If reach encroach into lower voltage level or Z3 setting of next lower line. Zone-3 Timing = 1.5 Sec.
12 CT Ratio 1000
14 CTR/PTR 0.275
19 Load Angle 30
20
B/U E/F Normal Inverse
characteristic TMS
TMS = t X ((Ir)^0.02-1)/0.14
Ir = I/Is,
Is =Relay setting current
I =Fault current
t (op. time)
Fault current contribution
through the Line for Remote
end Bus Fault
Is
TMS =
400 KV KASHIPUR
Km Double Circuit NO
Short Line NO
Voltage Level in KV 400
85.2507
85.2498
#DIV/0!
0.00
#DIV/0!
0.73333333
Impedance/Km
0.3321
Name of line
MORADABAD-BAREILLY
0.3321
Name of line
KASHIPUR-RISHIKESH
0.3321
Name of line
KASHIPUR-BAREILLY
59.225396825
59.580952381
#DIV/0!
Whether
Series
29.760 80 0.0 Compensati NO NO
on is
available at
17000.00 A
8000 A
ent
ever is lower
Setting Range
Parameter Ste Recommended Unit Description
Min Max
p
FL01 Fault Locator (RFLO)
LINE PARAMETRS
R1 = 0.0275
R0 = 0.088
ROM =
X1 = 0.331
X0 = 1.059
XOM =
Total Z(Secondary) = 10.2299
Menu Text
Line Length 112
Line Imp. 10.23
Line Angle 85.25
Zone Status Bit 0 : Zone-1X Enable : Set to 0
Bit 1: Zone-2 Enable Set to 1
Bit 2: Zone-P Disable Set to 0
Bit 3: Zone-Q Disable Set to 0
Bit 4: Zone-3 Enable Set to 1
Bit 5: Zone-4 Enable Set to 1
OTHER PARAMETERS
Series Cmp. Line DISABLE
Overlap Z Mode DISABLE
Z1m Tilt Angle 0
Z1p Tilt Angle 0
Z2 p/q Tilt Angle 0
Fwd Z Chg. Delay 0.03
V Mem Validity 10000
Earth I Detect. 0.05
Fault locator
kZm Mutual Comp 0.000
KZm Angle ( Degrees ) 0.00
Out of Step 1
Stable Swing 1
Overvoltage Protection
V> Measuring Mode Phase Neutral
V>1 Function DT
V>1 Voltage set 70
V>1 Time Delay 5
V>2 Status ENABLED
V>2 voltage set 95
V>2 Time set 0.1
V>3 Status DISABLED
V>4 Status DISABLED
VT Super vision
VTS time delay 5
VTS I2> & I0> inhibit 0.2
Detect 3p ENABLED
Threshold 3p 30
Delta I > 0.1
Disturbance Recorder
Duration 3
Trigger position 33%
Trigger Mode Extended
Analog Inputs
Channel 1 VA
Channel 2 VB
Channel 3 VC
Channel 4 VN
Channel 5 IA
Channel 6 IB
Channel 7 IC
Channel 8 IN
Configuration column
Minimum of (Min Load R x CTR/PTR x COS (Load Angle+90-Line Angle)/COS(90-Line Angle)) & (125 x CTR/PTR)
Minimum of (2 x (R3G-R4G) - delta R) & (75 x CTR/PTR)
Sec
ms
Sec
89L OPEN 06
DDB #069
&
10000
V< Dead Line
DDB #237 Pick-Up
0
ne Angle)) & (125 x CTR/PTR)
& Stub Bus Enable
DDB #1083
10000
Pick-Up 1 I>4 Timer Block
DDB #1064
0
Substation Line
Setting Range
Parameter RecommendedUnit
Min Max Step
ZMCPDIS1
Operation On/Of on On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward
Operation PP On/Of On
Operation PE On,Of On
IMinOpPP 10 30 1 10 %IB
IMinOpPE 10 30 1 10 %IB
IMinOpIN 5 30 1 5 %IB
Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS2
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward
Operation PP On/Of On
Operation PE On,Of On
X1FwPE 0.50 3000.00 0.01 44.48 ohm/p
IMinOpPP 10 30 1 10 %IB
IMinOpPE 10 30 1 10 %IB
Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS3
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir Forward
Operation PP On/Of On
Operation PE On,Of On
IMinOpPP 10 30 1 10 %IB
IMinOpPE 10 30 1 10 %IB
Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS4
Operation On/Of
Setting Range
Parameter Recommended Unit
Min Max Step
ZMCAPDIS5
Operation On/Of On
IBase 1 99999 1 1000 A
Ubase 0.05 2000.00 0.05 400 kV
OperationDir reverse Reverse
Operation PP On/Of On
Operation PE On,Of On
IMinOpPP 10 30 1 10 %IB
IMinOpPE 10 30 1 10 %IB
Setting Range
Parameter Recommended Unit
Min Max Step
DPRRDRE
Operation On/Of
PostFaultRec
0.1 0.5 0.1 s
T
TimeLimit 0.5 6.0 0.1 s
ZeroAngleRef 1 30 1 Ch
OpModeTest On/Of
Setting Range
Parameter Recommended Unit
Min Max Step
FDPSPDIS
IBase 1 99999 1 1000 A
UBase 0.05 2000 1 400 kV
IMinOpPP 5 30 1 10 %IB
IMinOpPE 5 30 1 10 %IB
Setting Range
Parameter Recommended Unit
Min Max Step
ZDSRDIR
Series Comp/
Operation SC Series Comp
No SeriesComp
IBase 1 99999 1 1000 A
UBase 0.05 2000 1 400 kV
IMinOpPE 5 30 1 10 %IB
IMinOpPP 5 30 1 10 %IB
AngDir 5 45 1 15 Deg
INReleasePE 10 100 1 20 %Ph
OperationLdC Of On On
Setting Range
Parameter Recommended Unit
Parameter Recommended Unit
Min Max Step
ZCVPSOF
Operation On/Of On
IBase 1 99999 1 1000 A
UBase 0.05 2000.00 0.05 400 kV
Impedence /UI
Mode Level /UI level & UILvI & Imp
Imp.
