Withdrawable module with vacuum circuit-breaker 3AE


and installation accessories
7.2 17.5 kV, 12.5 31.5 kA
7.2 17.5 kV, 40 kA
24 kV, 16 25 kA

OPERATING INSTRUCTIONS

Order no.: 9229 0002 176 0A


Order from: E D MV C MF115 Berlin
Siemens AG 2006. All rights reserved. AG 12.2008 en
For your safety
Warning and safety notices serve to enable you to avoid hazards and subsequent damage and are marked as fol-
lows:

DANGER
indicates, within the scope of these instructions and the warning notices
on the SION withdrawable module and the installation accessories
themselves that death, severe personal injury or substantial property
damage will result if proper precautions are not taken.

WARNING
indicates, within the scope of these instructions and the warning notices
on the SION withdrawable module and the installation accessories
themselves that death, severe personal injury or substantial property
damage can result if proper precautions are not taken.

CAUTION
indicates, within the scope of these instructions and the warning notices
on the SION withdrawable module and the installation accessories
themselves that slight personal injury or property damage can result if
proper precautions are not taken.

Note
indicates, within the scope of these instructions and the warning notices
on the SION withdrawable module and the installation accessories
themselves that the circuit-breaker or an object can be damaged if the
relevant notices are not complied with.

Qualified personnel
For the purpose of these operating instructions or warning notices on the withdrawable module and the SION
vacuum circuit-breaker, a "qualified person" is one who is familiar with the installation, construction, commission-
ing, maintenance and operation of the product and who has e.g. the following qualifications:
Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accor-
dance with established safety practices.
Is trained in the proper care and use of protective equipment in accordance with established safety practices.
Is trained in rendering first aid

Note
Product liability claims are valid only if the spare parts purchased
have been replaced by Siemens personnel trained and certified to
do so.

9229 0002 176 0A


2008-12-09
Contents

Transport/storage/packing ...........................................................................................................................................3
Transport ...............................................................................................................................................................3
Crane transport......................................................................................................................................................5
Storage ..................................................................................................................................................................6

Description...................................................................................................................................................................7
Structure ................................................................................................................................................................7
Scope of delivery ...................................................................................................................................................8
Versions - technical data .......................................................................................................................................8
Rating plate ...........................................................................................................................................................8

Installation....................................................................................................................................................................9
Preparations ..........................................................................................................................................................9
Fitting the withdrawable frame ............................................................................................................................10

Operation ...................................................................................................................................................................13
Using the SION vacuum circuit-breaker with a withdrawable section in the withdrawable frame.....................13

Installation accessories..............................................................................................................................................15
Assembling installation accessories....................................................................................................................15
Withdrawable frame with earthing switch ............................................................................................................19

Maintenance ..............................................................................................................................................................25
Maintenance ........................................................................................................................................................25
Accessories and spare parts Manufacturer's product liability Service ..........................................................25
Disposal ...............................................................................................................................................................26

Index ..........................................................................................................................................................................27

9229 0002 176 0A 1


2008-12-09
Blank page

2 9229 0002 176 0A


2008-12-09
Transport/storage/packing

Transport/storage/packing

WARNING
Risk of injury!
Pay attention to the weight!
Use means of transport suited to the requirements and load
carrying capacity!
Suspend the SION vacuum circuit-breaker in the with-
drawable frame from a crane only in the inserted state!

Transport
Unpacking
Open the packing from above.
Detach the packing at the sides
Cut through the adhesive tape holding the foil
covering in place and carefully remove the foil
Undo the hexagon screws (10 mm) on the
withdrawable frame, as shown in Fig. 1
Use the fitted transport beam to suspend the
withdrawable module in the withdrawable
frame from a crane.

Fig. 1 Unpacking the withdrawable module

9229 0002 176 0A 3


2008-12-09
Transport/storage/packing

CAUTION
Damage!
The SION withdrawable module with vacuum circuit-breaker and
earthing switch can tilt over after removal from the packing and
must be supported.

Open the packing from above


Remove cover board secured with clips in the
upward direction
Remove cross struts secured with clips
Remove side walls secured with clips

Fig. 2 Unpacking the SION withdrawable module with


earthing switch

Cut through the adhesive tape holding the foil


covering in place and carefully remove the foil
Undo the wood screws, as shown in Fig. 3
Undo the hexagon screws (10 mm) from the
brackets, as shown in Fig. 3, and remove the
brackets
Use suitable hoisting gear to lift the SION
withdrawable module with earthing switch out
of the packing.

