tested, installed, or operated in accordance with ASHRAEs Standards
or Guidelines or that any tests conducted under its Standards or Guidelines will be nonhazardous or free from risk.
When addenda, interpretations, or errata to this standard have been approved, they can be downloaded
free of charge from the ASHRAE Web site at http://www.ashrae.org.
SECTION PAGE
Foreword........................................................................................................................................................................................2
1 Purpose.................................................................................................................................................................................3
2 Scope ....................................................................................................................................................................................3
5 Test Procedures....................................................................................................................................................................8
Normative Annexes
Informative Annexes
Annex B8 Example Results for Building Thermal Envelope and Fabric Load Tests..............................................................68
Annex B10 Instructions for Working with Results Spreadsheet Provided with the Standard................................................112
Annex B11 Production of Example Results for Building Thermal Envelope and Fabric Load Tests ....................................114
Annex B13 COP Degradation Factor (CDF) as a Function of Part-Load Ratio (PLR) ..........................................................117
Annex B16 Quasi-Analytical Solution Results and Example Simulation Results for
HVAC Equipment Performance Tests...................................................................................................................................122
Annex B18 Validation Methodologies and Other Research Relevant to Standard 140 ........................................................146
adjusted net sensible capacity: the gross sensible capacity less apparatus dew point (ADP): the effective coil surface temper-
the actual fan power. (Also see gross sensible capacity.) ature when there is dehumidification; this is the temperature to
which all the supply air would be cooled if 100% of the supply
adjusted net total capacity: the gross total capacity less the air contacted the coil. On the psychrometric chart, this is the
actual fan power. (Also see gross total capacity.) intersection of the condition line and the saturation curve,
net sensible capacity: the gross sensible capacity less the solar heat gain coefficient (SHGC): dimensionless ratio of
default rate of fan heat assumed by the manufacturer; this rate solar heat gains to incident solar radiation, including transmit-
of fan heat is not necessarily the same as for the actual installed tance plus inward flowing fraction of absorbed solar radiation;
fan (see adjusted net sensible capacity). (Also see gross sensi- for windows, SHGC is dependent on incidence angle.
ble capacity.)
solar lost through window: fraction of total solar radiation
net total capacity: the gross total capacity less the default rate transmitted through the window(s) that is reflected by opaque
of fan heat assumed by the manufacturer; this rate of fan heat surfaces and retransmitted back out the window(s).
is not necessarily the same as for the actual installed fan (see
surface coefficient: see combined radiative and convective
adjusted net total capacity). (Also see gross total capacity.)
surface coefficient.
nonproportional-type thermostat: thermostat that provides
two position (on/off) control. zone air temperature: the temperature of just the zone air, not
including infrared radiation from the interior surfaces; such a
outdoor dry-bulb temperature (ODB): the temperature that a temperature would be measured by a sensor housed in a well-
thermometer would measure if exposed to outdoor air. This is aspirated containment shielded by a material with a solar and
the temperature of air entering the condenser coil. infrared reflectance of one; well-mixed air is assumed.
part-load ratio (PLR): the ratio of the net refrigeration effect zone cooling loads: sensible heat and latent heat loads asso-
to the adjusted net total capacity for the cooling coil. (Also see ciated with heat and moisture exchange between the building
net refrigeration effect and adjusted net total capacity.) envelope and its surroundings as well as internal heat and
moisture gains within the building. These loads do not include
quasi-analytical solution: mathematical solution of a model internal gains associated with operating the mechanical
of reality for a given set of parameters and boundary condi- system (e.g., air distribution fan heat).
Volume Altitude
ACH (m3) (m)
0.500 129.600 1609.000
* The interior film coefficient for floors and ceilings is a compromise between upward and downward heat flow for summer and winter.
** Underfloor insulation shall have the minimum density and specific heat the program being tested will allow, but not < 0.
*** Infiltration derived from:
ACH * Volume * (specific heat of air) * (density of air at specified altitude)
Property Value
Extinction coefficient 0.0196/mm
Number of panes 2
Pane thickness (standard 1/8 in. glass under the inch-pound [IP] system) 3.175 mm
Air gap thickness 13 mm
Index of refraction 1.526
Normal direct-beam transmittance through one pane in air 0.86156
Thermal conductivity of glass 1.06 W/mK
Conductance of each glass pane 333 W/m2K(R-0.003 m2K/W)
Combined radiative and convective heat transfer coef of air gap (hs) 6.297 W/m2K(R-0.1588 m2K/W)
Exterior combined surface coefficient (ho) 21.00 W/m2K(R-0.0476 m2K/W)
Interior combined surface coefficient (hi) 8.29 W/m2K(R-0.1206 m2K/W)
U-Value from interior air to ambient air 3.0 W/m2K(R-0.3333 m2K/W)
Hemispherical infrared emittance of ordinary uncoated glass 0.84
(Use 0.9 for simplicity of input. If the program being tested
must use 0.84 this is acceptable because the effect on outputs
will be less than 0.5%)
Density of glass 2500 kg/m3
Specific heat of glass 750 J/kgK
Curtains, blinds, frames, spacers, mullions, obstructions inside the window None
Double-pane shading coefficient (at normal incidence) 0.907
Double-pane solar heat gain coefficient (at normal incidence) 0.789
5.2.1.11 Transparent Window. Many programs use 10 0.747 0.065 0.053 0.136 0.789
different algorithms to calculate window transmittance and 20 0.745 0.066 0.053 0.136 0.787
therefore require different inputs. For example, SERIRES4 30 0.740 0.068 0.055 0.137 0.784
calculates transmittance, absorptance, and reflectance for
each hourly incidence angle given the index of refraction, 40 0.730 0.071 0.057 0.143 0.775
extinction coefficient, glazing thickness, and number of panes 50 0.707 0.075 0.058 0.160 0.754
in the window assembly. BLAST5 calculates extinction coef- 60 0.652 0.080 0.059 0.210 0.700
ficient, absorptance, reflectance, and angle-dependent trans-
mittance given the direct normal transmittance of a single 70 0.517 0.086 0.054 0.343 0.563
pane in air, glass thickness, index of refraction, and number of 80 0.263 0.094 0.041 0.602 0.302
panes. A great deal of information about the window proper- Note 1: Trans = transmittance, Refl = reflectance, Abs = absorptance, SHGC = solar
heat gain coefficient.
ties has therefore been provided so that equivalent input for
the window will be possible for many programs. Use only the
Incidence angle-dependent optical properties are given in
information that is relevant to the program being tested.
Table 7. For programs that need transmittance or reflectance at
Case 600 has 12 m of south-facing window area, with other angles of incidence, the user may interpolate between
windows located as shown in Figure 1 (Section 5.2.1.4). The the values in Table 7 using the cosine of the incident angle as
basic properties of the window are provided in Table 6. the basis for interpolation. Where other unspecified data are
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Window
Solar Fraction 0.642 0.168 0.038 0.038 0.053 0.026 0.035
needed, then values that are consistent with those quoted are
to be calculated. For further informational discussion related
to calculating angle-dependent glazing optical properties,
refer to informative Annex B6.
The windows have no sash area, so the rough openings
shown in Figure 1 contain only the double-pane glass
described in Tables 6 and 7.
5.2.1.12 Interior Solar Distribution. If the program
being tested does not calculate this effect internally but
requires distribution fractions from the user, then assume
100% of the incoming radiation strikes the floor first and that
all reflections are diffuse. Table 8 presents an approximate Figure 2 Section of south window overhang (Case 610).
calculation of solar distribution fractions.
In Table 8, fractional values for the walls with windows 5.2.1.13.2 Equipment Characteristics.
(i.e., the south wall) include the portion of the solar radiation
Heating capacity = 1000 kW (effectively
absorbed by the glass (as it passes back out the window) and
infinite).
conducted back into the zone. Solar radiation absorbed by the
glass (and conducted inward) as it initially passes into the Effective efficiency = 100%.
building is not included in the values in Table 8. Cooling capacity = 1000 kW (effectively
Informative Annex B7 gives background information infinite).
regarding the calculation technique used for developing these Effective efficiency = 100%.
solar fractions.
