Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
00
Printed in the U S . A , ( 198S Perg~trnon P r e ~ ].Id.
MEHDI N. BAHADORI
College of Architecture and Environmental Design, Arizona State University, Tempe. AZ 85287
USA
( Received 20 August 1984; revision received 16 November 1984: ate'opted 13 December 1984)
Abstract--A design is proposed to improve the performance of wind towers (or Baud-Geers) for natural
ventilation and passive cooling. Under similar climatological and design conditions, the new design
is capable of delivering air to the building at higher flow rates. It can also cool the air evaporatively
to lower temperatures. Higher airflow rates and the evaporative cooling capability of the new Baud-
Geer design can be fully utilized at night in summer to cool the building mass to lower temperatures.
Momentum, mass and energy analyses are carried out for the proposed design. The results are
presented in graphical forms which may be used as guidelines for employing the design for specific
applications in the hot, arid areas of the world. An example is worked out to show the use of the
results.
119
120 M. N. BAHADORI
Baud-Geers. The design, as shown in Fig. 2, con-
sists of three distinct improvements. They are
(a) A tower head which accepts wind blowing in
X any direction, and prevents the air from leaving
the other tower openings.
(b) An energy storing system or column with a sub-
\ stantial increase in the heat transfer area.
\ SECTION X-X (c) Full utilization of the potential of evaporative
\
\
FIRST cooling of air by wetting the wall areas of the
\
\ FLOOR column.
\ These concepts are further discussed in the follow-
\
ing sections.
\ . . . . i
\ \\\"
2.1 Design of the tower head
GROUND FLOOR
OR BASEMENT In areas with variable wind directions the tower
head may be designed with one-way dampers. Fig-
ure 2 shows a possible design. When the wind pres-
\\\ sure coefficient at a tower opening is positive the
damper at that opening is open, while the other
Fig. 1. Airflow pattern in a conventional wind tower. dampers are closed. The dampers may be such as
shown in the figure, or they may be of durable cur-
a design which is believed to improve the perform- tain material hung behind the screens. The screens
ance of the wind towers, and to eliminate or min- are of large openings which result in small pressure
imize some of the disadvantages mentioned above. losses and are considered to prevent birds and
Furthermore, the implementation of the design larger insects from entering the tower.
does not require sophisticated technology, and can An alternate design which reduces the costs ap-
readily be employed in most of the developing preciably is to eliminate the curved nature of the
countries. entrance region at the cost of allowing additional
In humid areas, where air motion with respect pressure drop in this section. The screens and dam-
to the skin plays an important role in maintaining pers (or curtains) are the same as the previous de-
thermal comfort, the proposed design can still be sign, but the tower head has no specially designed
used to maintain high air flow rates through the entrance section to reduce the pressure losses (see
building. For example, people seated at rest and Fig. 2).
wearing light-weight clothing, feel thermally com- Another design of the tower head is to make it
fortable under the following conditions of air dry- to swivel into the wind, admitting air into the tower
bulb temperature, relative humidity and speed[5]: when wind is blowing in any direction.
Tab = 27.2C, ~b = 20% and V = 0.2m/s; 2.2 Design of" thermal energy storage section of
the Baud-Geer
or
The convective heat transfer coefficient of air
Tab=28.2C, +=60% and V = l . 5 m / s , blowing over energy storing material is generally
low. Thus, for a given quantity of heat to be trans-
where the mean radiant temperature (Tmr) of the ferred to the material, the surface area must be
surrounding surfaces is assumed to be equal to the large. Large surface areas must be selected without
room air temperature. When Tmr is lower the same excessive pressure losses of air as it flows over
comfort can be accomplished at a higher air tem- them. Figure 2 shows the cross section of a possible
perature. design. The energy storage material is baked (but
In this article, after presenting the design, a the- unglazed) clay, made in the form of long conduits.
