Sei sulla pagina 1di 14

Software Window of the Site Maintenance Terminal System

The Site Maintenance Terminal System software window consists of the navigation pane,
view pane, and status pane, as shown in Figure 1.
Figure 1 Site Maintenance Terminal System Software Window

Setting the IP Address of the Site Maintenance Terminal PC


This describes how to set the IP address of the SMT PC to the same network segment as the
IP address (192.168.0.72/255.255.255.0) of the BTS.

Prerequisites

The TCP/IP protocol is installed on the SMT PC.

Procedure

1. To set the IP address of the PC, perform the following steps where the Windows XP
operating system is taken as an example: On Windows XP,
choose Start > Setting > Control Panel.
2. Double-click Network Connections in the displayed Control Panel window. Right-
click Local Area Connection in the displayed dialog box.
3. Choose Properties from the shortcut menu. The Local Area Connection
Properties dialog box is displayed.
4. Select Internet Protocol (TCP/IP), and click Properties. The Internet Protocol
(TCP/IP) Properties dialog box is displayed.
5. Select Use the following IP address.
6. Enter the correct IP address, subnet mask, and default gateway. Ensure that the IP
address of the SMT PC is in the same network segment as the IP addresses
(192.168.0.72/255.255.255.0) of the BTS so that a maintenance channel on the BTS
side can be established.
7. Click OK to complete the settings.

Locally Connecting the SMT PC to the BTS


This describes how to connect the Site Maintenance Terminal (SMT) PC to the Ethernet port
on the GTMU through an Ethernet cable. After they are connected, you can operate and
maintain the BTS on the SMT.

Prerequisites

The IP address and subnet mask of the SMT PC are set correctly. The IP address is in the
same network segment as the IP address (192.168.0.72/255.255.255.0) of the BTS.

Procedure

1. Connect the SMT PC to the BTS through an Ethernet cable. One end is connected to
the Ethernet port on the main control board of the basic cabinet, and the other end is
connected to the Ethernet port on the SMT PC (usually a portable PC).
2. Open the MS-DOS Prompt dialog box.

On the SMT PC (Windows 2000/XP), choose Start > Run. In the Run dialog box,
enter cmd, and press Enter. The MS-DOS prompt dialog box is displayed.

3. Run ping 192.168.0.72 to verify the network connection between the computer and
the BTS.

NOTE:

The 192.168.0.72 is the IP address of the BTS.

If the returned information is similar to that given in the example, the SMT PC and the
BBU can communicate normally.
Pinging 192.168.0.72 with 32 bytes of data:
Pinging 192.168.0.72 with 32 bytes of data:
Reply from 192.168.0.72: bytes=32 time=1ms TTL=253
Reply from 192.168.0.72: bytes=32 time=1ms TTL=253
Reply from 192.168.0.72: bytes=32 time=1ms TTL=253
Reply from 192.168.0.72: bytes=32 time=1ms TTL=253
Ping statistics for 192.168.0.72:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip times in milli-seconds:
Minimum = 1ms, Maximum = 1ms, Average = 1ms
Logging in to the BTS at the Local End
This describes the procedure to start the SMT. You can run the SMT to directly log in to the
BTS at the local end.

Prerequisites

The SMT PC is connected properly to the BTS.

The latest software of the SMT is installed in the SMT PC.

If the BTS OML has been established, run the LST BTSLOCALETHPORT command
on the BSC LMT to check whether the ETH port is enabled. If not, run the SET
BTSLOCALETHPORT command to enable the port.

NOTE:

If the BTS OML has not been established, the ETH port is enabled by default.

Context

Table 1 lists the mapping between BTS versions, default user names, and default passwords
for logging in to the SMT.

Table 1 Mapping between BTS versions, default user names, and default passwords for logging in
to the SMT

BTS Version Default User Name Default Password

V100R013C00 versions earlier than None None


V100R013C00SPC015

V100R013C00 versions from admin admin


V100R013C00SPC015 to
V100R013C00SPC042

V100R014C00 versions earlier than admin QW12qw


V100R014C00SPC008

V100R013C00 versions later than admin hwbs@com


V100R013C00SPC042

V100R014C00SPC008 and later


V100R014 versions
Table 1 Mapping between BTS versions, default user names, and default passwords for logging in
to the SMT

BTS Version Default User Name Default Password

V100R015C00 and later V100R015


versions

Procedure

If this is the first time you log in to the BTS at the local end, perform as follows:
1. Double click btsm.exe in the software package.
The Set Communication Port Parameter dialog box is displayed, as shown
in Figure 1.
Figure 1 Set Communication Port Parameter dialog box

2. In the Select Communication Port area, click Network Port. In


the Configure IP area, set the IP address.
3. Click OK.
The System Login dialog box is displayed.
4. Enter the User Name and Password in the System Login dialog box.