Sensible cooling only; no latent heat load
5.2.1.13 Mechanical System. The intent of the calculation.
mechanical system is to produce only pure heating load and
sensible cooling load outputs. That is, all equipment is 100% Waste heat from fan = 0.
efficient with no duct losses and no capacity limitations. Equipment efficiency is always 100% independent of part
The mechanical system shall be modeled with the follow- loading, indoor dry-bulb temperature and humidity ratio,
ing features as noted below and in Sections 5.2.1.13.1 and outdoor dry-bulb temperature and humidity ratio, and/or other
5.2.1.13.2: conditions.
(a) 100% convective air system, 5.2.2 Basic Tests. It is recommended to double check the
(b) the thermostat senses only the air temperature, Case 600 base building inputs and to diagnose Case 600
(c) nonproportional-type thermostat (see Section 5.2.1.13.1), results disagreements before going on to the other cases.
(d) no latent heat extraction. 5.2.2.1 Low Mass Tests. The low mass basic tests
5.2.1.13.1 Thermostat Control Strategy. The ther- shall be modeled as detailed in this section and its subsec-
mostat is nonproportional in the sense that when the condi- tions. The low mass basic tests include cases 600 through 650.
Once an accurate input description for Case 600 has been
tioned-zone air temperature exceeds the thermostat cooling
developed, the remaining low mass basic cases shall be input
setpoint, the heat extraction rate is assumed to equal the max-
by slightly modifying Case 600 as indicated case by case
imum capacity of the cooling equipment. Likewise, when the
below. Note that Case 620 provides the basis for Case 630.
conditioned-zone air temperature drops below the thermostat
heating setpoint, the heat addition rate equals the maximum 5.2.2.1.1 Case 610: South Shading. Case 610 is
capacity of the heating equipment. A proportional thermostat exactly the same as Case 600 except for changes noted in the
model can be made to approximate a nonproportional thermo- subsections below.
stat model by setting a very small throttling range (the mini- 5.2.2.1.1.1 South Overhang Geometry. The over-
mum allowed by the program being tested). hang detailed in Figure 2 is added. The horizontal overhang
The thermostat control strategy for Case 600 is: for south-facing windows is assumed to travel the entire
Heat = on if temperature <20C; otherwise, length of the south wall.
Heat = off. 5.2.2.1.1.2 Output Requirements.
Cool = on if temperature >27C; otherwise, a. All non-free-float case output in accordance with Section
Cool = off. 6.1.1
Note: temperature refers to conditioned-zone air temperature. b. Additional output in accordance with Section 6.1.3
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Windows
Solar Fraction 0.642 0.168 0.025 0.025 0.0525 0.0525 0.035
TABLE 10
Vent Fan Capacity Depending on the Presence of Automatic Altitude Adjustment
TABLE 13
Interior Solar Distribution Fractions by Surface, Case 960, Sun Zone
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Windows
Solar Fraction 0.6 0.06 0.02 0.02 0.2 0.03 0.07
Case Basis for that Case Case Basis for that Case Case Basis for that Case
220 600 250 220 400 600
210 220 270 220 395 400
215 220 280 270 410 400
200 210 290 270 420 410
195 200 300 270 430 420
230 220 310 300 440 600
240 220 320 270 800 430
810 900
TABLE 16
High Conductance Wall Properties
Property Value
Opaque pane thickness 3.175 mm
Thermal conductivity of opaque pane 1.06 W/mK
Conductance of each opaque pane 333 W/m K (R-0.003 m2K/W)
2
TABLE 17
Interior Combined Surface Coefficient Versus Surface Orientation, Case 210
5.2.3.1.3 Opaque Surface Radiative Properties. Note: temperature refers to the conditioned-zone air tem-
Interior and exterior opaque surface solar (visible and ultravi- perature.
olet wavelengths) absorptances and infrared emittances are This is a nonproportional thermostat as described in
included in Table 15. Listed infrared emittances are Section 5.2.1.13.1.
unchanged from Case 600.
5.2.3.1.6 Output Requirements. Only non-free-
5.2.3.1.4 High Conductance Wall/Opaque Win-
float case output in accordance with Section 6.1.1.
dow. An element, which may be thought of as a highly con-
ductive wall or an opaque window, replaces the 12 m2 of 5.2.3.2 Case 210: Interior Infrared Radiation. Case
transparent window on the south wall. 210 is exactly the same as Case 220 except for changes
The properties of the high-conductance wall are as described in the following subsections.
follows:
5.2.3.2.1 Opaque Surface Radiative Properties.
(a) Shortwave transmittance = 0. Interior infrared emittance = 0.1.
(b) Infrared emittances and solar absorptances are as listed in
Table 15. 5.2.3.2.2 Interior Combined Radiative and Con-
(c) The exterior surface coefficient is in accordance with Sec- vective Surface Coefficients. If the program being tested cal-
tion 5.2.1.9 (Case 600); if combined coefficients are culates interior surface radiation and convection, then
applied, use 21.0 W/m2K. The surface texture for the disregard this section. If the program being tested does not
high-conductance wall is very smooth, the same as glass. calculate these effects, then use the constant combined radia-
(d) The interior surface coefficient is in accordance with Sec- tive and convective surface coefficients given in Table 17.
tion 5.2.1.10 (Case 600). The radiative portion of these combined coefficients may
(e) Conductance, density, specific heat, and surface texture be taken as 0.57 W/m2K for cases with an infrared emittance
(very smooth) are the same as for the transparent window of 0.1.
listed in Table 16. If the program being tested does not allow scheduling of
5.2.3.1.5 Thermostat Control. Use the following these coefficients, use 3.73 W/m2K for horizontal surfaces. If
20,20 thermostat control configuration: different values can be justified, then use different values.
Heat = on if temperature < 20C Informative Annex B5 includes background information
Cool = on if temperature > 20C about combined radiative and convective film coefficients.
TABLE 19
Infiltration Rates Depending on the Presence of Automatic Altitude Adjustment, Case 230
TABLE 20
Interior Solar Distribution Fractions by Surface, Case 270
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Windows
Solar Fraction 0.903 0.039 0.013 0.013 0.018 0.008 0.006
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Windows
Solar Fraction 0.244 0.191 0.057 0.057 0.082 0.065 0.304
TABLE 22
Interior Solar Distribution Fractions by Surface, Case 300
Solar Lost
Surface Floor Ceiling East Wall West Wall North Wall South Wall Through Windows
Solar Fraction 0.903 0.039 0.008 0.008 0.018 0.018 0.006
In Table 20, fractional values for the walls with windows the change in orientation, the windows are exactly as in Case
(i.e., the south wall) include the portion of the solar radiation 270.
absorbed by the glass (as it passes back out the window) and 5.2.3.12.2 Interior Solar Distribution. If the pro-
conducted back into the zone. Solar radiation absorbed by the gram being tested does not calculate this effect internally but
glass (and conducted inward) as it initially passes into the requires distribution fractions from the user, then assume
building is not included in the values in Table 20. 100% of the incoming radiation strikes the floor first and that
Informative Annex B7 gives background information all reflections are diffuse. Table 22 presents an approximate
regarding the calculation technique used for developing these calculation of solar distribution fractions adjusted for the
solar fractions. geometry of Case 300.
5.2.3.10 Case 280: Cavity Albedo. Case 280 is exactly In Table 22, fractional values for the walls with windows
the same as Case 270 except for changes described in the fol- (i.e., the east and west walls) include the portion of the solar
lowing subsections. radiation absorbed by the glass (as it passes back out the
5.2.3.10.1 Opaque Surface Radiative Properties. window) and conducted back into the zone. Solar radiation
Interior shortwave absorptance = 0.1. absorbed by the glass (and conducted inward) as it initially
5.2.3.10.2 Interior Solar Distribution. If the pro- passes into the building is not included in the values in Table
gram being tested does not calculate interior solar distribution 22.
internally but requires distribution fractions from the user, Informative Annex B7 gives background information
then assume 100% of the incoming radiation strikes the floor regarding the calculation technique used for developing these
first and that all reflections are diffuse. Table 21 presents an solar fractions.
approximate calculation of solar distribution fractions corre- 5.2.3.13 Case 310: East/West Shading. Case 310 is
sponding to the interior solar absorptance of Case 280. Only exactly the same as Case 300 except shading devices are
use these approximations if the program being tested does not added to the east and west windows as detailed in Figures 4
provide a more detailed approach. and 5 (Section 5.2.2.1.3.1).
