VD4
Installation and service instructions
12 ... 36 kV - 630 ... 3150 A - 16 ... 50 kA
Index
I. Introduction 2
2. Checking on receipt 4
3. Storage 5
4. Handling 6
5. Description 7
7. Installation 52
9. Maintenance 61
1
I. Introduction II. Environmental protection
This publication contains the information needed to install programme
medium voltage VD4 circuit-breakers and put them into The VD4 circuit-breakers are manufactured in accordance
service. with the ISO 14000 Standards (Guidelines for environmental
For correct use of the product, please read it carefully. management).
Like all the apparatus we manufacture, the VD4 circuit- The production processes are carried out in compliance
breakers are designed for different installation configurations. with the Standards for environmental protection in terms of
However, this apparatus allows further technical-construction reduction in energy consumption as well as in raw materials
modifications (at the customers request) to adapt to special and production of waste materials. All this is thanks to
installation requirements. the medium voltage apparatus manufacturing facility
Consequently, the information given below may sometimes environmental management system.
not contain instructions concerning special configurations.
Apart from this manual, it is therefore always necessary to
consult the latest technical documentation (electric circuit
and wiring diagrams, assembly and installation drawings, any
protection coordination studies, etc.), especially regarding
any variants requested in relation to the standardised
configurations.
Only use original spare parts for maintenance operations.
For further information, please also see the technical
catalogue of the circuit-breaker and the spare parts
catalogue.
2
1. Packing and transport
3
2. Checking on receipt
test certification 5
-MO1 ... ... ... V
identification label Made by ABB
copy of the shipping documents
electric wiring diagram.
Other documents which are sent prior to shipment of the
apparatus are:
order confirmation Caption
A Circuit-breaker rating plate
original shipping advice note
B Operating mechanism rating plate
any drawings or documents referring to special
1 Type of apparatus
configurations/conditions.
2 Symbols of compliance with Standards
3 Serial number
4 Circuit-breaker characteristics
5 Characteristics of the operating mechanism auxiliaries
Fig. 1
4
3. Storage
5
4. Handling
Before carrying out any operations, always make sure that During handling, take great care not to stress the insulating
the operating mechanism spring is discharged and that the parts and the terminals of the circuit-breaker.
apparatus is in the open position.
To lift and handle the circuit-breaker, proceed as follows
(fig. 2):
use a special lifting tool (1) (not supplied) fitted with ropes The apparatus must not be handled by putting
with safety hooks (2); lifting devices directly under the apparatus itself.
insert the hooks (2) in the supports (3) fixed to the frame Should it be necessary to use this technique,
of the circuit-breaker and lift. Put the hooks (2) into the put the circuit-breaker onto a pallet or a sturdy
support holes (3) according to the type of apparatus (see supporting surface (see fig. 3).
table); In any case, it is always advisable to carry out
on completion of the operation (and in any case before lifting using the supports (3).
putting into service) unhook the lifting tool (1) and dismantle
the supports (3) from the frame.
C B A
1
3
3
Version Pole centre distance Rated current Hole
Fixed 150-210 mm up to 1250 A A
Fixed 275 mm from 1600 to 3150 A A
Fixed 210 mm from 1600 to 2000 A A
Fixed 210-275 mm up to 4000 A C
Withdrawable 150 mm up to 1250 A A
Withdrawable 210 mm from 1600 to 2500 A B
Withdrawable 275 mm up to 1250 A B
Withdrawable 275 mm from 1600 to 3150 A C
Withdrawable 210 mm up to 1250 A C
Withdrawable 210-275 mm up to 4000 A C
Fig. 2
Fig. 3
6
5. Description
11
8
1 4
5
6
2
12
3
7
9
10
Caption
1 Lever for manual closing spring charging
2 Signalling device for circuit-breaker open/closed
3 Rating plate
4 Opening pushbutton
5 Closing pushbutton
6 Signalling device for closing spring charged/discharged
7 Operation counter
8 Terminals
9 Earthing screw
1 0 Delivery terminal box
1 1 Cabling connection
1 2 Mechanical override of the undervoltage release (on request)
Fig. 4
7
5.4.1. General characteristics of fixed circuit-breakers
12
12
28
75
50-60
1600 1600 1600 1600 1600 1600 1600 2000 2000 2000 2000 2500 2500 2500 3150 3150
20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31,5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80
100 100 100 100 100 100
125 125 125 125 125 125
33 ... 60
10 ... 15
43 ... 75
60 ... 80
599 599 599 589 589 610 610 599 599 610 610 599 599 610 635 636
450 570 700 570 700 600 750 570 700 600 750 570 700 750 700 750
424 424 424 424 424 459 459 424 424 459 459 424 424 459 424 459
150 210 275 210 275 210 275 210 275 210 275 210 275 275 275 275
93 98 105 84 84 146 158 98 105 146 158 98 105 163 140 177
7407 7408 7407 7408 7407 7408
000050 003282 003285 003440 003441 003440 003441 003441 000149 003443
- 5 ... + 40
9
General characteristics of fixed circuit-breakers (17.5 kV)
10
17.5
17.5
38
95
50-60
1600 1600 1600 1600 1600 1600 2000 2000 2000 2000 2500 2500 2500 3150 3150
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
20 20 20 20 20 20 20
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
50 50 50 50 50 50 50
63 63 63 63 63 63 63
80 80 80 80 80 80 80
100 100 100 100 100 100
125 125 125 125 125 125
33 ... 60
10 ... 15
43 ... 75
60 ... 80
599 599 589 589 610 610 599 599 610 610 599 599 610 635 636
570 700 570 700 600 750 570 700 600 750 570 700 750 700 750
424 424 424 424 459 459 424 424 459 459 424 424 459 424 459
210 275 210 275 210 275 210 275 210 275 210 275 275 275 275
98 105 84 84 146 158 98 105 146 158 98 105 163 140 177
7407 7408 7407 7408 7407 7408
003282 003285 003440 003441 003440 003441 003441 000149 003443
- 5 ... + 40
11
General characteristics of fixed circuit-breakers (24 kV)
Circuit-breaker VD4 24
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) Ir [A] 630 630 1250 1250 1600 2000 2500
16 16 16 16 16 16
Rated breaking capacity 20 20 20 20 20 20
Isc [kA]
(rated short-circuit breaking current symmetrical) 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5
16 16 16 16 16 16
20 20 20 20 20 20
Rated short-time withstand current (3s) Ik [kA]
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
Making capacity Ip [kA]
63 63 63 63 63 63 63
80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60
Arcing time [ms] 10 ... 15
Total breaking time [ms] 43 ... 75
Closing time [ms] 60 ... 80
P P
H [mm] 631 631 631 631 642 642 642
Maximum W [mm] 570 700 570 700 700 700 700
overall
H D [mm] 424 424 424 424 424 424 424
dimensions
W D Pole distance P [mm] 210 275 210 275 275 275 275
Weight [kg] 100 104 100/106 (1)
104 110 110 110
TN 7409 7410 7409 7410 7411 7411 7411
Standardised table of dimensions
1VCD 000172 (1)
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC: 62271-1
(1) 31.5 kA version.
12
General characteristics of fixed circuit-breakers (36 kV)
Circuit-breaker VD4 36
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) Ir [A] 1250 1600 2000 2500 (* )
Rated breaking capacity
Isc [kA] 31.5 31.5 31.5 31.5
(rated short-circuit breaking current symmetrical)
Rated short-time withstand current (3s) Ik [kA] 31.5 31.5 31.5 31.5
Making capacity Ip [kA] 80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 35 ... 60
Arcing time [ms] 10 ... 15
Total breaking time [ms] 45 ... 75
Closing time [ms] 60 ... 80
P P H [mm] 564 564 564
Maximum W [mm] 778 778 778
overall
dimensions
H D [mm] 468 468 468
W D Pole distance P [mm] 275 275 275
Weight [kg] 150 150 170
Standardised table of dimensions TN 1VYN300901-LT 1VYN300901-LT 1VYN300901-LT
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC: 62271-1
(*) Contact ABB
13
5.4.2. Types of circuit-breakers available in the fixed version
VD4 fixed circuit-breaker without bottom and top terminals (12 kV)
14
Ur Isc Rated uninterrupted current (40 C) [A]
H=461 H=589 H=599 H=610 H=636
D=424 D=424 D=424 D=459 D=459
u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 Circuit-breaker type
kV kA
l/g=217.5 l/g=238 l/g=237.5 l/g=237 l/g=237
P=150 P=210 P=275 P=210 P=275 P=150 P=210 P=275 P=210 P=275 P=275
W=450 W=570 W=700 W=570 W=700 W=450 W=570 W=700 W=600 W=750 W=750
20 1600 VD4 12.16.20 p275
25 1600 VD4 12.16.25 p275
31.5 1600 VD4 12.16.32 p275
40 1600 VD4 12.16.40 p275
50 1600 VD4 12.16.50 p275
20 2000 VD4 12.20.20 p275
25 2000 VD4 12.20.25 p275
31.5 2000 VD4 12.20.32 p275
40 2000 VD4 12.20.40 p275
50 2000 VD4 12.20.50 p275
12
20 2500 VD4 12.25.20 p275
25 2500 VD4 12.25.25 p275
31.5 2500 VD4 12.25.32 p275
40 2500 VD4 12.25.40 p275
50 2500 VD4 12.25.50 p275
20 3150 VD4 12.32.20 p275
25 3150 VD4 12.32.25 p275
31.5 3150 VD4 12.32.32 p275
40 3150 VD4 12.32.40 p275
50 3150 VD4 12.32.50 p275
H = Height of the circuit-breaker.
W = Width of the circuit-breaker.
D = Depth of the circuit-breaker.
u/l = Distance between bottom and top terminal.
l/g = Distance between the bottom terminal and the resting surface of the circuit-breaker.
P = Pole horizontal centre distance.
VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV)
15
Ur Isc Rated uninterrupted current (40 C) [A]
H=461 H=589 H=599 H=610 H=635
D=424 D=424 D=424 D=459 D=459
u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 Circuit-breaker type
kV kA
l/g=217.5 l/g=238 l/g=237.5 l/g=237 l/g=237.5
P=150 P=210 P=275 P=210 P=275 P=150 P=210 P=275 P=210 P=275 P=275
W=450 W=570 W=700 W=570 W=700 W=450 W=570 W=700 W=600 W=750 W=750
16 1250 VD4 17.12.16 p210
20 1250 VD4 17.12.20 p210
25 1250 VD4 17.12.25 p210
31.5 1250 VD4 17.12.32 p210
40 1250 VD4 17.12.40 p210
50 1250 VD4 17.12.50 p210
20 1600 VD4 17.16.20 p210
25 1600 VD4 17.16.25 p210
31.5 1600 VD4 17.16.32 p210
40 1600 VD4 17.16.40 p210
50 1600 VD4 17.16.50 p210
20 2000 VD4 17.20.20 p210
25 2000 VD4 17.20.25 p210
31.5 2000 VD4 17.20.32 p210
40 2000 VD4 17.20.40 p210
50 2000 VD4 17.20.50 p210
20 2500 VD4 17.25.20 p210
25 2500 VD4 17.25.25 p210
31.5 2500 VD4 17.25.32 p210
16 630 VD4 17.06.16 p275
20 630 VD4 17.06.20 p275
25 630 VD4 17.06.25 p275
31.5 630 VD4 17.06.32 p275
16 1250 VD4 17.12.16 p275
17.5 20 1250 VD4 17.12.20 p275
25 1250 VD4 17.12.25 p275
31.5 1250 VD4 17.12.32 p275
40 1250 VD4 17.12.40 p275
50 1250 VD4 17.12.50 p275
20 1600 VD4 17.16.20 p275
25 1600 VD4 17.16.25 p275
31.5 1600 VD4 17.16.32 p275
40 1600 VD4 17.16.40 p275
50 1600 VD4 17.16.50 p275
20 2000 VD4 17.20.20 p275
25 2000 VD4 17.20.25 p275
31.5 2000 VD4 17.20.32 p275
40 2000 VD4 17.20.40 p275
50 2000 VD4 17.20.50 p275
20 2500 VD4 17.25.20 p275
25 2500 VD4 17.25.25 p275
31.5 2500 VD4 17.25.32 p275
40 2500 VD4 17.25.40 p275
50 2500 VD4 17.25.50 p275
20 3150 VD4 17.32.20 p275
25 3150 VD4 17.32.25 p275
31.5 3150 VD4 17.32.32 p275
40 3150 VD4 17.32.40 p275
50 3150 VD4 17.32.50 p275
H = Height of the circuit-breaker.
W = Width of the circuit-breaker.
D = Depth of the circuit-breaker.
u/l = Distance between bottom and top terminal.
l/g = Distance between the bottom terminal and the resting surface of the circuit-breaker.
P = Pole horizontal centre distance.
16
VD4 fixed circuit-breaker without bottom and top terminals (24 kV)
VD4 fixed circuit-breaker without bottom and top terminals (36 kV)
17
VD4 up to 24 kV VD4 up to 24 kV
VD4 - 36 kV
5.4.3. Standard fittings for fixed circuit-breakers set of ten circuit-breaker open/closed auxiliary contacts
Note: with the set of ten auxiliary contacts supplied as standard and the
The basic versions of the fixed circuit-breakers are three-pole
maximum number of electrical applications possible, three make contacts
and fitted with: (signalling circuit-breaker open) and five break contacts (signalling circuit-
EL type manual operating mechanism breaker closed) are available.
mechanical signalling device for closing spring charged/ lever for manual closing spring charging
discharged auxiliary circuit support terminal box.
mechanical signalling device for circuit-breaker open/closed
closing pushbutton, opening pushbutton and operation
counter
18
5.5. Withdrawable circuit-breakers The locks can only be activated by the handles with the truck
fully resting against the crosspiece.
The withdrawable circuit-breakers up to 24 kV are available The operating lever (16) must be fully inserted (also see
for UniGear ZS1 and UniSec switchgear, PowerCube modules par. 7.5.). A lock prevents the truck from advancing into the
(see fig. 5a) and for ZS8.4 switchgear (see fig. 5b). enclosure or fixed part when the earthing switch is closed.
The 36 kV circuit-breakers are available for ZS2 switchgear. Another lock prevents racking-in and racking-out with the
They consist of a truck on which the supporting structure of circuit-breaker closed. With the truck in an intermediate
the circuit-breaker is fixed. position between isolated and connected, a further lock
prevents circuit-breaker closing (either mechanical or
Circuit-breakers for UniGear ZS1 and UniSec switchgear electrical).
and for PowerCube modules (fig. 5a) A locking magnet is also mounted on the truck which, when
The cord with the connector (14) (plug) for connection of the de-energised, prevents the truck racking-in operation.
operating mechanism electrical accessories comes out of the On request, an interlock is available which prevents racking-in
connection (15). of the circuit-breaker with the door open, and door opening
The strikers for operating the contacts (connected/isolated) with the circuit-breaker closed.
placed in the switchgear are fixed in the top part of the The lever for loading the closing spring (1) in the manual mode
circuit-breaker. is built into the operating mechanism. The spring is loaded by
The shutter actuator (9) (roller (18) for UniSec version) are repeatedly lowering the lever with linear movements until the
provided for operating the segregation shutters of the medium yellow indicator (6) appears to show that loading is complete.
voltage contacts of the enclosure or of the switchgear are The spring can only be loaded with the switchgear door open.
fixed on the sides of the circuit-breaker. Comply with the instructions in the UniGear switchgear
The crosspiece with the handles (17) for hooking up the manual for the operations that can be performed with the
circuit-breaker for the racking-in/out operations by means of door open.
the special operating lever (16) is mounted on the front part of Note: on request, the closing spring loading device for withdrawable circuit-
the circuit-breaker truck. breakers for UniGear switchgear can be supplied with the lever outside the
operating mechanism and a rotary loading movement. This device is part of the
The circuit-breaker is completed with the isolating contacts (8). standard equipment for VD4/ZS8 withdrawable circuit-breakers only (see detail
The withdrawable circuit-breaker is fitted with special locks 1 of Fig. 5b on the next page). This rotary loading device allows the closing
spring to be loaded with the switchgear door closed.
on the front crosspiece, which allow hooking up into the
corresponding couplings of the switchgear.
13
14 18
15
4
1 5
16
6
2
12
3
7
9
8 11
17 10
Caption 9 Slide for operating the switchgear shutters (UniGear ZS1, PowerCube, ZS8.4)
1 Lever for manually charging the closing spring 1 0 Truck
2 Signalling device for circuit-breaker open/closed 1 1 Locks for hooking into the fixed part
3 R ating plate 1 2 Mechanical override of the undervoltage release (on request)
4 O pening pushbutton 1 3 Strikers for activating the contacts placed in the enclosure
5 C losing pushbutton 1 4 Connector (plug)
6 Signalling device for closing spring charged/discharged 1 5 Cabling connection
7 Operation counter 1 6 Operating lever for circuit-breaker racking-in/out
8 I solating contacts 1 7 Handles for activating the locks (11)
18 Shutters actuator (for UniSec version only)
Fig. 5a
19
Circuit-breakers for ZS8.4 switchgear (fig. 5b) 2) Prevention of traverse with socket-plug disconnected
The socket (13) takes the connector (plug) placed in the When the plug is not inserted in the socket (13), the stem (21
switchgear. - fig. 5c) prevents the plate (22 - fig. 5c) lifting and traverse of
The slides (9) for operating the segregation shutters of the the apparatus.
medium voltage contacts of the switchgear are fixed on the
sides of the circuit-breaker. 3) Prevention of switchgear door closing with socket-
The crosspiece with the handles (17) for hooking up the plug disconnected (*)
circuit-breaker for the racking-in/out operations by means of When the plug is not inserted in the socket (13), the feeler pin
the special operating lever (16) is mounted on the front part of (23 - fig. 5d) prevents door closing.
the circuit-breaker truck.
The circuit-breaker is completed with the isolating contacts (8).
The withdrawable circuit-breaker is fitted with special locks, 4) Prevention of circuit-breaker racking-out with the
described below (see fig. 5c - 5d). socket-plug connected (*)
When the plug is inserted in the socket (13), the lock bolt (29
- fig. 5d) hits the pin (30 - fig. 5d) preventing the apparatus
1) Prevention of traverse with circuit-breaker closed
from being racked out of the switchgear.
With the circuit-breaker closed, the feeler pin (16 - fig.
5c) prevents the shutter sliding (19 - fig. 5c) and therefore
insertion of the lever (20 - fig. 5c) for traverse of the
apparatus.
13 8 13
5
2
16
6
3
7
9
1 11
10 17
Fig. 5b
20
16 19 20 22 21
Fig. 5c
23 30 29
Fig. 5d
21
5.5.1. General characteristics of withdrawable circuit-breakers for UniGear ZS1 switchgear
22
12
12
28
75
50-60
1600 1600 1600 1600 2000 2000 2000 2000 2500 2500 3150 (2)
3150 (2)
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
50 50 50 50
63 63 63 63
80 80 80 80
100 100 100 100 100 100
125 125 125 125 125 125
33 ... 60
10 ... 15
43 ... 75
60 ... 80
691 691 691 691 691 691 691 691 691 691 730 742
653 853 681 853 653 853 681 853 853 853 853 853
641 642 643 643 642 642 643 643 640 643 640 643
210 275 210 275 210 275 210 275 275 275 275 275
174 176 180 193 160 166 190 205 186 225 221 240
7415 7416 7417
003284 003286 003444 003445 003444 003445 003446 000153 003447
- 5 ... + 40
23
General characteristics of withdrawable circuit-breakers for UniGear ZS1 switchgear (17.5 kV)
24
17.5
17.5
38
95
50-60
1600 1600 1600 1600 2000 2000 2000 2000 2500 2500 3150 (2)
3150 (2)
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40 40
50 50 50 50 50 50
50 50 50 50
63 63 63 63
80 80 80 80
100 100 100 100 100 100
125 125 125 125 125 125
33 ... 60
10 ... 15
43 ... 75
60 ... 80
691 691 691 691 691 691 691 691 691 691 730 742
653 853 681 853 653 853 681 853 853 853 853 853
641 642 643 643 642 642 643 643 640 643 640 643
210 275 210 275 210 275 210 275 275 275 275 275
174 176 180 193 160 166 190 205 186 225 221 240
7415 7416 7417
003284 003286 003444 003445 003444 003445 003446 000153 003447
- 5 ... + 40
25
General characteristics of withdrawable circuit-breakers for UniGear ZS1 switchgear (24 kV)
Circuit-breaker VD4/P 24
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 630 1250 1250 1600 2000 2500 (2)
3150 (3)
16 16 16 16 16 16 16
Rated breaking capacity 20 20 20 20 20 20 20
(rated short-circuit breaking current Isc [kA]
symmetrical) 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5
16 16 16 16 16 16 16
20 20 20 20 20 20 20
Rated short-time withstand current (3s) Ik [kA]
25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40
50 50 50 50 50 50 50
Making capacity Ip [kA]
63 63 63 63 63 63 63
80 80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60
Arcing time [ms] 10 ... 15
Total breaking time [ms] 43 ... 75
Closing time [ms] 60 ... 80
P P
H [mm] 794 794 794 794 838 838 838 838
Maximum W [mm] 653 853 653 853 853 853 853 853
overall
H D [mm] 802 802 802 802 790 790 790 790
dimensions
W D Pole distance P [mm] 210 275 210 275 275 275 275 275
Weight [kg] 140 148 140/146 (4)
148 228 228 228 277
TN 7413 7414 7413 7414 7418 7418 7418
Standardised table of dimensions
1VCD 000173 (4)
000177
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
(2) 2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
(3) 2700 A rated current guaranteed with natural ventilation; 3150 A rated current guaranteed with forced ventilation.
