Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
Motor Protection Philosophy
2
Motor Downtime
Motor initial cost could be as low as 2% of its lifetime
operational cost.
The driven process downtime in many cases is more
expensive than motor.
Motor downtime contributors are:
Power system failures.
Inadvertent shutdown because of organic interface
issues or motor protection mal-operation
Motor failure
Load failure
3
Motor Failure Rates and Cost
IEEE STUDY EPRI STUDY AVERAGE
FAILURE CONTRIBUTOR % FAILED COMPONENT % %
Persistent Overload 4.20% Stator Ground Insulation 23.00
Electrical
Normal Deterioration 26.40% Turn Insulation 4.00
Motor failure rate is Bracing 3.00
Related Failures
STATOR BEARINGS
ROTOR SHAFT
FRAME
5
Motor Management Relays
6
Motor Design
Motor characteristics are
determined by the design
7
Two Main Risks for an Overheated Motor
Stator Windings Insulation Degradation
110
100
90
A B F H
Insulation lifetime
decreases by half if
80
PERCENTAGE OF LIFE (%)
70 For F class
insulation stator
60
50
A-CLASS (105 C)
temperature of motor operating
165C causes motor
40
30
B-CLASS (130C)
lifetime to decrease temperature
F-CLASS (155 C)
to 50%
20
10
H-CLASS (180 C) exceeds thermal
0
0 50 100 150
TEMPERATURE (C)
200 250 limit by 10C
Rotor Conductors Deforming or Melting
In most cases, rotor thermal limit is defined by the allowed motor
stall time. These motors are classified as rotor limited.
8
Motor Thermal Limits Definitions
Running overload region
Failure to Accelerate
region
9
Motor Operating Regions
The instant the starter closes, voltage
is induced in the rotor, allowing large
currents to flow. N
Locked Rotor, so the frequency seen
at that moment by the rotor is full
60hz, meaning the XL is at max
XL=2* 3.14*F*L
So PF is very low as most of the Z is
inductive.
10
Motor Relay Zone of Protection
-Electrical Faults
-Abnormal Conditions
-Thermal Overloads
11
Setting of the motor protection relay is based
on the motor datasheets information and
system configuration
12
CT Selection
13
Phase CTs
The CT should be nominally sized at or
greater than motor FLA
Ideally FLA will be 75-150% of ct primary
value
The CT must have an accuracy class high
enough so that the voltage waveform
presented to the relay will allow the
overcurrent to operate
14
Phase CTs
A Motor has a FLA of 413 Amps
Maximum fault current is 22KA
15
Phase CTs
C100 If calculated magnitude is less than OC
pickup, the CT circuit will have to be
redesigned!
17
Motor Thermal Parameters
G
19
Settings Example
CT Rating, Voltage Sensing
FLA & Ground CT
Thermal Model Settings
Overload Pickup, Overload Curve, Unbalance Bias K Factor, Stopped & Running Cooling
Time Constants Hot/Cold Safe Stall Ratio, RTD Bias
20
Settings Example
Select CT Rating, Voltage Sensing
Phase CT
The phase CT should be chosen such that the
FLA is 75% to 150% of CT primary. Since the
FLA is 297 a 300:5 CT may be chosen.
Voltage Sensing
Enter the connection type and ratio. Enter
motor nameplate voltage. In this case, a
14400/120 PT will be used, so 120:1 ratio.
21
Settings Example
Select FLA, Ground CT
Motor FLA
Set the Motor Full Load Amps to 297A,
as specified by the data sheets.
Ground CT
For high resistive grounded systems
<25A, sensitive ground detection is
possible with the 50:0.025 CT. On
solidly grounded or low resistive
grounded systems where the fault
current is much higher, a 1A or 5A
secondary CT should be used. If
residual ground fault connection is to
be used, the ground fault CT ratio
must equal the phase CT ratio. If
residual connection is used, timer
must be set with respect to the
acceleration time to ride through.
The zero sequence CT chosen needs
to be able to handle all potential fault
levels without saturating.
Set:
FLA = 297 A
GF = System
22
***Importance of Curve Selection***
All algorithms of the thermal model are based on the protection curve
Improper curve selection will lead to false trips and increased lockout
times, which increases operational costs, as per the early slides
Selecting a curve that is too low (more conservative) will cause the relay to
interpret a given amount of load current as an ever greater percentage of
the available motor capacity causing a trip too early, while the motor could
still serve the process
For example, if the TCU used on start is greater than 67% of TC the
lockout will extend into the second time constant, 89% puts it into the 3rd
time constant, etc
In extreme cases the relay can interpret start TCU as 100% and RTD bias
will prevent reset until 100% TC is available, which implies 40C, unlimited
lockout possible, days long in hot environment.
