Name of Sub Station400 KV MORADABAD Name of Line:

1 Line Length 112

Line is having series compensation NO

2 Positive sequence Reactance (ohm/phase/km) X1 0.331


Positive sequence Resistance (ohm/phase/km) R1 0.0275
Zero sequence Reactance (ohm/phase/km) X0 1.059
Zero sequence Resistance (ohm/phase/km) R0 0.088
Mutual Zero sequence Reactance (ohm/phase/km) X0M
Mutual Zero sequence Resistance (ohm/phase/km) R0M
Positive sequence Impedance (ohm/phase/km) Z1 0.3321
Zero sequence Impedance (ohm/phase/km) Z0 1.0626
Mutual compensation Impedance (ohm/phase/km) Zm 0.0000

Line Angle 85.3

Earthfault Compensation factor Kn 0.733


Km 0.000
RE/RL 0.733
XE/XL 0.73
RM/RL 0.00
XM/XL 0.00

3 Total Positive sequence Reactance X1 37.072


Total Positive sequence Resistance R1 3.08
Total Zero sequence Reactance X0 118.608
Total Zero sequence Resistance R0 9.856
Total Mutual Zero sequence Reactance X0M 0
Total Mutual Zero sequence Resistance R0M 0
Total Positive Sequence Impedance Z1 37.1997
Total Zero Sequence Impedance Z0 119.0168
Impedance/Km
4 Shortest Line Length at Local Bus 93 Km
30.885 Ohm

5 Longest Line Length at Remote Bus 175.5 Km


58.284 Ohm

6 Shortest Line at Remote Bus 103 Km


34.206 Ohm

7 Transformer Imp at Remote Bus


Rating 1 3-phase Transformer Rating in MVA 315.000
No. of 3-phase Bank 1.000 Impedance
% Imp 11.660
Rating 2 3-phase Transformer Rating in MVA 315.000
No. of 3-phase Bank 1.000 Impedance
% Imp 11.730
Rating 3 3-phase Transformer Rating in MVA
No. of 3-phase Bank Impedance
% Imp
90% of total transformer Equivalent Imp. 26.731

If reach encroach into lower voltage level or Z3 setting of next lower line. Zone-3 Timing = 1.5 Sec.

8 Zone-1 Reach 60-80% of principal section 29.760 8.184

9 Zone-2 Reach 120-150% of principal section 44.640 12.276

10 Zone-3 Reach 100% of principal section 37.1997 31.509


100% of next longest line 58.284

11 Reverse Reach 50% of shortest line at local bu 30.885 4.247

12 CT Ratio 1000

13 PT Ratio 3636.36 400000:110

14 CTR/PTR 0.275

15 Fault MVA at Local End 11884.00

16 Fault MVA at Remote end 5749.00

17 Min Load Resistance: 130.8661

18 Thermal Rating of Conductor 714 A


No. Of conductor/phase 2

Nominal Current Rating of Bay 1000

19 Load Angle 30
20
B/U E/F Normal Inverse
characteristic TMS

TMS = t X ((Ir)^0.02-1)/0.14
Ir = I/Is,
Is =Relay setting current
I =Fault current
t (op. time)
Fault current contribution
through the Line for Remote
end Bus Fault
Is
TMS =
400 KV KASHIPUR

Km Double Circuit NO
Short Line NO
Voltage Level in KV 400

85.2507
85.2498
#DIV/0!

0.00
#DIV/0!
0.73333333

Impedance/Km
0.3321
Name of line
MORADABAD-BAREILLY
0.3321
Name of line
KASHIPUR-RISHIKESH
0.3321
Name of line
KASHIPUR-BAREILLY
59.225396825

59.580952381

#DIV/0!

e-3 Timing = 1.5 Sec. Local Bus Remote Bus

Whether
Series
29.760 80 0.0 Compensati NO NO
on is
available at

44.640 120 0.35

114.580 308.01 1.00


Swing Frequency in Hz

15.443 41.52 0.5

17000.00 A

8000 A

85% of system voltage


(1.5 times Thermal Rating of line or 1.5 times bay equipment current rating) which ever is lower

Sl. No. Type of Conductor Current Ratings(A)


1 ACSR Moose 714 A
2 ACSR Zebra 631 A
3 ACSR Snowbird 712 A
4 ACSR Bersimis 833 A
5 ACSR Lapwing 883 A
ormal Inverse 6 ACSR Panther 311 A
eristic TMS
7 AAAC Moose Equv. 686 A
r)^0.02-1)/0.14

ent

0.2 (Zone-3 Timing + 0.1 sec) x { (IFault / Ipickup)0.02 -1 }


0.44 0.14
Remote Bus

ever is lower
Setting Range
Parameter Ste Recommended Unit Description
Min Max
p
FL01 Fault Locator (RFLO)

R1A 0.001 1500.000 1.17 ohm/p Source resistance A (near end)