In Table 21, fractional values for the walls with windows 5.2.3.14 Case 320: Thermostat. Case 320 is exactly the
(i.e., the south wall) include the portion of the solar radiation same as Case 270 except the thermostat is the following 20,27
absorbed by the glass (as it passes back out the window) and deadband configuration:
conducted back into the zone. Solar radiation absorbed by the Heat = on if temperature < 20C; otherwise,
glass (and conducted inward) as it initially passes into the heat = off.
building is not included in the values in Table 21. Cool = on if temperature > 27C; otherwise,
Informative Annex B7 gives background information cool = off.
regarding the calculation technique used for developing these
Note: Temperature refers to the conditioned-zone air tem-
solar fractions.
perature.
5.2.3.11 Case 290: South Shading. Case 290 is exactly
This is a nonproportional thermostat as described in
the same as Case 270 except the overhang detailed in Figure
Section 5.2.1.13.1.
2 (Section 5.2.2.1.1.1) is added. The horizontal overhang for
south-facing windows is assumed to travel the entire length of 5.2.3.15 Case 400: Opaque Windows with Deadband
the south wall. Thermostat. Case 400 is exactly the same as Case 600 except
for the changes described in the following subsections.
5.2.3.12 Case 300: East/West Window Orientation.
Case 300 is exactly the same as Case 270 except for changes 5.2.3.15.1 Infiltration. Infiltration rate = 0 ACH, con-
described in the following subsections. tinuously (24 hours per day for the entire year).
5.2.3.12.1 Window Orientation. The window orien- 5.2.3.15.2 Internal Gains. Internal gains = 0 W, con-
tation is modified as detailed in Figure 3 (Section 5.2.2.1.2.1) tinuously (24 hours per day for the entire year).
such that there are 6 m2 of window area facing east and 6 m2 5.2.3.15.3 Opaque Surface Radiative Properties.
of window area facing west and no other windows. Other than Exterior solar absorptance = 0.1.
TABLE 25
Interior Combined Surface Coefficient versus Surface Orientation
Orientation of Surface and Heat Flow Interior Combined Surface Coefficient
Horizontal heat transfer on vertical surfaces 8.29 W/m2K (1.46 Btu/(hftF))
Upward heat transfer on horizontal surfaces 9.26 W/m2K (1.63 Btu/(hftF))
Downward heat transfer on horizontal surfaces 6.13 W/m2K (1.08 Btu/(hftF))
TABLE 27
Determination of Maximum Dry-Coil EWB Using Interpolation
EWB Adjusted Net Total Capacity Adjusted Net Sensible Capacity Compressor Power
(C) (kW) (kW) (kW)
15.0 7.19 7.66 1.62
Maximum
dry EWB 7.66* 7.66* 1.652*
16.75*
17.2 7.78 7.45 1.66
* Italicized values are not specifically listed with Table 26e; they are determined based on the accompanying discussion. Other data in this table are from Table 26e.
TABLE 28
Determination of Maximum Dry-Coil EWB Using Extrapolation
EWB Adjusted Net Sensible Capacity Compressor Power
(C) Adjusted Net Total Capacity (kW) (kW) (kW)
Maximum dry EWB
13.8* 6.87* 6.87* 1.598*
15.0 7.19 6.31 1.62
17.2 7.78 5.26 1.66
* Italicized values are not specifically listed with Table 26e; they are determined based on the accompanying discussion. Other data in this table are from Table 26e.
5.3.1.10.5.2 Tubes.
5.3.1.10.5.3 Fins.
5.3.1.10.6 Fans.
5.3.1.10.6.1 Indoor Air Distribution Fan. Figure 12 Evaporator coil detail, tube and fin geometry.
Indoor fan power = 230 W
Airflow rate = 0.425 m3/s = 1529 m3/h = 900 CFM
Total combined fan and motor efficiency = 0.5 5.3.2 HVAC Equipment Performance Parameter Vari-
Total fan pressure = 271 Pa = 1.09 in. w.g. (water gauge) ation Tests
Supply air temperature rise from fan heat = 0.44C = 5.3.2.1 Additional Dry Coil Test Cases
0.8F It is recommended to double check the Case E100 base
Air distribution efficiency = 100% (adiabatic ducts) case inputs and to diagnose Case E100 results disagreements
before going on to the other test cases.
For further discussion of these inputs, see Annex B15. This section describes sequential revisions to the base
The draw-through indoor air distribution fan cycles on case required to model additional dry-coil cases. The dry-coil
and off with the compressor. For calculating additional heating cases have no latent load in the zone. In many instances the
of the distribution air related to waste heat from the indoor base case for a given case is not Case E100; appropriate base
distribution fan, assume that the distribution fan motor is cases for a given dry-coil case are:
mounted in the distribution airstream so that 100% of the heat
from fan energy use goes to the distribution (supply) air. Case Basis for That Case
5.3.1.10.6.2 Outdoor Condenser Fan.
E110 E100
Outdoor fan power = 108 W. E120 E110
E130 E100
The draw-through outdoor condenser fan cycles on and
off with the compressor. E140 E130
TABLE 29
Daily Hourly Output Requirements for Building Thermal Envelope and Fabric Load Tests of Section 5.2
ANNEX A1
WEATHER DATA
A1.1 Weather Data for Building Thermal Envelope and Fabric Load Tests
The full-year weather data (DRYCOLD.TMY) on the CD provided with this standard method of test shall be used for
performing the tests called out in Section 5.2. Site and weather characteristics are summarized in Table A1-1.
TABLE A1-1
Site and Weather Summary for DRYCOLD.TMY Weather Data Used with
Building Thermal Envelope and Fabric Load Tests
TABLE A1-2
Weather Data for HVAC Equipment Performance Tests
Data Files Applicable Cases Applicable Cases Sections
HVBT294.TMY or HVBT294A.TM2 E110, E120, E140, E150, E160, E170, 5.3.2.1.1; 5.3.2.1.2; 5.3.2.1.4; 5.3.2.2.1;
E180, E190 5.3.2.2.2; 5.3.2.2.4; 5.3.2.2.5; 5.3.2.2.7
HVBT350.TMY or HVBT350A.TM2 E200 5.3.2.2.9
HVBT406.TMY or HVBT406A.TM2 E165 5.3.2.2.3
HVBT461.TMY or HVBT461A.TM2 E100, E130, E185, E195 5.3.1; 5.3.2.1.3; 5.3.2.2.6; 5.3.2.2.8
TABLE A1-3a
Site and Weather Summary for HVAC Equipment Performance TestsTMY Data
Weather Type Artificial Conditions
Weather Format TMY
Latitude 25.8 North
Longitude (local site) 80.3 West
Altitude 2 m (6.6 ft)
Time Zone (Standard Meridian Longitude) 5 (75 West)
Ground Reflectivity 0.2
Site Flat, unobstructed, located exactly at weather station
Dew Point Temperature (constant) 14.0C (57.2F)
Humidity Ratio 0.010 kg moisture/kg dry air
(0.010 lb moisture/lb dry air)
Mean 3-Month Wind Speed 4.4 m/s (9.8 miles/h)
Maximum 3-Month Wind Speed 12.4 m/s (27.7 miles/h)
Global Horizontal Solar Radiation 3-Month Total 1354 MJ/m (119.2 kBtu/ft)
Direct Normal Solar Radiation 3-Month Total 1350 MJ/m (118.8 kBtu/ft)
Direct Horizontal Solar Radiation 3-Month Total 817 MJ/m (71.9 kBtu/ft)
Diffuse Horizontal Solar Radiation 3-Month Total 536 MJ/m (47.2 kBtu/ft)
Quantities That Vary Between Data Sets Ambient Dry Bulb Ambient
Temperature (constant) Relative Humidity
HVBT294.TMY 29.4C (85.0F) 39%
HVBT350.TMY 35.0C (95.0F) 28%
HVBT406.TMY 40.6C (105.0F) 21%
HVBT461.TMY 46.1C (115.0F) 16%
A1.3 TMY Weather Data Format E varies roughly 15 minutes throughout the year
For those programs that do not have Typical Meteorolog- because of cosmology. Additional background information on
ical Year (TMY) weather processors, TMY weather data file the equation of time may be found in the references.10
format is provided in Table A1-4. This reprint of tables also Additional background regarding the difference between
includes some additional notes based on experience with solar time and standard time is included in informative Annex
TMY data. If this summary is insufficient, the complete docu- B11 (Section B11.3).