NOTE:
The BTS should be support the function that need enter User
Name and Password information.
The default User Name is admin.
The default Password for logging in to the SMT has been changed
to hwbs@com in V100R014C00SPC008 and later versions.
If the BTS version is V100R013 series versions before the upgrade,
the password for logging into the SMT is changed to hwbs@com after the
BTS is upgraded to V100R014C00SPC008 and later versions regardless of
whether the password for logging in to the SMT has been changed before
the upgrade.
If the BTS version is V100R014 series versions before the upgrade:
If the default password for logging into the SMT has been
changed before the upgrade, the new password takes effect upon the
next login after the BTS is upgraded to V100R015C00 and later
versions.
If the default password for logging into the SMT remains
unchanged before the upgrade, the password for logging into the SMT
is hwbs@com after the BTS is upgraded to V100R015C00 and later
versions.
A mechanism is added to lock the SMT when a user has failed to log
in to the SMT three times consecutively. When the SMT is locked, the user
cannot log in to the SMT for 10 min. During this time, the user can maintain
the BTS only by remotely logging in to the BSC LMT. In addition, the number
of consecutive login failures and lock duration can be configured by referring
to Set Login Failure Times and Lock Time.
Users can log in to the BSC LMT and run the SET
BTSUSERPWD command to change the password, withUsername and
Password Type set to USER_SELF_DEFINE, Username set to admin,
and Encrypted Mode set to ENCRYPTED.
Users are advised to change the default password after logging in to
the SMT for the first time. Otherwise, the BTS is vulnerable to malicious
attacks.
5. Click Submit.
If the number of login times exceeds the specified maximum number
of login times, logging into the system fails. The result is displayed on the
status bar in the System Login dialog box.
If the SMT PC communicates with the BTS normally, a window is
displayed, as shown in Figure 2. The SMT is started successfully.
If the SMT PC fails to communicate with the BTS,
the Communication failed dialog box is displayed, as shown inFigure 3. Go
to 6.
Figure 2 Site Maintenance Terminal system window
Figure 3 Communication failed dialog box

6. Click Yes.
The Set Communication Port Parameter dialog box is displayed, as shown
in Figure 1.
7. Perform steps 2 and 3, the Site Maintenance Terminal System window is
displayed, as shown in Figure 2.

NOTICE:
You must Obtaining the Site Management Rights after logging into the SMT.
Otherwise, related data cannot be configured. After OM operations on the SMT
are complete, you must Releasing the Site Management Rights.
If you have ever logged in to the BTS at the local end before, perform as follows:
1. Double click btsm.exe in the software package.
The System Login dialog box is displayed.
2. Perform steps 4 to 7.

Exiting the Site Maintenance Terminal


If you exit the Site Maintenance Terminal, the connection between the Site Maintenance
Terminal and the BTS is disrupted, and the Site Maintenance Terminal System window is
closed.

Procedure

If you do not have the site management rights:


1. Exit the site maintenance terminal by choosing Maintenance > Exit or
click Close in the Site Maintenance Terminal Systemwindow.
If you have obtained the site management rights:
1. In the Site Maintenance Terminal System window,
choose Maintenance > Exit or click Close.
The Warning Message dialog box is displayed, as shown in Figure 1.
Figure 1 Warning Message dialog box

2. Perform as follows:
If no follow-up operation at the local end is required, you are advised
to reset the BTS.
a. Select Immediately reset the BTS and Click OK.
The result is displayed on the status bar in the Warning
Message dialog box, as shown in Figure 2.
Figure 2 Warning Message dialog box
b. Click Cancel to return to Site Maintenance Terminal
System window.
c. Choose Maintenance > Exit or click Close to exit the SMT.
If follow-up operations at the local end are required, do not reset the
BTS. Select Quit the SMT without resetting the BTS and click OK to exit
the SMT.

Site Management Rights


The site management rights refer to the rights to set the parameters of a BTS. After a BTS is
powered on, the remote Site Maintenance System obtains the site management rights by
default. Before operating the BTS through the Site Maintenance Terminal System, you must
obtain the site management rights first.
When operating a BTS through the Site Maintenance Terminal System, pay attention to the
following:
Obtain the site management rights before writing data; otherwise, you may not be
able to write data, for example, load software or activate software. You can read data
from the BTS without the site management rights.
After a BTS is powered on, the remote Site Maintenance System obtains the site
management rights by default and performs all operations directly. Before operating the
BTS through the Site Maintenance Terminal System, you must obtain the site
management rights first. You cannot operate the BTS through the Site Maintenance
Terminal System and the remote Site Maintenance System at the same time.
After completing the local maintenance, you must release the site management
rights.

