InsulationResistance(IR)Values

MARCH23,2012 152COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2012/03/23/INSULATION
RESISTANCEIRVALUES/#COMMENTS)

Introduction:

Themeasurementofinsulationresistanceisacommonroutinetestperformedonalltypesofelectricalwiresandcables.Asa
productiontest,thistestisoftenusedasacustomeracceptancetest,withminimuminsulationresistanceperunitlengthoften
speciedbythecustomer.TheresultsobtainedfromIRTestarenotintendedtobeusefulinndinglocalizeddefectsinthe
insulationasinatrueHIPOTtest,butrathergiveinformationonthequalityofthebulkmaterialusedastheinsulation.

Evenwhennotrequiredbytheendcustomer,manywireandcablemanufacturersusetheinsulationresistancetesttotracktheir
insulationmanufacturingprocesses,andspotdevelopingproblemsbeforeprocessvariablesdriftoutsideofallowedlimits.

SelectionofIRTesters(Megger):

Insulationtesterswithtestvoltageof500,1000,2500and5000Vareavailable.
Therecommendedratingsoftheinsulationtestersaregivenbelow:

VoltageLevel IRTester
650V 500VDC
1.1KV 1KVDC
3.3KV 2.5KVDC
66KvandAbove 5KVDC
TestVoltageforMeggering:

WhenACVoltageisused,TheRuleofThumbisTestVoltage(A.C)=(2XNamePlateVoltage)+1000.
WhenDCVoltageisused(MostusedinAllMegger),TestVoltage(D.C)=(2XNamePlateVoltage).

Equipment/Cable DCTest
Rating Voltage
24VTo50V 50VTo100V
50VTo100V 100VTo250V
100VTo240V 250VTo500V
440VTo550V 500VTo1000V
2400V 1000VTo2500V
4100V 1000VTo5000V
MeasurementRangeofMegger:

Testvoltage Measurement
Range
250VDC 0Mto250G

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 1/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

500VDC 0Mto500G
1KVDC 0Mto1T
2.5KVDC 0Mto2.5T
5KVDC 0Mto5T

PrecautionwhileMeggering:

BeforeMeggering:

Makesurethatallconnectionsinthetestcircuitaretight.
Testthemeggerbeforeuse,whetheritgivesINFINITYvaluewhennotconnected,andZEROwhenthetwoterminalsare
connectedtogetherandthehandleisrotated.

DuringMeggering:

Makesurewhentestingforearth,thatthefarendoftheconductorisnottouching,otherwisethetestwillshowfaultyinsulation
whensuchisnotactuallythecase.
Makesurethattheearthusedwhentestingforearthandopencircuitsisagoodoneotherwisethetestwillgivewrong
information
Spareconductorsshouldnotbemeggeredwhenotherworkingconductorsofthesamecableareconnectedtotherespective
circuits.

AftercompletionofcableMeggering:

Ensurethatallconductorshavebeenreconnectedproperly.
TestthefunctionsofPoints,Tracks&Signalsconnectedthroughthecablefortheircorrectresponse.
Incaseofsignals,aspectshouldbeveriedpersonally.
Incaseofpoints,verifypositionsatsite.Checkwhetheranypolarityofanyfeedtakenthroughthecablehasgotearthed
inadvertently.

SafetyRequirementsforMeggering:

AllequipmentundertestMUSTbedisconnectedandisolated.
Equipmentshouldbedischarged(shuntedorshortedout)foratleastaslongasthetestvoltagewasappliedinordertobe
absolutelysafeforthepersonconductingthetest.
NeveruseMeggerinanexplosiveatmosphere.
Makesureallswitchesareblockedoutandcableendsmarkedproperlyforsafety.
Cableendstobeisolatedshallbedisconnectedfromthesupplyandprotectedfromcontacttosupply,orground,oraccidental
contact.
Erectionofsafetybarrierswithwarningsigns,andanopencommunicationchannelbetweentestingpersonnel.
Donotmeggerwhenhumidityismorethan70%.
GoodInsulation:Meggerreadingincreasesrstthenremainconstant.
BadInsulation:Meggerreadingincreasesrstandthendecreases.
ExpectedIRvaluegetsonTemp.20to30decreecentigrade.
Ifabovetemperaturereducesby10degreecentigrade,IRvalueswillincreasedbytwotimes.
Ifabovetemperatureincreasedby70degreecentigradeIRvaluesdecreasesby700times.

HowtouseMegger:

MeggersisequippedwiththreeconnectionLineTerminal(L),EarthTerminal(E)andGuardTerminal(G).

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 2/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

(hps://electricalnotes.les.wordpress.com/2012/03/q.png)

ResistanceismeasuredbetweentheLineandEarthterminals,wherecurrentwilltravelthroughcoil1.TheGuardterminalis
providedforspecialtestingsituationswhereoneresistancemustbeisolatedfromanother.Letsuscheckonesituationwhere
theinsulationresistanceistobetestedinatwowirecable.
Tomeasureinsulationresistancefromaconductortotheoutsideofthecable,weneedtoconnecttheLineleadofthemegger
tooneoftheconductorsandconnecttheEarthleadofthemeggertoawirewrappedaroundthesheathofthecable.

(hps://electricalnotes.les.wordpress.com/2012/03/qq.png)

InthiscongurationtheMeggershouldreadtheresistancebetweenoneconductorandtheoutsidesheath.
WewanttomeasureResistancebetweenConductor2ToSheathsbutActuallyMeggermeasureresistanceinparallelwiththe
seriescombinationofconductortoconductorresistance(Rc1c2)andtherstconductortothesheath(Rc1s).
Ifwedontcareaboutthisfact,wecanproceedwiththetestascongured.Ifwedesiretomeasureonlytheresistancebetween
thesecondconductorandthesheath(Rc2s),thenweneedtousethemeggersGuardterminal.

(hps://electricalnotes.les.wordpress.com/2012/03/qqq.png)

ConnectingtheGuardterminaltotherstconductorplacesthetwoconductorsatalmostequalpotential.Withlileorno
voltagebetweenthem,theinsulationresistanceisnearlyinnite,andthustherewillbenocurrentbetweenthetwoconductors.
Consequently,theMeggersresistanceindicationwillbebasedexclusivelyonthecurrentthroughthesecondconductors
insulation,throughthecablesheath,andtothewirewrappedaround,notthecurrentleakingthroughtherstconductors
insulation.
Theguardterminal(ifed)actsasashunttoremovetheconnectedelementfromthemeasurement.Inotherwords,itallows
youtobeselectiveinevaluatingcertainspeciccomponentsinalargepieceofelectricalequipment.Forexampleconsideratwo
corecablewithasheath.Asthediagrambelowshowstherearethreeresistancestobeconsidered.

(hps://electricalnotes.les.wordpress.com/2012/03/qqqq.png)

IfwemeasurebetweencoreBandsheathwithoutaconnectiontotheguardterminalsomecurrentwillpassfromBtoAand
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 3/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
IfwemeasurebetweencoreBandsheathwithoutaconnectiontotheguardterminalsomecurrentwillpassfromBtoAand
fromAtothesheath.Ourmeasurementwouldbelow.ByconnectingtheguardterminaltoAthetwocablecoreswillbeatvery
nearlythesamepotentialandthustheshuntingeectiseliminated.