Fig. 3 Unpacking the SION withdrawable module with


earthing switch

4 9229 0002 176 0A


2008-12-09
Transport/storage/packing

Crane transport

WARNING
Risk of injury!
Pay attention to the weight!
Use means of transport suited to the requirements and load carrying capacity!
Suspend the SION vacuum circuit-breaker in the withdrawable frame from a
crane only in the inserted state!

For crane transport, especially of heavy circuit-


breaker versions, we recommend use of a work-
shop crane, for example the Compac CC055 or
CC055 junior from the following company:
KSM ServiceTechnik GmbH & Co. KG
Bosch contract wholesaler
Robert-Koch-Strasse 8
21423 - Winsen / Luhe
Germany
www.ksm-wakon.de

! Max. 19 mm, min. 18 mm hook opening

Max. weight of the withdrawable module with the


SION vacuum circuit-breaker:
230 kg!

Fig. 4 Transporting the withdrawable module

! Max. 19 mm, min. 18 mm hook opening

Max. weight of the withdrawable module with the


SION vacuum circuit-breaker and earthing switch:
330 kg!

Fig. 5 Transporting the withdrawable module with earthing switch

9229 0002 176 0A 5


2008-12-09
Transport/storage/packing

Storage

CAUTION
Damage!
If the packing has been opened, make sure during storage that the
SION vacuum circuit-breaker is in the following state in the with-
drawable frame:

OPEN (OFF) position

Closing spring relaxed

Until it is installed, store the withdrawable module with the SION vacuum circuit-breaker (and earthing switch) in
closed, dry, well-ventilated and, as far as possible, dust-free rooms in its foil (dense packing for overseas trans-
port). Relative humidity in storage rooms should be less than 60 %.
The withdrawable module with the SION vacuum circuit-breaker (and earthing switch) can be stored and trans-
ported outside the context of its normal operating conditions within the limit temperature range of -40 C to +55 C
in closed foil (tight and closed packing).
As the stacking quantity depends on the weight of the packing unit, the load-carrying capacity of the packing and
its overall height, no more than three packing units should be stacked on one another. The weight of the packing
unit is documented on the delivery note.
The withdrawable module with the SION vacuum circuit-breaker (and earthing switch) for overseas transport are
packed with VCI foil. The VCI foil creates a protective atmosphere that safeguards the circuit-breaker against cor-
rosion. The protective atmosphere evaporates without residues after a short time when the VCI foil is removed, so
the circuit-breaker can be used directly out of the packing without any subsequent treatment.

6 9229 0002 176 0A


2008-12-09
Description

Description

Structure

Fig. 6 Withdrawable module with SION vacuum circuit-breaker


1 SION vacuum circuit-breaker
10 Withdrawable section
11 Shutter operating mechanism
12 Link
100 Withdrawable frame
110 Contact system
120 Contact arm (40 mm, 60 mm)
130 Shutter
131 Swivel lever
140 Bushing
141 Mating contact
142 Bushing cover
143 Busbar terminal

9229 0002 176 0A 7


2008-12-09
Description

Scope of delivery
Delivery includes:
SION vacuum circuit-breaker with withdrawable section
Withdrawable frame
Contact systems and contact arms
Mating contact, bushing and bushing cover (depending on the version)
Earthing switch (optional)
System-side isolation shells (optional)
Hand crank, circuit-breaker 3AX1530-2B (optional)
Handle, withdrawable section 3AX1430-2C (optional)
Handle, earthing switch 3AX1430-2D (optional)
Handle, earthing switch 3AX1430-3D (optional)
Operating instructions

Versions - technical data


Rated voltage Rated operating cur- Rated short-time Pole center distance Distance between
rent current top and bottom ter-
minals
Ur (kV) Ir (A) Ik (kA) mm mm

7,2 17,5 800 2500 12,5 -31,5 150*; 210 275*; 310
7,2 17,5 1250 3150 40 210 310
24 800 2500 12,5 -25 210; 275 310

