Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
User manual
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporations
(Eaton) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales
office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY
EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or
other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to
damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of
existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information,
recommendations and descriptions contained herein. The information contained in this manual is subject to change without
notice.
Contents
SAFETY
Definitions of symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
GENERAL
Instructions for using the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Description of the Power Xpert CXH system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Power Xpert CXH structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Power Xpert CXH busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Main busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Vertical busbar system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Power Xpert CXH incoming units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Power Xpert CXH outgoing units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
POWER XPERT CXH USER MANUAL MN019002EN October 2015 www.eaton.com iii
Power Xpert CXH
List of figures
Figure 1. Power Xpert CXH cubicles: width variants. . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 2. Power Xpert CXH cubicles: depth variants . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 3. Power Xpert CXH panelsmain busbars . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Figure 4. Power Xpert CXH panelsvertical busbars. . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 5. Power Xpert CXH panelsincomers and buscouplers . . . . . . . . . . . . . . . . .6
Figure 6. Power Xpert CXH panelswithdrawable units . . . . . . . . . . . . . . . . . . . . . .7
Figure 7. Power Xpert CXH panelsfixed units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 8. Detailed floor plan for Power Xpert CXH panel . . . . . . . . . . . . . . . . . . . . . .10
Figure 9. Placement and escape routes overview . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 10. Lifting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11. Busbar installation1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 12. Busbar installation2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 13. Busbar installation3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 14. Single busbar per phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 15. Double busbar per phase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 16. Main busbar coupling set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 17. Main busbar coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 18. Single main busbar connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 19. Double main busbar connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 20. Top side cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 21. Roof installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 22. Top cable entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 23. Bottom cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 24. Standard mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 25. Setting of NZM for protection of cables . . . . . . . . . . . . . . . . . . . . . . . . . .21
Figure 26. Setting of NZM for protection of motors . . . . . . . . . . . . . . . . . . . . . . . . .21
Figure 27. Series NRX and Magnum air circuit breakers . . . . . . . . . . . . . . . . . . . . . .21
Figure 28. Power Xpert CXH withdrawable motor control center . . . . . . . . . . . . . . .22
Figure 29. Typical MCC withdrawable unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 30. Withdrawable unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 31. Withdrawable unitdoor opened . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Figure 32. Withdrawable unitdrawer aligned with the compartment rails . . . . . . .23
Figure 33. Withdrawable unitrolling in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 34. Pushing down the lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 35. Withdrawable unit showing MCCB in OFF state . . . . . . . . . . . . . . . . . . .25
Figure 36. Withdrawable unit with doors closed and racking tool inserted . . . . . . . .25
Figure 37. Disconnect position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 38. Locked door and MCCB supply turned OFF . . . . . . . . . . . . . . . . . . . . . . .26
Figure 39. Withdrawable unit with doors closed and racking tool
inserted to disconnect the contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 40. View after opening the doorlock brace at the bottom position . . . . . . .27
List of tables
Table 1. Rating and cross sections of main busbars . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 2. Rating and cross sections of vertical busbars . . . . . . . . . . . . . . . . . . . . . . . .5
Table 3. Power Xpert incomers ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Table 4. Rating for the withdrawable units MCCB . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Table 5. Power Xpert fixed unit ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Table 6. Placement distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 7. Power Xpert fixed unit ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Table 8. Drawer sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Table 9. Power Xpert CXH safety interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Table 10. Sizes for top cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Table 11. Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Table 12. Enclosure spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Table 13. Busbar spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Table 14. Busbar spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Table 15. Data outgoing units400/415 for outgoing units . . . . . . . . . . . . . . . . . . . .56
Table 16. User connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Safety
Definitions of symbols
WARNING
This symbol indicates high voltage. It calls your
attentionto items or operations that could be dangerous
to you and other persons operating this equipment.
Read the message and follow the instructions carefully.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as
well as WARNING).
Warnings
WARNING
Never try to insert the drawer into the panel with circuit
breaker in the ON position.
WARNING
Never try to start this procedure of removal of the unit
with the MCCB in the ON position.
WARNING
Never try to switch the MCCB to ON position while
racking-in or racking-out the drawer.
WARNING
The vertical distribution busbars are not automatically
electrically dead when the door is opened.
POWER XPERT CXH USER MANUAL MN019002EN October 2015 www.eaton.com vii
Power Xpert CXH
viii POWER XPERT CXH USER MANUAL MN019002EN October 2015 www.eaton.com
General
General
Instructions for using the manual Description of the Power Xpert CXH system
Aim of the manual System overview
This manual contains instructions for the installation, The Power Xpert CXH is a low voltage motor control center
putting into operation, using and maintenance of the Eaton and/or a distribution system made of standard sheet metal
low voltage switchgear system type Power XpertCXH. cubicles.
Instructions for trouble shooting are also given. It is
important for the proper and safe functioning of the system The system is designed for a nominal service-voltage of
that these instructions are observed and carried out by a 400V up to 480 V (dependent of the build-in components).
skilled electrical engineer. The information corresponds as The nominal current of the Main busbar system can be from
closely as possible with the supplied product. However, 800 A to a maximum of 4000 A. The maximum rated short-
due to Eatons policy of continual product improvement, time current is 100 kA rms-1s. (Higher nominal currents are
itispossible that certain details will vary. realized by means of a double busbar system).