(1)IRValuesForElectricalApparatus&Systems:

(PEARLStandard/NETAMTS1997Table10.1)

Max.Voltage MeggerSize Min.IR


RatingOf Value
Equipment

250Volts 500Volts 25M

600Volts 1,000Volts 100M

5KV 2,500Volts 1,000M

8KV 2,500Volts 2,000M

15KV 2,500Volts 5,000M

25KV 5,000Volts 20,000M

35KV 15,000Volts 100,000M

46KV 15,000Volts 100,000M

69KV 15,000Volts 100,000M

OneMegohmRuleforIRValueforEquipment:

Baseduponequipmentrating:
<1KV=1Mminimum
>1KV=1M/1KV

AsperIERules1956:

Atapressureof1000VappliedbetweeneachliveconductorandearthforaperiodofoneminutetheinsulationresistanceofHV
installationsshallbeatleast1MegaohmorasspeciedbytheBureauofIndianStandards.
MediumandLowVoltageInstallationsAtapressureof500Vappliedbetweeneachliveconductorandearthforaperiodofone
minute,theinsulationresistanceofmediumandlowvoltageinstallationsshallbeatleast1Megaohmorasspeciedbythe
BureauofIndianStandards]fromtimetotime.

AsperCBIPspecicationstheacceptablevaluesare2MegaohmsperKV

(2)IRValueforTransformer:

Insulationresistancetestsaremadetodetermineinsulationresistancefromindividualwindingstogroundorbetweenindividual
windings.Insulationresistancetestsarecommonlymeasureddirectlyinmegohmsormaybecalculatedfrommeasurementsof
appliedvoltageandleakagecurrent.
Therecommendedpracticeinmeasuringinsulationresistanceistoalwaysgroundthetank(andthecore).Shortcircuiteach
windingofthetransformeratthebushingterminals.Resistancemeasurementsarethenmadebetweeneachwindingandall
otherwindingsgrounded.
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 4/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
otherwindingsgrounded.

(hps://electricalnotes.les.wordpress.com/2012/03/1dcopy.png)

Windingsareneverleftoatingforinsulationresistancemeasurements.Solidlygroundedwindingmusthavetheground
removedinordertomeasuretheinsulationresistanceofthewindinggrounded.Ifthegroundcannotberemoved,asinthecase
ofsomewindingswithsolidlygroundedneutrals,theinsulationresistanceofthewindingcannotbemeasured.Treatitaspartof
thegroundedsectionofthecircuit.
Weneedtotestwindingtowindingandwindingtoground(E).Forthreephasetransformers,Weneedtotestwinding(
L1,L2,L3)withsubstituteEarthingforDeltatransformerorwinding(L1,L2,L3)withearthing(E)andneutral(N)forwye
transformers.

IRValueforTransformer

(Ref:AGuidetoTransformerMaintenanceby.JJ.Kelly.
S.DMyer)

Transformer Formula
1PhaseTransformer IRValue(M)=CXE/
(KVA)
3PhaseTransformer IRValue(M)=CXE(Pn)/
(Star) (KVA)
3PhaseTransformer IRValue(M)=CXE(PP)/
(Delta) (KVA)
WhereC=1.5forOillledT/CwithOilTank,30forOil
lledT/CwithoutOilTankorDryTypeT/C.
TemperaturecorrectionFactor(Base20C):

TemperaturecorrectionFactor

OC OF Correction
Factor

0 32 0.25

5 41 0.36

10 50 0.50

15 59 0.720

20 68 1.00

30 86 1.98

40 104 3.95

50 122 7.85

Example:For1600KVA,20KV/400V,ThreePhaseTransformer

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 0 5/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

IRValueatHVSide=(1.5x20000)/1600=16000/40=750Mat200C
IRValueatLVSide=(1.5x400)/1600=320/40=15Mat200C
IRValueat300C=15X1.98=29.7M

InsulationResistanceofTransformerCoil

Transformer Megger Min.IRValue Min.IR


Size LiquidFilled ValueDry
CoilVoltage T/C TypeT/C

0600V 1KV 100M 500M

600VTo5KV 2.5KV 1,000M 5,000M

5KVTo15KV 5KV 5,000M 25,000M

15KVTo69KV 5KV 10,000M 50,000M

IRValueofTransformers:

Voltage Test Test MinIR


Voltage Voltage Value
(DC)LV (DC)HV
side side
415V 500V 2.5KV 100M
Upto6.6KV 500V 2.5KV 200M
6.6KVto11KV 500V 2.5KV 400M
11KVto33KV 1000V 5KV 500M
33KVto66KV 1000V 5KV 600M
66KVto132KV 1000V 5KV 600M
132KVto 1000V 5KV 650M
220KV
StepsformeasuringtheIRofTransformer:

Shutdownthetransformeranddisconnectthejumpersandlightningarrestors.
Dischargethewindingcapacitance.
Thoroughlycleanallbushings
Shortcircuitthewindings.
Guardtheterminalstoeliminatesurfaceleakageoverterminalbushings.
Recordthetemperature.
Connectthetestleads(avoidjoints).
Applythetestvoltageandnotethereading.TheIR.Valueat60secondsafterapplicationofthetestvoltageisreferredtoasthe
InsulationResistanceofthetransformeratthetesttemperature.
ThetransformerNeutralbushingistobedisconnectedfromearthduringthetest.
AllLVsurgediverterearthconnectionsaretobedisconnectedduringthetest.
Duetotheinductivecharacteristicsoftransformers,theinsulationresistancereadingshallnotbetakenuntilthetestcurrent
stabilizes.
Avoidmeggeringwhenthetransformerisundervacuum.

TestConnectionsofTransformerforIRTest(NotLessthan200M):

Twowindingtransformer:

1.(HV+LV)GND
2.HV(LV+GND)
3.LV(HV+GND)

Threewindingtransformer:
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 6/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Threewindingtransformer:

1.HV(LV+TV+GND)
2.LV(HV+TV+GND)
3.(HV+LV+TV)GND
4.TV(HV+LV+GND)

Autotransformer(twowinding):

1.(HV+LV)GND

AutoTransformer(threewinding):

1.(HV+LV)(TV+GND)
2.(HV+LV+TV)GND
3.TV(HV+LV+GND)

Foranyinstallation,theinsulationresistancemeasuredshallnotbelessthan:

HVEarth200M
LVEarth100M
HVLV200M

FactorsaectingonIRvalueofTransformer

TheIRvalueoftransformersareinuencedby

surfaceconditionoftheterminalbushing
qualityofoil
qualityofwindinginsulation
temperatureofoil
durationofapplicationandvalueoftestvoltage

(3)IRValueforTapChanger:

IRbetweenHVandLVaswellaswindingstoearth.
MinimumIRvalueforTapchangeris1000ohmpervoltservicevoltage

(4)IRValueforElectricmotor:

Forelectricmotor,weusedainsulationtestertomeasuretheresistanceofmotorwindingwithearthing(E).