* Ir 1250 A
Fig. 7 Versions with withdrawable module

Rating plate
1 Manufacturer
Q 14
600806
Kontr
2 Type identification
1 3 Year of manufacture
13
Typ 3AE1115-2 Bauform 1A
2 4 Rated operating current Ir
12 3
11
Nr. S 3AE/00000023 Baujahr 2005
4
5 Rated short-circuit duration tk
Ur 12 kV, 50/60 Hz Ir 1250 A
10
Isc 31,5 kA tk 3 s 5 6 Mass m
8/9 Ud/Up 28/75 kV m 180 kg 6 7 Classification to IEC 62271-200
0002-II-3de

8 Rated short-time AC voltage Ud


7
Klasse nach IEC 62271-200 9 Rated lightning impulse withstand voltage
MADE IN GERMANY Up
10 Rated short-circuit breaking current Isc
11 Rated voltage Ur
Fig. 8 Withdrawable frame rating plate 12 Works serial number
13 Type designation
14 Quality control stamp

8 9229 0002 176 0A


2008-12-09
TInstallationT

Installation

DANGER
High voltage! Mortal danger!
Do not touch live parts!
Make sure that the SION vacuum circuit-breaker in the with-
drawable frame is operated only by qualified personnel who
are familiar with the operating instructions and who comply
with the warning notices.

WARNING
Risk of injury!
Do not touch live parts!
Before and during installation in switchgear, check whether
minimum clearances from insulated and live parts, as well as
parts subject to spring force, are maintained.

Preparations
Before installation in the functional unit:
Remove packed accessories from the spaces
Move the SION vacuum circuit-breaker out of the withdrawable frame and remove it after opening the inter-
locks
Detach the transport beam.

1. Undo the screw on one side of the transport


beam.

2. Pull out the transport beam towards the other


side.

Fig. 9 Detaching the transport beam

9229 0002 176 0A 9


2008-12-09
TInstallationT

Fitting the withdrawable frame


Installing the withdrawable frame in the functional unit
To secure the withdrawable frame (100) in the func-
tional unit, 6.6 mm holes can be produced in the
functional unit's space in conformity with the hole
pattern of the withdrawable frame's side walls, and
steel L-brackets (see Fig. 10) can be placed under
it.
Insert the withdrawable frame and lower it onto the
L-brackets.

Fig. 10 Installing the withdrawable frame (100) in the


functional unit

Secure the withdrawable frame (100) in the func-


tional unit, for example with blind rivets to ISO
15979-6.4 x 12-St/St

Fig. 11 Securing the withdrawable frame (100) in the


functional unit

10 9229 0002 176 0A


2008-12-09
TInstallationT

Busbars before assembly:


Roughen
Clean
Grease with Vaseline to protect against corro-
sion

Clean and grease silver-plated busbar terminals


(143)!

Fig. 12 Preparing the busbar terminals (143)

Firmly bolt the busbars onto the busbar terminals


(143).
Tightening torque for M12: 40 4 Nm
Tightening torque applies to greased threads only!

Fit the bushing covers (142) (depending on the ver-


sion) onto the bushing (140) so that they engage in
the recesses (A).

Fig. 13 Securing the busbars onto the busbar terminals


(143)

9229 0002 176 0A 11


2008-12-09
TInstallationT

Earth the withdrawable frame (100) on the pressure


pads for the withdrawable section:
Screw suitable earthing cables or busbars
(2 x 100 mm2) with an M10 earthing screw onto the
through-holes (1) with the earthing symbol labels
( ).

Fig. 14 Earthing the withdrawable frame (100)

12 9229 0002 176 0A


2008-12-09
Operation

Operation

DANGER
High voltage! Mortal danger!
Do not touch live parts!
Make sure that the withdrawable module with the SION vac-
uum circuit-breaker is operated only by qualified personnel
who are familiar with the operating instructions and who com-
ply with the warning notices.

WARNING
Risk of injury!
During operation of electrical switching devices and systems, haz-
ardous voltages are present in parts of the withdrawable module
with the SION vacuum circuit-breaker.
Mechanical parts may move fast, also by remote control.
Do not remove covers!
Do not reach into openings!
Do not touch circuit-breaker poles!

Using the SION vacuum circuit-breaker with a withdrawable section in the


withdrawable frame
Insert the SION vacuum circuit-breaker with with-
drawable section in the fitted withdrawable frame
(100) and push it in the direction indicated by the
arrow.

Fig. 15 Inserting the SION vacuum circuit-breaker in the


withdrawable frame (100)

9229 0002 176 0A 13


2008-12-09
Operation

Slide the SION vacuum circuit-breaker with with-


drawable section into the withdrawable frame (100)
up to the side stops (large arrow); to do this, move
the locking handles towards the center of the cir-
cuit-breaker (small arrows).