oretical analysis is carried out to evaluate the per- The conduits may have circular, rectangular, or as
formance of the system under various environmen- in Fig. 2, square cross sections. A wall thickness
tal conditions. The results of this analysis will help of about 10 mm or less may be considered for the
architects or designers to select the size and di- conduits. For a wind tower cross section (normal
mensions of a Baud-Geer to provide natural ven- to the airflow) of 1 m 2 and square conduits of 10
tilation and passive cooling in a specific location. cm outside dimensions and 1 cm wall thickness, the
Finally, an example is worked out to demonstrate total heat transfer area, mass and the thermal ca-
the design procedure. pacitance of 50 conduits which can be placed in the
tower are, respectively, 36 m 2, 306 kg and 256
kJ/C per 1 m height of the tower. That is, in 1 m 3
2. THE PROPOSED DESIGN
of the wind tower, employing clay conduits as the
The proposed design attempts to eliminate or to energy storing material, the mass of the material is
minimize the disadvantages of the conventional 306 kg and the system has a heat transfer area of
An improved design of wind towers 121
VO
I--
SCREEN
ZcGRAVITY- SHUT Vo I )A-s|
I",,.
CRE
"-- WATER-SPRAYING
PIPES
CLAY CONDUITS AN ALTERNATE
WIND TOWER DESIGN OF THE
TOWER HEAD
FIRST FLOOR
C
ONT
R OL
VALVE I Ille
r
GROUN ~
BASEMENT
SUMP
~ A DETAL
I OFTHEC
OND
UT
I
ARRANGEMENT
SECT
O
INX-X
Fig. 2. A cross-section of the proposed design of the wind tower or Baud-Geer.
36 m 2. Compared with the conventional designs, 2.3 Evaporative cooling of air by n'etting t~[the
this is an increase of about five to ten times in the clay conduits
heat transfer area and not much change in the total The unglazed clay conduits proposed for thermal
mass of the thermal energy storing material. That energy storage can be wetted uniformly by spraying
is, while the mass of the storage material is basically (or pouring) water over them at the top of the col-
the same as in the conventional Baud-Geers, the umn. Water, uniformly sprayed over the conduits.
proposed design provides a substantial increase in will not run offthe walls quickly; rather, it will keep
the heat transfer area. the clay conduits uniformly moist as it flows down.
Another advantage of the proposed design with The excess water leaving the column is collected
small conduit wall thickness is that the temperature in a sump located at the bottom of the tower. This
gradient within the material normal to the wall sur- water may be reused or drained off.
face is very small. The response time to tempera- In addition to directing more air into the building
ture changes is small, and the material can be and storing and retrieving coolness more effec-
heated or cooled very rapidly. Furthermore, with tively, the proposed design can utilize the potential
large heat transfer area the temperature difference of evaporative cooling, and can deliver air to the
between the air and the walls of the conduits is also building at much lower temperatures. It has an ad-
small. Although the conduits with a desired spec- ditional advantage of removing some of the fine
ification may not be readily available in many coun- dust particles from the air, thus delivering cleaner
tries, it is, however, believed that they can be pro- air to the space. Entrance of dust into the living
duced by brick factories without much difficulty or space in desert regions is a major problem, and def-
excessive costs. initely one of the disadvantages of employing Baud-
122 M. N. BAHADORI
Geers for ventilation and passive cooling, as com- ommended design temperatures by about 3-7C.
pared with other cooling systems. Designing for the latter conditions, the size of Baud-
To remove some of the larger dust particles from Geer will be smaller, but one has to endure the ther-
the air before entering the living space, the air ve- mal discomfort which may be caused when the am-
locity can be reduced by increasing the flow area. bient air temperatures exceed these values.
For example, the air entering the first floor (in Fig.