mentation on TMY weather data9 can be obtained from the
National Climatic Data Center (NCDC) in Asheville, North A1.4 TMY2 Weather Data Format
Carolina. Their address is Federal Building, Asheville, NC For those programs that do not have Typical Meteorolog-
28801-2733, telephone 828-271-4800. Informative Annex B2 ical Year 2 (TMY2) weather processors, TMY2 weather data
contains additional background information regarding TMY file format is described below. If this summary is insufficient,
weather data. the complete documentation on TMY2 weather data11 can be
The hourly time convention for TMY weather data is obtained at http://rredc.nrel.gov/solar/pubs/tmy2.
solar time, where
A1.4.1 File Header. The first record of each file is the file
Solar Time = Standard Time + header that describes the station. The file header contains the
(4 minutes/degree) (Lst - Lloc) + E WBAN number, city, state, time zone, latitude, longitude, and
and where elevation. The field positions and definitions of these header
Lst = standard meridian longitude (degrees) elements are given in Table A1-5, along with sample FOR-
TRAN and C formats for reading the header. A sample of a
Lloc = local site longitude (degrees)
file header and data for January 1 is shown in Figure A1-1.
E = 229.2[0.000075 + 0.001868 cos(B)
0.032077 sin(B) 0.014615 cos(2B) A1.4.2 Hourly Records. Following the file header, 8,760
0.04089 sin(2B)] (minutes) hourly data records provide one year of solar radiation, illu-
minance, and meteorological data, along with their source and
where
uncertainty flags. Table A1-6 provides field positions, ele-
B = 360(n - 81)/365 (degrees) ment definitions, and sample FORTRAN and C formats for
n = day of the year, 1 n 365 reading the hourly records.
TAPE DECK
9734
Tape Field Numbera Tape Positionsa Element Tape Configuration Code Definitions and Remarks
002 001-005 WBAN Station number 0100198999 Unique number used to identify each station
003 006015 Solar time
41
42
TABLE A1-4 (Continued)
Typical Meteorological Year Data Format
107 049053 Engineering corrected Note: Recommend use of data in field 108.
data
049 Data code indicatord 09 Observed value corrected for known scale changes, station moves, recorder and sensor
050053 Datae 00004957 calibration changes, etc.
108 054058 Standard year Observed value adjusted to Standard Year Model. This model yields expected sky irradi-
Corrected data ance received on a horizontal surface at the elevation of the station. The value includes
Use for total horizontal 054 Data code indicatord 09 the effects of clouds. Note: All nighttime values coded as 80000 except stations noted as
solar radiation 055058 Datae 0004957 rehabilitated in the station list; for those stations, nighttime values are coded 99999.c
109, 110 059068 Additional radiation Supplemental fields A and B for additional radiation measurements: type of measure-
measurements ment specified in station-period of record list.
059064 Data code indicatorsd 09
060063 Datae
065068 Datae
111 069070 Minutes of sunshine 0060 For Local Standard Hour most closely matching solar hour. Note: Data available only for
when observations were made.
201 071072 Time of TD 1440 0023 Local Standard Hour of TD 1440 Meteorological Observation that comes closest to mid-
Observations point of the solar hour for which solar data are recorded.
202 073076 Ceiling height 00003000 Ceiling height in dekameters (dam = m 101); ceiling is defined as opaque sky cover of
0.6 or greater.
00003000 = 0 to 30,000 meters
7777 7777 = unlimited; clear
8888 8888 = unknown height of cirroform ceiling
203 077081 Sky condition Identifies observation after June 1, 1951. Coded by layer in ascending order; four layers
077 Indicator 0 are described; if fewer than four layers are present, the remaining positions are coded 0.
078081 Sky condition 00008888 The code for each layer is:
0=Clear or less than 0.1 cover
1=Thin scattered (0.10.5 cover)
2=Opaque scattered (0.10.5 cover)
3=Thin broken (0.60.9 cover)
4=Opaque broken (0.60.9 cover)
5=Thin overcast (1.0 cover)
6=Opaque overcast (1.0 cover)
7=Obscuration
8=Partial obscuration
204 082085 Visibility 00001600 Prevailing horizontal visibility in hectometers (hm = m 102).
00001600 = 0 to 160 kilometers
8888 8888 = unlimited
43
44
TABLE A1-4 (Continued)
Typical Meteorological Year Data Format
Prior to April 1970, ice pellets were coded as sleet. Beginning April 1970, sleet and small
hail were redefined as ice pellets and are coded as a 1, 2, or 3 in this position. Beginning
September 1956, intensities of hail were no longer reported and all occurrences were
recorded as a 5.
092 Occurrence of fog, blowing dust, 05 0 = None
or blowing sand 1 = Fog
2 = Ice fog
3 = Ground fog
4 = Blowing dust
5 = Blowing sand
099103 Station pressure 0800010999 Pressure at station level in kilopascals (kPa) and hundredths. 0800010999 = 80 to
109.99 kPa
207 104111 Temperature
104107 Dry bulb -700 to 0600 C and tenths
108111 Dew point -700 to 0600 -700 to 0600 = -70.0C to +60.0C
45
TABLE A1-5
Header Elements in the TMY2 Format (For First Record of Each File)
Each hourly record begins with the year (field positions 2- (with a few exceptions), observations or measurements were
3) from which the typical month was chosen, followed by the made at the hour indicated. A few of the meteorological
month, day, and hour information in field positions 4-9. The elements had observations, measurements, or estimates made
times are in local standard time (previous TMYs based on
at daily, instead of hourly, intervals. Consequently, the data
SOLMET/ERSATZ data are in solar time).
For solar radiation and illuminance elements, the data values for broadband aerosol optical depth, snow depth, and
values represent the energy received during the 60 minutes days since last snowfall represent the values available for the
preceding the hour indicated. For meteorological elements day indicated.
1 1 1 1 1
1 2 3 4 5 6 7 8 9 0 1 2 3 4
1234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789012
(for field position identification only)
Figure A1-1 Sample file header and data in the TMY2 format for January 1
47
TABLE A1-6
Data Elements in the TMY2 Format (For All Except the First Record)
DATE HOUR
04-Jan 15
HVAC BESTEST Cases E100-E200 Output Form Sec5- STANDARD 140 OUTPUT FORMMODELING NOTES
3out.XLS
INSTRUCTIONS: See Annex A2.
INSTRUCTIONS:
Physical Meaning of Option Used: Optional Settings or Modeling Capabilities (from simplest to
most detailed):
Simulated Effect:
SOLAR DISTRIBUTION = 0; SOLAR DISTRIBUTION = 1
Optional Settings or Modeling Capabilities:
Setting or Capability Used: SOLAR DISTRIBUTION = 1
Setting or Capability Used:
Physical Meaning of Option Used:
Physical Meaning of Option Used:
Beam radiation falling on each surface is calculated by ray
(Include more alternative feature descriptions using this tracing. Beam radiation not initially absorbed is diffusely
format if applicable to the test.) reflected.
Int interior
(This annex is not part of the standard. It is merely infor-
mative and does not contain requirements necessary for Intgen internally generated sensible heat gains
conformance to the standard. It has not been processed
according to the ANSI requirements for a standard and IR infrared radiation
may contain material that has not been subject to public
review or a consensus process. Unresolved objectors on L light mass
informative material are not offered the right to appeal
NA not applicable
at ASHRAE or ANSI.)