X1A 0.001 1500.000 13.41 ohm/p Source reactance A (near end)
R1B 0.001 1500.000 2.43 ohm/p Source resistance B (far end)
X1B 0.001 1500.000 27.73 ohm/p Source reactance B (far end)
R1L 0.001 1500.000 3.08 ohm/p Positive sequence line resistance
X1L 0.001 1500.000 37.07 ohm/p Positive sequence line reactance
R0L 0.001 1500.000 9.86 ohm/p Zero sequence line resistance
X0L 0.001 1500.000 118.61 ohm/p Zero sequence line reactance
Zero sequence mutual resistance for double
R0M 0.000 1500.000 0.00 ohm/p
circuit lines

Zero sequence mutual reactance for double


X0M 0.000 1500.000 0.00 ohm/p
circuit lines

Line length 0.0 10000.0 112.00 Km Length of line


Zs= 78.494 Primary Value
0.000 Secondary Value
Z1S= 0.000 Secondary Value
Z1L= 0.000 Secondary Value
Recommended settings for Relay
Type MiCOM P442/4
RELAY SETTING

Substation 400 KV MORADABAD


Line 400 KV KASHIPUR
Line Length 112
CT Ratio 1000
PT ratio 3636.36
Mode

LINE PARAMETRS
R1 = 0.0275
R0 = 0.088
ROM =
X1 = 0.331
X0 = 1.059
XOM =
Total Z(Secondary) = 10.2299

RELAY REACHES IN % OF LINE LENGTHS


Zone - 1 = 80
Zone - 2 = 120
Zone - 3 = 308
Zone - 4 = 41.52

RELAY REACHES IN OHMS


Zone - 1 = 8.184
Zone - 2 = 12.276
Zone - 3 = 31.509
Zone - 4 = 4.247

Menu Text
Line Length 112
Line Imp. 10.23
Line Angle 85.25
Zone Status Bit 0 : Zone-1X Enable : Set to 0
Bit 1: Zone-2 Enable Set to 1
Bit 2: Zone-P Disable Set to 0
Bit 3: Zone-Q Disable Set to 0
Bit 4: Zone-3 Enable Set to 1
Bit 5: Zone-4 Enable Set to 1

KZ1 Res Comp 0.741


KZ1 Angle -13.70
Z1 (Ohms) 8.184
R1-G (Ohms) 13.97
R1-Ph (Ohms) 8.47
TZ1 0

KZ2 Res Comp 0.741


KZ2 Angle -13.70
Z2 (Ohms) 12.276
R2-G (Ohms) 20.79
R2-Ph (Ohms) 15.59
TZ2 0.35

KZ 3/4 Res Comp 0.741


KZ 3/4 Angle -13.70
Z3 31.509
R3 G- R4 G (Ohms) 20.79
R3 Ph- R4 Ph (Ohms) 15.59
TZ3 1.00
Z4 4.247
TZ4 0.5

OTHER PARAMETERS
Series Cmp. Line DISABLE
Overlap Z Mode DISABLE
Z1m Tilt Angle 0
Z1p Tilt Angle 0
Z2 p/q Tilt Angle 0
Fwd Z Chg. Delay 0.03
V Mem Validity 10000
Earth I Detect. 0.05

Fault locator
kZm Mutual Comp 0.000
KZm Angle ( Degrees ) 0.00

Distance Protection Schemes


Program Mode STANDARD SCHEME
Standard Mode PUP Z2
Fault type BOTH ENABLED
Trip Mode 1P, Z1, Z2 AND CR
Aid dist Dly 0.02
tReversal Guard 0.02
Unblocking logic None
TOR-SOFT OOOOOOOOO1O1OOO
SOTF TIME DELAY 110
Z1 Extension on channel fail DISABLE

Weak infeed Mode status


Loss of load Mode status DISABLE

Power Swing Blocking (PSB)


Delta R ( Ohms ) 4.68
Delta X ( ohms ) 4.68
IN status ENABLED
IN>(% Imax) 40
I2 status ENABLED
I2>(% Imax) 30
Imax line status ENABLED
I max Line> 3
Unblocking delay 2
Blocking zones 111111

Out of Step 1
Stable Swing 1

Back up I> DISABLED


I>1 Function NA
I>2 Function NA
I>3 status NA
I>4 status NA
I>4 Current set NA
I>4 Time delay NA

Broken Conductor ENABLED


I2/I1 Setting 0.2
I2/I1 Time delay 5
I2/I1 Trip DISABLED

Earth Fault O/C


IN>1 Function IEC S INVERSE
IN>1 Direction Directional FWD
IN>1 VTS Block Non Directional
IN>1 Current Set 0.2
IN>1 Time delay
IN>1 Time VTS 1.5
IN>1 TMS 0.40
IN>1 RES CHAR
IN>1 tReset 0
IN>2 Function DISABLED
IN>3 Status DISABLED
IN>4 Status DISABLED
IN Char Angle -45
Polarization Zero Sequence

Overvoltage Protection
V> Measuring Mode Phase Neutral
V>1 Function DT
V>1 Voltage set 70
V>1 Time Delay 5
V>2 Status ENABLED
V>2 voltage set 95
V>2 Time set 0.1
V>3 Status DISABLED
V>4 Status DISABLED