2) can be made to flow through the basement (by 3.2 Fluid flow analysis
closing door 5) and admitting air into the first floor The driving potential for the air flow through the
through floor registers connecting the two spaces. Baud-Geer is the pressure difference between the
With low air velocity, most of the larger dust par- inlet section of the tower and the door or window
ticles will be collected on the floor. In this design through which the air leaves the building. This pres-
the door number 5 may be eliminated and the evap- sure difference may be expressed as
oration column can be extended down to point 6
(instead of point 3, such as shown in Fig. 2). Ap,, = (C,~ - C,,,,) ovg, (1)
Afghanistan Kabul 37 19 18
Australia Alice Springs 40 24 15
Greece Athens 35.5 22 10
Iran Mashad 37 20 16
Tehran 39 24 15
Iraq Baghdad 45.5 23 19
Jordan Amman 36 21 14
Mexico Guadalajara 34 20 16
Saudi Arabia Riyadh 43 25 18
Syria Damascus 39 22 20
Turkey Ankara 34.5 20 15.5
U.S.A. Phoenix, AZ 43 22 15
Prescot, AZ 35.5 16 17
Tucson, AZ 40 19 14.5
Yuma, AZ 44 I 22 15
Palm Springs, 44.5 I 22 19.5
CA
USSR Tashkand 35 ~ 22 16
*The daily range is the difference between the mean daily maximum and the
mean daily minimum temperatures in the warmest month.
Then, neglecting the pressure drops in the passages Or, combining with eqns (1), (2) and (8) we have
where the air velocities are small, or taking
~ v g -- ~ pV~ + Ap~. ~10)
AP~4 = &P46 = Ap67 = Aps,, ~ O,
Equation (10) was solved by iteration for Vo =
5, 10 and 15 m/s, and for the heights of the column
eqn (3) becomes
corresponding with H = 2, 4, 6, 8, and 10 m. The
pressure drop through the column, or Ap23, was de-
Apt = Apl + Ap12 + Ap23 + Al)7s + Ape (6)
termined by using the friction chart provided for
galvanized steel and a correction factor recom-
or
mended for the rough column surfaces. An absolute
Apt = ~'t pV~ + Ap23, (7) surface roughness factor of e = 3 mm (as compared
with e = 0.15 mm for galvanized steel) was chosen.
where Ct is a loss coefficients[5], accounting for the This value is recommended for rough concrete
pressure losses through all the sections (except for ducts[5]. Figure 3 shows the velocity Vl (at the en-
2-3) shown in Fig. 2. For the design considered in trance to the tower) and V2 (in the energy storage
this study, C, was calculated to be about 4. We or evaporation column) for different wind speeds
assume a value of C, = 5 to account for additional and for different heights of the column. The analysis
or miscellaneous pressure losses. Then, we have presented here can be repeated for the surfaces with
roughness factors other than = 3 mm. Then,
Apt = ~ oV~ + Ap23. (8) curves such as shown in Fig. 3 may be obtained for
any material employed as the evaporation column.
For any wind velocity V0, a flow is maintained
in the tower and the building so that 3.3 Heat transfer and energy storage anal, sis
The average convection heat transfer coefficient
Ap,, = Ap,. (9) for air flowing through a smooth duct or pipe may
124 M. N. BAHADORI
8 -
n V_ = 15 m/s
U
E ~..~..~ Vo : 5 m/s
E~
:=7
C--- 4
--I
I,i
>
I I I I t I 3"- -,--?
2 4 6 8 I0
HEIGHT OF THE COLUMN, m
Fig. 3. Air velocities V1 and V2 as functions of the column height and wind velocity.
The evaporation effectiveness of 60% was consid- +3 = 6 5 % and V3 = 1.5 m/s. When the wind ve-
ered to account for the non-perfect wetting of the locity changes to Vo = 15 m/s (with other conditions
conduit walls. It simply assumes that about 60% of remaining the same) we have (from Fig. 7) T~ =
the conduit wall area is available for mass transfer. 26.5C, ~b3 = 56% and V3 = 4.5 m/s. At night, as-
No heat gain from the surroundings was considered suming To - 25C, +o = 34% and Vo = 5 m/s, the
by the evaporation column. air leaving the Baud-Geer will be at T~ = 17.5C
The following procedure was followed for the (see Fig. 5), +3 = 78.5% and V3 = 1.5 m/s.
analysis: We first selected a column height H.