The information in this manual will guide the user of the The outgoing functions can be either fixed or withdrawable
product through all the facets of the operation for which type.
theproduct is designed.
Power Xpert CXH structure
The assembly instructions, and applications, etc., are
Power Xpert CXH Panels are made up of completely
however non-binding, serving for reference purposes.
compartmented cubicles
Eaton products are supplied in accordance with the general
terms and conditions of sales and supply which have been Height
lodged with the Chambers of Commerce. This product Power Xpert CXH cubicles are of a modular design. The
manual in no way affects these general conditions. standard height is 2300 mm. The space in which apparatus
can be fitted amounts to a maximum of 1900 mm in the
Structure of the manual fixed panels and 1750 mm in the withdrawable panels. The
In order to make the manual as useful as possible, it has 1750 mm equals 14 times the modular height of 125 mm.
been organized according to a strict system. The structure
of the manual is as follows. Depth
The manual is divided into chapters The standard cubicle depth is 600 mm up to a 4000 A rated
horizontal main busbar system. The Top cable option comes
Each chapter is divided into paragraphs with an additional panel thats connected at the back. This
panel comes in two depth variants of 275 mm and 475 mm
All illustrations have been numbered systematically for all widths.
All pages have been numbered systematically
Width
The width of the cubicles depends on the type and will be
explained in the following sub chapters. The available widths
are: 425 mm, 600 mm, 800 mm, 1000 mm, 1200 mm and
1350 mm. Refer to Figure 1 and Figure 2.
1900 50 2 x 40 x 10 350
1900 65 2 x 40 x 10 250
2500 65 2 x 60 x 10 350
1900 50 2 x 40 x 10 350
1900 65 2 x 40 x 10 250
2500 65 2 x 60 x 10 350
2500 80 2 x 60 x 10 250
2900 65 2 x 80 x 10 350
2900 80 2 x 80 x 10 250
3200 80 2 x 100 x 10 350
3200 100 2 x 100 x 10 250
3620 80 2 x 120 x 10 350
3620 100 2 x 120 x 10 250
Table 4. Rating for the withdrawable units MCCB Table 5. Power Xpert fixed unit ratings
Drawer Specifications Rating
Drawer dimensions (mm) Power rating
Direct on line
Direct on line and forward/reverse
Power ratings 110 kW250 kW
C012 125 H x 250 W Up to 18.5 kW
MCCB NZM2, NZM3
C01 125 H x 250 W Up to 22 kW
Panel dimensions (mm) 425 W x 600 D
C02 250 H x 500 W Up to 75 kW
Panel dimensions 425 W x 600 D
C04 500 H x 500 W Up to 132 kW top cable entry (mm)
Feeders Feeders
C012 125 H x 250 W Up to 63 kW Current ratings 4001600 A
C01 125 H x 250 W Up to 125 kW MCCB NZM2, NZM3, NZM4
C02 250 H x 500 W Up to 250 kW Phases 3P, 4P, 3P neutral, 3P neutral link (BS)
C04 500 H x 500 W Up to 500 kW Panel dimensions (mm) 425 W x 600 D, 600 W x 600 D
Panel dimensions 425 W x 875 D, 600 W x 875 D
Figure 6. Power Xpert CXH panelswithdrawable units top cable entry (mm)
Standards
Power Xpert CXH has been developed in accordance with
international standards, such as:
IEC/EN 61439-1
IEC/EN 61439-2
BS-EN 61439-2
IEC/TR 61641 criteria 1-7
IEC 60947-1 part 4-1 type 2 coordination
Seismic test acc. IBC/CBC/UBC/IEC/IEEE in standard
configuration ZPA 0.20/0.25g (RRS 0.625g) and with
seismic kit ZPA 0.5g (RRS 1.5g)
Shell DEP 33.67.01.31-Gen 8.5.3.106 and A1.5.2.1
The system meets the highest safety requirements and is
DEKRA approved.
Identification
Order number: _______________
Serial number: _______________
Supplied by: Eaton Industries (Netherlands)
B.V. P.O. Box 23, 7550 AA Hengelo,
The Netherlands
Tel: +31 74 246 4010
Fax: +31 74 246 4025
Internet: www.eaton.eu/CXH
The electrical room in which the switchgear is set up must Floor plan
comply with the following: The illustration on the next page gives an example of how
All safety regulations applicable locally equipment is set up.
The requirements set out in the chapter on safety Use the floor plan in the information pack to check that the
floor recesses are the right size and executed correctly.
The requirements in this paragraph
During transport and storage
Climate
If the switchgear panels are stored temporarily prior to
In accordance with IEC 61439-1 par. 7.1.1, the climate in the installation, or during transport:
switch room must comply with the following:
Do not unpack the switchgear panels
Humidity: 90% maximum relative over a period of 1 month.
In new buildings it is essential to dry out the area before Store the switchgear panels vertically in a dry and
installing the system. dust-free area
Temperature Ensure that the transport and storage environment
complies with the requirements of IEC 61439-1, par. 7.1.1
Maximum +40 C, measured over a period of 24 hours
Avoid condensation caused by rapid temperature changes
Average not more than +35 C, measured over a period
of 24 hours Note: If the installation is kept in poor conditions in the
Minimum not less than 5 C, measured over a period open air, corrosion and a reduction in the level of
of24 hours quality may result.