VT Super vision
VTS time delay 5
VTS I2> & I0> inhibit 0.2
Detect 3p ENABLED
Threshold 3p 30
Delta I > 0.1

CT Super vision DISABLED

Check Synchronization DISABLED

Auto Reclose ENABLED

Disturbance Recorder
Duration 3
Trigger position 33%
Trigger Mode Extended
Analog Inputs
Channel 1 VA
Channel 2 VB
Channel 3 VC
Channel 4 VN
Channel 5 IA
Channel 6 IB
Channel 7 IC
Channel 8 IN

Digital Inputs ENABLED


Channel allocation as per requ YES

Trigger position Trigger L/H

Configuration column

Restore Defaults No operation


Setting Group Select Via Menu
Active settings Group1
Save Changes No operation
Copy Form Group1
Copy to No operation
Settings group I ENABLED
Settings Group-2 DISABLED
Settings Group-3 DISABLED
Settings Group-4 DISABLED
Distance Protection ENABLED
Power Swing ENABLED
Back up O/C DISABLED
Negative Sequence O/C DISABLED
Broken Conductor ENABLED
E/F O/C EARTH FAULT O/C
Carrier Aided DEF DISABLED
Voltage Protection ENABLED
CB Fail ENABLED
VT Supervision ENABLED
CT Supervision DISABLED
Systems Checks DISABLED
Auto Reclose Function ENABLED
Input Labels VISIBLE
Output Labels VISIBLE
CT and VT ratios VISIBLE
Event Recorder VISIBLE
Disturbance Recorder VISIBLE
Common Settings VISIBLE
Commission Tests INVISIBLE
Settings Values SECONDARY
Minimum of (R2-G) & (Z1 x 10) & (50 x CTR/PTR)
Minimum of (R2-Ph) & (Z1 x 10) & (30 x CTR/PTR)

Minimum of (R3G-R4G) & (75 x CTR/PTR)


Minimum of (R3Ph-R4Ph) & (60 x CTR/PTR)
Sec

Minimum of (Min Load R x CTR/PTR x COS (Load Angle+90-Line Angle)/COS(90-Line Angle)) & (125 x CTR/PTR)
Minimum of (2 x (R3G-R4G) - delta R) & (75 x CTR/PTR)

Sec

ms
Sec

89L OPEN 06
DDB #069
&
10000
V< Dead Line
DDB #237 Pick-Up
0
ne Angle)) & (125 x CTR/PTR)
& Stub Bus Enable
DDB #1083

10000
Pick-Up 1 I>4 Timer Block
DDB #1064
0
Substation Line

Setting Range
Parameter RecommendedUnit
Min Max Step
ZMCPDIS1
Operation On/Of on On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward

Operation PP On/Of On

X1FwPP 0.50 3000.00 0.01 29.66 ohm/p

R1PP 0.10 1000.00 0.01 2.464 ohm/p

RFFwPP 1.00 3000.00 0.01 30.810 ohm/l

X1RvPP 0.50 3000.00 0.01 29.65 ohm/p

RFRvPP 1.00 3000.00 0.01 30.810 ohm/l

Timer tPP Of,On On

tPP 0.000 60.000 0.001 0.000 s

Operation PE On,Of On

X1FwPE 0.50 3000.00 0.01 29.65 ohm/p

R1PE 0.10 1000.00 0.01 2.46 ohm/p

X0PE 0.5 9000.00 0.01 92.42 ohm/p

R0PE 0.5 3000.00 0.01 23.40 ohm/p

RFFwPE 1.00 3000.00 0.01 50.810 ohm/l

X1RvPE 0.10 3000.00 0.01 29.65 ohm/p


RFRvPE 1.00 9000.00 0.01 50.810 ohm/l

Timer tPE Of,On On

tPE 0.000 60.000 0.001 0.000 s

IMinOpPP 10 30 1 10 %IB

IMinOpPE 10 30 1 10 %IB

IMinOpIN 5 30 1 5 %IB

Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS2
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward

Operation PP On/Of On

X1FwPP 0.50 3000.00 0.01 44.49 ohm/p

R1PP 0.10 1000.00 0.01 3.70 ohm/p

RFFwPP 1.00 3000.00 0.01 61.610 ohm/l

X1RvPP 0.50 3000.00 0.01 44.49 ohm/p

RFFwPP 1.00 3000.00 0.01 61.610 ohm/l

Timer tPP Of,On On

tPP 0.000 60.000 0.001 0.350 s

Operation PE On,Of On
X1FwPE 0.50 3000.00 0.01 44.48 ohm/p

R1PE 0.10 1000.00 0.01 3.58 ohm/p

X0PE 0.5 9000.00 0.01 138.63 ohm/p

R0PE 0.5 3000.00 0.01 35.10 ohm/p

RFFwPE 1.00 9000.00 0.01 76.210 ohm/l

X1RvPE 0.50 3000.00 0.01 44.48 ohm/p

RFRvPE 1.00 9000.00 0.01 76.210 ohm/l

Timer tPE Of,On On

tPE 0.000 60.000 0.001 0.350 s

IMinOpPP 10 30 1 10 %IB

IMinOpPE 10 30 1 10 %IB

Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS3
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward

