Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Cable Tag Part No. Voltage Size Type OD Area Weight Weight Tray Width Tray Depth No. Layers
(in.) (sq. ft.) (lb/1000ft) (lb/ft) (in.) (in.)
MV CABLES
P-001 571-21-3236 2400V 3/C-350kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.32 4.227 4705 4.71 36 6
P-002 571-21-3236 2400V 3/C-350kcmil w/ 3#6 GND MV-90 / MC-HL (CLX) 2.32 4.227 4705 4.71 36 6
P-003 571-21-3224 2400V 3/C-#4/0AWG w/ 3#7 GND MV-90 / MC-HL (CLX) 1.96 3.017 3075 3.08 36 6
P-004 571-21-3224 2400V 3/C-#4/0AWG w/ 3#7 GND MV-90 / MC-HL (CLX) 1.96 3.017 3075 3.08 36 6
P-005 571-21-3217 2400V 3/C-#2/0AWG w/ 3#8 GND MV-90 / MC-HL (CLX) 1.73 2.351 2160 2.16 36 6
n/a n/a n/a n/a 0.00 0.000 0 0.00 36 6
n/a n/a n/a n/a 0.00 0.000 0 0.00 36 6
I&C CABLES
C-001 0.212 36 6
C-002 0.454 36 6
C-003 1.080 36 6
C-004 0.554 36 6
C-005 0.212 36 6
C-006 0.454 36 6
C-007 1.080 36 6
C-008 0.554 36 6
C-009 0.212 36 6
C-010 0.189 36 6
C-011 0.212 36 6
C-012 0.189 36 6
C-013 0.212 36 6
C-014 0.189 36 6
Required Designed Notes [1] See NEC 392.22(C) and 392.80(B)(1)(2) for rules on MV cables.
Tray Width 36.00 in 36.00 in [2] I&C fill is based on mixed cables smaller than #4/0.
Total MV Width 10.29 in 14.00 in See NEC 2017, 392.22(A)(1)(b).
[3] Designed I&C area is 125% of calculated. Allowed I&C area per NEC
Req'd MV Tray Wid 20.58 in 28.00 in
2017,
I& Tray Width 15.42 in 8.00 in T392.22(A), Column 1.
Total I&C Cable Are 5.80 sq. in 7.25 sq. in [4] MV power cables and LV instrument / control cables are segregated by
28 in. 8 in.
I&C Cables
350 350 350 350 #4/ #4/ #4/ #4/ #2/ #2/
0 0 0 0 0 0
1000