23
***Importance of Curve Selection***
24
Settings Example
Select Overload Curve for Thermal Model using Damage curves
Overload Curve
Set the overload curve just below cold thermal limit and above hot
thermal limit. If only hot curve is provided by mfgr, then must set at or
below hot thermal limit
The best fitting curve is curve # 9 in this example.
25
Settings Example
Select Overload Curve for Thermal Model
Overload Curve
Set the overload curve below cold thermal limit and above hot thermal
limit. If only hot curve is provided by mfgr, then must set at or below
hot thermal limit. The best fitting curve is curve # 9 in this example.
This can be verified with Hot Stall Time of 30s at 540% FLA by using the
standard overload curve equation above.
26
Settings Example
Select Overload Curve for Thermal Model
Select overload curve using Hot Stall Time and Locked Rotor Current when
Overload Curves are not available:
Example: For Hot Stall Time = 30s and LRA = 540% FLA
*****Warning*****
This may leave the selected
curve above the motor curve
at the low end
Substitute in the above equation: True damage curves are
always preferred
30s = CURVE MULTPLIER x 2.2116623 Custom curve can be used to
(0.02530337 x 4.42 + 0.05054758 x 4.4) maximize protection
28
Settings Example
Thermal Overload Pickup
Overload Pickup
This setting defines the current level at which the
motor is considered to be overloaded.
29
Thermal Model - Current Unbalance
Rotor
A 3 phase motor can run with one phase completely absent, in these
circumstances extra heat is produced, but it does not necessarily mean the
motor must be tripped immediately
This allows the unbalance trip level to be set higher. **Note that once
unbalance trip is set, the relay will trip for single phase after 2 seconds if
the unbalance goes above 40%.
I EQ I M2 (1 K ( I 2 I 1 ) 2 )
31
Settings Example
Determine Unbalance Bias K Factor for Thermal Model
Unbalance Bias Of Thermal Capacity
Enable the Unbalance Bias of Thermal
Capacity so that the heating effect of
unbalance currents is added to the
Thermal Capacity Used.
32
Settings Example
Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 1)
LRTHOT
HCR
LRTCOLD
Hot/Cold Ratio =
30/35
=> 0.86
33
Settings Example
Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 2)
34
Thermal Model - RTD Biasing
35
Settings Example
Determine RTD Bias Setpoints for Thermal Model
MAX POINT
TEMP: 155C
TCU: 100%
MID POINT
TEMP: 130C
TCU: 25%
MIN POINT
TEMP: 40C
TCU: 0%
MAX POINT
TEMP: 155C
TCU: 100%
MID POINT
TEMP: 130C
TCU: 25%
MIN POINT
TEMP: 40C
TCU: 0%
38
Thermal Model - Motor Cooling
Thermal Model Cooling Motor Stopped Thermal Model Cooling Motor Tripped
When the motor is stopped, its thermal capacity used value will decay according to
a formula. If the thermal capacity used was at 100% before stopping the motor, the
thermal capacity used will take 5 time constants or 2.5 hours to decay. Note that after
only three time constants, the motor would be within 5% of its final value of zero from
its initial value. If the same motor were stopped with 85% of its thermal capacity
used, it would decay according to the same formula taking 5 time constants to decay
to zero completely and would be within 5% of zero from its initial value after 3 time
constants.
**As noted, RTD bias and the stopped motor cooling times can conspire to create long
unneeded lockouts if curve selection is too conservative, impacting process
39
Settings Example
Stopped & Running Cool Time Constants
41
Settings Example
Determine Current Unbalance Alarm/Trip Settings
A setting of 10-15% x FLA for the Unbalance Alarm with a delay of 5-10 seconds
would be appropriate.
Trip can be set to 20-40% x FLA with a delay of 2-5 seconds. The relay will trip for
single phase after 2 seconds for greater than 40% automatically
42
Settings Example
Ground Fault & Acceleration Trip Settings
Ground Fault
Limit the ground fault current to less than 7.5 to 10amps.
In this example, use 0.15 x CT or 0.15 x 50 = 7.5A
Acceleration Trip
Acceleration Trip, like Mechanical Jam, is load protection, not motor protection
This setpoint should be set higher than the maximum starting time to avoid
nuisance tripping when the voltage is lower or for varying loads during acceleration.
A value greater than 15 seconds should be entered (based on motor data sheet).