(4) 31.5 kA version.
26
General characteristics of withdrawable circuit-breakers for UniGear ZS2 switchgear and PowerCube modules (36 kV)
Circuit-breaker VD4/W 36
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 36
Rated insulation voltage Us [kV] 36
Withstand voltage at 50 Hz Ud (1 min) [kV] 70
Impulse withstand voltage Up [kV] 170
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 1250 1600 2000 2500 (* )
Rated breaking capacity
Isc [kA] 31.5 31.5 31.5 31.5
(rated short-circuit breaking current symmetrical)
Rated short-time withstand current (3s) Ik [kA] 31.5 31.5 31.5 31.5
Making capacity Ip [kA] 80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60
Arcing time [ms] 10 ... 15
Total breaking time [ms] 45 ... 75
Closing time [ms] 60 ... 80
P P
H [mm] 973 973 973 973
Maximum W [mm] 842 842 842 842
overall
H D [mm] 788 788 788 788
dimensions
W D Pole distance P [mm] 275 275 275 275
Weight [kg] 230 230 230
Standardised table of dimensions TN 1VYN300901-KG 1VYN300901-KG 1VYN300901-KG
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC: 62271-1
(*) Ask ABB
27
5.5.2. Types of withdrawable circuit-breakers available for UniGear ZS1 switchgear
28
VD4 withdrawable circuit-breaker (17.5 kV)
29
VD4 withdrawable circuit-breaker (24 kV)
30
VD4 up to 24 kV VD4 up to 24 kV
VD4 - 36 kV
5.5.3. Standard fittings of withdrawable circuit-breakers lever for manually charging the closing spring
for UniGear ZS1 switchgear (up to 24 kV) - UniGear isolating contacts
ZS2 and PowerCube modules (VD4 36 kV) cord with connector (plug only) for auxiliary circuits, with
The basic versions of the withdrawable circuit-breakers are striker pin which does not allow connection of the plug
three-pole and fitted with: in the socket if the rated current of the circuit-breaker is
EL type manual operating mechanism different from the rated current of the panel
mechanical signalling device for closing spring charged/ racking-in/out lever (the quantity must be defined according
discharged to the number of pieces of apparatus ordered)
mechanical signalling device for circuit-breaker open/closed locking electromagnet in the truck. This prevents the circuit-
closing pushbutton breaker from being racked into the panel with auxiliary
opening pushbutton circuits not connected (plug not inserted in the socket).
operation counter
set of ten auxiliary circuit-breaker open/closed contacts
Note: with the set of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications possible, three make contacts
(signalling circuit-breaker open) and four break contacts (signalling circuit-
breaker closed) are available.
31
5.5.4. General characteristics of withdrawable circuit-breakers for PowerCube modules
32
VD4/P 12 VD4/W 12
PB2 PB3 PB3
12 12 12
12 12 12
28 28 28
75 75 75
50-60 50-60 50-60
1250 1250 1600 1600 1600 2000 2000 2500 2500 3150 (2)
3150 (2)
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
50 50 50 50
63 63 63 63
80 80 80 80
100 100 100 100 100
125 125 125 125 125
33 ... 60 33 ... 60 33 ... 60
10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 43 ... 75
60 ... 80 60 ... 80 60 ... 80
691 691 691 691 691 690 691 691 691 730 691
653 681 653 653 681 653 681 853 853 853 853
641 643 642 641 643 642 643 640 643 640 643
210 210 210 210 210 210 210 275 275 275 275
174 180 160 174 180 160 190 186 225 221 240
7415 7415 7417
003284 003444 003284 003444 003444 003445 000152 003596
- 5 ... + 40 - 5 ... + 40 - 5 ... + 40
33
General characteristics of withdrawable circuit-breakers for PowerCube modules (17.5 kV)
34
VD4/P 17 VD4/W 17
PB2 PB3 PB3
17.5 17.5 17.5
17.5 17.5 17.5
38 38 38
95 95 95
50-60 50-60 50-60
1250 1250 1600 1600 1600 2000 2000 2500 2500 3150 (2) 3150 (2)
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
20 20 20 20
25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
50 50 50 50
63 63 63 63
80 80 80 80
100 100 100 100 100
125 125 125 125 125
33 ... 60 33 ... 60 33 ... 60
10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 43 ... 75
60 ... 80 60 ... 80 60 ... 80
691 691 691 691 691 690 691 691 691 691 730
653 681 653 653 681 653 681 853 853 853 853
641 643 642 641 643 642 643 640 643 643 640
210 210 210 210 210 210 210 275 275 275 275
174 180 160 174 180 160 190 186 225 240 221
7415 7415 7417
003284 003444 003284 003444 003444 003445 003596 000152
- 5 ... + 40 - 5 ... + 40 - 5 ... + 40
35
General characteristics of withdrawable circuit-breakers for PowerCube modules (24 kV)
Circuit-breaker VD4/P 24
PowerCube module PB4 PB5
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 24 24
Rated insulation voltage Us [kV] 24 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50 50
Impulse withstand voltage Up [kV] 125 125
Rated frequency fr [Hz] 50-60 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 1600 2000 2500 (2)
16 16 16 16 16
Rated breaking capacity 20 20 20 20 20
(rated short-circuit breaking Isc [kA]
current symmetrical) 25 25 25 25 25
31.5 31.5 31.5 31.5
16 16 16 16 16
Rated short-time 20 20 20 20 20
Ik [kA]
withstand current (3s) 25 25 25 25 25
31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
Making capacity Ip [kA]
63 63 63 63 63
80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60 33 ... 60
Arcing time [ms] 10 ... 15 10 ... 15
Total breaking time [ms] 43 ... 75 43 ... 75
Closing time [ms] 60 ... 80 60 ... 80
P P H [mm] 794 794 838 838 838
Maximum W [mm] 653 653 853 853 853
overall
H D [mm] 802 802 790 790 790
dimensions
W D Pole distance P [mm] 210 210 275 275 275
Weight [kg] 140 140/146 (3)
228 228 228
TN 7413 7413 7418 7418 7418
Standardised table of dimensions
1VCD 000173 (3)
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature.
(2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
(3) 31.5 kA version.
36
5.5.5. Types of withdrawable circuit-breakers available for PowerCube modules
37
VD4 withdrawable circuit-breaker (17.5 kV)
38
VD4 withdrawable circuit-breaker (24 kV)
39
5.5.7. General characteristics of withdrawable circuit-breakers for ZS8.4 switchgear
Circuit-breaker VD4/Z8
Panel without partitions
Panel with partitions
Preussen Elektra - EON (2)
Width [kV] 650 650 650 650 800 800
Depth [kV] 1000 1000 1000 1000 1200 1200
IEC 62271-100
Standards
VDE 0671
Rated voltage Ur [kV] 12 12 17.5 17.5 24 24
Rated insulation voltage Us [kV] 12 12 17.5 17.5 24 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 28 28 38 38 50 50
Impulse withstand voltage Up [kV] 75 75 95 95 125 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 1250 630 1250 630 1250
40
VD4/ZT8 VD4/ZS8
650 650 650 650 800 800 650 650 800 800
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
12 12 17.5 17.5 24 24 12 12 24 24
12 12 17.5 17.5 24 24 12 12 24 24
28 28 38 38 50 50 28 28 50 50
75 75 95 95 125 125 75 75 125 125
50-60 50-60
630 1250 630 1250 630 1250 630 1250 630 1250
16 16 16 16
20 20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25
16 16 16 16
20 20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25
40 40 40 40
50 50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63
33...60 40...60
10...15 10...15
43...75 50...75
60...80 60...80
579 579 579 579 680 680 579 579 680 680
503 503 503 503 653 653 503 503 653 653
638 638 638 638 646 646 638 638 646 646
150 150 150 150 210 210 150 150 210 210
116 116 116 116 140 140 116 116 140 140
000093 000134 000134 000134 000090 000136 000091 000133 000088 000135
5 ... + 40 5 ... + 40
41
5.5.8. General characteristics of withdrawable circuit-breakers for ZS8.4 switchgear
42
5.5.9. Standard fittings for withdrawable circuit-breakers 5.5.10. VD4/ZS8 (Preussen Elektra-EON version)
for ZS8.4 switchgear Device for recharging the closing spring, with door closed,
The basic versions of the withdrawable circuit-breakers are by means of removable rotary handle and outside the
always three-pole and fitted with: operating mechanism and the switchgear
EL type manual operating mechanism 64-pin Harting socket with mechanical interlock which
mechanical signalling device for closing spring charged/ prevents traverse of the circuit-breaker when the plug is not
discharged inserted in the socket
mechanical signalling device for circuit-breaker open/closed Interlock with the door which prevents insertion of the
closing pushbutton spring charging lever when the circuit-breaker is closed
opening pushbutton Interlock with the door and the 64-pin Harting socket which
operation counter prevents door closure when the plug is not inserted in the
set of ten auxiliary circuit-breaker open/closed contacts socket.
Note: with the set of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications possible, three make contacts 5.5.11. VD4/Z8 - VD4/ZT8
(signalling circuit-breaker open) and four break contacts (signalling circuit-
breaker closed) are available. Harting 64-pin socket with mechanical interlock which
lever for manually charging the closing springs incorporated prevents traverse of the circuit-breaker when the plug is not
in the operating mechanism for VD4/Z8 and VD4/ZT8, inserted in the socket.
external with rotary movement for VD4/ZS8
isolating contacts
cord with connector (only plug) for auxiliary circuits, with
striker pin which does not allow connection of the plug
in the socket if the rated current of the circuit-breaker is
different from the rated current of the panel
racking-in/out lever (the quantity must be defined according
to the number of pieces of apparatus ordered)
Caption
1) Device for spring charging with rotary handle
2) H arting 64-pin socket with mechanical interlock which prevents traverse when the socket is not inserted
3) Door-socket-spring charging device interlock (only VD4/ZS8 version)
43
5.5.12. General characteristics of withdrawable circuit-breakers for UniSwitch switchgear
and UniMix (24 kV) switchgear
25 25
40 (50) (5)
40 (50) (5)
40 40
Making capacity Ip [kA] 50 (63) (5)
50 (63) (5)
50 50
63 63
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60 33 ... 60 33 ... 60 33 ... 60
Arcing time [ms] 10 ... 15 10 ... 15 10 ... 15 10 ... 15
Total breaking time [ms] 43 ... 75 43 ... 75 43 ... 75 43 ... 75
Closing time [ms] 60 ... 80 60 ... 80 60 ... 80 60 ... 80
P P
H [mm] 680 680 680 680
Maximum W [mm] 653 653 653 653
overall
H D [mm] 742 742 742 742
dimensions
W D Pole distance P [mm] 210 210 210 210
Weight [kg] 125 125 125 125
Standardised table of dimensions 1VCD 000047 000047 000047 000047
Operating temperature [C] - 5 ... + 40 - 5 ... + 40 - 5 ... + 40 - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271
(1) Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature
(2) The value and duration of the rated short-time withstand current depends on the switchgear. See the specific catalogues of the UniSwitch and UniMix switchgear
(3) The top shutter activation wheels of the UniSwitch switchgear (CBW unit) are mounted and adjusted by the manufacturer of the UniSwitch switchgear
(4) The top shutter activation wheels of the UniMix switchgear (P1/E unit) are available on request
(5) The values in brackets refer to the 12 kV rated voltage.