Forratedvoltagebelow1KV,measuredwitha500VDCMegger.
Forratedvoltageabove1KV,measuredwitha1000VDCMegger.
InaccordancewithIEEE43,clause9.3,thefollowingformulashouldbeapplied.
MinIRValue(ForRotatingMachine)=(Ratedvoltage(v)/1000)+1

(hps://electricalnotes.les.wordpress.com/2012/03/12.png)

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 7/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

AsperIEEE43Standard1974,2000

IRValueinM
IR(Min)=kV+1 Formostwindingsmadebefore
about1970,alleldwindings,and
othersnotdescribedbelow
IR(Min)=100M Formostdcarmatureandac
windingsbuiltafterabout1970
(formwoundcoils)
IR(Min)=5M Formostmachineswithrandom
woundstatorcoilsandform
woundcoilsratedbelow1kV
Example1:For11KV,ThreePhaseMotor.
IRValue=11+1=12MbutasperIEEE43Itshouldbe100M
Example2:For415V,ThreePhaseMotor
IRValue=0.415+1=1.41MbutasperIEEE43Itshouldbe5M.
AsperIS732MinIRValueofMotor=(20XVoltage(pp/(1000+2XKW))

IRValueofMotorasperNETAATS2007.Section7.15.1

MotorNamePlate Test MinIR


(V) Voltage Value
250V 500VDC 25M
600V 1000VDC 100M
1000V 1000VDC 100M
2500V 1000VDC 500M
5000V 2500VDC 1000M
8000V 2500VDC 2000M
15000V 2500VDC 5000M
25000V 5000VDC 20000M
34500V 15000VDC 100000M
IRValueofSubmersibleMotor:

IRValueofSubmersibleMotor

MotorOutoWell(Without IRValue
Cable)
NewMotor 20M
Ausedmotorwhichcanbe 10M
reinstalled
MotorInstalledinWell(With
Cable)
NewMotor 2M
Ausedmotorwhichcanbe 0.5M
reinstalled

(5)IRValueforElectricalcableandwiring:

Forinsulationtesting,weneedtodisconnectfrompanelorequipmentandkeepthemisolatedfrompowersupply.Thewiring
andcablesneedtotestforeachother(phasetophase)withaground(E)cable.TheInsulatedPowerCableEngineers
Association(IPCEA)providestheformulatodetermineminimuminsulationresistancevalues.

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 8/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

R=KxLog10(D/d)

R=IRValueinMsper1000feet(305meters)ofcable.
K=Insulationmaterialconstant.(VarnishedCambric=2460,ThermoplasticPolyethlene=50000,CompositePolyethylene=30000)
D=Outsidediameterofconductorinsulationforsingleconductorwireandcable
(D=d+2c+2bdiameterofsingleconductorcable)
dDiameterofconductor
cThicknessofconductorinsulation
bThicknessofjacketinsulation

HVtestonnewXLPEcable(AsperETSAStandard)

Application TestVoltage MinIR


Value
NewcablesSheath 1KVDC 100M
Newcables 10KVDC 1000M
Insulation
AfterrepairsSheath 1KVDC 10M
Afterrepairs 5KVDC 1000M
Insulation
11kVand33kVCablesbetweenCoresandEarth(AsperETSAStandard)

Application TestVoltage MinIR


Value
11KVNewcablesSheath 5KVDC 1000M
11KVAfterrepairs 5KVDC 100M
Sheath
33KVnoTFsconnected 5KVDC 1000M
33KVwithTFsconnected. 5KVDC 15M

(hps://electricalnotes.les.wordpress.com/2012/03/2copy.png)

IRValueMeasurement(Conductorstoconductor(CrossInsulation))

TherstconductorforwhichcrossinsulationisbeingmeasuredshallbeconnectedtoLineterminalofthemegger.The
remainingconductorsloopedtogether(withthehelpofcrocodileclips)i.e.Conductor2andonwards,areconnectedtoEarth
terminalofmegger.Conductorsattheotherendareleftfree.
Nowrotatethehandleofmeggerorpresspushbuonofmegger.ThereadingofmeterwillshowthecrossInsulationbetween
conductor1andrestoftheconductors.Insulationreadingshallberecorded.
NowconnectnextconductortoLineterminalofthemegger&connecttheremainingconductorstoearthterminalofthemegger
andtakemeasurements.

IRValueMeasurement(ConductortoEarthInsulation)

ConnectconductorundertesttotheLineterminalofthemegger.
Connectearthterminalofthemeggertotheearth.
Rotatethehandleofmeggerorpresspushbuonofmegger.Thereadingofmeterwillshowtheinsulationresistanceofthe
conductors.Insulationreadingshallberecordedafterapplyingthetestvoltageforaboutaminutetillasteadyreadingis
obtained.

IRValueMeasurements:
Ifduringperiodicaltesting,insulationresistanceofcableisfoundbetween5and1M/kmatburiedtemperature,thesubject
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 9/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Ifduringperiodicaltesting,insulationresistanceofcableisfoundbetween5and1M/kmatburiedtemperature,thesubject
cableshouldbeprogrammedforreplacement.
Ifinsulationresistanceofthecableisfoundbetween1000and100K/km,atburiedtemperature,thesubjectcableshouldbe
replacedurgentlywithinayear.
Iftheinsulationresistanceofthecableisfoundlessthan100kiloohm/km.,thesubjectcablemustbereplacedimmediatelyon
emergencybasis.

(6)IRValueforTransmission/DistributionLine:

Equipment. MeggerSize MinIRValue


S/S.Equipments 5KV 5000M
EHVLines. 5KV 10M
H.T.Lines. 1KV 5M
LT/ServiceLines. 0.5KV 5M

(7)IRValueforPanelBus:

IRValueforPanel=2xKVratingofthepanel.
Example,fora5KVpanel,theminimuminsulationis2x5=10M.

(8)IRValueforSubstationEquipment:

GenerallymeggeringValuesofSubstationEquipmentsare.

.TypicalIRValueofS/SEquipments

Equipment Megger IR
Size Value(Min)
(PhaseEarth) 5KV,10KV 1000M

CircuitBreaker (PhasePhase) 5KV,10KV 1000M

ControlCircuit 0.5KV 50M

(PriEarth) 5KV,10KV 1000M

CT/PT (SecPhase) 5KV,10KV 50M

ControlCircuit 0.5KV 50M

(PhaseEarth) 5KV,10KV 1000M

Isolator (PhasePhase) 5KV,10KV 1000M

ControlCircuit 0.5KV 50M

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 10/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

L.A (PhaseEarth) 5KV,10KV 1000M

Electrical (PhaseEarth)
0.5KV 50M
Motor

LTSwitchgear (PhaseEarth) 0.5KV 100M

LT (PhaseEarth)
0.5KV 100M
Transformer

IRValueofS/SEquipmentsAsperDEPStandard

IRValueat IRValueat
Equipment Meggering Commissioning Maintenance
Time(M) Time(M)

HVBus 200M 100M

Switchgear LVBus 20M 10M

LVwiring 5M 0.5M

Cable(min100 HV&LV (10XKV)/KM (KV)/KM


Meter)