AutoInit On/Of On
ZMRPSB
Operation Of On On
X1InFw 0.10 3000.00 0.01 103.47 ohm
OperationLdC Of On On
IMinOpPE 5 30 1 %IB
IBase 1 99999 1 1000 A
Unblock On/Of s
Setting Range
Parameter Recommended Unit
Parameter Recommended Unit
Min Max Step
ZCRWPSCH
Current
On/Of Of
Reversal
Setting Range
Parameter Recommended Unit
Min Max Step
BRCPTOC
BRC1
Operation On
IBase 1 99999 3000 A
IUB> 50 90 50 %IB
Toper 0 60 5 s
Treset 0 60 s
Setting Range
Parameter Step Recommended Unit
Min Max
EF4PTOC
General
Operation Of/On - -
IBase 1 99999 1 A
UBase 0.05 2000 0.05 kV
AngleRCA 1 Deg
Voltage/ Current/
polMethod - -
Dual
UPolMin 1 100 1 %UB
2ndHarmSta
5 100 1 %
b
BlkParTransf Of / On - -
UseStartValu IN1>/IN2>,
- -
e IN3>, IN4
UnderTime/
SOTF - -
SOTF
ActivationSO Open/ Closed/
- -
TF Close Command
HarmResSOT
Of /On - -
F
tSOTF 0 60 0.001 s
Step-1 Of / Non-
DirMode1 directional - -
inv.,L.T. inv.,IEC
Characterist1 Forward Reverse - -
Norm. inv./IEC
IN1> 1 2500 1 %IB
t1 0 60 0.001 s
IN1Mult 1 10 0.1 -
Reset
TypeCrv1
tReset1 0 60 0.001 s
t1Min 10 60 0.001 s
HarmRestrain
Of/ On - -
1
Setting Range
Parameter Step Recommended Unit
Min Max
STBPTOC
STB1
Operation
IBase 1 99999 A
ReleaseMode
I> 1 2500 %IB
T 0 60 0.001 s
Setting Range
Parameter Recommended Unit
Min Max Step
OV2PTOV
General
Conn Type - PhNDFT -
Operation Of/On - ON -
UBase 0.05 2000 0.05 400.00 kV
Step 1
Operation Of/On - On -
curveA/
Charaterstic 1 Inverse curveB/ Inverse Definite Time
curve C/
1 out of 3/ 2out of 3/
OpMode1 1 out of 3
3 out of 3
U1> 1.000 200.000 1 110
t1 0.000 6000 1 5
OpDUDI Of / On On -
SealIn Of / On Of -
Description
Description
Description
Description
Description
Description
Disturbance Report
Operation Of / On
Description
Description
Description
Description
To be kept "OFF" if
binary input is available
Automatic swicth onto fault for "CB Closing
initialization command" for
manual/Autoreclosing
mode
Description
Description
Description
Scheme Communication
Operation Of / On
Scheme Type
Description
Description
Scheme Communication
Operating mode of Current
Reversal Logic
Pickup time of Current Reversal
Logic
Time delay to prevent carrier send
and local trip
Operating mode of WEI Logic
Coordination time for the WEI
Logic
Base setting for voltage level
Phase to Phase voltage for
detection of fault condition
Phase to Neutral voltage for
detection of fault condition
Description
BrokenCondCheck(PTOC,46)
Operation Of / On
Base current i.e rated current
Unbalance current operation level
in percent of max current
Minimum phase current for
operation of Iub> in % of Ibase
Operated time delay
Time delay in reset Advance Setting
Description
Operation Of / On
Base value for current settings
Base value for voltage settings
Relay characteristic angle (RCA)
Type of polarization
Minimum voltage level for
polarization in % of UBase
Minimum current level for
polarization in % of IBase
Real part of source Z to be used
for current polarization
Imaginary part of source Z to be
used for current polarization
Residual current level for Direction
release in % of IBase
Second harmonic restrain
operation in % of IN amplitude
Enable blocking at parallel
transformers
Current level blk at
parallel transf (step1, 2, 3 or 4)
SOTF operation mode
Select signal that shall activate
SOTF
Description
Stub(PTOC,50STB)
ONLY FOR ONE & HALF CB
SWITCHING SCHEME
Operation Of / On
Base current , i.e rated current
Release of stub protection
Operate current level
Time delay Advance Setting
Description
Operation Of / On
Selection of time delay curve type
for step 1
No. of phases required for
operation
Voltage setting start value
Definite time delay of step1
Min operate time for inverse curve
for step 1
Time multiplier for the inverse
time delay for step1
Absolute hysteresis in % of Ubase
Operation Of / On
Selection of time delay curve type
for step 2
No. of phases required for
operation
Voltage setting start value
Definite time delay of step2
Min operate time for inverse curve
for step 2
Time multiplier for the inverse
time delay for step2
Absolute hysteresis in % of Ubase
Description