44
5.5.13. General characteristics of withdrawable circuit-breakers for UniSec switchgear
Circuit-breaker VD4/SEC
IEC 62271-100
Standards
VDE 0671; CEI EN 62271-100- File 7642
Rated voltage Ur [kV] 24
Rated insulation voltage Us [kV] 24
Withstand voltage at 50 Hz Ud (1 min) [kV] 50
Impulse withstand voltage Up [kV] 125
Rated frequency fr [Hz] 50-60
Rated normal current (40 C) (1)
Ir [A] 630 - 1250
16
Rated breaking capacity
Isc [kA] 20
(rated symmetrical short-circuit current)
25
Rated short-time 16
withstand current (3 s) Ik [kA] 20
25
40
Making capacity Ip [kA] 50
63
Operation sequence [O - 0.3 s - CO - 15 s - CO]
Opening time [ms] 33 ... 60
Arcing time [ms] 10 ... 15
Total breaking time [ms] 43 ... 75
Closing time [ms] 60 ... 80
P P
H [mm] 743
Maximum W [mm] 653
overall H
dimensions D [mm] 742
W D Pole distance P [mm] 210
Weight [kg] 133
Standardised table of dimensions 1VCD 000190
Operating temperature [C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271
(1) Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature.
45
5.5.14. Standard fittings for withdrawable circuit-breakers 5.6. Characteristics of the electrical
for UniSwitch, UniMix and UniSec switchgear
accessories
The basic versions of the withdrawable circuit-breakers are
three-pole and provided with: Shunt opening release (-MO1)
EL type manual operating mechanism Additional shunt opening release (-MO2)
Mechanical signalling device for closing spring charged/ Shunt closing release (-MC)
discharged Locking magnet on the actuator (-RL1)
Mechanical signalling device for circuit-breaker open/closed
Un 24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V
Closing pushbutton
Un 48 - 60 - 110 - 120 - 127 - 220 ... 240 V~ 50 Hz
Opening pushbutton
Un 110 - 120 - 127 - 220 - 240 V~ 60 Hz
Operation counter
Operating limits 70 110% Un
Set of ten circuit-breaker open/closed auxiliary contacts
Inrush power (Ps) DC 200 W; AC = 200 VA
Note: with the set of ten auxiliary contacts supplied as standard and
the maximum electrical accessories, three break contacts are available Inrush time approx. 100 ms
(signalling circuit-breaker open) and four make contacts (signalling circuit- Continuous power (Pc) DC = 5 W; AC = 5 VA
breaker closed). Opening time 35 ... 60 ms
Lever for manual charging of the closing spring incorporated Closing time 30 ... 80 ms
in the operating mechanism Insulation voltage 2000 V 50 Hz (for 1 min)
Isolating contacts
Racking-out/racking-in lever (the quantity must be Undervoltage release (-MU)
established according to the number of pieces of apparatus
Un 24 - 30 - 48 - 60 - 110 - 125 - 220 - 250 V
ordered).
Un 48 - 60 - 110 - 120 - 127 - 220 ... 240 V~ 50 Hz
Un 110 - 120 ... 127 - 220 ... 240 V~ 60 Hz
VD4 withdrawable circuit-breaker for switchgear
Operating limits
UniSwitch (type unit CBW) and UniMix (type unit P1/E)
circuit-breaker opening 35-70% Un
Ur Isc Rated uninterrupted current (40 C) [A] circuit-breaker closing 85-110% Un
UniSwitch CBW UniMix P1/E Inrush power (Ps) DC 200 W; AC = 200 VA
P=210 P=210 Inrush time approx. 100 ms
kV kA Circuit-breaker type
u/l=310 u/l=310 Continuous power DC = 5 W; AC = 5 VA
=35 =35 Opening time 60 ... 80 ms
16 630 (1)
630 VD4/US 24.06.16 p210 Insulation voltage 2000 V 50 Hz (for 1 min)
20 630 (1)
630 VD4/US 24.06.20 p210
25 630 VD4/US 24.06.25 p210 Electronic time delay device for undervoltage release
24
16 1250 (1)
1250 VD4/US 24.12.16 p210 (mounted outside the circuit-breaker)
20 1250 (1)
1250 VD4/US 24.12.20 p210
Un 24 ... 30 - 48 - 60 - 110 ... 127 - 220 ... 250 V
25 1250 VD4/US 24.12.25 p210
Un 48 - 60 - 110 ... 127 - 220 ... 240 V~ 50/60 Hz
(1) 25 kA Isc at the 12 kV rated voltage
P = Pole horizontal centre distance. Adjustable opening time
u/l = Distance between bottom and top terminal. (release + time delay 0.5-1-1.5-2-3 s
= Diameter of the isolating contact. device)
46
Motor for motorised truck (-MT) (only for withdrawable Cos Rated current Breaking capacity
circuit-breakers for UniGear ZS1, UniSec and ZS8.4 220 V AC 0.7 2.5 A 25 A
switchgear) 380 V AC 0.7 1.5 A 15 A
Un 24-30-48-60-110-220 V DC 500 V AC 0.7 1.5 A 15 A
Operating limits 85 ... 110% Un 660 V AC 0.7 1.2 A 12 A
Rated power (Pn) 40 W Time constant
1 ms 10 A 12 A
Motor operator (-MS) 15 ms 10 A 12 A
24 V DC
50 ms 8A 10 A
Characteristics
200 ms 4A 7.7 A
Un 24...30 - 48...60 - 110...130 - 220...250 V
1 ms 8A 10 A
Un 100...130 - 220...250 V ~ 50/60 Hz
15 ms 6A 8A
Operating limits 85 110% Un 60 V DC
50 ms 5A 6A
40 kA 50 kA
Inrush power (Ps) DC=600 W; DC=900 W; 200 ms 4A 5.4 A
AC=600 VA AC=900 VA 1 ms 6A 8A
DC=200 W; DC=350 W; 15 ms 4A 5A
Rated power (Pn) 110 V DC
AC=200 VA AC=350 VA
50 ms 2A 4.6 A
Inrush time 0.2 s 0.2 s
200 ms 1A 2.2 A
Charging time 6-7 s 6-7 s
1 ms 1.5 A 2A
Insulation voltage 2000 V 50 Hz (for 1 min) 2000 V 50 Hz (for 1 min)
15 ms 1A 1.4 A
220 V DC
50 ms 0.75 A 1.2 A
Auxiliary contacts of the circuit-breaker
200 ms 0.5 A 1A
Rated insulation voltage 660 V AC Note
according to VDE 0110, Group C 800 V DC With the set of 10 auxiliary contacts supplied as standard, the following are available:
3 NO contacts + 5 NC contacts for fixed circuit-breakers
Rated voltage 24 V... 660 V 3 NO contacts + 4 NC contacts for withdrawable circuit-breakers
Insulation-test test voltage 2.5 kV With the set of 15 auxiliary contacts (+5 contacts on request compared to the 10 sup-
plied as standard), the following are available:
Maximum rated current 10 A for fixed circuit-breaker, as desired, 6 NO contacts + 7 NC contacts or 5 NO con-
Number of contacts 5 tacts + 8 NC contacts or 3 NO contacts + 10 NC contacts
for withdrawable circuit-breakers, depending on the applications required, a maxi-
Stroke 6 mm ... 7 mm mum of 6 NO contacts + 6 NC contacts and a minimum of 5 NO contacts + 5 NC
Contact force 26 N contacts are available.
On resistance 3 m
Storing temperature range - 20 C ... + 120 C Locking magnet on the truck (-RL2) (*)
Operating temperature range - 20 C ... + 70 C 24 - 30 - 48 - 60 - 110 - 125 - 127 - 132 - 220
Un
Contact over temperature 20 K - 240 V
Operating cycles 30,000 24 - 30 - 48 - 60 - 110 - 125 - 127 - 220 -
Un
Unlimited short circuit stability by using fuses of max. 10 A time-lag 230 ... 240 V~ 50/60 Hz
Operating limits 85 110% Un
Inrush power (Ps) DC = 250 W; AC = 250 VA
Continuous power (Pc) DC = 5 W; AC = 5 VA
Inrush time 150 ms
(*) Not available for versions with motorized truck.
47
6. Instructions for operating the circuit-breaker
6.1. Safety indications If the operations are prevented, do not force the
mechanical interlocks and check that the operating
The VD4 circuit-breakers guarantee a minimum IP2X sequence is correct.
degree of protection when installed in the following Racking the circuit-breaker in and out of the
conditions: switchgear must be done gradually to avoid shocks
fixed circuit-breaker, installed behind a protective which may deform the mechanical interlocks.
metal net Due to safety reasons, the circuit-breaker has to be
withdrawable circuit-breaker, installed in treated as "switched on" if the switching position
switchgear. cannot be clearly determined.
Under these conditions the operator is totally In this case all high voltage connections to the
guaranteed against accidental contact with moving circuit-breaker have to be de-energized and zero
parts. potential on the primary side of the circuit-breaker
Should mechanical operations be carried out on the has to be confirmed prior to commissioning,
circuit-breaker outside of the switchgear, take great operation, maintenance or repair work.
care of the moving parts.
3 10
Caption
1 Key lock (if provided) (*)
2 Lever for manually charging the closing spring (except version VD4/ZS8 - see figure 6b)
3 Coupling lever for racking-out operation (withdrawable circuit-breakers only)
4 Opening pushbutton
5 Closing pushbutton
6 Signalling device for circuit-breaker open/closed
7 Signalling device for closing springs charged/discharged
8 Operation counter.
9 Handles for operating the truck locks (only for withdrawable circuit-breakers)
10 Operating lever for circuit-breaker racking-in/out (there is a special version for VD4/ZS8)
11 Mechanical undervoltage release override (on request).
(*) Warning! To activate the key lock: open the circuit-breaker, keep the opening pushbutton depressed, then turn the key and remove it from the housing.
Fig. 6a
48
6.3. Circuit-breaker closing and opening b) Electrical spring charging operation
On request, the circuit-breaker can be fitted with the following
operations
accessories for electrical operation:
Circuit-breaker operation can be either manual or electrical geared motor for automatic closing spring charging
(fig. 6 - fig. 7). shunt closing release
a1) Manual closing spring charging for VD4 circuit- shunt opening release.
breakers for UniGear switchgear and PowerCube The geared motor automatically recharges the spring after
modules (fig. 7a) each closing operation until the yellow indicator (7) appears.