Operation PP On/Of On

X1FwPP 0.50 3000.00 0.01 152.89 ohm/p

R1PP 0.10 1000.00 0.01 12.31 ohm/p

RFFwPP 1.00 3000.00 0.01 77.010 ohm/l

X1RvPP 0.50 3000.00 0.01 152.89 ohm/p


RFRvPP 1.00 3000.00 0.01 77.010 ohm/l

Timer tPP Of,On On

tPP 0.000 60.000 0.001 1.000 s

Operation PE On,Of On

X1FwPE 0.50 3000.00 0.01 152.89 ohm/p

R1PE 0.10 1000.00 0.01 12.31 ohm/p

X0PE 0.5 9000.00 0.01 476.53 ohm/p

R0PE 0.5 3000.00 0.01 120.67 ohm/p

RFFwPE 1.00 9000.00 0.01 127.010 ohm/l

X1RvPE 0.50 3000.00 0.01 152.89 ohm/p

RFRvPE 1.00 9000.00 0.01 127.010 ohm/l

Timer tPE Of,On On

tPE 0.000 60.000 0.001 1.000 s

IMinOpPP 10 30 1 10 %IB

IMinOpPE 10 30 1 10 %IB

Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS4
Operation On/Of
Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS5
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir reverse Reverse

Operation PP On/Of On

X1FwPP 0.50 3000.00 0.01 15.39 ohm/p

R1PP 0.10 1000.00 0.01 1.24 ohm/p

RFFwPP 1.00 3000.00 0.01 77.01 ohm/l

X1RvPP 0.50 3000.00 0.01 15.39 ohm/p

Timer tPP Of,On On

tPP 0.000 60.000 0.001 0.450 s

Operation PE On,Of On

X1FwPE 0.50 3000.00 0.01 15.39 ohm/p

R1PE 0.10 1000.00 0.01 1.24 ohm/p

X0PE 0.5 9000.00 0.01 47.96 ohm/p

R0PE 0.5 3000.00 0.01 12.15 ohm/p

RFFwPE 1.00 9000.00 0.01 127.01 ohm/l

X1RvPE 0.50 3000.00 0.01 15.39 ohm/p

RFRvPE 1.00 9000.00 0.01 127.01 ohm/l

Timer tPE Of,On On

tPE 0.000 60.000 0.001 0.450 s

IMinOpPP 10 30 1 10 %IB
IMinOpPE 10 30 1 10 %IB

Setting Range
Parameter Recommended Unit
Min Max Step
DPRRDRE
Operation On/Of

PreFaultRecT 0.05 0.30 0.01 s

PostFaultRec
0.1 0.5 0.1 s
T
TimeLimit 0.5 6.0 0.1 s

Post Retrig On/Of

ZeroAngleRef 1 30 1 Ch

OpModeTest On/Of
Setting Range
Parameter Recommended Unit
Min Max Step
FDPSPDIS
IBase 1 99999 1 1000 A
UBase 0.05 2000 1 400 kV

INBlockPP 10 100 1 40 %Ph

INReleasePE 10 100 1 20 %Ph

RLdFw 1.00 3000.00 0.01 64.80 ohm/p

RLdRv 1.00 3000.00 0.01 64.80 ohm/p

ArgLd 5.00 70.00 1 25.00 Deg

X1 0.50 3000.00 0.01 112.87 ohm/p


X0 0.50 9000.00 0.01 324.14 ohm/p
RFFwPP 0.50 3000.00 0.01 100.00 ohm/l

RFRvPP 0.50 3000.00 0.01 100.00 ohm/l

RFFwPE 1.00 9000.00 0.01 102.00 ohm/l

RFRvPE 1.00 9000.00 0.01 102.00 ohm/l

Timer tPP Of,On

tPP 0.00 60.00 0.00 s

Timer tPE Of,On

tPE 0.00 60.00 0.00 s

IMinOpPP 5 30 1 10 %IB

IMinOpPE 5 30 1 10 %IB

Setting Range
Parameter Recommended Unit
Min Max Step
ZDSRDIR
Series Comp/
Operation SC Series Comp
No SeriesComp
IBase 1 99999 1 1000 A
UBase 0.05 2000 1 400 kV