Then, for a given wind velocity and the ambient air
4. MAINTAININGTHERMALCOMFORTIN THE BUILDING
conditions, we determine V2 (from Fig. 3), th,,, h ....
and then solved eqns (18) and (19), as was explained Thermal comfort depends on several factors, the
before. The conditions (dry-bulb temperature and most important of which are[5]
humidity ratio) of air leaving the column of height 1. The metabolic rate.
H were then determined. The process was repeated 2. The insulating effect of clothing.
for all other variables indicated before. Figure 5 3. The air temperature.
shows the results of the computations. The case of 4. The air relative humidty.
ambient air condition of Ta~, - 25C and T,,~, = 15C 5. The air velocity with respect to the skin.
was considered to explore the evaporative cooling 6. The mean radiant temperature of the surround-
potential of the column at night. Figure 5 shows that ing surfaces.
even with a moderate height of 5 m, the air leaving While the first two parameters are generally deter-
the evaporative cooling column at night is very mined by the occupants, it is the other four param-
cold. Air at such a low temperature can be used to eters which may be controlled to provide thermal
cool the building structure at night. This process is comfort.
of a great significance in the passive cooling of Design of a Baud-Geer and the building to be
buildings in the hot, arid regions. cooled by it should be considered together. This is
Conditions of air (that is, the dry-bulb temper- important from the point of view of providing a de-
ature, relative humidity and velocity) leaving a col- sirable airflow through the building and also in stor-
umn with a selected height H are given in Figs. 6 ing the ambient air coolness within the building
and 7 for wind velocities of 5 and 15 m/s. It can be structure at night. With higher air velocity in the
seen from Fig. 6 that when, for example, H = 5 m, space and lower wall temperatures (which is a result
and when the ambient air is at To - 40C (dry-bulb of the stored coolness in the structure), thermal
temperature), ~bo - 15% and wind velocity is Vo = comfort can be maintained at higher air tempera-
5 m/s, the air leaving the column is at T~ = 25C, tures and relative humidities.
45 I, n TO =45C , ~o = 12% ~ Vo = 15 m / s
,z~ T o =40C , ~o : 15% ~-- V o= 5 m/s
e,o To : 35"C , @o : 18%
40
~ ' % .,v To : 25C , @o= 33%
35
30 _
1-
25
I
~: 20
15
I0 I I I I I I I I I [
0 2 4 6 8 l0
HEIGHT OF T H E COLUMN , m
Fig. 5. Dry-bulb temperature of air leaving the evaporative cooling column.
An improved design of wind towers 127
o T0:45C ,@ =12%
45
A TO:40C ,@:i5%
o To : 35"C ,@:18"/.
,., 40
~- 35 100
~RATURE RELATIVE
HUMIDITY
Q_
~ 3O C2 80
>-
F-- I--
en AI
.._1 E 60
~ 25 1-
I "l-
o ii I I laJ
_>
~ 20 -2S
LmJ I---
hi
rr"
1 5 ~ 20
I01 I I I I I I I t 1 [0
0 2 4 6 8
HEIGHT OF THE COLUMN, rn
Fig. 6. Condition of air leaving the evaporative cooling column for a wind velocity of 5 m/s.
To find out if the design proposed here can in- (c) Mean radiant temperature equal to the air tem-
deed provide thermal comfort for a building, we perature.
make the following assumptions: (d) An air velocity in the space about 1/15 (ratio of
(a) Sedentary level of physical activity, corre- A3 to Ar in Fig. 2) of the air velocity in Baud-
sponding with a metabolic rate of 1 Met. Geer.