Note
If an undervoltage release 3AX1103 is fitted, it
must be connected to control voltage for switching
operations (mechanical or electrical), as otherwise
closing is not possible.

Fig. 16 Inserting and locking the SION vacuum circuit-


breaker with withdrawable section in the with-
drawable frame (100)

CAUTION
When moving it on the withdrawable section, make sure that the SION vacuum
circuit-breaker is in the following state:

OPEN (OFF) position

Closing spring relaxed

Insert the handle of the withdrawable section


3AX1430-2C in the withdrawable section's coupling
and turn it clockwise to move the SION vacuum
circuit-breaker up to a tangible stop.

Fig. 17 Moving the SION vacuum circuit-breaker with


withdrawable section in the withdrawable frame
(100)

14 9229 0002 176 0A


2008-12-09
Installation accessories

Installation accessories

DANGER
High voltage! Mortal danger!
Do not touch live parts!
Make sure that the SION vacuum circuit-breaker in the with-
drawable frame is operated only by qualified personnel who
are familiar with the operating instructions and who comply
with the warning notices.

WARNING
Risk of injury!
Do not touch live parts!
Before and during installation in switchgear, check that mini-
mum clearances from insulated and live parts, as well as parts
subject to spring force, are maintained.

Assembling installation accessories


Fitting contact arms and systems
1. Grease the screwed-in parts of the threaded
rods with Vaseline.
2. Screw in the threaded rod, paying attention to
correct choice of the screw-in depths.

Fig. 18 Cleaning and fitting threaded rods for contact


arms

9229 0002 176 0A 15


2008-12-09
Installation accessories

1. Firmly screw threaded rods onto contact faces.


Tightening torque for
M12: 40 4 Nm
M16: 100 10 Nm
Tightening torques apply to greased threads
only.
2. Roughen the faces of the copper contact arms,
clean them and

grease them with Vaseline.
Clean faces with silver-plated contact faces
and grease
them with Vaseline.

Fig. 19 Cleaning and fitting contact arms (120)

Fig. 20 Fitting contact arms (120)

16 9229 0002 176 0A


2008-12-09
Installation accessories

For contact arms (120) (in the case of rated operat-


ing current Ir 1250 A), insert them with 40 mm
contact arm adapters in the contact system (110):
1. Grease the contact finger in the contact sys-
tem (110) with Molykote Longterm 2
2. Adjust the contact arm adapter in the contact
system (110) with the screw, washers and nut

3. Tighten the contact arm adapter with an open-


ended wrench in the contact system (110)
4. Undo the screw with washers and nut.

Fig. 21 Preparing contact systems (120) (up to 24 kV,


1250 A)

Fit the contact system (110) onto the threaded rod


and contact arm (120), paying attention to the posi-
tion of the contact system (round outer edge to-
wards the contact arm).

Firmly screw down the contact system (110) with a


torque wrench.
Tightening torque for M12: 40 4 Nm
Tightening torques apply to greased threads only.
Grease the other side of the contact system (110)
with Molykote Longterm 2.

Fig. 22 Securing contact systems (110) on contact arms


(120) with 40 mm

9229 0002 176 0A 17


2008-12-09
Installation accessories

On one side (round outer edge), grease the inside


of the contact system (110, on the contact fingers)
with Molykote Longterm 2.
In the case of contact arms (120) with 60 mm
(rated operating current Ir > 1250 A), fit contact sys-
tems (110) without a contact arm adapter onto the
threaded rod and contact arms (pay attention to the
contact system's position: round outer edge to-
wards the contact arm).

Firmly screw down the contact system (110) with a


torque wrench.
Tightening torque for M16: 100 10 Nm
Tightening torque applies to greased threads only!
Grease the other side of the contact system (110)
with Molykote Longterm 2.

Fig. 23 Securing contact systems (110) on contact arms


(120) with 60 mm

Fitting the bushing and mating contact


Screw bushings (140) with mating contacts (141),
each with
4 saucer-head screws DIN 603 M8x25-8.8 with
a square neck
contact washers and
hexagon nuts
onto a non-ferromagnetic steel sheet in the func-
tional unit or the rear of the withdrawable frame
(100).
Tightening torque: 25 2 Nm
Tightening torque applies to greased threads only!

Fit the bushing cover (142) from the other side.