IMinOpPE 5 30 1 10 %IB

IMinOpPP 5 30 1 10 %IB

AngNegRes 90 175 1 115 Deg

AngDir 5 45 1 15 Deg
INReleasePE 10 100 1 20 %Ph

INBlockPP 10 100 1 40 %Ph

OperationLdC Of On On

RLdFw 1.00 3000.00 0.01 64.80 ohm/p

RLdRv 1.00 3000.00 0.01 64.80 ohm/p

ArgLd 5.00 70.00 1 26.00 Deg

X1FwPP 0.50 3000.00 0.01 112.87 ohm/p

R1PP 0.10 1000.00 0.01 7.76 ohm/p

RFFwPP 0.50 3000.00 0.01 100.00 ohm/l

X1RvPP 0.50 3000.00 0.01 112.00 ohm/p

RFRvPP 0.50 3000.00 0.01 100.00 ohm/l

X1FwPE 0.50 3000.00 0.01 112.87 ohm/p

R1PE 0.10 1000.00 0.01 7.76 ohm/p

X0FwPE 0.50 9000.00 0.01 324.14 ohm/p

R0PE 0.5 3000.00 0.01 78.31 ohm/p

RFFwPE 0.50 3000.00 0.01 102.00 ohm/l

X1RvPE 0.50 3000.00 0.01 112.87 ohm/p


X0RvPE 0.50 9000.00 0.01 324.14 ohm/p

RFRvPE 1.00 9000.00 0.01 102.00 ohm/l

Setting Range
Parameter Recommended Unit
Parameter Recommended Unit
Min Max Step

ZCVPSOF

Operation On/Of On
IBase 1 99999 1 1000 A
UBase 0.05 2000.00 0.05 400 kV
Impedence /UI
Mode Level /UI level & UILvI & Imp
Imp.

AutoInit On/Of On

IPh< 1 100 1 20 %IB

Uph< 1 100 1 25 %UB

tDuration 0.000 60.000 0.001 0.020 s

tSOTF 0.000 60.000 0.001 0.200 s

tDLD 0.000 60.000 0.001 0.500 s

Note: The used zone (Non-directional zone-2) is selected in application


If CB input is already hard wired for SOTF enabling, the same to b
Setting Range
Parameter Recommended Unit
Min Max Step

ZMRPSB

Operation Of On On
X1InFw 0.10 3000.00 0.01 103.47 ohm

R1LIn 0.10 1000.00 0.01 8.54 ohm


R1FInFw 0.10 1000.00 0.01 110.00 ohm

X1InRv 0.10 3000.00 0.01 103.47 ohm

R1FInRv 0.10 1000.00 0.01 5.54 ohm

OperationLdC Of On On

RLdOutFw 0.10 3000.00 0.01 64.80 ohm

ArgLd 5.00 70.00 26 Deg

RLdOutRv 0.10 3000.00 0.01 64.80 ohm

kLdRFw 0.50 0.90 0.01 0.9 Mult

kLdRRv 0.50 0.90 0.01 0.9 Mult

t P1 0.000 60.000 0.001 s

t P2 0.000 60.000 0.001 s

tW 0.000 60.000 0.001 s

tH 0.000 60.000 0.001 s

tEF 0.000 60.000 0.001 2.000 s

tR1 0.000 60.000 0.001 s

tR2 0.000 60.000 0.001 s

IMinOpPE 5 30 1 %IB
IBase 1 99999 1 1000 A

Note: Blocking of trip from PSB is decided by programming of blocking


Setting Range
Parameter Recommended Unit
Min Max Step
LMBRFLO
R1A 0.001 1500.000 0.56 ohm/p
X1A 0.001 1500.000 6.38 ohm/p
R1B 0.001 1500.000 0.52 ohm/p
X1B 0.001 1500.000 5.90 ohm/p
R1L 0.001 1500.000 3.05 ohm/p
X1L 0.001 1500.000 36.94 ohm/p
R0L 0.001 1500.000 30.76 ohm/p
X0L 0.001 1500.000 106.08 ohm/p

R0M 0.000 1500.000 0.00 ohm/p

X0M 0.000 1500.000 0.00 ohm/p

Line length 0.0 10000.0 111.20 Km


Setting Range
Parameter Recommended Unit
Min Max Step
ZCPDCH
Operation On/Of On
Of/Intertrip/PUR/POR/
Scheme Type Permissive UR A
blocking

tCoord 0 60.00 0.01 0.00 s

tSendMin 0 60.00 0.01 0.01 s

Unblock On/Of s

tSecurity 0 60.00 0.01 s

Setting Range
Parameter Recommended Unit
Parameter Recommended Unit
Min Max Step
ZCRWPSCH
Current
On/Of Of
Reversal

tPickUpRev 0 60.00 0.001 0.02 s

tDelayRev 0 60.00 0.001 0.06 s

WEI Of/Echo/Echo & Trip Of s


tPickUpWEI 0 60.00 0.01 0.01 s
Ubase 0.05 2000 0.05 400.00 kV

UPP< 10 90.00 1 70.00 % Ub

UPN< 10 90.00 1 70.00 % Ub

Setting Range
Parameter Recommended Unit
Min Max Step
BRCPTOC
BRC1
Operation On
IBase 1 99999 3000 A

IUB> 50 90 50 %IB

IP> 5 100 20 %IB

Toper 0 60 5 s
Treset 0 60 s
Setting Range
Parameter Step Recommended Unit
Min Max

EF4PTOC

General
Operation Of/On - -
IBase 1 99999 1 A
UBase 0.05 2000 0.05 kV
AngleRCA 1 Deg
Voltage/ Current/
polMethod - -
Dual
UPolMin 1 100 1 %UB