Motor&Generator PhaseEarth 10(KV+1) 2(KV+1)

TransformerOil HV&LV 75M 30M


immersed

HV 100M 25M
TransformerDry
Type
LV 10M 2M

Fixed PhaseEarth 5K/Volt 1K/Volt


Equipments/Tools

Movable PhaseEarth 5M 1M
Equipments

Distribution PhaseEarth 5M 1M
Equipments

MainCircuit 2M/KV
CircuitBreaker
ControlCircuit 5M

D.CCircuit 40M
Earth

LTCircuit 50M
Relay Earth

LTD.CCircuit 40M

LTLT 70M

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 11/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

(9)IRValueforDomestic/IndustrialWiring:

Alowresistancebetweenphaseandneutralconductors,orfromliveconductorstoearth,willresultinaleakagecurrent.This
causedeteriorationoftheinsulation,aswellasinvolvingawasteofenergywhichwouldincreasetherunningcostsofthe
installation.
TheresistancebetweenPhasePhaseNeutralEarthmustneverbelessthan0.5MOhmsfortheusualsupplyvoltages.
Inadditiontotheleakagecurrentduetoinsulationresistance,thereisafurthercurrentleakageinthereactanceoftheinsulation,
becauseitactsasthedielectricofacapacitor.Thiscurrentdissipatesnoenergyandisnotharmful,butwewishtomeasurethe
resistanceoftheinsulation,soDCVoltageisusedtopreventreactancefrombeingincludedinthemeasurement.

1PhaseWiring:

TheIRtestbetweenPhaseNaturaltoearthmustbecarriedoutonthecompleteinstallationwiththemainswitcho,withphase
andneutralconnectedtogether,withlampsandotherequipmentdisconnected,butwithfusesin,circuitbreakersclosedandall
circuitswitchesclosed.
Wheretwowayswitchingiswired,onlyoneofthetwostripperwireswillbetested.Totesttheother,bothtwowayswitches
shouldbeoperatedandthesystemretested.Ifdesired,theinstallationcanbetestedasawhole,whenavalueofatleast0.5M
Ohmsshouldbeachieved.

(hps://electricalnotes.les.wordpress.com/2012/03/a.png)

3PhaseWiring:

Inthecaseofaverylargeinstallationwheretherearemanyearthpathsinparallel,thereadingwouldbeexpectedtobelower.If
thishappens,theinstallationshouldbesubdividedandretested,wheneachpartmustmeettheminimumrequirement.

(hps://electricalnotes.les.wordpress.com/2012/03/aa.png)

TheIRtestsmustbecarriedoutbetweenPhasePhaseNeutralEarthwithaminimumacceptablevalueforeachtestof0.5M
Ohms.

IRTestingforLowvoltage

circuitvoltage Testvoltage IR
Value(Min)
ExtraLowVoltage 250VDC 0.25M
Upto500Vexceptfor 500VDC 0.5M
above

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 12/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles

500VTo1KV 1000VDC 1.0M


MinIRValue=50M/NoofElectricaloutlet.(AllElectricalPointswithing&Plugs).

MinIRValue=100M/NoofElectricaloutlet.(AllElectricalPointswithouting&Plugs).

RequiredPrecautions:

Electronicequipmentlikeelectronicuorescentstarterswitches,touchswitches,dimmerswitches,powercontrollers,delay
timerscouldbedamagedbytheapplicationofthehightestvoltageshouldbedisconnected.
Capacitorsandindicatororpilotlampsmustbedisconnectedoraninaccuratetestreadingwillresult.
Whereanyequipmentisdisconnectedfortestingpurposes,itmustbesubjectedtoitsowninsulationtest,usingavoltagewhich
isnotlikelytoresultindamage.TheresultmustconformwiththatspeciedintheBritishStandardconcerned,orbeatleast0.5
MOhmsifthereisnoStandard.

Advertisements

29%

80%

FILEDUNDERUNCATEGORIZED

AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan14years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststondsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

152ResponsestoInsulationResistance(IR)Values

modupallisays:
March23,2012at10:16pm
OutstandingStu.ThanksForSharing..

Reply
Dejajacobsays:
March25,2014at1:01am
WHATARETHEGOODRESISTANCEVALUE?

Reply
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 13/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Reply
Jignesh.Parmarsays:
March25,2014at4:10pm
GOODmeans.ALLsuspectedvalueaccordingtoequipmentsarealreadygiven

maheshchanderguptasays:
June28,2015at3:50pm
iwishtocontactmrparmarbyemail

Reply
SIVANAIKsays:
July2,2015at4:07pm
Thanksforyourinformation

HowtomeasuretheIRvalueacrossthe(XLPE,1.1kVgrade)straightthroughjoint?

Regards,
SIVANAIK

Reply
MATHEWKKsays:
February12,2016at8:55am
Thanksforsharinginformationandknowledgeonthetopic.Theseinformationisusefultoeventechnicianlevelfor
understandingthetheoryoftestingusingMegger.Iliketounderstandtheinformationandknowledgethoroughly.
Thanksforthededicationexhibited.

vilasK.says:
April11,2012at8:30am
DearSirHatsO!!&manythanxforyourinvaluablecontributioninenrichingtheexperienceofElect.Engineers&making
themavailablethefabulousdataataglance..Plkeepposted.IfUcanthrowsomelightonselectionofMCB/MCCB&contactors
inrelationtotheirdicharacteristics.

Reply
Jignesh.Parmarsays:
April11,2012at2:19pm
YoucanndTypeofMCB/MCCBandCharofAlltypeofContactorfromELECTRICALNOTESpageofthisBlog

Reply
maheshchanderguptasays:
June28,2015at3:52pm
iwishtocontactmrj.parmarbyemail.plsendyouremailtome

varghesesays:
April15,2012at12:25pm
dearsirisagreatwork.thanks

coulduplsexplaintheeectsofriseintemperatureoninsulationresistanceoftransformer.

Reply
BarunMajumdersays:
May7,2012at10:48am
Dearsirmanymanythanksforsharingvaluablearticleofelectricalengineering.Iwanttoknowmoreaboutelectricaldesign
(Distribution,industrial&commercial)andprotectionsystemfromyourendpointtopoint.Ifyouhaveanybook/siteforthose
designpleaseletmeknowthename.
Iamworkingasadesignengineerbutiamnotenoughcondentaboutmydesignandprotectionsystem.iwantyourvaluable
assistanceinthiseld.

Thankingyou
Yoursfaithfully
BarunMajumder

Kolkata

Reply
kumereshanPSsays:
May13,2012at4:17am
Sir,
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 14/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Sir,
greatwork,iwanttoknowtheISstandardsforIRvalueofSubstationequipment

Withregards

Kumereshan

Reply
anandsays:
October5,2012at8:19am
thankforgoodinfrmabotelecyrhghc

Reply
TuuliaPalorantasays:
May29,2012at5:49am
Honestlyiamnotquitegoodonelectricthingandthisoneisverygoodformetostudysowellandlearnalotmanythanksfor
thisarticle.