ODB outdoor dry-bulb temperature
ANNEX B1
TABULAR SUMMARY OF TEST CASES Orient orientation
Tables B1-1a and B1-1b include a tabular summary of the
PLR part-load ratio
building thermal envelope and fabric load test cases described
in Section 5.2, in SI units only. Tables B1-2a and B1-2b S south
include a tabular summary of the HVAC Equipment Perfor-
mance test cases described in Section 5.3, in SI and I-P units, Shade window shading device: horizontal overhang
respectively. and/or vertical fins
Nomenclature SHR sensible heat ratio
Abbreviations and symbols used in Tables B1-1a, B1-1b,
B1-2a and B1-2b are listed below. SS sunspace
1.0mH horizontal overhang projecting 1 meter SW shortwave (solar spectrum) radiation
perpendicular to window surface as in Figure 2
(Section 5.2.2.1.1.1) V forced ventilation cooling
SET-
POINTS OPAQUE SURFACE OPAQUE SURFACE
53
54
TABLE B1-1a Standard 140 Case Descriptions, Low Mass In-Depth (Continued)
SET-
POINTS OPAQUE SURFACE OPAQUE SURFACE
SET-
POINTS OPAQUE SURFACE OPAQUE SURFACE
55
shading/mass interaction.
56
TABLE B1-1b Standard 140 Case Descriptions, Basic and In-Depth Cases (Continued)
SET-
POINTS OPAQUE SURFACE OPAQUE SURFACE
ANNEX B3 ANNEX B4
INFILTRATION AND FAN ADJUSTMENTS EXTERIOR COMBINED RADIATIVE AND
FOR ALTITUDE CONVECTIVE SURFACE COEFFICIENTS
The decline in air density with altitude may be expressed
according to the following exponential curve fit: ASHRAE and some simulation programs (e.g., BLAST
3.0 Level 193, using its option for simple outside surface
Pair,u = Pair,0 e(a)(elev) conductance) calculate the exterior combined radiative and
convective surface coefficient as a second order polynomial in
where wind speed of the form:
Pair,u = air density at specified elevation
Pair,0 = air density at sea level h = a1 + a2V + a3V2,
e = inverse Ln
a = -1.219755 10-4/m where the units of h are W/m2K, and the a coefficients are
elev = elevation in meters (m) dependent on the surface texture. Assuming a surface texture
of brick or rough plaster and a mean annual wind speed of 4.02
Air density at sea level = 1.201385 kg/m3. m/s, then the information in Table B4-1 is applicable.16
For cases where the exterior infrared emittance = 0.9, the
Air density at 1609 m = 0.987298 kg/m3. exterior combined surface coefficient for all walls and roofs
will be 29.3 W/m2K, and the exterior combined surface coef-
The corrected infiltration rate for 1609 m altitude = (spec-
ficient for glass and high-conductance walls/opaque windows
ified rate) (0.987298/1.201385). (For example, 0.5 ACH
will be 21.0 W/m2K.
becomes 0.41 ACH, and 1 ACH becomes 0.822 ACH.)
The corrected vent-fan capacity for 1609 m altitude = For cases where the exterior infrared emittance = 0.1, the
(specified capacity under standard conditions at sea level) exterior combined surface coefficient for all walls and roofs
(0.987298/1.201385).a (For example, 1703.16 Sm3/h will be 25.2 W/m2K, and the exterior combined surface coef-
becomes 1400 m3/h.)b ficient for high-conductance walls/opaque windows will be
16.9 W/m2K.
For convenience of input, the exterior combined radiative
and convective surface coefficient for the transparent window
and the opaque window are assumed to be the same, even
though the hemispherical infrared emittance of ordinary
uncoated window glass is usually 0.84. This is equivalent to
assuming that the emittance of the glass is 0.9.
Convective and radiative portions of these coefficients are
disaggregated in Annex B5.
TABLE B4-1
Polynomial Coefficients for Describing Exterior
Surface Coefficient as a Function of Wind Speed
Material a1 a2 a3
Stucco 11.58 5.894 0.0
Brick/rough 12.49 4.065 0.028
plaster
Concrete 10.79 4.192 0.0
a Standard conditions (S) = U.S. Standard Atmospheric Condi- Clear pine 8.23 4.0 -0.057
tions: dry air behaving as a perfect gas, 15C, 101.321 kPa (2001
ASHRAE HandbookFundamentals,3 p. 6.1). Smooth plaster 10.22 3.1 0.0
b Sm3/h = standard cubic meters per hour. Glass 8.23 3.33 -0.036
ANNEX B5 ANNEX B6
INFRARED PORTION OF FILM COEFFICIENTS INCIDENT ANGLE-DEPENDENT WINDOW OPTICAL
PROPERTY CALCULATIONS
The infrared portion of film coefficients is based on the B6.1 Calculation of Optical Properties Listed in Table 7
linearized gray-body radiation equation:17 In Table 7 (Section 5.2.1.11) window transmittance and
inner and outer pane absorptances are based on data from, and
hi = 4T3, the calculation methods associated with, Table B6-1. In
Table 7, the absorptance values for incidence angles of 10 and
where 50 are from cosine-of-incident-angle interpolations of values
= infrared emittance listed in Table B6-1. Reflectances listed in Table 7 are based
on the formula:
= 5.67 * 10-8 W/m2K4 (Stefan-Boltzmann constant)
Reflectance = 1 - (transmittance) - (outer pane absorptance) -
T = average temperature of surrounding surfaces [assumed (inner pane absorptance).
10C (283 K) for outside, 20C (293 K) for inside]
Solar heat gain coefficients (SHGC) are calculated based
K = Kelvin (absolute 0 = -273.16C) on the equations of the 1993 ASHRAE Handbook
hi = infrared radiation portion of surface coefficient Fundamentals18 (p. 27.18) using the optical properties listed
in Table 7 and the thermal properties listed in Table 6 (Section
hc = convective portion of surface coefficient 5.2.1.11).
hs = total combined interior surface coefficient Nomenclature and associated equations for calculating
the angle-dependent solar transmittance of glass in air listed in
ho = total combined outside surface coefficient Table B6-1 are listed below. Inner and outer pane solar absorp-
For convenience of input, the interior combined radiative tances listed in Table B6-1 were calculated using the program
and convective surface coefficient for the opaque window and ESP-WIN.19
the transparent window are assumed the same, even though the
hemispherical infrared emittance of ordinary uncoated Nomenclature
window glass is usually 0.84. This is equivalent to assuming ABSi inner window pane solar absorptance
that the emittance of the glass is 0.9. ABSo outer window pane solar absorptance
TABLE B5-1 AOI angle of incidence
Disaggregation of Film Coefficients AOR angle of refraction
Versus Surface Infrared Emittance INDRA index of refraction for air = 1.0
for Various Surface Types INDRG index of refraction for glass = 1.526 (for this
case)
Very Smooth Surface Outsidea = 0.9 = 0.84 = 0.1
RPERP perpendicular reflectance (component of
(T = 10C) (283 K) polarization)
hi (W/m2K) 4.63 4.32 0.51 RPAR parallel reflectance (component of
2
ho (W/m K) polarization)
21 20.69 16.88
hc (W/m2K) = ho - hi 16.37 16.37 16.37 R reflectance: (RPERP + RPAR)/2
Inside Surface n number of panes of glass = 2 (for this case)
(T = 20C) (293 K) Tr transmittance due to reflectance losses
hi (W/m2K) 5.13 4.79 0.57 (transmittance if there were just reflectance
2 losses and no absorptance losses)
hs (W/m K) 8.29 7.95 3.73
Tabs transmittance due to absorptance losses
hc (W/m2K) = hs - hi 3.16 3.16 3.16 (transmittance if there were just absorptance
Brick/Rough Plaster Outsidea losses and no reflectance losses)
(T = 10C) (283 K) T total transmittance Tr Tabs
hi (W/m2K) 4.63 0.51 K extinction coefficient = 0.0196/mm (for this
case)
ho (W/m2K) 29.3 25.18
TH thickness of glass = 3.175 mm (for this case)
hc (W/m2K) 24.67 24.67 L path length = TH/(cos AOR)
a
Based on a mean annual wind speed of 4.02 m/s for outside ARCSIN INVSIN
surfaces. e INV Ln = EXP (value)
AOI
(deg) INDRA INDRG n K (mm) TH (mm) AO (rad) AOR (rad)
89.99 0.0011 0
ANNEX B7
DETAILED CALCULATION OF SOLAR FRACTIONS
B7.1 Solar Fraction Approximation Algorithm
Solar fraction approximations are calculated from
SFn = B1n + B2n + B3n + BRn,
Figure B7-1 Shape factor for adjacent rectangles in
where perpendicular planes sharing a common edge.20
n = a particular surface
SF = total solar fraction.