IPolMin 2 100 1 %IB

RNPol 0.5 1000 0.01 ohm

XNPol 0.5 3000 0.01 ohm

IN>Dir 1 100 1 %IB

2ndHarmSta
5 100 1 %
b

BlkParTransf Of / On - -

UseStartValu IN1>/IN2>,
- -
e IN3>, IN4
UnderTime/
SOTF - -
SOTF
ActivationSO Open/ Closed/
- -
TF Close Command

StepForSOTF Step 2/ Step 3 - -

HarmResSOT
Of /On - -
F
tSOTF 0 60 0.001 s
Step-1 Of / Non-
DirMode1 directional - -
inv.,L.T. inv.,IEC
Characterist1 Forward Reverse - -
Norm. inv./IEC
IN1> 1 2500 1 %IB
t1 0 60 0.001 s

k1 0.05 999 0.01 -

IN1Mult 1 10 0.1 -

Reset
TypeCrv1
tReset1 0 60 0.001 s

t1Min 10 60 0.001 s

HarmRestrain
Of/ On - -
1
Setting Range
Parameter Step Recommended Unit
Min Max
STBPTOC

STB1

Operation
IBase 1 99999 A
ReleaseMode
I> 1 2500 %IB
T 0 60 0.001 s
Setting Range
Parameter Recommended Unit
Min Max Step

OV2PTOV

General
Conn Type - PhNDFT -
Operation Of/On - ON -
UBase 0.05 2000 0.05 400.00 kV
Step 1
Operation Of/On - On -
curveA/
Charaterstic 1 Inverse curveB/ Inverse Definite Time
curve C/
1 out of 3/ 2out of 3/
OpMode1 1 out of 3
3 out of 3
U1> 1.000 200.000 1 110
t1 0.000 6000 1 5

t1min 0.000 60.000 110 5

k1 0.05 1.1 0.01 0.05

Hystabs1 0 100 0.1 0.5 %


Step 2
Operation Of/On - Off -
curveA/
Charaterstic 2 Inverse curveB/ Inverse
curve C/
1 out of 3/ 2out of 3/
OpMode2
3 out of 3
U2> 1.000 200.000 1
t2 0.000 6000 1

t2min 0.000 60.000 110

k1 0.05 1.1 0.01

Hystabs2 0 100 0.1 %


Setting Range
Parameter Recommended Unit
Min Max Step
SDDRFUF
Operation Of / On - On -
IBase 1 99999 1 1000 A
UBase 0.05 2000 0.05
Of/UNsINs/UZsIZs/UZsIZs 400.00 kV
OpMode OR UNsINs / UZsIZs AND UZslZs -
UNsINs
3U0> 1 100 1 70 %UB
3I0< 1 100 y 10 %IB

3U2> 1 100 1 70 %UB

3I2< 1 100 1 10 %IB

OpDUDI Of / On On -

DU> 1 100 1 40 %UB

DI< 1 100 1 20 %IB

UPh> 1 100 1 70 %UB

IPh> 1 100 1 10 %IB

SealIn Of / On Of -

USealln< 1 100 1 70 %UB

IDLD< 1 100 1 20 %IB

UDLD< 1 100 1 25 %UB


400KV MORADABAD-KASHIPUR S/C LINE

Description

Zone 1 Setting (PDIS, 21)


Operation Of / On
Base current i.e rated current
Base voltage i.e.rated voltage
Operation mode of directionality
Operation mode Of/On of Ph-Ph
loops
Positive sequence reactance reach

Positive sequence resistance reach

Fault resistance reach in


ohm/loop , Ph-Ph
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-Ph
Operation mode Of/On of Zone
timer, Ph-Ph
Time delay of trip,Ph-Ph
Operation mode Of/On of Ph-E
loops
Positive sequence reactance reach

Positive sequence resistance reach

Zero sequence reactance reach


Zero sequence resistance for zone
characteristic angle
Fault resistance reach in
ohm/loop , Ph-E
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-E
Operation mode Of/On of Zone
timer, Ph-E
Time delay of trip,Ph-E
Minimum operate delta current for
Phase-Phase loops
Minimum operate delta current for
Phase-Earth loops
Minimum operate residual current
for Phase-Earth loops

Description

Zone 2 Setting (PDIS, 21)


Operation Of / On
Base current i.e rated current
Base voltage i.e.rated voltage
Operation mode of directionality
Operation mode Of/On of Ph-Ph
loops
Positive sequence reactance reach

Positive sequence resistance reach

Fault resistance reach in


ohm/loop , Ph-Ph
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-Ph
Operation mode Of/On of Zone
timer, Ph-Ph
Time delay of trip,Ph-Ph
Operation mode Of/On of Ph-E
loops
Positive sequence reactance reach

Positive sequence resistance reach

Zero sequence reactance reach


Zero sequence resistance for zone
characteristic angle
Fault resistance reach in
ohm/loop , Ph-E
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-E
Operation mode Of/On of Zone
timer, Ph-E
Time delay of trip,Ph-E
Minimum operate delta current for
Phase-Phase loops
Minimum operate delta current for
Phase-Earth loops