Reply
keyursays:
June8,2012at2:53pm
Thanksforsharingyourvaluableexp.anditisveryhelpfulformebecauseIamdiplomaholderandIamworkingingulf
countryaselectricalsupervisorsoitisusefulformeand
Thanks
keyur

Reply
MANOHARsays:
June14,2012at5:20am
Dearsir

IneedcalculationformulaofIRValuesofanelectdrives

Reply
Madanmohansays:
June16,2012at5:50am
Wonderfulexplanation.Reallyverymuchusefuldocument.Thnakyouverymuch

Reply
satheshsays:
July9,2012at5:59pm
Verynicesir..Thanku..

Reply
rehansays:
July13,2012at9:58pm
goodinformation,thanksforyourtime.

Reply
custommilagrossays:
July15,2012at4:20pm
2thumbsup.

Reply
GurmeetSinghsays:
July20,2012at4:49am
Very2Thankssir

Reply
preetisays:
July25,2012at11:52am
thanks,verygoodinformation

Reply
osarenkhoenosaglorysays:
August11,2012at9:15am
thisisabsolutelynice.awellwriendocument.thanks.
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 15/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
thisisabsolutelynice.awellwriendocument.thanks.

Reply
Naveensays:
August12,2012at6:23am
ThankyouSir,muchappreciated

Reply
A.Hasasnsays:
August12,2012at2:15pm
DearSir;
Reallyyourthisarticleisveryveryimportantforelectricalrelatedpeople.Yourthiscontributionisexcellant.Alotofthankssir.
KindRegardrs

Reply
K.M.Pandeysays:
August18,2012at5:04am
RespectedSir.

ThisarticleveryimportantandusefulforallthosepersonwhoarerelatedwithElectricaleld.Thanksalotforsharingyour
knowledgewithallpeople.Reallyyouareniceandgentleman.
Withregards,
K.M.Pandey,

Reply
subodhkumarpandeysays:
August26,2012at1:20pm
veryveryimportantforelectricalengineers.
lotofthanks

Reply
ahmednawazsays:
September21,2012at3:40pm
Ch.AhmedNawaz

thankssirforgivingveryusefullinformation.

Reply
radhakishanpawarsays:
September30,2012at6:28am
thankssirihavenowordtoexplainhowmuchitisusefultostudent.
thanksagain

Reply
THAKORSANJAYsays:
October5,2012at1:17pm
IAMATESTINGENGINEER.THISINFO.ISVERYUSEFULFORME
VERYVERYTHANKSFORTHIS

Reply
VilasG.says:
October11,2012at11:01am
Thanks.valuablenoteforelectricalengineers.

Reply
SteveArreolasays:
October23,2012at8:44pm
Thankyoumuchfortakingthetimetosharethisinformation

Reply
Mr.JudyDianosays:
October31,2012at11:45am
Thankyousomuch,forsharingSir,IlearnedalotofyourlinkGODBLESS

Reply
arshadsays:
November30,2012at6:23pm
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 16/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
November30,2012at6:23pm
thanksforbeautifulnotes

Reply
JetPaliangayansays:
December3,2012at12:11pm
howtodoIRtestforsinglecorepvc/xlpe/pvccables

Reply
jamestryresays:
December12,2012at2:49am
greatinfo,thx

Reply
Thiyagasays:
December19,2012at10:41am
Incrediblework.Hatsoforyourawesomearticles.plkeeppostingmoreandmore

Reply
sambasivaraochagantipatisays:
December25,2012at7:46pm
Veryusefulinformation

Reply
rohtashverma(Himachalpradesh)says:
December29,2012at2:02am
ThanksparmarjiveryusefullinformationregardingIRvalueofelectricmotors

Reply
M.Zamansays:
January8,2013at10:56am
thanksforvaluableinformation.

Reply
FELIXJr.says:
January10,2013at7:44am
Please,youmustalsoincludeherethePolarizationIndex(PI)aswellforitssignicanceandexplainwhyitisrequiredwith
respecttotheIRtestbeingdoneontheelectricalequipmentandtheelectricalcablesandinstallations,asanadditional
informationforthenewcommissioningengineersandenthusiasts.Supressingothercommentsarenotatallinterestingand
helpfull.

Reply
Jignesh.Parmarsays:
January10,2013at2:38pm
YesYouarerightPIvalueisasimportantasIRValuespeciallyHVEquipments.
HereIgaveonlyOverviewofIRTestinganditsvalue.
Torisecommentistotallydependuponthereader.
InnearfutureIwilldenitelycovertheTopicofPI.

Reply
deepakparmarsays:
June6,2013at12:18pm
IwanttoknowtheacceptableleakagecurrentvaluesintheHVtestingasperIECstandards.

Andthanksfortheinfoprovidedabove

sateeshsays:
January21,2013at11:18am
excellentexplanationaboutIRtest
thanksalot.

Reply
vincentsays:
February4,2013at7:23pm
Goodknowledge.thankyou.

Reply
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 17/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Reply
Andersonsays:
February6,2013at5:41pm
Excelentetrabajo,quierosabercualessonlasnormasquerigenestaspruebasysiexistealgunaestandarizacinderesultados.
Gracias

Reply
DebraScriversays:
February11,2013at10:53pm
Thanksforsuchagreatarticle.Veryinterestingandinformative.ThanksBuddy

Reply
Digantaku.Raysays:
February23,2013at3:12pm
Thankyousomuchsir,thishelpmealotinmyeld.itsveryveryusefulforthoseareinelectricalline.

Reply
JAYESHPATELsays:
February28,2013at4:57am
howmanyInsulationResistanceoftheWholeInstallationpermissible?
howmanyInsulationResistanceBetweenConductors?
howmanyInsulationResistanceBetweenEachConductor&Earth?

Reply
honestforexsignalssays:
March4,2013at5:26am
Helloveryniceblog!!Man..Excellent..Amazing..Iwillbookmarkyourwebsiteandtakethefeedsadditionally?

Iamgladtondnumeroushelpfulinfohereintheputup,wewantworkoutmorestrategiesonthisregard,thankyoufor
sharing.

.....

Reply
fayyazsays:
March10,2013at10:12pm
thksgoodinformationcanyoumailmehowtocheckinsulationofdc24voltsystem.
alsoiwanttoknowhowinsulationmonitorworks.

Reply
khanwasimsays:
March11,2013at5:01pm
Thanksalot

Reply
sonukumarsays:
March14,2013at2:40pm
thanksforthisvalueabledata.

Reply
AshokOKaleKalesays:
March21,2013at12:05pm
Thanx.

Reply
DEBASHISHBHATTACHARYAsays:
April2,2013at5:10pm
Excellentinformation.Reallyappreciatetheknowledgeyouhavesharedwithreaders.
SircanyouplstellmewhatshouldbeminimumvalueofIRforPVCmakebusbootusedfor11KV,22KV,33KVand66KV.

Regards
DebashishBhaacharya

Reply
Geraldsays:
April3,2013at10:50am
Thanksforsharing
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 18/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Thanksforsharing

Reply
CPRvialsays:
May1,2013at12:46pm
excellentarticle.
theformulaforinsulationresistanceofacableper1000ft.
howtocalculateitpermeterorperfeet.
plexplain

Reply
jigyeshsharmasays:
May8,2013at1:49am
whatprecautionsishouldtakewhenCTisconnectedinHTboardandihavedomegger.?