Fig. 24 Securing the bushing (140) with mating contact


(141) onto the withdrawable frame (100) or sheet

18 9229 0002 176 0A


2008-12-09
Installation accessories

Withdrawable frame with earthing switch


Fitting the withdrawable frame with earthing switch
Prepare fitting of the withdrawable frame with
earthing switch as described in Section
Preparations, page 9.
To secure the withdrawable frame with earthing
switch in the functional unit, 6.6 mm holes can be
produced in the functional unit's space in conformity
with the hole pattern of the withdrawable frame's
side walls, and steel L-brackets (see Fig. 25) can
be placed under it.
Insert the withdrawable frame with earthing switch
and lower it onto the L-brackets.

Fig. 25 Fitting the withdrawable frame with earthing


switch

Note
When securing the withdrawable frame with
earthing switch in the functional unit, ensure that
the earthing switch is installed so that easy access
is possible if it later becomes necessary to replace
the earthing switch gearing.

Fig. 26 Earthing switch gearing detail

9229 0002 176 0A 19


2008-12-09
Installation accessories

For connection of the main conductors, the busbars


with the geometries and dimensions
shown in Fig. 27 must be used in accor-
dance with the switch version listed in
Fig. 28.
The busbars must be dimensioned in compliance
with DIN 43670 (aluminium busbars) or DIN 43671
(copper busbars).

Fig. 27 Busbars

Switch version Busbar Dimensions


version
A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) J (mm) K () L (mm)

a/f: 275 mm 1) 87,5 237,5 146 59 32 30 16 30 20 115 -


Ur 17.5 kV;
Ir 1250 A,
Isc 31.5 kA
a/f: 310 mm 1) 87,5 257,5 146 59 32 30 16 30 20 115 -
Ur 17.5 kV;
Ir 1250 A,
Isc 31.5 kA

Ur 17.5 kV; 1) 37,5 267,5 174,1 59 32 35 23,5 35 20 135 -


Ir > 1250 A,
Isc 31.5 kA

Ur 24 kV; 1) 37,5 320,5 164 59 32 30 15 30 20 135 -


Ir 1250 A,
Isc 25 kA

Ur 24 kV; 1) 37,5 320,5 164 59 32 35 23 35 20 135 -


Ir > 1250 A,
Isc 25 kA

Ur 17.5 kV; 2) 27,2 221,5 171 32 - 35 23,5 30 - 135 2x 12.5


Ir 3150 A,
Isc 40 kA

a/f: width across flats, distance between top and bottom contact arms
Ur: Rated voltage
Ir: Rated operating current
Isc: Rated short-circuit breaking current

Fig. 28 Busbar dimensions

20 9229 0002 176 0A


2008-12-09
Installation accessories

Note
The busbars of the earthing switch must be stabi-
lized during their connection.

Fig. 29 Connecting busbars

Operation
To operate the earthing switch
Push the slider up (vertical arrow)
Insert the earthing switch handle 3AX1430-2D
(or 3AX1430-3D in the case of the 7.2
17.5 kV, 40 kA version) completely

Fig. 30 Preparing operation of the earthing switch with


withdrawable module and SION vacuum circuit-
breaker

9229 0002 176 0A 21


2008-12-09
Installation accessories

To switch on
Turn the earthing switch handle 3AX1430-2D (or
3AX1430-3D) clockwise through 180.

To switch off
Turn the earthing switch handle 3AX1430-2D (or
3AX1430-3D) counterclockwise through 180.

Note
Due to a built-in return lock, it is only possible to
turn back the earthing switch handle when the end
position has been reached and 180 rotation has
been completed.

Fig. 31 Closing the earthing switch with withdrawable


module and SION vacuum circuit-breaker

Remove the earthing switch handle when the


earthing switch is activated.
The opening for the earthing switch handle stays
open, and the indicator of the earthing switch
shows:

Fig. 32 Earthing switch with withdrawable module and


SION vacuum circuit-breaker earthed

22 9229 0002 176 0A


2008-12-09
Installation accessories

Interlocks
Position of the vacuum circuit-breaker

Remo- Insert/ Disconnected po- Move Connected posi-


ved remove* sition tion

Circuit-breaker pri-
mary contacts closed Circuit-breaker X Circuit-breaker
cannot be moved cannot be moved

Circuit-breaker pri-
mary contacts open
Earthing switch closed
X Circuit-breaker X X
cannot be moved

Earthing switch open

Possible
X Not possible
* Inserting or removing the circuit-breaker into/from the withdrawable frame

Fig. 33 Interlocks

Note
Earthing switch handle 3AX1430-2D (or 3AX1430-3D) inserted or earthing switch activated
Moving the withdrawable unit not possible
Handle for withdrawable section 3AX1430-2C cannot be inserted
Withdrawable section cannot be removed from the withdrawable frame.