Description

Zone 3 Setting (PDIS, 21)


Operation Of / On
Base current i.e rated current
Base voltage i.e.rated voltage
Operation mode of directionality
Operation mode Of/On of Ph-Ph
loops
Positive sequence reactance reach

Positive sequence resistance reach

Fault resistance reach in


ohm/loop , Ph-Ph
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-Ph
Operation mode Of/On of Zone
timer, Ph-Ph
Time delay of trip,Ph-Ph
Operation mode Of/On of Ph-E
loops
Positive sequence reactance reach

Positive sequence resistance reach

Zero sequence reactance reach


Zero sequence resistance for zone
characteristic angle
Fault resistance reach in
ohm/loop , Ph-E
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-E
Operation mode Of/On of Zone
timer, Ph-E
Time delay of trip,Ph-E
Minimum operate delta current for
Phase-Phase loops
Minimum operate delta current for
Phase-Earth loops

Description

Zone 4 Setting (PDIS, 21)


Operation Of / On

Description

Zone 5 Setting (PDIS, 21)


Operation Of / On
Base current i.e rated current
Base voltage i.e.rated voltage
Operation mode of directionality
Operation mode Of/On of Ph-Ph
loops
Positive sequence reactance reach

Positive sequence resistance reach

Fault resistance reach in


ohm/loop , Ph-Ph
Positive sequence reactance reach
Operation mode Of/On of Zone
timer, Ph-Ph
Time delay of trip,Ph-Ph
Operation mode Of/On of Ph-E
loops
Positive sequence reactance reach

Positive sequence resistance reach

Zero sequence reactance reach


Zero sequence resistance for zone
characteristic angle
Fault resistance reach in
ohm/loop , Ph-E
Positive sequence reactance reach
Fault resistance reach in
ohm/loop , Ph-E
Operation mode Of/On of Zone
timer, Ph-E
Time delay of trip,Ph-E
Minimum operate delta current for
Phase-Phase loops
Minimum operate delta current for
Phase-Earth loops

Description

Disturbance Report
Operation Of / On

Pre-Fault recording time

Post-Fault recording time

Fault recording time limit


Post-fault retrig enabled (On) or
not (Of)
Trip value recorder , Phasor
reference channel
Operation mode during test mode

Description

Phase Selection (PDIS,21)


Base current , i.e rated current
Base voltage , i.e rated voltage
3Io limit for blocking phase-to-
phase measuring loops
3Io limit for blocking phase-to-
earth measuring loops
Forward resistive reach within the
load impedance area
Reverse resistive reach within the
load impedance area
Load angle determining the load
impedance reach (Assumed)
Positive sequence reactance reach
Zero sequence reactance reach
Fault resistance reach Ph-Ph,
forward
Fault resistance reach Ph-Ph,
reverse
Fault resistance reach Ph-E,
forward
Fault resistance reach Ph-E,
reverse
Operation mode Of/On of Zone
timer, Ph-Ph
Time delay of trip,Ph-Ph
Advance Setting
Operation mode Of/On of Zone
timer, Ph-E
Time delay of trip,Ph-E
3Io limit for blocking phase-to-
phase measuring loops
3Io limit for blocking phase-to-
earth measuring loops

Description

Directional Impedance (RDIR)


Special directional criteria for
voltage reversal
Base current , i.e rated current
Base voltage , i.e rated voltage
3Io limit for blocking phase-to-
earth measuring loops
3Io limit for blocking phase-to-
phase measuring loops
Angle of blinder in second
quadrant for forward direction
Angle of blinder in fourth quadrant
for forward direction
3Io limit for blocking phase-to-
earth measuring loops
3Io limit for blocking phase-to-
phase measuring loops
Operation of load discrimination
characteristic
Forward resistive reach within the
load impedance area
Reverse resistive reach within the
load impedance area
Load angle determining the load
impedance reach (Assumed)
Positive sequence reactance reach

Positive sequence resistance reach

Fault resistance reach Ph-Ph,


forward
Positive sequence reactance reach
Fault resistance reach Ph-Ph,
reverse
Positive sequence reactance reach

Positive sequence resistance reach

Zero sequence reactance reach


Zero sequence resistance for zone
characteristic angle
Fault resistance reach Ph-E,
forward
Positive sequence reactance reach
Zero sequence reactance reach
Fault resistance reach Ph-E,
forward

Description
Description

Automatic Switch onto Fault


Logic (PSOF)
Operation Of / On
Base current , i.e rated current
Base voltage , i.e.rated voltage
Mode of operation of SOTF
function

To be kept "OFF" if
binary input is available
Automatic swicth onto fault for "CB Closing
initialization command" for
manual/Autoreclosing
mode

Current level for detection of dead


line in % IB
Voltage level for detection of dead
line in % UB
Time delay for UI detection
Drop of delay time of swicth onto
fault function
Delay time for activation of dead
line detection
elected in application configuration.
abling, the same to be continued