43
Settings Example
Enable Start Inhibit
44
TCU / Start Inhibit Example
If Motor is Stopped:
When the motor has cooled and the level of
thermal capacity used has fallen to 66%, a
start will be permitted.
45
Settings Example
Starts/Hr, Time Between Starts
Starts/Hour
Starts/Hour can be set to the # of cold starts as per the data sheet.
For this example, it is 2
Mechanical relays had no memory and so starts per hour was devised as a
way to protect the rotor primarily.
**Motor thermal capacity calculations will always over rule starts/hour
settings so if curve selection is conservative the relay may not allow desired
number of starts
46
Settings Example
RTD Alarm & Tripping
Stator RTDs
RTD trip level should be set at the maximum temperature rating of the
insulation as a final trip precaution if motor temp continue to rise but
currents stay below pickup. For example, a motor with class F insulation
that has a temperature rating of 155C could have the Stator RTD Trip level
be set to 150-155C The RTD alarm level should be set to a level to provide a
warning that the motor temperature is rising, 130-135C for a class B rise,
depending on max local ambient this alarm could be lowered.
Bearing RTDs
The Bearing RTD alarm and trip settings will be determined by evaluating
the temperature specification from the bearing manufacturer.
47
Settings Example
Phase Differential
Core Balance Method
Summation/Residual Method
48
Settings Example
Phase Differential - Six CTs:
Biased differential protection method allows for
different ratios for system/line and the neutral
CTs
This method has a dual slope characteristic. Main
purpose of the percent-slope characteristic is to
prevent a mis-operation caused by unbalances
between CTs during external faults. CT
unbalances arise as a result of CT accuracy errors
or CT saturation.
Characteristic allows for very sensitive settings
when the fault current is low and less sensitive
settings when the fault current is high and CT
performance may produce incorrect operating
signals
49
Settings Example
Phase Differential
Core Balance Method
Summation/Residual Method
50
Settings Example
Undervoltage & Overvoltage Tripping
The overall result of an under or overvoltage condition is an increase in
current and motor heating and a reduction in overall motor performance.
51
Motors Operated on VFD
No traditional inrush as the motor always operates in
the v/hz region and as a result there are no starts per
hour considerations
53
Motor Starting
A weak electrical system gives a similar effect to a soft-start
A soft-start works by reducing the amount of voltage impressed on the
motor windings, thereby limiting the amount of induced current flow
An Autotransformer does this by using fixed taps
A solid state (ss) soft-start uses SCRs as a chopper circuit to reduce
the voltage to the motor
Each has strengths and weaknesses. An Auto-tx can produce more
torque for a given voltage, but a SS can provide a softer ramp in,
easier on the equipment
In all cases, this is a fixed frequency application and so the torque
produced is directly related to the square of the voltage.
The more you reduce the voltage to reduce current inrush and
flicker, the more the torque is reduced
There are practical limits to how low you can go before the motor
refuses to turn
To use a softstart to limit starting current to 300% would imply ~50%
voltage limit, which then would allow the motor on the next page to
produce 25% of LRT
Since the motor LRT is ~50% of FLT, in this situation the motor could
only develop 20% of FLT
54
Motor Starting - MV
55
Motor Starting - MV
56
Motor Starting - LV
57
Motor Health Heat Rejection
58
Motor Protection Enhancements
59
Motor Protection Enhancements - VFD
Source Side VFD Protection Load Side Motor Protection Combined, economical
Figure 7b
60
Motor Protection Enhancements - VFD
Motor Load Filter Interval
Frequency tracking switched from
voltages to currents
Frequency range of 3Hz to 72Hz.
Thermal Model Voltage Dependent
(VD) function is blocked
VFD Not Bypassed operand could be
used to block the voltage elements.
All motor current functions except
Short Circuit, Ground Fault and
Differential elements are using Motor
Load Filter Interval
Elements that use filtered current
Acceleration Time When VFD configuration support
Current Unbalance Function is enabled and Bypass
Mechanical Jam Switch is closed, then frequency
Overload tracking source will be switched back
Thermal Model from currents to voltages, all voltages
Undercurrent elements will work as normal
Power Factor All motor functions will then be using
Power
the normal RMS currents
61
Broken Rotor Bar Detection
62
Broken Rotor Bar Detection
Traditional VS Modern approach
63
Broken Rotor Bar Detection
64
Stator Turn-Turn Fault Detection
The method is based on measuring
the Cross Coupled Impedance of the
motor
65
CT Saturation
2ms 18.7ms
869 469
66