The room must be free from dust, corrosive, or flammable Escape routes inside a room
gases and salts. The width of the escape route in front of any cubicle, with
If the installation has to operate in a less suitable operating its door opened 90 degrees, shall be at least 500 mm. It is
environment, it may be necessary to take special recommended that a lifting trolley be used for the removal
precautions. Users should consult Eaton in that case. of air circuit breakers (handling safety requirement).
Room for extension The use of a lifting trolley for circuit breakers will require
additional space (at least 400 mm) for access and
If necessary, reserve sufficient space for later extension of maneuverability of the trolley. Refer to Figure 9 for details
the installation. The system can be extended on both sides. on placement of switchgear inside a room.
Floor Distances from wall
The floor of the operating area should comply with the The minimum distance between the backside of CXH panel
following: and the wall is 50 mm, according to Figure 9 on next page,
and this value is not depending on the busbar rating.
The floor must be flat and level to within 2 mm
The floor must not have any raised areas (bumps) though Entrances
indentations are permitted Entrances to the switch room and escape routes must
The floor must be of adequate strength be kept clear at all times. Entrances must be provided at
suitable places and must be at least as wide as the width
Sections or foundation frames set in the floor can be used of panel plus 0.2 m and the height of panel plus 0.2 m.
as the support surface for the installation. The area between For details of the width and height of panel, see panel
the floor sections and the panel must always be filled in dimensions in Table 3. They must be accessible via the
with filler plates to create a suitable support surface. escape routes. It must be possible to open doors outwards
from both sides without the use of aids.
Shipment See that the work area is clean and safe; obey the local
statutory provisions
On-site delivery is contingent on the presence of an
appropriate access route. Never stand under a hoisted load
A Power Xpert CXH installation is normally transported in The angle of the lifting chain or strap relative to the lifting
individual sections. The sections can be assembled on site. point must never be larger than 90
When they are shipped with more than 1 section then The lifting operation has to be stopped if the wind force
the maximum length is 2400 mm. The sections are placed exceeds force 7 on the scale of Beaufort (more than
onto pallets and are packed in styrofoam and plastic foil 13.917 m/s). If lifting takes place at great height lifting
to prevent against damage. The pallets are attached to the must be stopped earlier
equipment by means of steel straps.
Lifting
Lifting under normal conditions
See that the work area is clean and safe; obey the local
statutory provisions
Never stand under a hoisted load
The angle of the lifting chain or strap relative to the lifting
point must never be larger than 90
4. Carefully push the Power Xpert CXH towards its final Note: By using and reusing packing materials, we can save
location. on raw materials. This also reduces the amount of
waste.
5. Remove the lifting trolleys in reverse order.
Procedure
Inside cranes
Transport by indoor cranes is done in the same way as 1. As required, remove the packaging materials from the
outside transport. Please refer to the applicable paragraph equipment.
above. 2. Dispose the packaging materials in an environmental
friendly manner.
Forklift trucks
Transport by forklift trucks is done in the same way as
outside transport. Please refer to the applicable paragraph
above.
Busbar support for one busbar per phase Main busbars connection between panels
Figure 14 shows the position of the busbar supports for When it is required to extend the main busbars into other
one busbar per phase, for the various cubicles. panels an inter-panel busbar coupling set is used as shown
in Figure 17. The main busbars of two panels are coupled
using this set. Refer to Figure 16.
Figure 14. Single busbar per phase
For torque ratings, please see Data outgoing units on
page 56.
Interpanel MBB
connection
Closing off the busbar compartment Figure 20. Top side cover
Once the main busbars are fixed in position and the
vertical busbars are electrically connected, the main busbar
compartment can be closed. In order to close the busbar
compartment:
Place the top side cover and fasten it to the frame using
fasteners provided. Refer to Figure 20
Proceed to placing the top roof in place. Refer to Top side
cover
Figure 21
Cable entry and connection for incoming and outgoing Fixation of CXH panels on the floor
feeders In general the CXH system can be mounted to the floor
Cables running from the CXH system to the outside world using standard M8 x 323092390 bolts in the front left and
can enter/exit the system in 2 variations; these are called back right corner of the bottom frame.
respectively bottom cable entry or top cable entry.
In case of an earthquake or marine/offshore application the
As the names suggest, the bottom cable entry configuration system has to be bolted to the floor using all 4 connection
feeds the cable through the bottom plate to the outside points in the corners of the bottom frames.
world. The top cable entry configuration guides in or
For these specific environmental situations, additional
outgoing cables through an additional panel in the back
reinforcements are needed.
tothe top of the system.
In both cases, the cable are fed through a detachable
synthetic plate. Cable can be sealed using a plastic foam, Figure 24. Standard mounting
rubber grommets or cable glands.
In all cases, the cables enter the system in a dedicated
cable compartment where connections can be made to
theappropriate component and position.
Note: During isolating and reconnecting the ACB the panel Connected processes and other apparatus may be
remains closed. The panel is to be opened when the energized
ACB is fully disconnected only. When it concerns an incomer, the powering cables in the
cable compartment may be live
Before switching off the ACB, ensure that:
Supporting automatic control circuits when present must
Connected processes and other apparatus are
not interfere with the operation
de-energized
When it concerns an incomer, the powering cables in the After all precautions have been taken, the connecting
cable compartment remain live procedure can start.