If the power is cut off during charging, the geared motor stops
Repeatedly activate the charging lever (2) (maximum rotation
and automatically starts recharging the springs again when
angle of the lever: about 90) until the yellow indicator (7)
the power returns.
appears.
In any case, it is always possible to complete the charging
The maximum forces which can normally be applied to the
operation manually.
lever are < 150 N for the EL1operating mechanism, < 200 N
for the EL2 operating mechanism and < 250 N for EL3
c) Circuit-breaker closing
operating mechanism.
EL1 Twin and EL2 Twin type operating mechanisms are The operation can only be carried out with the closing spring
provided for circuit-breakers with 50 kA breaking capacity. completely charged.
For manual charging, the additional lever (1) should be For manual closing, press the pushbutton (5 - fig. 6b).
inserted fully, as indicated in fig. 7c. In this way, the maximum When there is a shunt closing release, the operation can also
force to be applied is < 200 N. For the type of operating be carried out remotely by means of a special control circuit.
mechanism, please refer to the rating plate in fig. 1. Closing having taken place is indicated by the signalling
device (6 - fig. 6b).
a2) Closing spring loading in the manual mode for
withdrawable VD4 circuit-breakers for UniGear d) Circuit-breaker opening
switchgear equipped with a hand-operated rotary
For manual opening, press the pushbutton (4 - fig. 6b).
loading device for the closing spring (refer to fig. 6b
When there is a shunt opening release, the operation can also
for indicative details)
be carried out remotely by means of a special control circuit.
Rotate the charging lever (2) (rotate about 12 times) until Opening having taken place is indicated by the signalling
the yellow indicator (7) appears. The maximum force which device (6 - fig. 6b).
can normally be applied to the lever is < 150 N for the EL1
operating mechanism and < 230 N for the EL3 operating
mechanism.
The operation can be carried out with the door either open or
closed and the circuit-breaker either withdrawn or connected.
WARNING (fig. 6b): Fit the hand-operated loading lever of
the closing spring (2b) into its housing (2a). Turn the lever
clockwise (about 12 times) until the yellow indicator (7)
appears to show that loading is complete. Once this happens,
the lever will continue for half a turn without loading (without
exercising any force), after which it will lock owing to a
sudden load increase. Do not exercise force or try to continue
loading as this will damage the device.
49
10
1 5
2
7
1
9 3 6
2b
Caption
1 Key lock (if provided)
2 Lever for manually charging the closing spring
2a Coupling for manual closing spring charging (when lever 2 is not
provided)
2b Lever for manual closing spring charging for rotary charging device
3 Coupling for racking-out operation lever (only for withdrawable circuit-
breakers)
4 Opening pushbutton
2a 5 Closing pushbutton
6 Signalling device for circuit-breaker open/closed
7 Signalling device for closing spring charged/discharged
8 Operation counter.
9 Handles for operating the truck locks (only for withdrawable circuit-breakers)
10 Operating lever for circuit-breaker racking-in/out.
Fig. 6b
50
90
7
2
Fig. 7a
2 7 2 7
Fig. 7b
Fig. 7c
51
7. Installation
Humidity
The average value of the relative humidity, measured for a period longer
than 24 hours, must not exceed the 95%.
The average value of the pressure of the water vapour, measured for a
period longer than 24 hours, must not exceed 2.2 kPa.
The average value of the relative humidity, measured for a period longer
than 1 month, must not exceed the 90%.
The average value of the pressure of the water vapour, measured for a
period longer than 1 month, must not exceed 1.8 kPa.
Altitude
< 1000 m above sea level.
Fig. 8a
52
N. N.
Fig. 8b Fig. 8c
N. N.
Fig. 8d Fig. 8e
53
N. N.
Fig. 8f Fig. 8g
N. N. 12/17.5 kV
24/36/40.5 kV
Fig. 8h Fig. 8i
54
In = 1250 A In = 1250 A
In = 1600 A
In = 2000 A
N. N.
Fig. 8l Fig. 8m
7.3. Preliminary operations mechanical lock and by the circuit-breaker release device) to
carry out the function of interrupting the shunt closing release
Clean the insulating parts with clean dry cloths. circuit (-MC) during traverse from isolated and vice versa.
Check that the top and bottom terminals are clean and In ABB trucks, this function is carried out by the -BT1 and
free of any deformation caused by shocks received during -BT2 auxiliary contacts which cut of the release power supply
transport or storage. during and before activation of the mechanical lock of the
screw truck racking-in device. This means that the shunt
closing release power supply can only by applied at the end
7.4. Installation of fixed circuit-breakers of activation of the mechanical lock. In this way it is certain
that no electrical impulse can activate the shunt closing
The circuit-breaker can be mounted directly on supporting
release with the circuit-breaker in an intermediate position.
frames to be provided by the customer, or on a special
supporting truck (available on request).
The circuit-breaker, with supporting truck, must be suitably 7.5. Installation of withdrawable circuit-
fixed to the floor of its own compartment by the customer. breaker
The floor surface in correspondence with the truck wheels
The withdrawable circuit-breakers are preset for use
must be carefully levelled.
in UniGear ZS1, UniGear ZS2, UniSec switchgear and
A minimum degree of protection (IP2X) must be guaranteed
PowerCube modules.
from the front towards live parts.
For racking-in/racking-out of the switchgear, fully insert
the lever (1) (fig. 9) in the appropriate seat (2) and work it
7.4.1. Mounting the circuit-breaker on a truck made by
clockwise for racking-in, and anti-clockwise for racking-out,
other manufacturers
until the limit switch positions are reached.
The VD4 circuit-breakers which are not installed on ABB Circuit-breaker racking-in/-out must be carried out gradually
trucks, but on trucks made by the customer, must be fitted to avoid shocks which may deform the mechanical interlocks
with one or two additional auxiliary contacts (activated by the and the limit switches.
55
The torque normally required to carry out racking-in and Insert the manual racking-in lever (1) in the special coupling
racking-out is <25 Nm. (2) Fig. 9, and take the motorized truck to about half its run
This value must not be exceeded. If operations are prevented between the isolated for test and the connected position.
or difficult, do not force them and check that the operating The torque needed to carry out truck handling is < 25 Nm.
sequence is correct. In the case of accidental inversion of the truck motor power
supply polarity, this operation allows a possible error in
Note direction to be dealt with without any damage. Verification
To complete the racking-in/out operation, about 20 rotations of the lever are
checks:
required for circuit-breakers up to 17.5 kV, and about 30 rotations for 24 kV
circuit-breakers. a) motor rotation clockwise during circuit-breaker racking-in.
b) motor rotation anticlockwise during circuit-breaker
When the circuit-breaker has reached the isolated for test/ racking-out.
isolated position, it can be considered racked into the Remove the manual lever (1) from the coupling (2) Fig. 9
switchgear and, at the same time, earthed by means of the Supply the truck motor circuit.
truck wheels. Activate the control for the electrical racking-in operation.
Withdrawable circuit-breakers of the same version, and When racking-in has taken place, check correct changeover
therefore with the same dimensions, are interchangeable. of the relative auxiliary contact.
However, when, for example, different electrical accessory On completion, activate the control for the electrical
fittings are provided, a different code for the plug of the racking-out operation. When racking-out has taken place,
auxiliary circuits does not allow incorrect combinations check correct changeover of the relative auxiliary contact.
between panels and circuit-breakers. In the case of a motor fault during a racking-in or racking-
For the circuit-breaker installation operations, also refer to the out operation, in an emergency the truck can be taken to
technical documentation of the above-mentioned switchgear. the end of its run manually, after first cutting off the power
supply to the motor power supply circuit and then, using
The racking-in/-out operations must always be the manual lever, work in the same way as with the manual
carried out with the circuit-breaker open. truck.
When putting into service for the first time, it is
Note
advisable to charge the circuit-breaker operating
By means of the chain transmission, truck handling carried out using the
mechanisms manually so as not to overload the manual lever makes the truck motor armature rotate which, behaving like a
auxiliary power suply circuit. generator, can cause inverse voltage at the connection terminals.
This may damage the permanent magnet of the motor, therefore all the truck
racking-in and racking-out operations carried out using the manual lever must
7.5.1. Circuit-breakers with withdrawable motorized truck
be done without power supply in the motor circuit.
Carry out the racking-in/racking-out test of the motorized
truck in the same way as for a manual truck, following the
instructions below:
Rack the circuit-breaker into the switchgear in the open and
isolated position, with the power supply to the motor circuit
cut off and with the enclosure door closed.
Racking-in
Max 25 Nm
Racking-out
Fig. 9
56
7.6. Power circuit connections of fixed T2
57
VD4 circuit-breaker for UniGear switchgear and PowerCube module.
1 2
Fig. 10
58
8. Putting into service
8.1. General procedures Before putting the circuit-breaker into service, carry out the
following operations:
All the operations regarding putting into service check tightness of the power connections to the circuit-
must be carried out by ABB personnel or by breaker terminals;
suitably qualified customer personnel with in-depth establish the setting of the primary electronic overcurrent
knowledge of the apparatus and of the installation. release (if provided);
Should the operations be prevented, do not force check that the value of the power supply voltage of the
the mechanical interlocks and check that the auxiliary circuits is between 85% and 110% of the rated
operating sequence is correct. voltage of the electrical accessories;
The operating forces which can be applied for check that no foreign bodies, such as bits of packing, have
racking-in withdrawable circuit-breakers are got into the moving parts;
indicated in paragraph 7.5. check that there is a sufficient exchange of air in the
installation place to avoid overtemperatures;
also carry out the checks indicated in table T3.
59
T3
ITEM INSPECTED PROCEDURE POSITIVE CHECK
1 Insulation resistance. Medium voltage circuit
With a 2500 V megger, measure the insulation resistance The insulation resistance should be at least 50
between the phases and the exposed conductive part of the Mohm and in any case constant over time.
circuit.
Auxiliary circuits
With a 500 V megger (if the apparatus installed allows this), The insulation resistance should be a few
measure the insulation resistance between the auxiliary circuits Mohm and in any case constant over time.
and the exposed conductive part.
2 Auxiliary circuits. Check that the connections to the control circuit are correct: Operations and signals normal.
proceed at the relative power supply.
3 Manual operating mechanism. Carry out a few closing and opening operations (see cap. 6). The operations and relative signals take place
N.B. Supply the undervoltage release and the locking magnet normally.
on the operating mechanism at the relative rated voltage
(if provided).
4 Motor operator (if provided). Supply the spring charging geared motor at the relative rated The spring is charged normally.
voltage. The signals are normal.
With the spring charged, the geared motor
stops.
Carry out a few closing and opening operations.N.B. Supply the The geared motor recharges the spring after
undervoltage release and the locking magnet on the operating each closing operation.
mechanism at the relative rated voltage (if provided).