Reply
ibnusays:
May11,2013at2:53am
lightningcableforcranethereare2pointearthterminal,eachhasindividualgroundcable,imeggar1kVbothcable,gives
dierentreading200Mohm&almostinnityforanotherone.why?canacceptthevalue?

Reply
ibnusays:
May11,2013at2:57am
can11kvcable,meggarat1kvonly,duringbefore&afterhipottest?(hipotat30.5kv)

Reply
parveenkumarsays:
May11,2013at2:33pm
dearsiriwanttoknowwhyusedintransformersecondarysideverythinwire

Reply
FELIXJr.says:
May12,2013at4:57am
Yes,youcanuse1kVDCMEGGERTESTERpriortoHIPOTTestingifyourelectricalcableisrated11kVandHIGHERandifit
has130%ratedinsulation.AfterHIPOTtest,ifsuccessful,youcanmeggeritagainwith1kVonlyatnomorethan1minutejust
tomakesurenodamagehasoccurredduringandafterHIPOTTEST.

ByFMSJr./AbuDhabi,UAE

Reply
NasurudheenKamalBashasays:
May13,2013at9:22am
Usefulstu..Thanksforsharing!!

Reply
MOHAMMADsays:
June17,2013at11:02am
THANKSALOTVERYGREATFULINFO

Reply
PushkarSinghsays:
June23,2013at11:12am
Thanksforsharingexcellentinformation.
PushkarSinghONGC

Reply
AVNPhanindrasays:
July4,2013at7:01am
thankusomuchsiritsverybriefandsimpletounderstandclearly.

Reply
ASMAsays:
July20,2013at10:16am

WHATWOULDBETHEMEGGARREULTOFAGOODCONDITION25KVATRANSFORMER?
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 19/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
WHATWOULDBETHEMEGGARREULTOFAGOODCONDITION25KVATRANSFORMER?
IWILLBEOBLIGED..KINDLYHELPME.

Reply
FELIXJr.says:
July21,2013at5:29am
GOODDAY!YourpostedquestionabouttheMEGGERresultforagoodconditionfor25kVATransformerisverygeneralas
youdidnotspecifytheinputandoutputvoltagesofthiselectricalequipmentandifitisoilimmersedordrytype.Atanyrate,
assumingitsoillledstepuptransformer,outdoorpolemounted,foragoodIRresultforprimarywinding,normallyit
shouldnotbelessthan500MegaohmandthesecondarywindingsIRreadingshouldbenotlessthan300Megaohmwith
respecttoearthandhigherbetweenwindings.Again,theseareassumptionsonlyandthehigherthevoltageratingofthe
transformerthehigherIRreadingshouldresult.DefectiveinsulationswillreadlowvaluesofIRreadingsandcontaminated
oilinsulation,foroilimmersedtypetransformers.FordrytypeTransfomers,thegoodIRreadingsofthewindingsarealsoin
thatvicinitybutlowerthanoilimmersedtype.

Reply
J.RBohrasays:
July20,2013at11:48pm
veryveryhelpful
Thanks
J,RBohra
UniqueEngineerNoida

Reply
DiptiranjanNayaksays:
July23,2013at5:10am
Thankusir,
IamclearaboutIRvalue.

Reply
raghavsays:
July26,2013at4:37am
dearsir,
ineedmoreinformationabouthowtocalculateirvaluesandwhatprincipleitrequirestocalculateirvalues?

Reply
Musasays:
August22,2013at3:25am
Anybodycananswermyquery?

Wehave25kVACsystemforOverheadLineEquipment(OHE).ThissystemisinstalledforElectriedTrainsystem(Railway
project).

WehaveconductIRtestingbeforechargingthelinesforeachelectricalsubsection(thelongestsectionabout20km).Theresultwe
achieved0.5MOhm5MOhm(takenduringnighttime)and200MOhm700MOhm(takenduringnighttime).Thetemperature
duringnighttimeisaround2728degreeCelsius(inMalaysia).

Weinjectingmeggersize5kVandresultachievedasabove.Asmentionedinthearticle(ithinkitissimilartooursystemIR
valuefortransmission/distributionline)whichisstatedMin.IRvaluesshallbe10MOhm.

Isittheresultweachievedokay,especiallytheresulttakenduringnighttime?

Reply
sampathsays:
September3,2013at6:28am
thankformoreinformationnowiharrytocheckinsulationresistancelong132Kvtransmissionline&willhavecalledyouafter
testing

Reply
SYAMsays:
September4,2013at9:00am
DearJignesh,

JustforcuriositycanyoupleasetellmewhatisthefullformofDEPstandardswhichyouhavementionedunderthesection
IRValueofS/SEquipmentsAsperDEPStandard.

Hopeyouwillreply
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 20/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Hopeyouwillreply

Regards

SYAM

Reply
SekarRamsays:
September12,2013at12:58pm
MrJignesh
ThisisoneofthegreatestselesseortsIhaveseen.Thisispuresocialservice.Hatso!!

Reply
Stephensays:
September13,2013at1:46pm
Hello.Question,ifwehave5conductorsperphaseonalugsandwewanttomeggerthegroups,ie:phasetophaseandphaseto
groundandthereadingsareabove1Mohm,isthatOK?Wehadpreviouslymeggeredallthecabelsindividuallypriorto
installing.Thejobwasshutdownforawhile,andthisisforaprecaution,priortoreenergizing.

Reply
vijaysays:
September25,2013at11:39am
dearjigneshsir,

Canihavetheentirenotesinsiteinformofbook?Howmuchdoesitcost?

Reply
vijayendraraokvsays:
November2,2013at10:48am
veryveryusefulandverythanksformademedoubtclear..

Reply
Michelsays:
November29,2013at10:49am
thanksBrothatistoogooooooooooooooodforus

Reply
ESAKKIPANDIsays:
December5,2013at5:16am
theexplanationisexcellent

Reply
rahuljangmesays:
January5,2014at2:41pm
thankyousir

Reply
alisays:
January12,2014at1:18pm
thankyousomuchDr

Reply
DomaHudusays:
February8,2014at2:26pm
thanksir.Ineedacopyviamyemail.pleaseamwaitforyourresponseSir.

Reply
Srinivasansays:
February12,2014at3:40am
Thankyousir.Usefuldetailinformation.

Reply
abysays:
February20,2014at10:17am

Sir,
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 21/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Sir,
appreciateyourideasandprocedures.
Mayiknow,whetherthereisanynecessityormandatoryrulessayingthatthespeakercablestobemeggered?
ifyes,thenwhatshouldbetheappliedvoltage?

Reply
roopsays:
February23,2014at6:17am
dearmrParmarrstofallthanksforsharingtheinformation

Reply
roopsays:
February23,2014at6:22am
wearebuildinga9kmroadtunnel,weusuallyfacingproblemwithhtcable,wheneveritisdamagedittook3to4hourfor
jointing,lotofproductionlosspleaseadviseanyalternatemeansoftransmissionofhtcableoranyhtjointavailablearoundthe
worldtodothejointingquickly.