(b) Light clothing, corresponding with an insulat- With these assumptions we can now determine if
ing effect of 0.5 clo. the air leaving a Baud-Geer and entering the space
45 To : 4 5 * C , @ o : 1 2 %
TO : 4 0 * C , ~ b o : 15 %
To : 35"C, 4o : 18 */,
40
nr-
N 35
MPERATURE ~ 100
O.
HUMIDITY
~ 3o 80 .~
F- E BI C2
).,..
en
j-
_>-. 1--
_J
~ 25 6 I- 60 7'
I 0
._1
laJ
- -
"~ 20 5 n.-
A ~ -
4.0
lAIR VELOCITY-7
15 I C3 20 ,.-I,
F
I
IC 3 I I I 1 I I I 0
0 2 4 6 8
HEIGHT OF THE COLUMN, m
Fig. 7. Condition of air leaving the evaporative cooling column for a wind velocity of 15 m/s.
128 M. N. BAHADORI
can maintain thermal comfort in the building. Using and the psychrometric chart, with a sensible heat
thermal comfort charts[5], and referring to Figs. 6 factor of 0.65. From eqn (20) we find h,. = 59.44
and 7, we find (by trial and error) points Aj, B~ and kJ/kg C, and from the psychrometric chart we find
C~ on curves A, B and C so that the air leaving the Tr = 25.95C and Cbr = 64%, where the subscript
Baud-Geer and reaching the occupants at these r refers to the condition of air in the room before
conditions can maintain thermal comfort. The reaching the occupants. With L , +r and V,. = 0.1
heights of the evaporative cooling column corre- m/s we note that the condition of thermal comfort
sponding with points AI, Bt or Cj represent the min- (under the assumptions stated earlier) is satis-
imum values. Heights lower than these cannot de- fied[5]. The height of the evaporative cooling col-
liver air to the space at suitable thermal conditions. umn is (from Fig. 6) about 5 m, and the velocity of
That is, for a given ambient air condition and wind air leaving the wind tower (from Figs. 3 or 6) is
velocity the evaporative cooling column should about 1.5 m/s. This leads to a cross-sectional area
have a height at least equal to that represented by of 2 m 2 for the Baud-Geer. For a better air distri-
line A~ Bj C~. (Use linear interpolation for condi- bution in the building, we select two wind towers,
tions which are within the ranges considered in each with a cross-sectional area of about 1 m 2.
Figs. 6 and 7.) Of course, the air supplied to the
space should be cooler so that when it reaches an
5. SYSTEMCONTROL
occupant (after having picked up some of the space
heat gains), it is still at a thermally comfortable Baud-Geers may be designed to meet the peak
level. cooling demands (as in the above example). For
To show how the height of the evaporation col- partial loads one has the following options:
umn and the size of the Baud-Geer may be deter- (a) Control the evaporative cooling by reducing the
mined to provide thermal comfort in a building we wetted area of the conduit walls by controlling
treat the following example. the rate of water sprayed on the conduit walls.
Example: It is desirable to provide thermal (b) Control the airflow through the Baud-Geer.
comfort in a residential building employing the ven- The first option may be carried out by controlling
tilation and passive cooling design proposed here. the amount of water which is sprayed on top of the
The building, 10 x 10 x 3 m in dimensions, is lo- column, while the second one is accomplished by
cated in Tucson, Arizona, and has~a peak cooling partially closing the openings admitting air into
demand of ~2 = 10 kW, with a sensible heat factor (from Baud-Geer), or out of the building. In winter,
of about 0.65. The air reaching the occupants may or any time when no cooling is needed, the openings
be assumed to have been heated (through the build- between the Baud-Geer and the building have to be
ing heat gains), as an average, by about 1/2 of the completely shut.