5 Undervoltage release Supply the undervoltage release at the relative rated voltage and The circuit-breaker closes normally.
(if provided). carry out the circuit-breaker closing operation. The signals are normal.
Cut off power to the release. The circuit-breaker opens.
The signalling changes over.
6 Shunt opening release and Close the circuit-breaker and supply the shunt opening release The circuit-breaker opens normally.
additional shunt opening at the relative rated voltage. The signals are normal.
release (if provided).
7 Shunt closing release Open the circuit-breaker and supply the shunt closing release at The circuit-breaker opens normally.
(if provided). the relative rated voltage. The signals are normal.
8 Key lock (if provided). Open the circuit-breaker, keep the opening pushbutton Neither manual nor electrical closing takes
depressed, then turn the key and remove it from the housing. place.
Attempt the circuit-breaker closing operation.
Put the key back in and turn it 90. Both electrical and manual closing take place
Carry out the closing operation. normally; in this position the key cannot be
removed.
9 Locking electromagnet (-RL1) With the circuit-breaker open, spring charged and locking Closing is not possible.
(if provided). electromagnet not supplied, attempt circuit-breaker closing both
manually and electrically.
10 Auxiliary contacts in the Insert the auxiliary contacts in suitable signalling circuits. Signals take place normally.
operating mechanism. Carry out a few closing and opening operations.
11 Locking electromagnet on the With the circuit-breaker open, in the isolated for test position Racking-in is not possible.
truck circuit-breaker (-RL2) and the locking electromagnet not supplied, attempt racking-in
(if provided). of the circuit-breaker.
Supply the locking electromagnet and carry out the racking-in Racking-in takes place correctly.
operation.
12 Auxiliary transmitted contacts Insert the auxiliary contacts in suitable signalling circuits. The signals due to the relative operations take
for signalling circuit-breaker With the circuit-breaker racked into the enclosure, carry out a place normally.
racked-in, isolated (UniGear few traverse operations from the isolated for test position to the
switchgear or PowerCube connected position.
modules). Take the circuit-breaker to the racked-out position.
60
9. Maintenance
The maintenance operations are aimed at keeping the switching device, actuator and transmission system: up
apparatus in good working condition for as long as possible. to 30,000 operations, under normal operating conditions,
In accordance with what is specified in the IEC 61208 / DIN according to the type of circuit-breaker and with regular
31 051 Standards, the following operations must be carried maintenance (see par. 9.3.2.);
out. with operations correctly executed it is possible to carry out
Inspection: Finding out the actual conditions up to 1000 racking-out/in operations (as prescribed in the
Overhauling: Measures to be taken to maintain the specific IEC 60271-200 Standards);
conditions the data regarding the operating life are basically applicable
Repairs: Measures to be taken to restore the specific to all the components which cannot be directly affected
conditions. by operator activity. The manually operated components
(moving parts of isolatable parts, etc.) can vary their
behaviour.
9.1. General
The vacuum circuit-breakers are characterised by simple,
sturdy construction and a long life.
9.2. Inspections and functionality tests
The operating mechanism requires maintenance and 9.2.1. Interruption devices in general
functional inspections to reach the expected operating-life Check the conditions of the interruption devices with regular
(see par. 9.3.2.). inspections.
The vacuum interrupters are maintenance-free for their whole Inspection at fixed intervals can be avoided when the
operating life. apparatus is permanently under the control of qualified
Vacuum interruption does not produce any harmful effects personnel.
even when there are frequent interruptions at the rated and The checks must, first of all, include visual inspection
short-circuit current. to check for any contamination, traces of corrosion or
The interventions during service and their aim are determined electrical discharge phenomena.
by the ambient conditions, by the sequence of operations and Carry out more frequent inspections when there are unusual
by the short-circuit interruptions. operating conditions (including severe climatic conditions)
Note and in the case of environmental pollution (e.g. high level of
Respect the following Standards for maintenance work: contamination or an atmosphere with aggressive agents).
the relative specifications given in the chapter on Standards and
Visual inspection of the isolating contacts.
Specifications;
work safety regulations in the chapter on Putting into service and
It is recommended to turn the contact system alternately
operations; in order to keep the internal surface of the contact areas
standards and specifications of the country where the apparatus is installed. clean. The contact areas must be cleaned when there
The maintenance operations must only be carried out by are signs of overheating (discoloured surface) (also see
trained personnel and who follow all the safety regulations. Repairs).
Furthermore, it is advisable to call on ABB personnel, at least In the case of abnormal conditions, take suitable
in cases for checking the performances in service and for overhauling measures (see Overhauling par.).
repairs.
Cut the power supply off and put the apparatus under safe 9.2.2. Stored energy operating mechanism
conditions during the maintenance operations. Carry out the functional test of the operating mechanism after
5,000 operations or during ordinary maintenance operations
Before carrying out any operations, check that the as specified in par. 9.2.1.
circuit-breaker is open, with the spring discharged Before doing the test, open the circuit-breaker and carry out
and that it is not supplied (medium voltage circuit the following operations:
and auxiliary circuits). in the case of withdrawable circuit-breakers, take the
circuit-breaker to the isolated for test position
in the case of fixed circuit-breakers: cut off the power
9.1.1. Operating life expectancy
supply to the medium voltage circuit.
The operating life expectancy for the VD4 circuit-breakers is
as follows: Note
vacuum interrupters: up to 30,000 operations, according to Insulate the work area and make it safe, following the safety regulations
specified in the IEC/DIN VDE Standards.
their type (see par. 7.2.3. Trip curves);
61
Functional test Check correct electrical and mechanical operation of the
With the circuit-breaker not connected to the load, carry out various devices, with particular attention to the interlocks.
a few opening and closing operations. The screws and nuts are tightened in the factory and
If foreseen, cut the power supply to the spring charging correct tightening is marked with a collared sign. No further
motor off. Discharge the spring by closing and opening tightening operations are foreseen during the operating life
the circuit-breaker by means of the closing and opening of the circuit-breaker. However, following any maintenance
pushbuttons. interventions, should it be necessary to re-tighten the screws
Visually inspect the lubrication conditions of the tulip or nuts, it is recommended to always replace the screws and
isolating contacts, of the sliding surfaces, etc. nuts and to keep to the values indicated in fig. 12.
25 Nm 15 Nm 15 Nm
15 Nm
15 Nm
25 Nm
EL Twin actuator - 50 kA
15 Nm 15 Nm
15 Nm
Fig. 12
62
9.2.3. Circuit-breaker pole Circuit-breakers up to 17.5 kV, 40 kA and 24 kV, 31.5 kA
No other check except what has already been specified in To ensure correct operation of the circuit-breaker, inspection
par. 9.2.1. is necessary. and maintenance of the tripping devices is recommended
every 10,000 operations. For this purpose, please contact the
9.2.4. Withdrawable assembly (truck and circuit-breaker) ABB Service office.
Visually inspect the components, especially those which may Complete replacement of the actuator must be carried out
be damaged by incorrect operations (also see table in chap. 8). every 10,000 operations.
Visually inspect the isolating contacts and that all the contact Complete replacement of the shock absorber and of the other
elements are clean, especially in cases where signs of transmission system parts (shaft, main levers, safety rings,
overheating are found (also see par. 9.4.). etc.) must be carried out after 30,000 operations.
Visually inspect and carry out the functional tests of the
locks, checking their correct operation and activation without Circuit-breakers up to 17.5 kV, 3150 A, 40 kA
abnormal force maximum 25 N (also see table in chap. 8). To ensure correct operation of the circuit-breaker, inspection
and maintenance of the tripping devices must be carried out
every 5,000 operations. For this purpose, please contact the
9.3. Overhauling ABB Service office.
Complete replacement of the shock absorber and of the other
9.3.1. Interruption devices in general
part of the transmission system (shaft, main levers, safety
Should it have been necessary to clean the devices during the rings, etc.) must be carried out after 10,000 operations.
inspections, according to what is specified in par. 9.2.1., use
the following procedure: Circuit-breakers up to 17.5 kV, 50 kA and EL twin actuator
insulate the work area and make it safe, following the safety
To ensure correct operation of the circuit-breaker, inspection
regulations specified in the IEC/DIN VDE Standards;
and maintenance of the tripping devices must be carried out
general cleaning of the surfaces:
every 10,000 operations. For this purpose, please contact
dry and eliminate light deposits of dirt with a soft dry
ABB Service.
cloth;
Complete replacement of the shock-absorber and of the other
more resistant deposits of dirt can be removed using
parts of the transmission system (shaft, main levers, safety
slightly alkaline domestic type detergent or Rivolta BWR
rings, etc.) must be carried out every 10,000 operations.
210 type detergent;
cleaning insulating surfaces and conductive parts: Note
light dirt: with Rivolta BWR 210 detergent; Dismantling and replacement of the operating mechanism (trip box) can only
be carried out by ABB personnel or by skilled and specially trained personnel,
resistant dirt: with cold detergent type 716.
particularly for the necessary adjustments.
After cleaning, rinse thoroughly with clean water and dry
carefully.
Details regarding overhauling
Note When foreseen, cut of the power supply to the spring
Only use detergents without halogens and never 1.1.1-trichloroethane, charging motor and manually discharge the operating
trichloroethylene or carbon tetrachloride!
mechanism spring by closing and opening the circuit-
breaker.
9.3.2. Tripping device: actuator and transmission system
Replace the parts subjected to mechanical stress or stress
Circuit-breakers up to 17.5 kV, 2500 A, 31.5 kA and up to due to particular environmental conditions, (contact and
24 kV, 2500 A, 25 kA ABB service centre).
To ensure correct operation of the circuit-breaker, inspection
Note
and maintenance of the tripping devices is recommended
These operations can only be carried out by ABB personnel or by skilled and
every 10,000 operations. For this purpose, please contact the specially trained personnel.
ABB Service office.
Complete replacement of the actuator, shock absorber and of
the other transmission system parts (shaft, main levers, safety
rings, etc.) must be carried out after 30,000 operations.
63
9.3.3. Circuit-breaker pole 9.4. Repairs
The circuit-breaker pole and relative vacuum interrupter are
Replacement of spare parts and accessories must only
maintenance-free until the maximum number of electrical
be carried out by ABB personnel or suitably qualified and
operations for the type of interrupter is reached (see par.
specially trained personnel.
7.2.3. Trip curves).
Always work with the circuit-breaker open and locked so that
The operating life of the vacuum interrupter is defined by the
it cannot be closed again, with the work area insulated and
sum of the ultimate currents corresponding to the specific
made safe.
type of interrupter in accordance with what is indicated in the
The operating mechanism spring must be discharged.
graphs of par. 7.2.3. Trip curves: when the sum of the ultimate
All power supply sources must be disconnected and made
currents is reached, the whole pole must be replaced.
safe against any reclosing during removal and installation
Note work.