Supporting automatic control circuits when present must 1. The ACB must be in the OFF position, the contact status
not interfere with the operation indicator now must indicate: O open. Place the ACB in
the cassette. For lifting the ACB in the cassette, use a
After all precautions have been taken, the isolating lifting tool. Close the door when the ACB is completely
procedure can start. pushed into the cassette (still in the disconnected
position [green: indicated color-coded breaker position
1. Check that the spring status indicator is in the position indicator]).
charged. Usually the spring is recharged after closing, in
this way the ACB has enough energy for the sequence. 2. Rack in the ACB (with the door closed) using the racking
If not, charges the spring using the manual charging tool to the racking mechanism behind the levering
handle. device access door. When racking in first the Test
position (yellow) will be reached, indicated color-coded
2. Switch off the ACB using the push off button, the breaker position indicator on the right-hand side of the
contact status indicator now must indicate: O open. racking door. When racking in is proceeded, the Connect
3. Rack out the ACB with the door closed using the racking position (red) will be reached.
tool to the racking mechanism behind the levering 3. In case of a bus-tie the possibility that both sides of the
device access door. When racking out, the first test ACB may be energized should be considered.
position (yellow) is reached. This indicates the color-
coded breaker position on the right-hand side of the 4. In case of an incomer or feeder the procedure for
indicator racking door. When racking out is proceeded, energizing a LV switchboard must be followed. Check
the disconnect position (green) is reached. that the spring status indicator is in the position charged.
4. Now the ACB is completely racked out and the bus is 5. When ready switch on the ACB using the push on
disconnected from the cable. If the ACB is an incomer or button, the contact status indicator now must indicate:
a feeder or the two busses are disconnected in case of 1 closed.
a bus-coupler.
5. The door can be opened to take the breaker out of the Note: Please see ACB manual for details of ACB operating
cassette (cradle), if required. Use the extension to pull instructions.
the ACB out the cassette. For lifting the ACB out of the
cassette, use a lifting tool.
Setting timers etc., within control schemes. Withdrawable units are available in various sizes and with
different power ratings.
Table 8 shows the drawer sizes. The first digit in the naming
Figure 25. Setting of NZM for protection of cables
convention denotes the height and the last digit denotes
how many drawers can be stacked in a row.
C012 125 2
C01 125 1
C02 250 1
C04 500 1
Figure 26. Setting of NZM for protection of motors Operating the withdrawable unit
The withdrawable units are independent units, with
each one operating independently of the other units. The
modules have rollers that slide on the guide rail(s) and using
this construction, the withdrawable units are inserted into
the panel.
Each module is connected to the vertical distribution
busbars through means of independent moving contacts
for each module. These contacts are controlled through a
mechanism that can be actuated using a tool with the doors
closed. The cable compartment is besides the withdrawable
unit section of the motor control center.
Figure 27. Series NRX and Magnum air circuit breakers The customer can further connect the equipment to
the withdrawable units through cables in the cable
compartment. The modules also have an interlock, which
ensures that it is not possible to withdraw the unit while it
is in the on state, and also its only possible to withdraw the
unit with front door closed, besides other safety features.
The racking mechanism is used to connect the sliding
contacts (power and control) into the distribution busbars.
The racking option is important for the safety of the
operator, as all the operations involving connection and
disconnection of the contacts happen only with the front
doors closed.
Figure 28. Power Xpert CXH withdrawable motor Inserting a withdrawable unit
control center
The withdrawable unit can be inserted into Power Xpert
CXH panel as follows:
Locate the empty compartment where withdrawable unit
is to be inserted Figure 30
Open the door to the compartment concerned
Despite the security mechanism, make sure that the
drawer to be inserted is with the circuit breaker in the
OFF position, and also that the connection pins of the
racking mechanism are fully retracted
WARNING
Never try to insert the drawer into the panel with circuit
breaker in the ON position.
Roll in the withdrawable units by using the guide rails
in the dividing plate and push it all the way to the end
(Figure 32)
Lock the withdrawable unit in place by pushing down
the locking brace at the front of the unit (Figure 33 and
Figure 34)
Close the door of the withdrawable unit compartment
(Figure 35)
You will be able to start moving the racking mechanism of
the connection pins just after the door closed (Figure 36)
Figure 29. Typical MCC withdrawable unit Figure 30. Withdrawable unit
Lock brace
Figure 36. Withdrawable unit with doors closed and racking tool inserted
Removing a withdrawable unit Open the door of the withdrawable unit by unlocking
the knob (Figure 40). You will be able to unlock the knob
The withdrawable unit can be removed from the Power just after the MCCB is switched to OFF position, and the
Xpert CXH panel as follows: racking mechanism is in the Disconnected position. The
Switch off the MCCB. This also disengages the interlock interlocking system will not allow you to open the door
system (Figure 37 and Figure 38) unless the MCCB is in OFF condition and the racking
mechanism is in Disconnected position. Dont try to
unlock the knob before doing this procedure as it can
WARNING cause damage to the interlocking system
Never try to start this procedure of removal of the unit Lift the lock brace present at front of the unit to unlock
with the MCCB in the ON position. the withdrawable unit (Figure 41)
Ensure the contacts are in the Disconnected position Press in the locking button and use the lock brace to pull
(Figure 39). You will be able to do this by rotating the out the withdrawable unit (Figure 42 and Figure 43)
racking mechanism, only after the MCCB is switched
toOFF position Be careful on the pulling out procedure, especially when
racking out the large units, like C02 and C04, due to the
weight of the units
Figure 39. Withdrawable unit with doors closed and racking tool inserted to disconnect the contacts
Figure 40. View after opening the doorlock brace at the bottom position
Lift up the
lock brace
Lock brace
Figure 45. Locked door and MCCB power supply turned OFF
5. Remove the tool. Test the auxiliary circuit as the auxiliary 6. With the indicator in the Connected position, and door
power is connected to the drawer circuitry. security closed, you will be now allowed to switch the
MCCB to ON position, when required.