Reply
FelixJrSanBuenaventurasays:
March26,2014at4:44am
THESEAREGOODINFORMATIONANDREFERENCEFORALLELECTRICALENGINEERSANDCOMMISSIONING
ENGINEERSBEITINDESIGNENGINEERINGORINCOMMISSIONINGWORKSOFPROJECTSRELATEDTOELECTRICAL
POWERGENERATION,TRANSMISSIONANDINDISTRIBUTIONSYSTEMSTHEWORLDOVER.TIKE!,SALAMATPO!,
GRACIAS!,QZIQZI!,TERIMAKASIH!

Reply
SBsays:
March27,2014at7:26am
Thankyoueversomuch!Forsharingsuchgoodinfo,extremelyrelevant.

Reply
rdsays:
June14,2014at8:28am
Whatistheminimumacceptableinsulationresistancefor1.8kvDCcables?temperatureisaround50degC.Myunderstanding
isthatIRdecreaseswhenthereisincreaseintemperature.SohowdoicalculateInsulationresistanceconsideringthe
temperature?

Reply
jakesays:
July30,2014at6:29am
whatcanweexpectfortransformerbeingenergizenotmeetingtheminimumstandardforinsulationresistance?thefutureeect
ofit?

Reply
golfziimosays:
August4,2014at12:38pm
thankyouforgoodinformation

Reply
AenBalisays:
August14,2014at6:36am
PlztellmeCTPTvalueinHT&LTsideproperload

50Hp

Reply
reshisays:
August28,2014at12:50pm
Dearsir,
wehavehaywardtyler480V,60HZ,100HPsubmersiblepumpmotorinoutfacilityusedforboilerwatercirculation.Thedemin
waterisusedforthestatorcoolingintheclosedloopmeanswaterisdirectlyenteringthestatorwinding.

Themotorwassendtoworkshopformechanicalrepair.AfterinstallingbackTheI.Rvalueis0.3MOhm,canwetestthemotor
andrunit.

ForyoursuggestionThanksinanticipation.
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 22/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
ForyoursuggestionThanksinanticipation.

Reply
praneethsays:
September4,2014at3:34pm
thankUforthepost,veryhelpful
veryfewpeoplesharetheirknowledge.
hatso.

Reply
AbdulHameedsays:
September18,2014at6:36am
goodinformation.appreciateitverymuch.thankstoall

Reply
nacykoesays:
September25,2014at11:17am
IRinstrumentfromIECorIEEEstandard?

Reply
Jagadishsays:
October1,2014at3:31am
WhatshouldbetheminimumvalueofInsulationresistanceforLowVoltageSwitchgearpanels?

Reply
VVGsays:
October12,2014at6:01am
DearSir
InouroneoftheapplicationsweneedtochecktheHighVoltagetestinourproduct,(Automotivepart).wherecustomerisasking
asktochecktheHVtestwith1.5KV

Aspercustomerdemand,nowweneedtomakeaHVinstrumenttodetectthecurrentleakagewhenapplyinhHighvolt(1.5KV)
betweentwoterminals.(opencircuit)
Customerrequirementisthatwhenthedistancebetweentheterminalsifitislessthan1.2mmourinstrumentmustdetectit.
Nowwearefacingtheproblemashowtoderivetheresistancebetweentwoterminals(inair)whenweapplyinghighvolt.Kindly
helpus

Regards
VVG

Reply
diptisays:
October27,2014at2:01pm
verygoodstu,sousefull

Reply
nikeshsrstsays:
December5,2014at3:03am
thanksforhelpus.towriteaboutits

Reply
Samsays:
December10,2014at1:47am
HelloJigneshParmar,

Manythanksforyouraboveusefularticle.

Ihaveaquickquestionandwillappreciateitifyoucanhelpmetondtheanswerplease.ItisaboutIRValueforElectrical11kV
and22kVcableswithXLPEinsulation.AsfarasIknow,thereisaminvalueforIRinambienttemperature,butmyquestionis:
isthereanyhighlimitforthisvalueinambienttemperature?

IamaskingthisquestionbecauseIhavegotatestresultfromafactorywithveryveryhighvaluesmorethanusualforIRin
ambienttemperature.

Thanksandlookingforwardtoreceiveyouranswer.
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 23/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Thanksandlookingforwardtoreceiveyouranswer.
Regards;
Sam

Reply
ashishsays:
December29,2014at6:50pm
132/33kvtransformertheLVresistanceis.02perunitresistancereferredtoHV

Reply
himanshupatelsays:
January5,2015at2:39am
suchaknowledgeablethingaboutourworkforreferencetointroduceusinsmartwork

Reply
Asifsays:
January5,2015at8:05am
Dearall,

AquestionisthatwhatistheIRacceptancecriteriaforbusbarswhichareinstalledinMCCpanels?

Reply
K.Raghuveersays:
January7,2015at4:32pm
Dearsir,

Thanksfortheinformation,

K.Raghuveer

Reply
kushrusays:
January17,2015at8:49am
Iwouldliketoknowifawireratedfor1100vaccanwithstandabreakdownvoltageof4kv

Reply
karanjanisays:
January24,2015at9:31am
sirThankyouforsharingyourKnowledgeijusthaveonequeryrelatedtotheH.vCabletest.IsismandatorytohavePITeston
H.vCablesalongwiththeIrvalue?

Reply
AkhtarKsays:
January24,2015at11:07am
Hii;

VeryniceandgoodinformationofelectricalIR.

Thanksforsharingtheallnecessarytechnicalinformation.

Withallrespect;
AkhtarKhatib

Reply
SujeetDubeysays:
April14,2015at6:47am
ThanksSir
Itsverycomplicatedshare.

Reply
lalitKaliharisays:
April16,2015at3:08pm
HelloMr.JigneshParmar,

PleaseletmeknowthedocumentaryevidenceofacceptableIRlimitsreferingtoIEC61439standard.

Thanks&Regards,
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 24/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Thanks&Regards,
LalitKK

Reply
Owaissays:
April30,2015at8:30am
PleasegiveIRvalueinformationofCoreEarth,FrameEarth,CoreFrame.Alsogivetheircorrectionfactoraspertemperature.
AlsopleaseindicatewhethertheTemperaturedierenceisofInsulationorAmbient.

Reply
E.Eng.Ghanimsays:
May5,2015at5:21am
Iwanttoknowthevaluemeasurementsofresistanceformotoritiscapacityis1MW&theappliedvoltageis600VbecauseIhave
arewindingmotorandIwanttocomparingtheresultswithslanderedvalues

Reply
NAEEMsays:
May9,2015at12:03pm
dearwhatshouldbetheminimuminsulationResistance(IR)ofACGeneratorinaccordancetoIECstandardsbothatthetimeof
CommissioningandatthetimeofMaintenance

Reply
govindarajangssays:
May28,2015at11:05am
veryvaluablewriteupwithlotofexperiencebehindit

Reply
jangchuSinhgyesays:
June5,2015at7:43am
SirwhatistheminimummeggervalueofIRfor120kNdiscinsulator?