Description

Power swing detection


(RPSB,78)
Operation Mode On/Of
Inner reactive boundary , forward
Line resistance for inner
characteristic angle
Fault resistance coverage to inner
resistive line , forward
Inner reactive boundary , reverse
Fault resistance line to inner
resistive boundary , reverse
Operation of load discrimination
characteristic
Outer resistive load boundary ,
forward
Load angle determining load
impedance area
Outer resistive load boundary ,
reverse
Multiplication factor for inner
resistive load boundary , forward
Multiplication factor for inner
resistive load boundary , reverse
Timer for detection of initial power
swing
Timer for detection of subsequent
power swings
Advance Setting
Waiting timer for activation of tP2
timer
Timer for holding power swing
START output
Timer for overcoming single - pole
reclosing dead time.
Timer giving delay to inhibit by
Advance Setting
residual current
Timer giving delay to inhibit at
very slow swing
Minimum operate current in % of
Ibase.
Base setting for current level
settings.
ramming of blocking input and the configuration in CAP

Description

Fault Locator (RFLO)


Source resistance A (near end)
Source reactance A (near end)
Source resistance B (far end)
Source reactance B (far end)
Positive sequence line resistance
Positive sequence line reactance
Zero sequence line resistance
Zero sequence line reactance
Zero sequence mutual resistance
for double circuit lines
Zero sequence mutual reactance
for double circuit lines
Length of line

Description

Scheme Communication
Operation Of / On

Scheme Type

Coordination time for blocking


communication scheme
Mininum duration of carrier send
signal
Operation mode of unblock logic
Secutiry timer for loss of carrier
guard detection

Description
Description

Scheme Communication
Operating mode of Current
Reversal Logic
Pickup time of Current Reversal
Logic
Time delay to prevent carrier send
and local trip
Operating mode of WEI Logic
Coordination time for the WEI
Logic
Base setting for voltage level
Phase to Phase voltage for
detection of fault condition
Phase to Neutral voltage for
detection of fault condition

Description

BrokenCondCheck(PTOC,46)

Operation Of / On
Base current i.e rated current
Unbalance current operation level
in percent of max current
Minimum phase current for
operation of Iub> in % of Ibase
Operated time delay
Time delay in reset Advance Setting

Description

Back up E/F Prtn. Residual


OverCurrent

Operation Of / On
Base value for current settings
Base value for voltage settings
Relay characteristic angle (RCA)
Type of polarization
Minimum voltage level for
polarization in % of UBase
Minimum current level for
polarization in % of IBase
Real part of source Z to be used
for current polarization
Imaginary part of source Z to be
used for current polarization
Residual current level for Direction
release in % of IBase
Second harmonic restrain
operation in % of IN amplitude
Enable blocking at parallel
transformers
Current level blk at
parallel transf (step1, 2, 3 or 4)
SOTF operation mode
Select signal that shall activate
SOTF

Selection of step used for SOTF

Enable harmonic restrain function


in SOTF
Time delay for SOTF

Directional mode of step 1


Time delay curve type for step 1
Operate residual current level for
step 1 in % of IBase
Independent (defenite) time delay
of step 1
Time multiplier for the dependent
time delay for step 1
Multiplier for scaling the current
setting value for step 1

Reset curve type for step1

Reset time delay


Minimum operate time for inverse
curves for step 1
Enable block of step 1 from
harmonic restrain

Description

Stub(PTOC,50STB)
ONLY FOR ONE & HALF CB
SWITCHING SCHEME
Operation Of / On
Base current , i.e rated current
Release of stub protection
Operate current level
Time delay Advance Setting

Description

Two Step Over Voltage


Protection

Group selector for connection type


Operation Of / On
Base value for voltage settings

Operation Of / On
Selection of time delay curve type
for step 1
No. of phases required for
operation
Voltage setting start value
Definite time delay of step1
Min operate time for inverse curve
for step 1
Time multiplier for the inverse
time delay for step1
Absolute hysteresis in % of Ubase

Operation Of / On
Selection of time delay curve type
for step 2
No. of phases required for
operation
Voltage setting start value
Definite time delay of step2
Min operate time for inverse curve
for step 2
Time multiplier for the inverse
time delay for step2
Absolute hysteresis in % of Ubase

Description

Fuse Failure Supervision


Operation Of / On
Base current
Base voltage
Operating mode
residual overvoltage element in %
of Ubase
Operate level of residual
undercurrent element in % of
Ibase
Operate level of neg seq
overvoltage element in % of Ubase
Operate level of neg seq
undercurrent element in % of
Ibase
Operation of change based
function Of/On
Operate level of residual
overvoltage element in % of Ubase
Operate level of residual
undercurrent element in % of
Ubase
Operate level of phase voltage in
% of Ubase.
Operate level of phase current in
% of IBase
Seal in functionality Of/On
Operate level of seal-in phase
voltage in %of Ubase
Operate level for open phase
current detection in % of IBase
Operate level for open phase
voltage