Insert the racking tool. In order to rack to Connect
position, rotate the racking tool for 15 cycles until the
indicator indicates Connect position as shown in
Figure 51.
WARNING
The vertical distribution busbars are not automatically
electrically dead when the door is opened.
Figure 53. Contact dummies 3. Closing off empty withdrawable unit slots.
Once a withdrawable unit is removed from the slot, then
the blind cover should be used to close the opening
window on the cover.
Cable connections for withdrawable units Figure 60. Cable connection points
Before connecting the cables, ensure that the MCCB switch
is in OFF position.
Open the cable compartment door
Take the cables into the cable compartment through
the gland plates at the bottom of the cable connection
section for a bottom entry configuration
Connect the cables to the outgoing contacts located to
the right of the specific withdrawable unit in the order of
phases as the mentioned labels
Ensure that the connection torques mentioned are
adhered to (for the torques, see Technical data and
spare parts on page 51)
Once connected, lock the door in Closed position
Rack in the connections to the Test position and then
theConnected position by using the racking mechanism,
as described in Operating the racking mechanism on
page 29
After concluding the racking procedure, you can switch
onthe MCCB
Between position
Disconnect Test Connect Disconnect to test Test to connect
Main switch Allowed Allowed Allowed Blocked Blocked
Door lock Allowed Allowed Blocked Blocked Blocked
Tool insertion/extraction Allowed Allowed Allowed Blocked Blocked
(with door locked)
Contacts
Line Disengaged Disengaged Engaged Static Moving
Load Engaged Engaged Engaged Static Static
Auxiliary Disengaged Engaged Engaged Moving Static
Communication Engaged Engaged Engaged Static Static
Changing compartments
This section describes the modification of the drawer
layout in the withdrawable version. The CXH withdrawable
MCC section can accommodate up to 28 C012 drawers in
one section. If it is desired, the layout of a cubicle can be
changed according to the application requirements.
2. Push the left sheet metal plate of the partition plate a bit
leftwards and remove it by pulling it out.
Figure 70. Removing the auxiliary contact brace and the dividing plate
WARNING
The vertical distribution busbars are not automatically
electrically dead when the door is opened.
Mechanical coding of drawers on the shelf and on the underside of the body in the
appropriate positions or combinations. After applying the
CXH may be provided with a mechanical coding system coding system it is thus impossible to position equal-
for the drawers. The coding system prevents accidental height withdrawable units incorrectly. The fixable metal
interchanging of withdrawable units by assigning each rollers mustbe ordered as an accessory. Refer to
withdrawable unit to a particular shelf. Coding is performed Figure 74 withthe possibilities of combinations by
by using 7 fixable metal rollers which are tightly screwed usingthemechanical coding.
Figure 77. Transition panel installed to connect Open the lower door of the incomer
Capitole40 installations to CXH installations Feed the main power cable through the gland plate and
gland the cable
Connect the cables
Connect the cable using an appropriate cable shoe
Use the strain relief bar to support the cables
The earthing bar is located on the bottom of the
installation
Tighten the connection bolts
Close the door of the incomer
Operation of withdrawable air circuit breakers (ACBs) Door operation for incomers
The ACBs can be either a Magnum or a Series NRX.
Figure 80. Incomer with door open
Type Rating
Series NRX RF Up to 4000 A
Magnum DN Up to 4000 A
List of standard torques In order to achieve good connection when using 2.5 mm2
solid wire, the bare conductor must be bent double for
each connection to the main connection-block
Table 11. Torques
When connecting twined cables up to 16 mm2 to the
Metric Self-tapping screws Screws (8.8 and A4-70)
thread (Nm) mechanical (Nm) mechanical main connection-block, it is advisable to use cable-end
sleeves
M3 1.5 0.9
M4 3 2.0 All 160 A drawout units, 2 x 125 mm high and larger,
M5 4.5 4.1 may, on request, be supplied with terminals for optimum
M6 7 7
connection of 2 x 95 mm2 (copper)
M8 14 When two or three drawout units are placed next to
M10 28 each other in one compartment, connection is made
M12 40 to terminals located in the cable-compartment 1). The
connection range of the respective terminals is:
M16 60
Main current, maximum 10 mm2
Required depths and heights are dependent on current
Auxiliary current, maximum 2.5 mm2
rating and arrangement of cables to be attached.
A maximum of twenty 2.5 mm2 leads may be connected
Connection possibilities and ranges to the auxiliary connection-block
Cubicles with an incoming or one outgoing feeder.
