Sei sulla pagina 1di 4

Date Project Name

5-Apr-2017 Cable Tray Tag / Plant Area

Cable Tag Part No. Voltage Size Type OD Area Weight Weight Tray Width Tray Depth No. Layers
(in.) (sq. ft.) (lb/1000ft) (lb/ft) (in.) (in.)
MV CABLES
P-001 571-21-3236 2400V 3/C-350kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.32 4.227 4705 4.71 36 6
P-002 571-21-3236 2400V 3/C-350kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.32 4.227 4705 4.71 36 6
P-003 571-21-3224 2400V 3/C-#4/0AWG w/ 3#7 GND MV-90 / MC-HL (CLX) 1.96 3.017 3075 3.08 36 6
P-004 571-21-3224 2400V 3/C-#4/0AWG w/ 3#7 GND MV-90 / MC-HL (CLX) 1.96 3.017 3075 3.08 36 6
P-005 571-21-3217 2400V 3/C-#2/0AWG w/ 3#8 GND MV-90 / MC-HL (CLX) 1.73 2.351 2160 2.16 36 6
n/a n/a n/a n/a 0.00 0.000 0 0.00 36 6
n/a n/a n/a n/a 0.00 0.000 0 0.00 36 6
I&C CABLES
C-001 0.212 36 6
C-002 0.454 36 6
C-003 1.080 36 6
C-004 0.554 36 6
C-005 0.212 36 6
C-006 0.454 36 6
C-007 1.080 36 6
C-008 0.554 36 6
C-009 0.212 36 6
C-010 0.189 36 6
C-011 0.212 36 6
C-012 0.189 36 6
C-013 0.212 36 6
C-014 0.189 36 6

Required Designed Notes [1] See NEC 392.22(C) and 392.80(B)(1)(2) for rules on MV cables.
Tray Width 36.00 in 36.00 in [2] I&C fill is based on mixed cables smaller than #4/0.
Total MV Width 10.29 in 14.00 in See NEC 2017, 392.22(A)(1)(b).
[3] Designed I&C area is 125% of calculated. Allowed I&C area per NEC
Req'd MV Tray Wid 20.58 in 28.00 in
2017,
I& Tray Width 15.42 in 8.00 in T392.22(A), Column 1.
Total I&C Cable Are 5.80 sq. in 7.25 sq. in [4] MV power cables and LV instrument / control cables are segregated by

Sheet: 350623967.xlsx / MV Tray Page 1 / 4 Printed: 04/05/2017 @ 17:09:39


Allowed I&C Area 10.50 sq. in 9.50 sq. in a metallic barrier.

28 in. 8 in.

I&C Cables
350 350 350 350 #4/ #4/ #4/ #4/ #2/ #2/
0 0 0 0 0 0

Sheet: 350623967.xlsx / MV Tray Page 2 / 4 Printed: 04/05/2017 @ 17:09:39


Okonite
Part No. Voltage Description Type OD Area
571-21-3193 2400V 3/C-#8AWG w/ 3#12 GND MV-90 / MC-HL (CLX) 1.08 0.92
571-21-3196 2400V 3/C-#6AWG w/ 3#10 GND MV-90 / MC-HL (CLX) 1.17 1.08
571-21-3200 2400V 3/C-#4AWG w/ 3#10 GND MV-90 / MC-HL (CLX) 1.30 1.33
571-21-3204 2400V 3/C-#2AWG w/ 3#10 GND MV-90 / MC-HL (CLX) 1.45 1.65
571-21-3208 2400V 3/C-#1AWG w/ 3#8 GND MV-90 / MC-HL (CLX) 1.53 1.84
571-21-3212 2400V 3/C-#1/0AWG w/ 3#8 GND MV-90 / MC-HL (CLX) 1.65 2.14
571-21-3217 2400V 3/C-#2/0AWG w/ 3#8 GND MV-90 / MC-HL (CLX) 1.73 2.35
571-21-3224 2400V 3/C-#4/0AWG w/ 3#7 GND MV-90 / MC-HL (CLX) 1.96 3.02
571-21-3228 2400V 3/C-250kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.09 3.43
571-21-3236 2400V 3/C-350kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.32 4.23
571-21-3244 2400V 3/C-500kcmil w/ 3#5 GND MV-90 / MC-HL (CLX) 2.61 5.35
571-21-3248 2400V 3/C-750kcmil w/ 3#4 GND MV-90 / MC-HL (CLX) 3.10 7.55
571-21-3252 2400V 3/C-1000kcmil w/ 3#4 GND MV-90 / MC-HL (CLX) 3.59 10.12
n/a n/a n/a n/a 0.00 0.00
Wgt. (lb/1000ft) Wgt. (lb/ft)
565.0 0.565
740.0 0.740
960.0 0.960
1270.0 1.270
1520.0 1.520
1835.0 1.835
2160.0 2.160
3075.0 3.075
3470.0 3.470
4705.0 4.705
6405.0 6.405
9220.0 9.220
12075.0 12.075
0.0 0.000

1000

Potrebbero piacerti anche