No transmitted solar radiation is assumed to be directly The example results of informative Annex B8 are drawn
absorbed by the zone air at any time during this analysis. from IEA BESTEST.14 The IEA BESTEST test specification
Table B7-1 summarizes the interior solar distribution contained a minor error in its approximate solar fractions table
fractions for the various window configurations and interior for interior = 0.9. In the affected cases (270, 290, 300, 310,
surface absorptances that arise in the standard. and 320) two of the sets of example results used the approxi-
Fractional values for the walls with windows include the mate solar fractions for inputs: SERIRES/SUNCODE 5.721
portion of the solar radiation absorbed by the glass (as it passes and SERIRES 1.2.22 Results from the other programs are not
back out the window) conducted into the zone. Solar radiation affected because they use various methods for automatically
absorbed by the glass (and conducted inward) as it initially calculating interior solar distribution as discussed in IEA
passes into the building is treated separately by most programs BESTEST, and DOE-2.1D23 was not able to vary interior solar
in their window optical algorithms, so it is therefore not absorptance on exterior walls. We were able to correct the
included in the values in Table B7-1. inputs for SERIRES/SUNCODE 5.7 and provide new exam-
In the cases with windows oriented east and west, solar ple results for the standard; however, we were not able to
fractions are assumed to be the same as for the south-oriented adjust the SERIRES 1.2 results. Table B7-2 compares the
cases with similar interior solar absorptance, except that the current Standard Method of Test (revised) and prior IEA
fractions are adjusted in proportion to the change in the opaque BESTEST (erroneous) solar fractions; the value for solar lost
areas of the east, west, and south walls caused by moving the did not change. The effect of changing the solar fractions is
windows. shown using SERIRES/SUNCODE 5.7 in Table B7-3; there is
For Case 960 (sunspace) solar loss was calculated using only a minor effect on heating and sensible cooling annual
the same assumptions as for the south window orientation total loads and annual peak hourly loads.
TABLE B7-1
Interior Solar Distribution Fractions Versus Window Orientation and Interior Shortwave Absorptance
TABLE B7-3
Sensitivity Test Results of Varying Solar Fractions using SERIRES/SUNCODE 5.7
ANNEX B8 Nomenclature
EXAMPLE RESULTS FOR BUILDING THERMAL Results are grouped by case numbers; e.g., 395 is Case
ENVELOPE AND FABRIC LOAD TESTS
395 (Section 5.2.3.16). Sensitivity results are listed using two
The example results from various detailed building case numbers separated by a minus sign; e.g., 610-600 is the
energy simulation programs that applied the tests of Section difference between Case 610 (Section 5.2.2.1.1) and Case 600
5.2 are presented here in tabular and graphic form. These (Section 5.2.1).
results can be used for a comparison with the software being ALLCODE relating to a summary of all listed results
tested. Alternatively, a user can run a number of different
BEL/UK Belgium, Vrije Universiteit / United
programs through this standard method of test and draw
Kingdom, Building Research Establishment
comparisons from those results independently or in conjunc-
tion with the results listed here. In either case, when making BLAST BLAST 3.0 level 193 v. 1 (see Table B11-1)
comparisons the user should employ the diagnostic logic C sensible cooling load sensitivity
presented in informative Annex B9, Section B9.4. CLDY cloudy day results
The building energy simulation computer programs used CLR clear day results
to generate example results are described in informative COOL annual sensible cooling load sensitivity
Annex B11. These computer programs have been subjected to
DELTA sensitivity between listed cases
a number of analytical verification, empirical validation, and
comparative testing studies. However, there is no such thing as DOE2 DOE2.1D 14 (see Table B11-1)
a completely validated building energy simulation computer ESP ESP-RV8 (see Table B11-1)
program. All building models are simplifications of reality. ESP-DMU ESP-RV8 (see Table B11-1)
The philosophy here is to generate a range of results from EW.SHADE east and west windows with overhangs and
several programs that are generally accepted as representing fins
the state-of-the-art in whole building energy simulation
EW.WIN east and west windows
programs. Regarding the presented results, to the extent possi-
ble input errors or differences have been eliminated. Thus, for HIMASS heavyweight construction
a given case the range of differences between results presented HEAT annual heating load sensitivity
in the informational Annex B8 represents algorithmic differ- H heating load sensitivity
ences among these computer programs for comparative enve- HR hour
lope tests. For any given case, a tested program may fall
KW kilowatt
outside this range without necessarily being incorrect.
However, it is worthwhile to investigate the source of signifi- KWH/M2 kilowatt-hours per square meter
cant differences, as the collective experience of the authors of LOMASS lightweight construction
this standard is that such differences often indicate problems MAX maximum
with the software or its usage, including, but not limited to, MAX/MIN maximum minimum
(a) user input error, where the user misinterpreted or MIN minimum
mis-entered one or more program inputs;
MWH megawatt-hour
(b) a problem with a particular algorithm in the program;
NT.VENT night ventilation control strategy
(c) one or more program algorithms used outside their
intended range. OP.WIN opaque window/high conductance wall
Also for any given case, a program that yields values in OP.WINDOW opaque window/high conductance wall
the middle of the range established by the example results PCOOL peak hour sensible cooling load sensitivity
should not be perceived as better or worse than a program that PHEAT peak hour heating load sensitivity
yields values at the borders of the range. S south
For the convenience to users who wish to plot or tabulate S.SHADE south overhang
their results along with the example results, an electronic
version of the example results has been included with the file S.WIN south window
RESULTS5-2.XLS on the accompanying CD. Documentation S.WINDOW south window
regarding RESULTS5-2.XLS has been included with the file SERIRES SERIRES 1.2 (see Table B11-1)
CODENAME: ESP BLAST DOE2.1D SUNCODE SERIRES S3PAS TRNSYS TASE ALLCODE ALLCODE
COUNTRY:
CASE # UK-DMU US/IT USA USA UK SPAIN BEL/UK FINLAND MAX/MIN MEAN
920WEST 0.674 0.681 0.687 0.657 0.641 0.654 0.648 1.072 0.663
900SOUTH 0.650 0.671 0.652 0.650 0.628 0.647 0.623 1.078 0.646
CODENAME: ESP BLAST DOE2.1D SUNCODE SERIRES S3PAS TRNSYS TASE ALLCODE ALLCODE
COUNTRY:
CASE # UK-DMU US/IT USA USA UK SPAIN BEL/UK FINLAND MAX/MIN MEAN
930/920 W 0.182 0.346 0.196 0.216 0.329 0.339 1.902 0.268
910/900 S 0.170 0.209 0.165 0.188 0.183 0.205 0.115 1.822 0.177
B9.4.3 Mass Interaction Tests. Further diagnostic infor- if a disagreement is uncovered for one of the cases, then fix it
mation can be obtained regarding thermal mass interactions and rerun all the E100 series cases.
using the diagnostic logic flow diagram of Figure B9-4. When
disagreement among results occurs, this diagram sometimes B9.5.2 Consideration of Quasi-Analytical Solution
returns to the low-mass, in-depth diagnostics (Figure B9-2) Results. As a minimum, the user should compare output with
even though the program may have already showed agree- the quasi-analytical solution results found in Annex B16. The
ment in the low-mass basic tests. The reason for this is that the user may also choose to compare output with the example
high-mass cases may reveal disagreements that the low-mass simulation results in Annex B16 or with other results that
cases did not expose because were generated using Section 5.3 of this test procedure. Infor-
(a) the disagreement is more readily detectable when mass is mation about how the quasi-analytical solutions and example
present, simulation results were produced is included in Annex B17.