Miscellaneous equipment
There are various possibilities for the connection of these
Fuse links
groups:
DIN 00: cables up to 95 mm2 (copper). For cables with solid
Connection using cable-lugs, maximum of two per phase,
cores up to 4 mm2 and stranded cores up to 10 mm2 the
with the exception of 630 A equipment for which a
use of cable-end sleeves is recommended.
connection-set has been developed for three cables per
phase (copper) DIN 0: connection-bolt M8
Using cable-clamping blocks on switches exceeding DIN 1: connection-bolt M10
1000A, for one or more cables
DIN 2: connection-bolt M10
A connection-set is also available on request for switches
exceeding 1000 A, for five cables per phase maximum of DIN 3: connection-bolt M10
240 mm2 (copper) DIN 4: connection-bolt M16
Compartments with drawout units When connecting cables, it should be ensured that the
Drawout units are connected to the main connection-block. connection-strips are not bent due to inexpert connection of
Main connection-blocks have the following connection cables.
ranges:
160 A: 2.595 mm2, Cu
250 A: 3550 mm2, Cu
315 A: 501 x 240 mm2, Cu
400 A: 502 x 240 mm2, Cu
630 A: 502 x 240 mm2, Cu
Spare parts
List of spare parts
Refer to Figure 86 and Figure 87.
Enclosure
Note: Component numbers also apply to panels with cable entry on the left-hand side
(Capitole 40 with removable outgoing panels in IP41/42/54 version).
Pv total RDF = 1
incl. contactor
(motors) [kW]
Coordination
Power rating
at 400V [A]
coil [W]
Cable
type
DOL C012 0.55 1.5 2 2.7 HMCPE003A0C DILM17 DILM17 ZEB32-5/KK 2.5 0.210
DOL C012 0.75 1.9 2 3.1 HMCPE003A0C DILM17 DILM17 ZEB32-5/KK 2.5 0.210
DOL C012 1.1 2.7 2 4.2 HMCPE003A0C DILM17 DILM17 ZEB32-5/KK 2.5 0.210
DOL C012 1.5 3.6 2 5.8 HMCPE007C0C DILM17 DILM17 ZEB32-5/KK 2.5 0.210
DOL C012 2.2 4.9 2 9 HMCPE007C0C DILM17 DILM17 ZEB32-20/KK 2.5 0.210
DOL C012 3 6.5 2 14.2 HMCPE007C0C DILM17 DILM17 ZEB32-20/KK 2.5 0.210
DOL C012 4 8.5 2 12.1 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 0.210
DOL C012 5.5 11.5 2 18.5 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 0.210
DOL C012 7.5 15.5 2 8 HMCPE030H1C DILM40 DILM40 ZEB32-20/KK 10 0.210
DOL C012 11 22 2 11.8 HMCPE030H1C DILM40 DILM40 ZEB32-45/KK 10 0.210
DOL C012 15 29 2 17.3 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 10 0.210
DOL C012 18.5 35 2 23.2 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 10 0.210
DOL C01 0.37 1.1 2 2.4 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
DOL C01 0.55 1.5 2 2.7 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
DOL C01 0.75 1.9 2 3.1 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
DOL C01 1.1 2.7 2 4.2 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
DOL C01 1.5 3.6 2 5.8 HMCPE007C0C DILM17 DILM17 ZEB32-5 2.5 2.595
DOL C01 2.2 4.9 2 9 HMCPE007C0C DILM17 DILM17 ZEB32-20 2.5 2.595
DOL C01 3 6.5 2 14.2 HMCPE007C0C DILM17 DILM17 ZEB32-20 2.5 2.595
DOL C01 4 8.5 2 12.1 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 2.595
DOL C01 5.5 11.5 2 18.5 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 2.595
DOL C01 7.5 15.5 2 8 HMCPE030H1C DILM40 DILM40 ZEB32-20/KK 10 2.595
DOL C01 11 22 2 11.8 HMCPE030H1C DILM40 DILM40 ZEB32-45/KK 10 2.595
DOL C01 15 29 2 17.3 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 10 2.595
DOL C01 18.5 35 2 23.2 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 16 2.595
DOL C01 22 41 2 26.5 HMCPE050K2C DILM50 DILM40 ZEB32-45/KK 16 2.595
DOL C02 30 55 2 25.8 HMCPE100R3C DILM80 DILM80 ZEB150-100 50 2.595
DOL C02 37 66 2 34.7 HMCPE100R3C DILM80 DILM80 ZEB150-100 50 2.595
DOL C02 45 80 2 48.2 HMCPE100R3C DILM95 DILM80 ZEB150-100 50 2.595
DOL C02 55 97 2 39.5 NZMH2-S125 DILM115 DILM95 ZEB150-100 cu 20x5 25150
DOL C02 75 132 2 71.4 NZMH2-S160 DILM150 DILM250 ZEB32-5/KK + HF4C 400/5A