Dismantling and replacement of the pole can only be carried out by ABB
personnel or by skilled and specially trained personnel, particularly for the
Should maintenance be carried out by the
necessary adjustments.
customers personnel, responsibility for the
To carry out the interrupter test without dismantling the interventions remains with the customer.
circuit-breaker pole, use: The replacement of parts not included in the List
of spare parts/accessories (par. 12.1.) must only
the VIDAR vacuum tester, made by the company
be carried out by ABB personnel. In particular:
Programma Electric GmbH, Bad Homberg v.d.H.
complete pole with bushings/connections
To check vacuum tightness of the interrupter, the following
actuator and transmission system
test values must be set on the VIDAR tester:
closing spring set
Rated voltage of the circuit-breaker d.c. test voltage opening spring
12 kV 40 kV shock-absorber.
17.5 kV 40 kV
24 kV - 36 kV 60 kV
Note
The tester connection cables can produce an indication due to the capacitive
effect. In this case the cables must not be removed.
64
10. Application of the X-ray emission Standards
65
11. Spare parts and accessories
66
12. Electric circuit diagrams
67
13. Overall dimensions
450
Fixed circuit-breakers 248
95
VD4 32
A
TN 1VCD000050
20 20
12 kV 2XM10 PROF.20
Ur
310
17.5 kV 4XM12 PROF.25
Ir 1600 A
599
12
20 kA
20
475
56 31
435
20
Isc 25 kA
16
12
31.5 kA
237.5
14
170
77.5
97
56
236 28
DETAIL A
49 28 345* 44* SCALE 1 : 2 . 5
25 400 250
45 114 12
150 150 409
424
160
12
22
Fixed circuit-breakers
450
VD4
45
248 32
TN 7405 95 2xM10 PROF.18
M12 PROF.25
12 kV
Ur
17.5 kV A
630 A
22
Ir 115
1250 A
205
16 kA
31
435
475
461
16
20 kA
56
Isc
25 kA 22
217.5
31.5 kA
170
77.5
DETAIL A
56
SCALE 1:2
236 28
345* 44*
49 28
409
12
68
Fixed circuit-breakers
570
VD4
32 45
TN 7406 308
95
2XM10 PROF.20
12 kV M12 PROF. 25
Ur
17.5 kV A
630 A
22
Ir 115
205
1250 A
31
16 kA
461
475
435
56
16
20 kA 22
Isc
25 kA 170
217.5
31.5 kA DETAIL A
77.5
SCALE 1:2
24
296 28
345 * 44 *
49 28
12
Fixed circuit-breakers
570
VD4 95
308
TN 1VCD003282 11 11
12 kV
Ur
11
17.5 kV M12x25 deep
1250 A
Ir eep
x18 d
310
M10
11
1600 A
A
Isc 40 kA
30
589
16
475
435
56
A (1:4)
238
171
77.5
24
296 28
345 * 44 *
49 28
45 250 114
520
409
210 210
422 12
160
26
12
69
Fixed circuit-breakers
700
VD4 11 11
95
TN 1VCD003285 373 M12x25 deep
M10x18 deep
11
12 kV
Ur A
17.5 kV
1250 A
Ir
310
1600 A
11
Isc 40 kA 30
589
16
435
475
56
238
24
171
77.5
36 28 45 250 114
361 49 28 345 * 44
25 650 422 12
275 275
213
22
12
Fixed circuit-breakers
700
VD4
373 95 45
TN 1VCD000051 2XM 10 PROF. 18
32 M12 PROF. 25
12 kV
Ur A
17.5 kV
22
205
630 A 115
Ir
1250 A
475
56 31
461
22
435
16
16 kA
14
217.5
77.5
20 kA
24
DETAIL A
170
Isc SCALE 1 : 2
97
25 kA
31.5 kA 236 28
345 * 44 *
49 28
45 250 114 12
25 650
409
424
275 275
213
12
22
70
Fixed circuit-breakers
12 kV 32
A
Ur
17.5 kV
1600 A
310
Ir 2000 A
2500 A
31
599
616
20 kA
475
435
56
Isc 25 kA 16
237
31.5 kA
170
78
VD4
24
361 28 345 * 44 *
TN 7408 49 28 45 250 114
20 20
12 kV 25 650 409 12
Ur 2XM10 PROF.20
17.5 kV 424
20
275 275
12
2000 A
Ir 213
2500 A
12
Isc 40 kA
20
4XM12 PROF.25
DETAIL A
SCALE 1:2
12
22
Fixed circuit-breakers
Ur 12 kV A
Ir 2500 A 32
20 kA
310
25 kA
Isc
599
31.5 kA
31
616
40 kA
435
475
56
16
237.5
VD4
170
77.5
TN 7407
Ur 12-17.5 kV 296 28
24
345 * 44 *
1600 A 49 28
45 250
Ir
2000 A 25 520 409 12 2XM10 deep 20
20 kA 424 20 20
210 210
25 kA 4XM12 deep 25
Isc 160
31.5 kA
20
12
40 kA
12
20
DETAIL A
SCALE 1:2
22
12
71
Fixed circuit-breakers
373 424
VD4
20 20
95 307
TN 1VCD000149
12 kV
Ur
20
12
17.5 kV
32
3150 A
Ir
12
310
20
4000 A (**)
A
20 kA
635
30
25 kA
435
474
2x
5
th 2
M1
Isc 31.5 kA
0
dep
56
de
16
237
40 kA
pth
A (1:4)
12
171
4xM
2.5
20
24
77.5
50 kA
28
142
25 49
345* 44*
361 28
45 250 114
650
700 409
275 275
213
22
12
Fixed circuit-breakers
600
VD4
323 4xM12 deep 25
459
TN 1VCD003440 130
300 2xM10 deep 20
12 kV
20
Ur
12
17.5 kV 74
1250 A
12
32 20
20
20
Ir 1600 A
310
2000 A
610
30
Isc 50 kA
16
475
435
56
237
171
24
77.5
2.5
156
135 116 28 31 172 142
2.5
40 165 28 404
520 428
210 210
22
12
72
Fixed circuit-breakers
750 459
VD4 4xM12 deep 25
398
130
TN 1VCD003441 375 2xM10 deep 20
20
12 kV
12
Ur 74
17.5 kV
20
12
32
20
1250 A 20
310
1600 A
Ir
610
2000 A
30
16
2500 A
475
435
Isc 50 kA
56
237
24
171
24
78
135 116 28
2.5
2.5
165 28 69.5 270 64.7 225
30.5 689
404 24
31 428
275 275
22
12
Fixed circuit-breakers
750 459
VD4 4xM12 deep 25
398 240 2xM10 deep 20
189
TN 1VCD003443 189
375 130
12 kV
20
Ur
12
118
17.5 kV 74
Ir 3150 A (*) 32
20
12
20
Isc 50 kA 20
310
636
30
16
475
435
56
237
171
24
24
2.5
135 172
2.5
116 28
69.5 270 64.5 225
30.5 165 28
404 24
689 31 428
275 275
12
22
12
73
Fixed circuit-breakers
570
VD4 95
308
TN 7409 45
A
Ur 24 kV 32 2XM10 PROF.20
M12 PROF.25
630 A
Ir
1250 A
310
22
115
16 kA
22
Isc 20 kA
631
31
25 kA 22
475
435
56
16
282.5
170
DETAIL A
77.5
SCALE 1:2
24
296 28 M12 345* 39*
49 28 45 250 114 12
25 520 409
424
210 210
160
Fixed circuit-breakers
700
VD4 95 22
373 2XM10 PROF.18 M12 PROF.25
TN 7410
A
Ur 24 kV
32
630 A
22
Ir
1250 A
310
115
16 kA
45
Isc 20 kA
631
31
25 kA
475
435
16
282.5
56
170
77.5
DETAIL A
361 28 345 * 44 * SCALE 1:2
24
49 28 45 250 114 12
25 650 409
424
275 275
213
22
12
74
Fixed circuit-breakers
Ur 24 kV
1600 A
Ir 2000 A
310
2500 A
16 kA
661
647
20 kA 31
16
Isc
25 kA
475
435
31,5 kA
282.5
56
170
361 28 345 * 44 *
24
77.5
45 250 114
49 28
409
25 650 424
20 20
275 275
20
12
12
20
4XM12 DEEP 25
22
DETAIL A
SCALE 1:2
Fixed circuit-breakers
570
VD4 95 85
308
TN 1VCD000172
4XM12 DEEP25 2XM10 DEEP 20
Ur 24 kV
40
Ir 1250 A
32
Isc 31.5 kA
310
12
72
22
647
12
31
475
435
16
56
282.5
77.5
72
17 0
DETAIL A
24
SCALE 1 : 2
296 28
M12 45 250 114
49 28
344.5 * 39*
25 520
409
210 210
424
160
22
75
Fixed circuit-breakers
784
VD4
TN 1VYN300901-LT
Ur 36 kV
1250 A 245
Ir 1600 A R16
328
2000 A
Isc 31.5 kA
31.17
57.9
876
612
571
482.5
15.5
305
28
49
104.5
87.5
28
786
331
275 275
447
470 22
478.5
76
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
10
630 A
Ir
91
79
98
1250 A
16 kA
205
35
35
624.5
31
20 kA 618
628
Isc
25 kA 16
56
71 38
31.5 kA
260
213
154
19
76
340
19.5
18
4
503 14 25 320
24
531
370
501 383
490
416 53
456
150 150 438
662
55
609
124
121
38
48
636
VD4/W
44 230 119
111
TN 7420 49 28
8
62.5
12 kV 36 28
Ur
17.5 kV
630 A 36
35
Ir
1250 A
310
16 kA 303
691
688
31
Isc 25 kA
691
688
16
31.5 kA
71 38
56
280
213
165
76
18
653 14 25 320
21.5
19.5
4
650 359.5
640 370
626 383
550 416 53
642
210 210
55
589
119
111
48
38
77
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
636 125
VD4/P
44 230 111 17
TN 1VCD003284 49 28 62.5
8
12 kV 36 28
Ur
17.5 kV
1250 A 37
Ir
1600 A
310
Isc 40 kA
688
30
688
691
303
16
79
71 38
56
280
214
165
76
21.5
4
19.5
18
4
653 14 320
25
650 359.5
640 370
626 383
552
416 53
210 210
640
55
587
640
53
38
842
VD4/P
144 230 119
TN 1VCD003286 49 28
111 17
122
36 28
8
12 kV
Ur
17.5 kV
1250 A 303
Ir 37
1600 A
310
Isc 40 kA
691
688
30
16
688
79
71 38
56
280
213
165
76
19.5
25 320
21.5
4
853 14
4
359.5
850
370
836
383
806
416 53
750
640
275 275
55
587
53
38
78
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
636
VD4/P 119
44 230 111 17
TN 7415 49 28 62.5
122
8
12 kV 36 28
Ur
17.5 kV
1600 A 36 303
Ir
310
2000 A
79
20 kA
688
691
688
31
Isc 25 kA
16
71 38
31.5 kA 56
280
213
165
VD4/P
76
TN 7415 653 14
4
25 320
19.5
21.5
4
12 kV 359.5
650
Ur 370
17.5 kV 640 383
626 416 53
Ir 2000 A
550 640
Isc 40 kA 210 210
55