Reply
Ksalvisays:
June7,2015at4:50am
CanwedomeggeringofPowercablesinSandstorm.Ifnotthenwhy??

Reply
mahalingamsays:
June18,2015at7:28pm
verythankyousir,veryusefulmycarrier

Reply
EMMANUELMANTEAWsays:
June24,2015at7:45pm
ihaveachallengewithmymegger.Idisconnectedthecablestobemeggered.andsetmytestvoltageto500V.Butwhenistart
mytestigetmytestvoltagedecreasing.andeventuallyanIRreadinginKiloohmswhilstmyexpectedvalueisatleast1
GigaOhm.kindlyadvice.Thanks

Reply
pradeepsays:
June30,2015at7:42am
whatisthedierencebetweeninsulationresistanceandPItest

Reply
PLJsays:
July1,2015at1:51am
Veryusefuldocument.Thankyou

Reply
zensays:
July7,2015at8:53am
notmeggershouldbeinsulationresistancemeter

Reply
S.G.Jayakumarsays:

July11,2015at10:07am
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 25/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
July11,2015at10:07am
whicttypeofwiresareusedtoIRtest.PVC,PUR,Teoninsulationwires.PleasesendthereplyIamstruuglingtheoneproject

Reply
PhuTaQuocsays:
July13,2015at3:43am
Ok,Thankyouverymuch.

Reply
kesarinathullengalsays:
July16,2015at5:46pm
Yourinformationregardingalltthetestisverymuchusefull.Isthereanyappforthisforandriodsoitwllhelptoeasyviewand
information.Thanksonceagain
Regards
kesariullengal

Reply
RajKumarsays:
August12,2015at4:40am
Thanksforsuchvaluabledatashared.

Reply
RonalManuelsays:
November9,2015at5:59am
Doesanyoneknowhowtocomputetheminimumrecommendedvalueforbusbars.letssayfromgeneratortotransformer.

Reply
Rajashekar.Vsays:
November27,2015at5:44am
HelloJigneshParmar,

Manythanksforyouraboveusefularticle.

Ihaveaquickquestionandwillappreciateitifyoucanhelpmetondtheanswerplease.Itisaboutmeggerinstrumentwhich
haveing(analoginstrumentwithhandgenerater)theanalogreadingneedelintherightandmovestoleftbutinallthe
instrumentsitwillinlefttorightWhy?

Thanksandlookingforwardtoreceiveyouranswer.
Regards;
Rajashekar

Reply
rajsays:
December31,2015at11:37am
thankyousomuch

Reply
arifsays:
January26,2016at11:47pm
Dearsir
whatistheminimuminsulationresistancevalueisacceptablefor415voltLVcable

Reply
ghanimyousifsays:
February7,2016at6:13am
DearSirTheminimuminsulationresistancevalueacceptancefor415Vshouldbeatleast1KV&notmorethan2KVBR
Ghanim

OnThu,Feb4,2016at4:04PM,ElectricalNotes&Articleswrote:

>arifcommented:Dearsirwhatistheminimuminsulationresistancevalue>isacceptablefor415voltLVcable>

Reply
Nitinvishwakarmasays:
February19,2016at5:02am
thankyousirvaryinformation.
Reply
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 26/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Reply
bharatsays:
March11,2016at7:04am
explanationgood

Reply
KiranUfadesays:
March24,2016at11:11am
usefulinformationsirthanks

Reply
SaurabhGuptasays:
March29,2016at12:04pm
IwanttoknowIRvaluefor160KN&210KNCompositePolymerLongRodInsulatorsusinginTransmissionlinetower

Reply
SaurabhGuptasays:
March29,2016at12:07pm
JigneshSir,IwanttoknowIRvaluesof160KNand210KNcompositepolymerlongrodinsulators,whichweareusingnowa
daysinsteadofPorcelaintypes.
Please!

Reply
ajojacobsays:
April9,2016at8:42am
whatistheIRacceptancecriteriaforLVtoearthintransformer

Reply
Magdysourorsays:
April20,2016at9:35am
veryusefulinformation.
Thanksfortheeortdone

Reply
AsifNazirsays:
May16,2016at10:01am
Greatwork

Reply
ZaineBintiAbdulKarimsays:
May25,2016at2:26am
HiMr.JigneshParmar,thankyouforyourtechnicalwriteupitisveryuseful.However,Iwouldliketoaskwhatisthe
recommendedIRvalueforaFuelGasSuperheaters(poweredfrom400VAC,loadis550kW).HeatersIRisnotcoveredinyour
article,canyouassistmeonthis,becausewedohavesomeissueswithourpresentinstallation.

Fortherestofreaders,kindlychipintooifyouguysknowtheanswertomyquestionabove.Thankyouall.

Reply
AmilaDeSilvasays:
May25,2016at3:10pm
Hi,oneofourdrainagepumpinstalledinadrywellcaughttoood.nowwhenwemeggeritincludingthecable(nowthewell
isdry)itshowszero.whatcanbethereason.

Pleaseadvise

Reply
Rajapandiyarsays:
June11,2016at6:12pm
Gooddetailsforus

Reply
ManishGuptasays:
June16,2016at8:52am
Hi,whatisthehipottestvoltagefor24VDCeldwirelinetosecondaryside(forandigitalIOcard)usedinPLCproduct.I
believeitis500Vrmsor707VDC,canyoupleaseconrm.

Reply
https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 27/28
3/28/2017 InsulationResistance(IR)Values|ElectricalNotes&Articles
Reply
sreedevisays:
June17,2016at10:09am
HowmuchdcvoltagehastobeappliedinmeggerformeasuringIRin4paircableharness

Reply
YEEGUOQUANsays:
June21,2016at4:22am
IveseenotherppldoingmeggertestwheretheyshortL1,L2,L3,NtoEandgettheohmvalue.
Isthisthecorrectmethod?ifsohowdoesitwork?mindtoshare?TQ

WarmestRegards,

DannyYee

Reply
TusharMahajansays:
June22,2016at2:16pm
Good

Reply
NileshAmreliasays:
July15,2016at4:59am
Interestinginformationshared.Thanks

Reply
Amansays:
July19,2016at4:10pm
howmanyIrValueof120&210kninsulator

Reply
Martinsays:
July20,2016at7:34am
DearParmar..

ThanksfortheUsefullPost..

ItsveryHelpfullfortheBeginnerleveloftheMeggerTester

KeepitUp

Reply
IECsays:
August6,2016at7:13am
ieccodeonline.comprovideeasywaytogetIECwithin3to7workingdays.ifyouarelookingiecconsultantinIndia,Pleasecall
ustoday+919540195222

Reply
GauravShahsays:
August20,2016at3:41am
ThanksJigneshbhai

Reply
GaneshNamasays:
September6,2016at2:16am
dearsir,thisinformationisveryusefullforuspeople,aboutbasicknowledge.

thankyouverymuch.

Reply

https://electricalnotes.wordpress.com/2012/03/23/insulationresistanceirvalues/ 28/28

Potrebbero piacerti anche