Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
electric
shower
Installation and
operating
instructions
Installers please note these instructions are to be left with the user
CONTENTS Page
Spare parts 24 25
Fault finding 26 27
Guarantee, service policy, etc. rear cover
To check the product suitability for commercial and multiple installations, please contact
Tritons specification advisory service before installation.
Telephone: 0870 067 3767
0870 067 3334
Facsimile:
technical@tritonshowers.co.uk
E mail:
ii
Opal
Opal
Opal
9. Solenoid valve
8 5
10. Guide pockets
11. Can and element assembly
12. Thermal cut-out (main) 9 Inlet
Pack contents
Shower unit 17
Five position showerhead
Riser rail kit and fittings
Soap dish
Flexible hose
Screw fixing kit
Instructions, guarantee, etc.
16
Opal
Table A
Shower
RCD unit
(can be part of Circuit protection
consumer unit)
unit cartridge
rating mcb fuse
Opal
parts of other appliances and services the cord of a cord operated switch, and
in the room in which the shower is to should be placed so that it is not possible
be installed, to conform to current IEE to touch the switch body while standing
regulations. in a bath or shower cubicle. It should be
5.1 All exposed metallic parts in the bathroom readily accessible to switch off after using
must be bonded together using a cable of the shower.
at least 4mm cross sectional area. These 8 Where shower cubicles are located in any
parts include metal baths, radiators, water rooms other than bathrooms, all socket
pipes, taps and waste fittings. outlets in those rooms must be protected
6 For close circuit protection do not use by a 30mA RCD.
a rewireable fuse. Instead use a suitably 9 The current carrying capacity of the cable
rated miniature circuit breaker (MCB) or must be at least that of the shower circuit
cartridge fuse (see table A). protection (see table B).
6.1 In the interest of electrical safety a 30mA 9.1 To obtain full advantage of the power
residual current device (RCD) should be provided by the shower, use the shortest
installed in all UK electric and pumped cable route possible from the consumer
shower circuits. This may be part of the unit to the shower.
consumer unit or a separate unit. 9.2 It is also necessary to satisfy the
7 A 45 amp double pole isolating switch disconnection time and thermal
with a minimum contact gap of 3mm in constraints which means that for any given
both poles must be incorporated in the combination of current demand, voltage
circuit. drop and cable size, there is a maximum
7.1 It must have a mechanical indicator permissible circuit length.
showing when the switch is in the 10 The shower circuit should be separated
OFF position, and the wiring must be from other circuits by at least twice the
connected to the switch without the use of diameter of the cable or conduit.
a plug or socket outlet. 10.1 The current rating will be reduced if the
7.2 The switch must be accessible and clearly cabling is bunched with others, surrounded
identifiable, but out of reach of a person by thermal loft or wall insulation or placed
using a fixed bath or shower, except for in areas where the ambient temperature
is above 30C. Under these conditions,
Table B derating factors apply and it is necessary to
select a larger cable size.
Twin and earth PVC insulated cable
10.2 In the majority of installations, the
current carrying capacity cable will unavoidably be placed in one
clipped direct or or more of the above conditions. This
installed in an in conduit buried in a non being so, it is strongly recommended
insulated wall or trunking insulated wall to use a minimum of 10mm cabling
6mm 6mm 6mm throughout the shower installation.
32A 38A 46A 10.3 In any event, it is essential that individual
10mm 10mm 10mm site conditions are assessed by a competent
43A 52A 63A electrician in order to determine the
correct cable size and permissible circuit
16mm 16mm 16mm
57A length.
69A 85A
Opal
Opal
Opal
Warning!
Check there are no hidden cables or
pipes before drilling holes for wall
plugs. Use great care when using
power tools near water. The use of
a residual current device (RCD) is
recommended.
Opal
20mm
Fig.12
Opal
PLUMBING CONNECTIONS
Warning! Plumbing to be carried out before wiring
The outlet of the shower acts as a Do not use jointing compounds on any pipe
vent and must not be connected to fittings for the installation.
anything other than the hose and Do not solder fittings near the shower unit as
showerhead supplied. heat can transfer along the pipework and may
damage components.
Compression fittings must be used to connect
to the inlet of the shower. (Push-on fittings must
not be used as full engagement cannot be
guaranteed).
Note: An additional service valve (complying
with Water Regulations) must be fitted in
the mains water supply to the shower as an
independent means of isolating the water supply
should maintenance or servicing be necessary.
Important: Before completing the
connection of the water supply to the inlet
of the shower, flush out the pipework to
remove all swarf and system debris. This can
be achieved by connecting a hose to the
pipework and turning on the mains water
supply long enough to clear the debris to
waste.
Procedure
Turn off water supply either at the mains stop
valve or the isolating service valve. Connect the
mains water supply to the inlet of the shower
via 15mm copper, stainless steel or plastic pipe
using a 15mm x 15mm elbow compression
fitting.
Do not use excessive force when making these
connections.
Make sure the backplate is square on the wall
and tighten the two retaining screws which hold
it to the wall.
Turn on the mains water supply and check for
leaks in the pipework connection to the shower.
IMPORTANT: Using a suitable sealant, always
seal around the incoming pipework to
prevent water entering the wall.
Note: At this stage no water can flow through
the unit.
10
Opal
ELECTRICAL CONNECTIONS
Fig.13
Switch off the electricity supply at
the mains. L
1
Fig.13 shows a schematic wiring diagram.
N
The cable entry points are shown in fig.1. The 6
E 2
cable can be surface clipped, hidden or via
4
20mm conduit.
Note: Conduit entry can only be from rear.