(b) the disagreement was not previously detectable because For convenience to users who wish to plot or tabulate their
of compensating differences, results along with the quasi-analytical solution or example
(c) the disagreement was not previously detectable because simulation results, or both, an electronic version of the exam-
of other unknown interactions.
ple results has been included with the file RESULTS5-3.XLS
B9.5 Diagnostic Logic Flow Diagram for HVAC Equip- on the accompanying CD. Regarding determination of agree-
ment Performance Tests (Section 5.3) ment of results discussed in B9.2.2, in making this determina-
B9.5.1 General Description. The E100 series cases tion for the HVAC equipment performance tests of Section
(E100 through E200) are steady-state cases that test basic per- 5.3, the user should consider that the quasi-analytical solution
formance map modeling capabilities and utilize comparisons results given in Annex B16 represent a mathematical truth
with quasi-analytical solutions. The diagnostic logic flow dia- standard (i.e., a mathematically provable and deterministic
gram for these cases (Figure B9-5) indicates similar diagnos- set of results based on acceptance of the underlying physical
tics for dry-coil and wet-coil (without and with assumptions represented by the case specifications). Note that
dehumidification) cases. This is really one continuous diag- although the underlying physical assumptions of the case def-
nostic path to be implemented for both dry-coil and wet-coil initions of the mechanical equipment are consistent with
cases. Performing and analyzing results of the E100 series those of typical manufacturer equipment performance data,
tests in blocks, such as E100E140 and E150E200, or E100 they are by definition a simplification of reality and may not
E200, all at once is recommended. For the E100 series cases fully represent real empirical behavior.
Sheet Description
A Raw data compilation.
YD For inputting new results (your data); see above for instructions.
B G, L Results from each simulation program. E is blank.
H J Results from the quasi-analytical solutions.
Q Formatted summary results tables including quasi-analytical solutions, simulations and statistics. Your data auto-
matically appears on the right side of each table. See below for Sheet Q table locations.
R Formatted summary results tables and statistics for quasi-analytical solutions only. See below for Sheet R table
locations. (Sheet R is not reproduced in the hardcopy.)
COP thru QCL- 26 summary charts (one per sheet). Import of your data into these charts is not automated. However the data does
QZL automatically appear on the right side of the tables used for making the charts. See below.
(26 sheets)
Data-x (last 5 5 data sheets that the 26 data charts are linked to. Your data automatically appears on the right side of each data
sheets) table.
Contents of Sheet Q:
Contents of Sheet R:
TABLE B11-1
Computer Programs, Program Authors, and Producers of Example Results
TABLE B11-2
Ability of Participating Computer Programs to
Explicitly Model In-Depth Cases That Vary Selected Radiative Properties
outputs is standard time, while the time convention for Typical (This annex is not part of the standard. It is merely infor-
Meteorological Year (TMY) weather data is solar time (see mative and does not contain requirements necessary for
Annex A1, Section A1.3, for discussion of the difference conformance to the standard. It has not been processed
between solar time and standard time). The time convention is
therefore most correctly modeled by software that rebins according to the ANSI requirements for a standard and
TMY data into hourly data based on local standard time. A may contain material that has not been subject to public
tabulation of how the time convention was modeled by some review or a consensus process. Unresolved objectors on
of the software used to generate the example results given in informative material are not offered the right to appeal
informative Annex B8 is noted in Table B11-3. at ASHRAE or ANSI.)
Since software being tested by Standard 140 may not be
rebinning TMY data, it is important to understand the poten-
tial differences in Standard 140 results that can be generated ANNEX B12
by applying a time convention different from that specified in TEMPERATURE BIN CONVERSION PROGRAM
Section 5.1.1. In Standard 140 such differences are mini-
mized, and are primarily related to the equation of time (see To reduce calculation time in Section 6.1.7.1, a computer
Annex A1, Section A1.3) because the building site has been program or spreadsheet binning function may be used. An
located within 0.1 longitude of the standard meridian. For this example of such a computer program is described below.
reason Standard 140 does not provide a good test for the ability Included on the attached CD is an executable program
to calculate solar incidence angles for longitudes far away
from the standard meridian. (TMPBIN.EXE) that may be used for sorting annual hourly
To estimate the potential difference caused by deviating temperature output into bins of 1C. The bins range from
from the time convention in Section 5.1.1, a series of sensitiv- -50C to 99C. The program will abort if temperatures outside
ity tests were performed using DOE-2.1D.23 In these tests this range are encountered.
solar incidence angle calculations were intentionally distorted The annual hourly temperature file must be sequential,
by specifying the longitude of the site in the input deck as
different from the longitude used in the TMY weather data and each line must not contain more than one occurrence of the
processor. Such a site longitude shift is based on 1 of plane- temperature of interest. The program reads either free format
tary rotation per 4 minutes and was limited to 4.3 correspond- or formatted data. In free format mode the number of the
ing to the maximum shift that would be caused by the equation column in which the data resides is needed (the program inter-
of time. actively explains this input). No alpha characters are allowed
The effect of distorting the calculations was negligible in the data columns in free format mode. A line with alpha
(1%) for most outputs. The most significant potential differ- characters in the data column will be escaped.
ences identified are:
It is advisable to use the formatted option in which alpha-
3% for annual peak sensible cooling load in the east/ numeric characters prior to the data of interest are skipped
west window cases (with or without shading present); over, using X format. The limitation is that the format has to
8% for hourly sensible cooling loads without window be in either F or E FORTRAN formats. Even if the
shading (9% with shading present) and 8% for hourly temperature data in the file were integers, the format has to be
solar transmission (with or without shading present) for a REAL type number. In such cases integers must be read
during hours when the equation of time causes the max-
imum difference between solar time and standard time in F format with 0 digits (F3.0).
occurring in February, October, and November. How- Output from the bin program is written into a file with the
ever, the differences for these worst case hours cancel same name as the temperature data file but with the extension
out on an annual basis and are not coincident with .BND.
occurrence of annual peak loads so that the effect on
results required to be entered in the standard output The program will prompt the user for input with some
report is negligible. explanatory remarks. It displays dots after each 10 lines
Since the worst potential difference for results required to processed to show it is running. When finished it will show the
be entered in the standard output report is 3%, and that for just number of lines processed and the number of lines that
peak sensible cooling loads in the cases with east/west contained errors or unreadable characters. If the number of
windows, it is reasonable to conclude that the potential differ-
ence in results generated for Standard 140 due to deviating errors is substantial then the input file and format should be
from the solar time convention of the TMY weather data is corrected. Run and error information is stored in a file with the
negligible. same name as the input data file but with the extension .INF.
ANNEX B13
COP DEGRADATION FACTOR (CDF) AS
A FUNCTION OF PART-LOAD RATIO (PLR)
TABLE B17-1
Participating Organizations and Computer Programs
Model Authoring Organization Implemented By Abbreviation
Quasi-analytical solution Hochschule Technik & Architektur Luzern, Hochschule Technik & Architektur HTAL1
with ideal controller model Switzerland (HTAL) Luzern, Switzerland
Quasi-analytical solution Hochschule Technik & Architektur Luzern, Hochschule Technik & Architektur HTAL2
with realistic controller Switzerland Luzern, Switzerland
model
Quasi-analytical solution Technische Universitt Dresden, Germany Technische Universitt Dresden, TUD
with ideal controller model (TUD) Germany
CA-SIS V1 Electricit de France, France (EDF) Electricit de France, France CA-SIS
CLIM2000 2.1.6 Electricit de France, France Electricit de France, France CLM2000
DOE-2.1E-088 LANL/LBNL/ESTSC,a,b,c USA d
CIEMAT, Spain DOE21E/CIEMAT
DOE-2.1E-133 LANL/LBNL/JJH,a,b,e USA NREL/JNA, USA f
DOE21E/NREL
ENERGYPLUS 1.0.0.023 LBNL/UIUC/CERL/OSU/GARD Analytics/ GARD Analytics, USA Energy+
FSEC/DOE-OBT,a,g,h,i,j,k
TRNSYS 14.2-TUD with University of Wisconsin, USA; Technische Technische Universitt Dresden, TRN-id
ideal controller model Universitt Dresden, Ger. Germany TRNSYS-ideal
TRNSYS 14.2-TUD with University of Wisconsin, USA; Technische Technische Universitt Dresden, TRN-re
real controller model Universitt Dresden, Ger. Germany TRNSYS-real
aLANL:
Los Alamos National Laboratory
b
LBNL: Lawrence Berkeley National Laboratory
c
ESTSC: Energy Science and Technology Software Center (at Oak Ridge National Laboratory, USA)
d
CIEMAT: Centro de Investigaciones Energeticas, Medioambientales y Tecnologicas
e
JJH: James J. Hirsch & Associates
fNREL/JNA: National Renewable Energy Laboratory/J. Neymark & Associates
gUIUC: University of Illinois Urbana/Champaign
hCERL: U.S. Army Corps of Engineers, Construction Engineering Research Laboratories
iOSU: Oklahoma State University
jFSEC: University of Central Florida, Florida Solar Energy Center
kDOE-OBT: U.S. Department of Energy, Office of Building Technology, State and Community Programs, Energy Efficiency and Renewable
Energy
solution process for a model can be perfect, while the model (h) ETNA BESTEST Empirical Validation Test Specification
remains faulty or inappropriate for a given physical situation or (i) Daylighting HVAC Interaction Tests for the Empirical
purpose; for example, using a one-dimensional conduction Validation of Building Energy Analysis Tools44
model where two-dimensional conduction dominates.