Handle for withdrawable section 3AX1430-2C inserted or withdrawable section between connected and discon-
nected positions:
Activating the earthing switch not possible
Opening for the earthing switch handle 3AX1430-2D (or 3AX1430-3D) cannot be operated.

9229 0002 176 0A 23


2008-12-09
Installation accessories

Blank page

24 9229 0002 176 0A


2008-12-09
Maintenance

Maintenance

DANGER
Risk of injury!
Working on the withdrawable module with the SION vacuum cir-
cuit-breaker activated/deactivated and with the spring energy store
charged can lead to mortally serious injuries.
Disconnect the operating voltage and switch off the low-
voltage supply before performing maintenance work!
Close and open the vacuum circuit-breaker manually. By doing
so, you will make sure that the circuit-breaker is open and that
the spring energy store is relaxed.
Close and open the vacuum circuit-breaker manually. By doing
so, you will make sure that the circuit-breaker is open and that
the spring energy store is relaxed.

Maintenance
General
The SION vacuum circuit-breaker requires no maintenance under normal conditions. We nevertheless recom-
mend a regular visual check.
For optimum insulation, the insulating parts must be clean:
Switch off the low-voltage supply before performing maintenance work!
In the event of heavy soiling, wipe off all other parts with a lint-free cleaning cloth.
Grease the contact faces to busbars with Vaseline.

Accessories and spare parts Manufacturer's product liability Service


Accessories
Accessories Order number

Circuit-breaker hand crank 3AX1530-2B

Withdrawable section handle 3AX1430-2C

Earthing switch handle 3AX1430-2D or


3AX1430-3D (for 7.2 17.5 kV,
40 kA version)

Molykote Longterm 2 contact grea- 3AX1133-2L


se

Operating instructions 9229 0002 176

Fig. 34 Accessories available for ordering

Replacing spare parts


To ensure that the unit remains in reliable working order, spare parts may only be replaced by trained and certified
personnel.

9229 0002 176 0A 25


2008-12-09
Maintenance
Product liability
The manufacturer's product liability will be rendered null and void if at least one of the following criteria applies:
Original Siemens spare parts are not used.
Fitters performing replacement have not been trained and certified by Siemens PTD M C.
Parts have been incorrectly fitted or adjusted.
Settings are not made in accordance with Siemens specifications.
After installation and setting, no final check is performed with a tester approved by PTD M C including docu-
mentation of the test results.
So that documentation can be kept complete, it is important for measurement results to be submitted to PTD M C
Q.

Service
For details of contacts for service work, consult Siemens PTD Services
Tel.: +49 180/5247000
Fax: +49 180/5242471 or
on the Internet at the Web address: www.siemens.com/energy-support
by e-mail: support.energy@siemens.com
or any local Siemens office.

Disposal
If possible, the materials of the withdrawable module should be recycled. Disposal of the withdrawable module
with minimum environmental impact is possible on the basis of existing legal regulations.
The components of the withdrawable module, of the SION vacuum circuit-breaker and of the installation accesso-
ries can be recycled as mixed scrap, although dismantling to the maximum extent possible into sorted scrap and
mixed scrap residues is more environmentally sustainable.
Electronic scrap must be disposed of in accordance with applicable regulations.
The withdrawable module with the SION vacuum circuit-breaker consists of the following materials:
Steel (partly phosphatized, galvanized and yellow chromated)
Copper (partly silver-plated)
Aluminum (partly silver-plated)
Plastics (polyamide, polyester, polycarbonate, ABS-PC mixture; partly fiberglass-reinforced)
Rubber materials
Ceramics
Lubricants
When delivered by Siemens, the circuit-breaker does not contain any hazardous substances in terms of the haz-
ardous substances regulations applicable to the territory of the Federal Republic of Germany. For operation out-
side the Federal Republic of Germany, the applicable local laws and regulations must be complied with.
Packing materials, consisting of galvanized sheet steel, wood, cardboard, plastic foils (VCI foil, PE and PP) and
hoops (PET), should also be recycled after correct sorting or should be passed on for disposal.
Contact your Siemens service center if you require further information.