cooling load, and that it has a velocity of about 0. l
m/s. Determine the dimensions of the Baud-Geer,
6. CONCLUSIONS
the height of its evaporative cooling column and the
condition of the air reaching the occupants. Assume AS compared with conventional wind towers and
a wind velocity of Vo = 5 m/s for Tucson. for given climatological conditions, the proposed
Solution: First we have to determine the design supplies air to the building at higher flow
amount of air which has to be delivered by the rates and with less dust. Furthermore, the air de-
Baud-Geer. With the building dimensions and the livered to the building is cooled evaporatively to
relative air velocity in the building specified, we lower temperatures. Without evaporative cooling,
select an air flow rate of about 3 m3/s to be supplied the cooling effect of the tower (due to the storage
by the Baud-Geer. We further assume that the of night air coolness) is very small. The theoretical
curve labelled B in Fig. 6 (for T d h - - 4 0 C , Cbo = analysis carried out in this study may be used as a
15%, 7",+ -- 20C and V0 = 5 m/s) can represent guideline for designing natural ventilation and pas-
the design conditions for Tucson. Unknowns are sive cooling systems in the hot, arid areas of the
the cross-sectional area (A4) of the Baud-Geer and world.
the height H which can deliver the needed quantity
of air at desirable conditions. The point represent- Acknowledgements--The author wishes to thank J. E.
ing the condition of air leaving the tower has to be Brooks for typing the manuscript, and R. Koopmans for
to the right of B~ (see Fig. 6). By a trial and error drawing the figures.
procedure, point B4 is found which is at T4 = 25C
REFERENCES
and +4 = 65%. From the psychrometric chart[5] we
obtain enthalpy and density of this air to be about 1. M. N. Bahadori, "Thermal performance of old build-
h4 = 58.0 kJ/kg C and p4 = 1.156 kg/m 3. The con- ings in central Iran employing air towers," Passive
dition of air reaching the occupants can be deter- Solar Heating and Cooling Conference, Los Alamos
Scientific Laboratory, New Mexico, Report No. LA-
mined from 6637-C, pp. 157-159, May 1976.
2. M. N. Bahadori, Passive cooling systems in Iranian
~Q = p4 v4 (hr - h4), (20) architecture. Sci. Am. 238(2), 144-154 (1978).
An improved design of wind towers 129
3. M, N. Bahadori. "Natural Cooling in Hot Arid Re- 7. C. Karakatsanis, M. N. Bahadori and B. J. Vickery,
gions," in Solar Energy Application in Btdldings pp. Evaluation of pressure coefficients and estimation of
195-225 (Edited by A. A. M. Sayighl. Academic airflow in buildings employing wind towers. Submit-
Press, New York (1979). ted for publication.
4. M. N. Bahadori, "Passive and hybrid convective 8. F. Kreith, Principles of Heat Transfer, 3rd Edn., In-
cooling systems," International Passive and Hybrid text Educational Publishers, New York (1973).
Cooling Conference, American Section of the Inter- 9. G. A. Kemeney and J. A. Cyphers, Heat transfer and
national Solar Energy Society, Miami Beach. Florida, pressure drop in an annular gap with surface spoilers.
pp. 715-727, Nov. 1981. J. Heat Transfer 83, 189-198 (196[).
5. " A S H R A E Handbook, 1981, Fundamentals," Amer- 10. D. F. Dipprey and R. H. Sabersky, Heat and mo-
ican Society of Heating, Refrigerating and Air- Con- mentum transfer in smooth and rough tubes at various
ditioning Engineers, Inc., Atlanta, Georgia, 1981. Prandtl numbers. Int. J. Heat and Mass Tran~f~r 6,
6. M. N. Bahadori, "Pressure coefficients to evaluate 329-353 (1963).
air flow pattern in wind towers," International Passive l l. V. Kolar, Heat transfer in turbulent flow of fluids
and Hybrid Cooling Conference, American Section of through smooth and rough pipes. Int. J. Heat and
the International Solar Energy Society. Miami Beach, Mass Tran,~fer 8, 639-653 (19651.
Florida. pp. 206-211), Nov. 1981.