The methodologies may be further subdivided within (j) Economizer Control Tests for the Empirical Validation
each category as building envelope tests and mechanical of Building Energy Analysis Tools
equipment tests, creating a matrix of six areas for testing (k) A number of test suites that are being developed by
including: National Renewable Energy Laboratory and researchers
(a) Comparative Tests - Building Envelope in International Energy Agency (IEA) member nations
(b) Comparative Tests - Mechanical Equipment under auspices of IEA Solar Heating and Cooling Task 34
(c) Analytical Verification - Building Envelope and IEA Energy Conservation in Buildings and Commu-
(d) Analytical Verification - Mechanical Equipment nity Systems Annex 43 (IEA SHC 34/ECBCS 43).45
(e) Empirical Validation - Building Envelope
(f) Empirical Validation - Mechanical Equipment. (Note: Since items e, g, h, and j are works in progress, no
references can yet be cited for them.)
B18.2 Other Relevant Research
There are a number of other simulation test suites in vari- B18.2.1 ASHRAE RP-105239 These tests are analytical
ous stages of completion that could eventually be included in verification tests that focus on the ability to model thermal
Standard 140. These include, among others: physics related to the building fabric. The tests were devel-
(a) ASHRAE RP-1052, Development of an Analytical Veri- oped by Oklahoma State University as an ASHRAE research
fication Test Suite for Whole Building Energy Simulation project. Cases allow the comparison of analytical solutions to
Programs Building Fabric39 program results for the purpose of testing the ability of pro-
(b) Home Energy Rating System Building Energy Simula- grams to model steady-state convection and conduction, exte-
tion Test (HERS BESTEST)40 rior and interior infrared radiation, exterior solar radiation,
(c) ASHRAE RP-865, Development of Accuracy Tests for transient conduction, infiltration, convective and radiant
Mechanical System Simulation41 internal gains, ground coupling, solar transmission through
(d) Building Energy Simulation Test and Diagnostic windows, internal (transmitted) solar radiation distribution,
Method for Heating, Ventilating, and Air-Conditioning and external shading.
Equipment Models (HVAC BESTEST), Fuel-Fired Fur- B18.2.2 HERS BESTEST HERS BESTEST40 is similar
nace Test Suite42 to the current test included in Section 5.2 of Standard 140 in
(e) International Energy Agency Building Energy Simula- that it is a comparative test that focuses on the building enve-
tion Test and Diagnostic Method for Heating, Ventilating, lope. However, HERS BESTEST was designed for testing
and Air-Conditioning Equipment Models (HVAC BEST- more simplified building energy analysis tools commonly
EST), Volume 2: Cases E300-E545 used for residential modeling and specifically for home
(f) RADTEST Radiant Heating and Cooling Test energy rating systems. As such, it goes into less detail in test-
Cases43 ing specific building physics algorithms than Standard 140
(g) Proposed IEA BESTEST Ground-Coupled Cases and uses more realistic test cases.
TABLE C-1
Addendum to ANSI/ASHRAE Standard 140-2001
This standard is maintained under continuous maintenance procedures by a Standing Standard Project Committee (SSPC) for
which the Standards Committee has established a documented program for regular publication of addenda or revisions, includ-
ing procedures for timely, documented, consensus action on requests for change to any part of the standard. SSPC consider-
ation will be given to proposed changes at the Annual Meeting (normally June) if proposed changes are received by the MOS
no later than December 31. Proposals received after December 31 shall be considered by the SSPC no later than at the Annual
Meeting of the following year.
Proposed changes must be submitted to the Manager of Standards (MOS) in the latest published format available from the
MOS. However, the MOS may accept proposed changes in an earlier published format, if the MOS concludes that the differ-
ences are immaterial to the proposed change submittal. If the MOS concludes that a current form must be utilized, the proposer
may be given up to 20 additional days to resubmit the proposed changes in the current format.
FORM FOR SUBMITTAL OF PROPOSED CHANGE TO
ASHRAE STANDARD UNDER CONTINUOUS MAINTENANCE
NOTE: Use separate form for each comment. Submittals (MS Word 2000 preferred) may be attached to e-mail (preferred),
submitted on diskettes or CD, or submitted in paper by mail or fax to ASHRAE, Manager of Standards, 1791 Tullie Circle,
NE, Atlanta, GA 30329-2305. E-mail: change.proposal@ashrae.org. Fax +1-404/321-5478.
1. Submitter:
Affiliation:
I hereby grant the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) the non-exclusive royalty rights,
including non-exclusive rights in copyright, in my proposals. I understand that I acquire no rights in publication of the standard in which my
proposals in this, or other analogous, form is used. I hereby attest that I have the authority and am empowered to grant this copyright release.
Use underscores to show material to be added (added) and strike through material to be deleted (deleted). Use additional pages if needed.
5. Proposed change:
[ ] Check if attachments or referenced materials cited in this proposal accompany this proposed change. Please verify that all
attachments and references are relevant, current, and clearly labeled to avoid processing and review delays. Please list your
ELECTRONIC PREPARATION/SUBMISSION OF FORM FOR
PROPOSING CHANGES
An electronic version of each change, which must comply with the instructions in the Notice and the Form, is the pre-
ferred form of submittal to ASHRAE Headquarters at the address shown below. The electronic format facilitates both
paper-based and computer-based processing. Submittal in paper form is acceptable. The following instructions apply to
change proposals submitted in electronic form.
Use the appropriate file format for your word processor and save the file in either Microsoft Word 7 (preferred) or
higher or WordPerfect 5.1 for DOS format. Please save each change proposal file with a different name (example,
prop001.doc, prop002.doc, etc., for Word filesprop001.wpm, prop002.wpm, etc., for WordPerfect files). If supple-
mental background documents to support changes submitted are included, it is preferred that they also be in electronic
form as wordprocessed or scanned documents.
Electronic change proposals may be submitted either as files (MS Word 7 preferred) attached to an e-mail (uuencode
preferred) or on 3.5 floppy disk. ASHRAE will accept the following as equivalent to the signature required on the
change submittal form to convey non-exclusive copyright:
Files attached to e-mail: Electronic signature on change submittal form (as a picture; *.tif,
or *.wpg).
Files on disk: Electronic signature on change submittal form (as a picture; *.tif,
or *.wpg), or a letter with submitters signature accompanying
the disk or sent by facsimile (single letter may cover all of propo-
nents proposed changes).
The form and instructions for electronic submittal may be obtained from the Standards section of ASHRAEs Home
Page, http://www.ashrae.org, or by contacting a Standards Secretary, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305.
Phone: 404-636-8400. Fax: 404-321-5478.
Email: standards.section@ashrae.org.
POLICY STATEMENT DEFINING ASHRAES CONCERN
FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES
ASHRAE is concerned with the impact of its members activities on both the indoor and outdoor environment. ASHRAEs
members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and
components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted
standards and the practical state of the art.
ASHRAEs short-range goal is to ensure that the systems and components within its scope do not impact the indoor and
outdoor environment to a greater extent than specified by the standards and guidelines as established by itself and other
responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive technical committee structure,
continue to generate up-to-date standards and guidelines where appropriate and adopt, recommend, and promote those new
and revised standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date standards and design considerations as the material is
systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek
out and disseminate information from other responsible organizations that is pertinent, as guides to updating standards and
guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the systems
intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAEs primary concern for environmental impact will be at the site where equipment within ASHRAEs scope
operates. However, energy source selection and the possible environmental impact due to the energy source and energy
transportation will be considered where possible. Recommendations concerning energy source selection should be made by
its members.
86469
PC 12/04