DOL C04 90 160 2 80 NZMH2-S200 DILM185A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL C04 110 195 2 117.5 NZMH2-S200 DILM225A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL C04 132 230 2 154.9 NZMH3-S320 DILM250 DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 110 195 2 0 NZMH2-S200 DILM225A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 132 230 2 0 NZMH3-S320 DILM250 DILM400 ZEB32-5/KK + HF4C 400/5A
Current le rating
Pv total RDF = 1
incl. contactor
(motors) [kW]
Coordination
Power rating
at 400V [A]
coil [W]
Cable
type
Unit Unit Container Contactor 1st size size
type size MCP type Q1 type K1 type K1 Overload/relay type [mm2] [mm2]
DOL CF4 160 280 2 0 NZMH3-S320 DILM300A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 200 350 2 0 NZMH3-S400 DILM400 DILM400 ZEB32-5/KK + RM60N-E3C 500/5A
DOL CF4 250 430 2 0 NZMH3-S500 DILM500 ZEB32-5/KK + RM60N-E3C 500/5A cu 30x10
DOL CF4 110 195 2 0 NZMH2-S200 DILM225A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 132 230 2 0 NZMH3-S320 DILM250 DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 160 280 2 0 NZMH3-S320 DILM300A DILM400 ZEB32-5/KK + HF4C 400/5A
DOL CF4 200 350 2 0 NZMH3-S400 DILM400 DILM400 ZEB32-5/KK + RM60N-E3C 500/5A
DOL CF4 250 430 2 0 NZMH3-S500 DILM500 ZEB32-5/KK + RM60N-E3C 500/5A cu 30x10
Forward/reverse
FR C01 0.37 1.1 2 2.4 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
FR C01 0.55 1.5 2 2.7 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
FR C01 0.75 1.9 2 3.1 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
FR C01 1.1 2.7 2 4.2 HMCPE003A0C DILM17 DILM17 ZEB32-5 2.5 2.595
FR C01 1.5 3.6 2 5.8 HMCPE007C0C DILM17 DILM17 ZEB32-5 2.5 2.595
FR C01 2.2 4.9 2 9 HMCPE007C0C DILM17 DILM17 ZEB32-20 2.5 2.595
FR C01 3 6.5 2 14.2 HMCPE007C0C DILM17 DILM17 ZEB32-20 2.5 2.595
FR C01 4 8.5 2 12.1 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 2.595
FR C01 5.5 11.5 2 18.5 HMCPE015E0C DILM40 DILM40 ZEB32-20/KK 2.5 2.595
FR C01 7.5 15.5 2 8 HMCPE030H1C DILM40 DILM40 ZEB32-20/KK 10 2.595
FR C01 11 22 2 11.8 HMCPE030H1C DILM40 DILM40 ZEB32-45/KK 10 2.595
FR C01 15 29 2 17.3 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 10 2.595
FR C01 18.5 35 2 23.2 HMCPE050K2C DILM40 DILM40 ZEB32-45/KK 16 2.595
FR C01 22 41 2 26.5 HMCPE050K2C DILM50 DILM40 ZEB32-45/KK 16 2.595
FR C02 30 55 2 25.8 HMCPE100R3C DILM80 DILM80 ZEB150-100 50 2.595
FR C02 37 66 2 34.7 HMCPE100R3C DILM80 DILM80 ZEB150-100 50 2.595
FR C02 45 80 2 48.2 HMCPE100R3C DILM95 DILM80 ZEB150-100 50 2.595
FR C02 55 97 2 39.5 NZMH2-S125 DILM115 DILM95 ZEB150-100 cu 20x5 25150
FR C02 75 132 2 71.4 NZMH2-S160 DILM150 DILM250 ZEB32-5/KK + HF4C 400/5A
FR C04 90 160 2 80 NZMH2-S200 DILM185A ZEB32-5/KK + HF4C 400/5A cu 20x6 25150
FR C04 110 195 2 117.5 NZMH2-S200 DILM225A ZEB32-5/KK + HF4C 400/5A cu 20x6 25150
FR C04 132 230 2 154.9 NZMH3-S320 DILM250 ZEB32-5/KK + HF4C 400/5A cu 20x6 25150
Feeder
FE3P C012 20 6.6 EGC3020AFG 10 0.216
FE3P C012 25 10.3 EGC3025AFG 10 0.216
FE3P C012 32 16.9 EGC3032AFG 10 0.216
FE3P C012 40 19.5 EGC3040AFG 16 0.216
FE3P C012 45 24.7 EGC3050AFG 16 0.216
FE3P C01 20 6.6 EGC3020AFG 10 2.595
Current le rating
Pv total RDF = 1
incl. contactor
(motors) [kW]
Coordination
Power rating
at 400V [A]
coil [W]
Cable
type
Unit Unit Container Contactor 1st size size
type size MCP type Q1 type K1 type K1 Overload/relay type [mm2] [mm2]
Feeder, continued
FE3P C01 32 16.9 EGC3032AFG 10 2.595
FE3P C01 40 16.4 EGC3040AFG 16 2.595
FE3P C01 50 25.6 EGC3050AFG 16 2.595
FE3P C01 55 30.9 EGC3063AFG 16 2.595
FE3P C01 80 31 EGC3080AFG 35 2.595
FE3P C01 100 48.5 EGC3100AFG 35 2.595
FE3P C02 113 49.9 EGC3125AFG 50 2.595
FE3P C02 160 54.9 NZMH2-A160 cu 20x5 25150
FE3P C02 200 85.8 NZMH2-A200 cu 20x5 25150
FE3P C02 220 103.8 NZMH2-A250 cu 20x5 25150
(415 V)/
2x240
(480 V)
FE3P C04 320 134.8 NZMH3-A320 cu 30x10 2x240
