ISOLATED FOUNDATION DESIGN CALCULATION USING STAAD REACTION

GIVEN DATAS:
Concrete Grade = M25
Concrete Compressive Strength = 30
Grade of Reinforcement Steel = Fy 415
Unit Weight of Concrete = 24 kN/M3
Unit Weight of sand = 18 kN/M3
Unit Weight of Steel = 78 kN/M3
Friction factor of Soil (Cf) = 0.4
Safe Bearing Capacity of Soil = 40 kN/M2
Allowable FOS against Sliding = 1.5
Allowable FOS against Overturning = 1.75

FOUNDATION INPUT
Length of Footing (L) = 2.3 m
Breadth of Footing (B) = 2.2 m
Depth of Footing (D) = 1.5 m
Thickness of Footing (Th) = 0.3 m
Length of Pedestel (Pl) = 0.6 m
Breadth of Pedestel (Pb) = 0.6 m
Height of Pedestel Above GL = 0.3 m

UNFACTORED LOAD DETAILS FROM STAAD


LOADS Horizontal Vertical Horizontal Moment
L/C Fx kN Fy kN Fz kN Mx kNm My kNm Mz kNm
113 DL+EMP+WIND(-X)2.95 6.398 0 0 0 -7.119
107 DL+MAX+WIND(+X)-3.25 7.078 -0.6 -2.55 0 8.394
101 DL+MAX -0.3 7.078 -0.6 -2.55 0 1.275
102 DL+EMP 0 6.398 0 0 0 0
114 DL+EMP+WIND(-Z)0 6.398 2.91 6.949 0 0
108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499 0 1.275
114 DL+EMP+WIND(-Z)0 6.398 2.91 6.949 0 0
108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499 0 1.275
114 DL+EMP+WIND(-Z)0 6.398 2.91 6.949 0 0
108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499 0 1.275
107 DL+MAX+WIND(+X)-3.25 7.078 -0.6 -2.55 0 8.394
113 DL+EMP+WIND(-X)2.95 6.398 0 0 0 -7.119

LOADS FROM FOOTING


Self Weight of the Footing = 36.43 kN/M3
Self Weight of the Pedestel = 12.96 kN/M3
Overall Weight of the Footing = 49.39 kN/M3
Weight of Soil Cover = 101.52 kN/M3
Load Along X axis = 0 kN
Load along Z axis = 0 kN
Moment about X Axis (Mx) = 0
Moment about Z Axis (MZ) = 0

SAFE BEARING CAPACITY CHECK, SLIDING CHECK & OVERTURNING CHCK

Total Load Vertical Load (P) = 150.91


Area of the Footing = 5.06 m2
Maximum Soil Pressure
(P/A+Mx/Z+Mz/Z)
Minimum Soil Pressure
Base Pressure Check
(P/A-Mx/Z-Mz/Z)
Sliding FOS Restoring Force
=
Sliding Force
Restoring Force = P x Cf kN
= 60.364 kN

Overturning FOS Restoring Force


=
Overturning Moment
Restoring Moment in X = P x L/2

Restoring Moment in X = P x B/2

Horizontal Vertical Horizontal Moment MAX SOIL


Fx kN Fy kN Fz kN Mx kNm My kNm Mz kNm PRESSURE
2.95 6.398 0 0 0 -7.119 27.42
-3.25 7.078 -0.6 -2.55 0 8.394 34.18
-0.3 7.078 -0.6 -2.55 0 1.275 30.51
0 6.398 0 0 0 0 31.09
0 6.398 2.91 6.949 0 0 34.83
-0.3 7.078 -3.51 -9.499 0 1.275 26.76
0 6.398 2.91 6.949 0 0 34.83
-0.3 7.078 -3.51 -9.499 0 1.275 26.76
0 6.398 2.91 6.949 0 0 34.83
-0.3 7.078 -3.51 -9.499 0 1.275 26.76
-3.25 7.078 -0.6 -2.55 0 8.394 34.18
2.95 6.398 0 0 0 -7.119 27.42
SAFE

STRENGTH CHECK OF THE FOUNDATION


FOOTING THICKNESS CHECK
ONE WAY SHEAR CHECK
MIN SOIL OVERTURN
SLIDING X SLIDING Z
PRESSURE ING
34.76 20.46 #DIV/0! 24.38
28.27 18.57 100.61 11.65
31.94 201.21 100.61 22.31
31.09 #DIV/0! #DIV/0! #DIV/0!
27.34 #DIV/0! 20.74 3.59
35.69 201.21 17.2 1.9
27.34 #DIV/0! 20.74 3.59
35.69 201.21 17.2 1.9
27.34 #DIV/0! 20.74 3.59
35.69 201.21 17.2 1.9
28.27 18.57 100.61 11.65
34.76 20.46 #DIV/0! 24.38
SAFE #DIV/0! SAFE
LOADS Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kNm
Max Fx 1 113 DL+EMP+WIND(-X) 2.95 6.398 0 0
Min Fx 1 107 DL+MAX+WIND(+X) -3.25 7.078 -0.6 -2.55
Max Fy 1 101 DL+MAX -0.3 7.078 -0.6 -2.55
Min Fy 1 102 DL+EMP 0 6.398 0 0
Max Fz 1 114 DL+EMP+WIND(-Z) 0 6.398 2.91 6.949
Min Fz 1 108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499
Max Mx 1 114 DL+EMP+WIND(-Z) 0 6.398 2.91 6.949
Min Mx 1 108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499
Max My 1 114 DL+EMP+WIND(-Z) 0 6.398 2.91 6.949
Min My 1 108 DL+MAX+WIND(+Z) -0.3 7.078 -3.51 -9.499
Max Mz 1 107 DL+MAX+WIND(+X) -3.25 7.078 -0.6 -2.55
Min Mz 1 113 DL+EMP+WIND(-X) 2.95 6.398 0 0
My kNm Mz kNm
0 -7.119
0 8.394
0 1.275
0 0
0 0
0 1.275
0 0
0 1.275
0 0
0 1.275
0 8.394
0 -7.119