26 9229 0002 176 0A


2008-12-09
Index

Index

A Locking ....................................................................15
Accessories ............................................................ 27 Locking handles ......................................................15
Assembly ................................................................ 17 M
B Main conductor........................................................22
Busbar .................................................. 12, 13, 22, 23 Maintenance............................................................27
Busbar terminal......................................................... 8 Mass..........................................................................9
Busbar version........................................................ 22 Mating contact .................................................8, 9, 20
Bushing..................................................... 8, 9, 12, 20 Mixed scrap .............................................................28
Bushing cover ........................................... 8, 9, 12, 20 Molykote Longterm 2...................................19, 20, 27
C O
Circuit-breaker hand crank 3AX1530-2B................ 27 Operation.................................................................14
Classification to IEC 62271-100 ............................... 9 P
Connected position ................................................. 25 Packing..............................................................3, 4, 7
Contact arm ............................ 8, 9, 17, 18, 19, 20, 22 Pole center distance..................................................9
Contact arm adapter ............................................... 19 Pressure pad ...........................................................13
Contact face...................................................... 18, 27 Primary contacts......................................................25
Contact finger ......................................................... 19 Product liability ........................................................28
Contact system ......................................... 8, 9, 19, 20
Control voltage........................................................ 15 R
Crane transport..................................................... 3, 6 Rated frequency ........................................................9
Rated lightning impulse withstand voltage ................9
D Rated operating current ................................9, 19, 22
Data, technical .......................................................... 9 Rated short-circuit breaking current ....................9, 22
Disconnected position............................................. 25 Rated short-circuit duration .......................................9
Disposal .................................................................. 28 Rated short-time AC voltage .....................................9
E Rated short-time current ...........................................9
Earthing .................................................................. 13 Rated voltage ......................................................9, 22
Earthing switch ............................. 7, 9, 21, 23, 24, 25 Rating plate ...............................................................9
Earthing switch handle 3AX1430-2D or 3D ............ 27 Return lock ..............................................................24
Earthing switch indicator......................................... 24 S
E-mail...................................................................... 28 Scope of delivery.......................................................9
F Service ....................................................................28
Fitting ...................................................................... 11 Service work............................................................28
Functional unit ...................................... 10, 11, 20, 21 Shutter.......................................................................8
Shutter operating mechanism ...................................8
G Spare parts..............................................................27
Grease ...................................... 12, 17, 18, 19, 20, 27 Storage......................................................................7
H Switch version .........................................................22
Hand crank, circuit-breaker 3AX1530-2B ................. 9 Swivel lever ...............................................................8
Handle, earthing switch 3AX1430-2D or 3D. 9, 23, 24 System-side isolation shells ......................................9
Handle, withdrawable section 3AX1430-2C ........... 15 T
Handle, withdrawable section 3AX1430-2C (optional) Technical data ...........................................................9
.............................................................................. 9 Threaded rod.........................................17, 18, 19, 20
Hole pattern ...................................................... 11, 21 Transport ...................................................................3
Humidity, relative ...................................................... 7 Transport beam ...................................................3, 10
I Type designation .......................................................9
Inserting .................................................................. 15 Type identification .....................................................9
Installation............................................................... 10 U
Installation accessories........................................... 17 Undervoltage release ..............................................15
Interlocks .......................................................... 10, 25 Unpacking .................................................................3
Internet.................................................................... 28
V
L Vacuum circuit-breaker ...............................................
L-bracket........................................................... 11, 21 ... 3, 4, 6, 7, 8, 9, 10, 14, 15, 17, 23, 24, 25, 27, 28
Link ........................................................................... 8
9229 0002 100 0A 27
2008-12-09
Index
Vaseline ................................................12, 17, 18, 27 Withdrawable section ......................... 8, 9, 13, 14, 15
Versions .................................................................... 9 Withdrawable section handle 3AX1430-2C............ 27
Works serial number................................................. 9
W
Workshop crane ....................................................... 6
Weight ....................................................................... 6
Width across flats.................................................... 22 Y
Withdrawable frame ..3, 6, 8, 9, 11, 13, 14, 15, 20, 25 Year of manufacture ................................................. 9
Withdrawable module .................3, 6, 8, 9, 23, 24, 28