FE3P C04 400 210.6 NZMH3-A400 cu 30x10 2x240
FE3P C04 425 237.7 NZMH3-A500 cu 30x10 2x240
FE4P C012 20 6.6 EGC7020AFG 10 0.216
FE4P C012 25 10.3 EGC7025AFG 10 0.216
FE4P C012 32 16.9 EGC7032AFG 10 0.216
FE4P C012 40 19.5 EGC7040AFG 16 0.216
FE4P C012 45 24.7 EGC7050AFG 16 0.216
FE4P C01 20 6.6 EGC7020AFG 10 2.595
FE4P C01 25 10.3 EGC7025AFG 10 2.595
FE4P C01 32 16.9 EGC7032AFG 10 2.595
FE4P C01 40 16.4 EGC7040AFG 16 2.595
FE4P C01 50 25.6 EGC7050AFG 16 2.595
FE4P C01 55 30.9 EGC7063AFG 16 2.595
FE4P C01 80 31 EGC7080AFG 35 2.595
FE4P C01 100 48.5 EGC7100AFG 35 2.595
FE4P C02 113 49.9 EGC7125AFG 50 2.595
FE4P C02 160 54.9 NZMH2-4-A160 cu 20x5 25150
FE4P C02 200 85.8 NZMH2-4-A200 cu 20x5 25150
FE4P C02 220 103.8 NZMH2-4-A250 cu 20x5 25150
(415 V)/
2x240
(480 V)
FE4P C04 320 134.8 NZMH3-4-A320 cu 30x10 2x240
FE4P C04 400 210.6 NZMH3-4-A400 cu 30x10 2x240
FE4P C04 425 237.7 NZMH3-4-A500 cu 30x10 2x240
FE3P CF4 400 0 NZMH3-AE400 cu 30x10
Current le rating
Pv total RDF = 1
incl. contactor
(motors) [kW]
Coordination
Power rating
at 400V [A]
coil [W]
Cable
type
Unit Unit Container Contactor 1st size size
type size MCP type Q1 type K1 type K1 Overload/relay type [mm2] [mm2]
Feeder, continued
FE3P CF4 630 0 NZMH3-AE630
FE3P CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
FE3P CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE3P+N CF4 400 0 NZMH3-AE400 cu 30x10
FE3P+N CF4 630 0 NZMH3-AE630
FE3P+N CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P+N CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
FE3P+N CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P+N CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE3P+N-link CF4 400 0 NZMH3-AE400 cu 30x10
FE3P+N-link CF4 630 0 NZMH3-AE630
FE3P+N-link CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P+N-link CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
FE3P+N-link CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P+N-link CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE4P CF4 400 0 NZMH3-4-AE400 cu 30x10
FE4P CF4 630 0 NZMH3-4-AE630
FE4P CF6 800 0 NZMH4-4-AE800
(NZML4-4-AE800)
FE4P CF6 1000 0 NZMH4-4-AE1000
(NZML4-4-AE1000)
FE4P CF6 1250 0 NZMH4-4-AE1250
(NZML4-4-AE1250)
FE4P CF6 1600 0 NZMH4-4-AE1600
(NZML4-4-AE1600)
FE3P CF4 400 0 NZMH3-AE400 cu 30x10
FE3P CF4 630 0 NZMH3-AE630
FE3P CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
Current le rating
Pv total RDF = 1
incl. contactor
(motors) [kW]
Coordination
Power rating
at 400V [A]
coil [W]
Cable
type
Unit Unit Container Contactor 1st size size
type size MCP type Q1 type K1 type K1 Overload/relay type [mm2] [mm2]
Feeder, continued
FE3P CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE3P+N CF4 400 0 NZMH3-AE400 - - - cu 30x10
FE3P+N CF4 630 0 NZMH3-AE630
FE3P+N CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P+N CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
FE3P+N CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P+N CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE3P+N-link CF4 400 0 NZMH3-AE400 - - - cu 30x10
FE3P+N-link CF4 630 0 NZMH3-AE630
FE3P+N-link CF6 800 0 NZMH4-AE800
(NZML4-AE800)
FE3P+N-link CF6 1000 0 NZMH4-AE1000
(NZML4-AE1000)
FE3P+N-link CF6 1250 0 NZMH4-AE1250
(NZML4-AE1250)
FE3P+N-link CF6 1600 0 NZMH4-AE1600
(NZML4-AE1600)
FE4P CF4 400 0 NZMH3-4-AE400 - - - cu 30x10
FE4P CF4 630 0 NZMH3-4-AE630
FE4P CF6 800 0 NZMH4-4-AE800
(NZML4-4-AE800)
FE4P CF6 1000 0 NZMH4-4-AE1000
(NZML4-4-AE1000)
FE4P CF6 1250 0 NZMH4-4-AE1250
(NZML4-4-AE1250)
FE4P CF6 1600 0 NZMH4-4-AE1600
(NZML4-4-AE1600)
1250 4x 300
1600 6x 300
2000 6x 300
2500 8x 300
3150 10x 300
4000 7x 630
5000 8x 630
6300 10x 630
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
2015 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. MN019002EN / Z16983 / 6099564 All trademarks are property
October 2015 of their respective owners.