Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Installation
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-3
Profibus Segment
This pair of wires can be turned into a Profibus segment by
y Adding a Profibus Interface Card.
y Adding a Profibus Slave device.
y Connecting a Profibus cable from the Master to a Slave device.
y Usage of the terminators.
Profibus
T T
Interface
Slave Slave
device device
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-4
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-5
Profibus DP Interface Card
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-6
Profibus DP Interface Card
The Profibus DP Interface Card connections are:
y Connecting Profibus Cable Input wires to the terminal block by terminals:
J1 A1 (Green)
J2 S (Black)
J3 B1 (Red)
y Connecting Profibus Cable Output wires to the terminal block by terminals:
J4 A2 (Green)
J5 S (Black)
J6 B2 (Red)
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-7
Terminators
y Terminators prevent distortion and signal loss.
y Terminators are an impedance matching module used at each end of the
transmission line.
y Two, and only two, per segment (end of segment).
Profibus
Interface T T
Slave
B device
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-8
Terminators
y Terminator in Cable Connector can be switched ON and OFF depending on if it
is used at the end of the segment
Profibus
T T
Interface
Slave
device
Off On
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-9
Expanding the Segment
200 meters
Profibus
Interface
T T Profibus T T
Repeater
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-10
Cable Length Restrictions
The use of repeaters expand the total segments length. This would only be necessary if
the additional cable was a long stretch.
y Total segment length is limited to 200 meters with a baud rate of 1500 kbit/s.
y The total number of segments can be 10 depending of the type of repeaters
(use vendor specs)
y Maximum admissible distance between two devices
(NO_REP + 1)* Segment length
Note: In the example above, the number of repeaters is 1 and the segment length is
200 meters.Therefore, 1 + 1 x 200 = 400 meters.
NO_REP = Depends on repeater type
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-11
Summary
y List three items required to build a Profibus DP segment.
y Define Profibus DP segment.
y State one absolute rule for locating a terminator.
y Write the formula for calculating the Total Segment Length.
EMERSON Process Management Educational Services Course 7034 - Rev 6 - 3/15/04 Copyrighted Material / Duplication Prohibited
15-12