587
119
111
53
38
842
VD4/P 119
144 230
TN 7416 110
49 28
122
62.5
8
12 kV 36 28
Ur
17.5 kV
1600 A 303
36
Ir
2000 A
310
79
688
20 kA
31
691
688
Isc 25 kA
71 38
56
16
31.5 kA
280
213
165
VD4/P
76
TN 7416
19.5
21.5
4
853 14 25 320
359.5
12 kV
Ur 850 370
17.5 kV 836 34 383
806 416 53
Ir 2000 A 640
750
Isc 40 kA 275 275
55
587
119
111
53
38
79
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
842
VD4/P 119
144 230
TN 7417 49 28 111 17
152
36 28 62.5
12 kV
8
Ur
17.5 kV
Ir 2500 A
303
20 kA
109
36
310
25 kA
Isc
31
691
688
16
31.5 kA
688
40 kA
56
71 38
280
213
165
76
19.5
25 320
21.5
853 14
4
4
359.5
850
370
836
383
806
416 53
750
640
275 275
587
55
119
111
53
38
636
VD4/P
44 220 25 119
TN 1VCD003444 165 28
111 16
10
12 kV 135 116 28
Ur
17.5 kV
122
1250 A
36 433
Ir 1600 A 20
310
2000 A
79
30
16
688
691
Isc 50 kA
688
478
56
26
280
19.5
213
165
19
76
21.5
12
605
4
25
4
4
14 653 14 320
370
650
359.5 49.5
640
34 383
626
416 53
550
590
210 210
29
590
360
303
4
12
23
80
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube modules
842
VD4/P
144 217.5 25 119
TN 1VCD003445 111 16
165 28
12 kV
Ur 135 116 28
10
17.5 kV
122
1600 A
Ir 433
36
2000 A
310
20
Isc 50 kA
79
688
691
688
30
16
478
56
26
280
213
165
19
76
25 4
19.5
805
4
21.5
12
4
320
14 853 14
370
850 359.5 49.5
836 34 383
806 416 53
750 590
275 275
29
590
360
303
4
22
12
842
VD4/P
143 217.5 119
25
TN 1VCD003446 164 28 111 16
12 kV 136 115 28
Ur
10
17.5 kV
152
Ir 2500 A
36
Isc 50 kA 20
310
433
109
688
30
691
688
16
478
56
280
19.5
26
213
165
19
12
76
25
21.5
805
4
320
14 853 14 370
850 359.5 49.5
836 34 383
812 417
750 590
275 275
29
590
360
303
4
12
22
81
Withdrawable circuit-breakers for PowerCube modules
842
VD4/W
361 25
119
TN 1VCD003596 129 30 240 111 16
10
12 kV 130
Ur 165 28
17.5 kV 135 116 28
118
152
Ir 3150 A (*)
Isc 50 kA
36
20
310
433
742
109
742
730
732
678
30
16
478
56
280
26
213
19,5
165
19
76
805 25 4
21,5
4
12
4
14 853 320
850 370
836 359,5 49,5
806 34 383
416,5 53
750 590
275 275
29
189
590
360
303
4
12
22
842
VD4/P
361 25
TN 1VCD003447 240 111 16
10
165 28
12 kV 130
Ur 135 116 28
17.5 kV
118
152
Ir 3150 A (*)
Isc 50 kA 20
36
433
310
109
730
742
678
733
30
16
478
56
280
26
213
19.5
165
19
76
805 25 4
21.5
4
12
14 853
4
320
850 370
836
359.5 49.5
806
34 383
416 53
750 590
275 275
29
189
589
360
303
4
12
22
82
Withdrawable circuit-breakers for UniGear ZS1 switchgear
842 111 17
VD4/P 373.5
17kV 93
10
49 12kV
TN 1VCD000153
28
12 kV
2
36 86
Ur
17.5 kV
166
149
Ir 3150 A (*) 52
20 kA
310
25 kA 730
30
732
Isc
31.5 kA
109
16
40 kA
280
56
214
165
19
76
356
19.5
21.5
303 53
4
4
853 14
25 320
850
836 360
806 370
750
34 382
275 275
416
640
16
8
55
587
4
96
189
12
22
39
Isc 20 kA
770
775
25 kA
770
31
16
71 38
56
325
213
197
72
650 370
641 383
610 458
800
98
79
79
36
747
55
35
35
19
119
83
Withdrawable circuit-breakers for UniGear ZS1 switchgear
20
49 28
630 A 36 28
Ir
1250 A 48
310
16 kA
790
775
770
7
Isc 20 kA
31 3
25 kA 16
56
71 38
325
5
197
213
72
25 320
4
4
853 14 370
383
850
458
836
303 53
805
800
275 275
79
98
79
747
35
35
36
55
19
119
53
49 30
1600 A 36 28
Ir 2000 A
2500 A (1)
310
834
16 kA
31
810
817
16
20 kA
Isc
25 kA
345
56
31.5 kA
233
197
72
25 320
4
853 14
4
370
850 383 46
836 303 53
805 458
785
275 275
132
732
79
55
119
52
(1) The rated uninterrupted current of 2300 A is guaranteed with natural ventilation. The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.
84
Withdrawable circuit-breakers for UniGear ZS1 switchgear
636
VD4/P 119 23
44 232 19
TN 1VCD000173
20
Ur 24 kV
1250 A
79
Ir 49 28
Isc 31.5 kA 36 28 48
310
35
775
770
770
71
56 31
16
326
213
197
72
4
4
653 13.5 25 320
303 53
650 370
641 383
610 458
800
210 210
747
55
119
19
842
VD4/P
141 233
TN 1VCD000177
Ur 24 kV 49 28
2700 A 36 28
166
Ir
3150 A
310
Isc 31.5 kA
109
834
817
810
31
16
56
345
233
25 320 46
4
853 14
4
370
850
383
836 303
805 458 53
787
275 275
734
55
119
52
85
Withdrawable circuit-breakers for PowerCube modules
842
VD4/W 125 17
144 230
111
TN 1VCD000152
10
49 92
12kV 17kV
12 kV 28
86
Ur 36
17.5 kV
149
166
Ir 3150 A (*) 52
20 kA
310
730
25 kA
30
Isc
742
31.5 kA
109
16
40 kA
280
56
214
165
19
76
356
19.5
303 53
4
853 14
25 320
850
360
836
370
806
34 382
750
275 275 416
640
16
8
29
55
587
302
94
4
189
38
12
22
86
Withdrawable circuit-breakers for ZS8.4 switchgear
91
Ur 12 kV
Ir 630 A
20 kA
Isc
25 kA
205
35
563
510
260
4
503 53
548
150 150
55
495
Ur 12 kV
Ir 630 A
20 kA
Isc
25 kA
205
35
563
510
260
153
503 195
4
486 380 53
150 150 640
55
584
87
Withdrawable circuit-breakers for ZS8.4 switchgear
91
Ur 12 kV
Ir 630 A
5
20 kA
Isc
205
25 kA
35
563
524
510
260
153
86
69
4
195
503
486 380 53
150 150 640
55
584
67
5
20 kA
Isc
25 kA
98
205
35
563
524
514
260
153
86
69 195
4
503 380 53
486 637
150 150
55
583
67
88
Withdrawable circuit-breakers for ZS8.4 switchgear
205
Ir
84
35
1250 A
20 kA
563
507
Isc
25 kA
260
503
53
150 150
55
495
VD4/ZT8 530
486 303 52
TN 1VCD000134
455
12 kV
Ur
17.5 kV
630 A
Ir
1250 A
205
98
35
20 kA
563
Isc
514
25 kA
260
153
503 195
4
486 383 53
150 150 637
55
583
89
Withdrawable circuit-breakers for ZS8.4 switchgear
VD4/ZS8 681
3 303 52
636
TN 1VCD000088
91
Ur 24 kV 611
Ir 630 A
16 kA
310
Isc 20 kA
35
25 kA
680
563
524
325
86
69
4
653 195
636 380 53
640
210 210
55
583
67
VD4/Z8
681 3 303 52
TN 1VCD000089
Ur 24 kV
91
Ir 630 A
16 kA
310
Isc 20 kA
35
25 kA
680
563
325
653
4
53
210 210 640
55
583
90
Withdrawable circuit-breakers for ZS8.4 switchgear
310
Isc 20 kA
84
35
25 kA
677
563
325
653 53
4
210 210 640
55
587
Isc 20 kA
35
25 kA
680
563
325
653 195
4
636
380 53
210 210
640
55
585
91
Withdrawable circuit-breakers for ZS8.4 switchgear
VD4/ZT8 681
303 52
636
TN 1VCD000136
Ur 24 kV
611
Ir 1250 A
16 kA
310
Isc 20 kA
84
35
25 kA
677
563
325
653
4
195
636
210 210 380 53
640
55
587
VD4/ZS8 681
636 303 52
TN 1VCD000135
Ur 24 kV
611
Ir 1250 A
16 kA
310
Isc 20 kA
84
35
25 kA
677
563
524
325
86
69
4
195
653
636 380 53
640
210 210
55
587
67
92
Withdrawable circuit-breakers for UniSwitch / UniMix switchgears
310
16 kA
A
35
35
Isc 20 kA
48
25 kA
435,5
38
325
653 13,5 25 320
4
650 370 23
383
36.3
210 210 303 53
742
DETAIL A
SCALE 1 : 2
55
Ur 24 kV
3
45
630 A
Ir
1250 A
16 kA
3101
Isc 20 kA A
35
35
25 kA 42
739
4351
38
3251
18
653 14 25 320
4
650 370 23
383
36.3
303
2101 2101 415
648 1.5 53
DETAIL A
742
SCALE 1 : 2
55
93
Withdrawable circuit-breakers for UniGear ZS2 switchgear and PowerCube modules (36 kV)
842
VD4
TN 1VYN300901-KG
Ur 36 kV
"A"
1250 A
Ir 1600 A 776
380
2000 A
Isc 31.5 kA
953
956
973
480
125
198
853 4 4
880 460 53
736
275 275
736
Breaker type A mm
VD4 36.12.32 35
VD4 36.16.32 - VD4 36.20.32 79
94
14. Product quality and environmental protection
The apparatus are produced in compliance with the requirements of international standards for the quality management system
and environmental management system. In these fields, the excellent level is proved by quality certificates according to ISO
9001 and by the EMS according to ISO 14 001.
Methods of disposal
Disposal can either be carried out thermally in an incineration plant or by storing on a waste site.
95
Notes
96
For more information please contact:
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
D-40472 Ratingen
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: powertech@de.abb.com
www.abb.com
The data and illustrations are not binding. We reserve the right to make
changes without notice in the course of technical development of the
product.