NOTE:
Remote Site Maintenance: maintaining the BTS through the LMT on the BSC side
Site Maintenance Terminal: maintaining the BTS by directly connecting the Site
Maintenance Terminal PC to the BTS through the Ethernet ports

Obtaining the Site Management Rights


This function is performed to obtain the rights for setting parameters of the BTS.

Prerequisites

You have logged in to the BTS through the SMT.

Context

NOTICE:
You are advised to reset the BTS before releasing the site management rights or exiting from
the SMT when all the following conditions are met:
The BTS is connected to the BSC.
The BTS works properly.
The BTS has been configured on the SMT after the site management rights are
obtained.

Otherwise, the BTS services are affected. After the BTS is reset, the SMT automatically
releases the site management rights.

Procedure

1. Logging in to the BTS at the Local End.


2. Select Site255 in the navigation tree and then double-click Site Management
Right in the Function area.
The Site Management Right dialog box is displayed.
3. Click Get.
The Warning Message dialog box is displayed, as shown in Figure 1.
Figure 1 Warning Message dialog box

4. Click OK.
Then the result is displayed in the Site Management Right dialog box, as shown
in Figure 2.
Figure 2 Site Management Right dialog box

5. Click Close on the dialog box to end the operation.

Releasing the Site Management Rights


This function is performed to release the rights for setting parameters of the BTS. After
completing the local maintenance, you must release the site management rights.
Prerequisites

You have logged in to the BTS through the SMT.

Context

After completing the local maintenance, you should release the site management rights to
facilitate remote maintenance. If you do not release the site management rights at the local
end, the writing operation cannot be performed at the remote end.

Procedure

1. Log in to the SMT. Select Site255 in the navigation tree and then double-click Site
Management Right in the Function area.
The Site Management Right dialog box is displayed.
2. Click Release.
The Warning Message dialog box is displayed, as shown in Figure 1.
Figure 1 Warning Message dialog box

3. Perform as follows:
If no follow-up operation at the local end is required, you are advised to reset
the BTS. Select Immediately reset the BTS and click OK.
The result is displayed in the Site Management Right dialog box, as shown
in Figure 2.
Figure 2 Site Management Right dialog box
If follow-up operations at the local end are required, do not reset the BTS.
Select Release the management rights without resetting the BTS and
click OK.
The result is displayed in the Site Management Right dialog box, as shown
in Figure 3.
Figure 3 Site Management Right dialog box

4. Click Close on the dialog box to end the operation.

Monitoring Environment
This function is performed to monitor and manage the environment parameters in a site. By
performing this function, you can view the current temperature and humidity and set the
temperature and humidity thresholds. The BTS can run normally in a safe and suitable site
environment. You can also clear a burglar alarm or a smoke alarm and disable an EAC alarm.

Prerequisites

You have logged in to the BTS through the SMT and obtained the site management right.

Context

Table 1 describes the parameters.


Table 1 Parameters in the Environment Monitor dialog box

Parameter Meaning Value Range

Clear Robbery Alarm Clearing the infrared alarm and the door -
status alarm

Set Temperature and Set the upper and lower thresholds of -


Humidity Threshold temperature and humidity. Based on the
thresholds, the alarm box reports temperature
alarm and humidity alarm.

Relay Operation Control the relay status. The relay is used to -


start or close the refrigeration device,
heating device, dehumidifier, humidifier, fire
extinguisher, and anti-burglar device. The
default state is Close.

Disable the EAC Alarm Disable the reporting of alarms in a short -


time. In the maintenance of equipment, the
related personnel can select the option to
disable the reporting of alarms for ten
minutes. After ten minutes, the alarms can be
reported. If the equipment is maintained for
more than 10 minutes, restart the alarm
masking.

Get Current View the temperature and humidity associated -


Temperature and with the base station in operation. This
Humidity parameter can be used for querying the status
of the environment alarm.

Clear Smoke Alarm Clearing the smoke alarm -

Procedure

1. Log in to the SMT. Select Site255 in the navigation tree and then double-
click Environment Monitor in the Function area.
The Environment Monitor dialog box is displayed, as shown in Figure 1.
Figure 1 Environment Monitor dialog box

2. Perform the following operations in the Select Operation Type area:

Select... Then...

Clear Robbery Alarm Go to 3.

Set Temperature and In the Temperature and Humidity


Humidity Threshold Threshold area, set the thresholds. Then,
go to3.

Relay Operation In the Relay Operation area, set the


related options to start or stop the
equipment. Then, go to 3.

Disable the EAC Alarm Go to 3.

Get Current Temperature Go to 3.


and Humidity
Select... Then...

Clear Smoke Alarm Go to 3.

3. Click OK.

Potrebbero piacerti anche