3
Route the cable into the shower unit and
connect to the terminal block (fig.14) as 8
follows:
11
Opal
Commissioning
Fig.15
WARNING!
Before normal operation of the
shower, it is essential the following
Valve commissioning procedure is
spindle
completed correctly.
12
Opal
13
Opal
REPLACING THECOVER
Fig.20
Important: Before finally fitting the cover,
the following steps must be taken:
a. Check plumbing connections are
Valve watertight.
spindle
b. Check terminal block screws are fully
tightened.
c. Make sure the pipe and cable entering
the unit do not prevent the cover locating
correctly to the backplate.
d. Rotate the valve spindle fully clockwise
until the arm hits the stop (fig.20).
Fig.21 e. Turn the temperature control on the cover
to position 10 (fig.21).
Offer the cover to the unit.
Carefully locate the cover tags into the guide
pockets on the backplate and make sure the
wires are not trapped.
Guide the cover into position so that the knob
spindle locates correctly (minor adjustment may
be necessary to align the knob and spindle).
Should any difficulty arise, recheck the points
above.
While applying slight pressure to the front
cover, secure in position with the three retaining
screws.
Turn the electric supply back on at the isolating
switch. The POWER indicator will light. No
water will flow until one of the three buttons are
pressed.
Note: It is recommended that the water and
electric supplies to the shower are turned off
while the riser rail kit is being installed.
The flexible hose can be left attached to the
shower outlet. Make sure the supplied sealing
washer is fitted.
14
Opal
15
Opal
16
Opal
OPERATING FUNCTIONS
WARNING!
Power on indicator (fig.23)
After any servicing of mains water
When the electricity supply to the shower is
switched on at the isolating switch, the power supply, always make sure the unit is
indicator will light. started on COLD in order to purge
any air in the pipework.
Low pressure indicator (fig.23)
If this indicator lights, this means the water
pressure has fallen below the minimum required Fig.23
for correct operation of the shower, resulting in
the low pressure cut-out operating. This switches
off power to the heating elements preventing
any undue temperature rises (water will continue
to flow). Power will automatically be restored
when adequate water pressure returns.
Temperature limiter
During normal operation if an overheat
temperature is sensed, power to the elements
will be reduced. Water will continue to flow.
When the temperature has cooled sufficiently,
power to the elements will be automatically
restored to the previous setting at the time of
interruption.
Safety cut-out
The unit is fitted with a non-resettable
thermal cut-out safety device. In the event of
abnormal operation which could cause unsafe
temperatures within the unit, the device will
disconnect the heating elements. It will require a
visit from a qualified engineer to determine the
nature of the fault and replace the safety device,
once the unit has been repaired.
17
Opal
18
Opal
Showerhead
Holder
19
Opal
Fig.35
20
Opal
CLEANING
Fig.36 Fig.37
WARNING!
Do not use powerful abrasive or
solvent cleaning fluids when cleaning
the shower as they may damage the
plastic fittings.
21
Opal
22
Opal
23
Opal
Spare parts
10
24
Opal
Spare parts
16
17
18
25
Opal
Fault Finding
IMPORTANT: Switch off the electricity at the mains supply and remove the circuit fuse before
attempting any fault finding inside the unit.
Problem/Symptom Cause Action/Cure
1 Shower 1.1 Interrupted power 1.1.1 Blown fuse or circuit breaker. Check
inoperable, no water supply. supply. Renew or reset fuse or circuit breaker. If
flow. it fails again, consult a qualified electrician.
1.1.2 Power cut? Check other appliances and if
necessary, contact local Electricity Supply Co.
1.2 Unit malfunction. 1.2.1 Have unit checked. Ring Customer
Service.
2 Water too hot. 2.1 Not enough water 2.1.1 Increase the flow rate via temperature
flowing through the control.
shower. 2.1.2 Blocked showerhead clean blocked
sprayplate.
2.2 Blockage in supply. 2.2.1 Check if stop taps are fully open. Check if
blockage in inlet filter.
2.3 Increase in ambient 2.3.1 Switch to economy power setting and
water temperature. readjust flow rate to give required temperature.
3 Water 3.1 Heater cycling on 3.1.1 See 'Water too hot' causes 2.1, 2.2 and
temperature cycling outer temperature limiter. 2.3 and their action/cures. If it continues,
hot/cool at intervals. contact Customer Service.
4 Water too cool 4.1 Too much flow. 4.1.1 Reduce flow rate via temperature control.
or cold. 4.2 Water pressure below 4.2.1 Check low pressure indicator. If lit,
minimum stated on rating continue with remainder of checks. If not lit, see
label. 4.1 & 4.4.
4.2.2 Is water supply mains or tank fed?
4.2.3 If tank fed, replumb to mains water
supply or see 4.2.5.
4.2.4 If mains fed, make sure the mains service
valve is fully open and that there are no other
restrictions in the supply while shower is in use,
or see 4.2.5.
4.2.5 Fit a pump to give minimum pressure
contact Customer Service for advice.
4.3 Reduction in ambient 4.3.1 Switch to full power setting and readjust
water temperature. the flow rate via the temperature control to give
required temperature.
4.4 Electrical malfunction 4.4.1 Have unit checked by suitably qualified
or safety cut-out has electrician or contact Customer Service.
operated.
26
Opal
Fault Finding
5 Shower varies 5.1 Water pressure 5.1.1 Wait until the water pressure resumes to
from normal has dropped below normal. Low pressure indicator extinguishes.
temperature to cold minimum required.
during use. Indicator lit.
6 Pressure relief 6.1 Blocked showerhead. 6.1.1 Clean sprayplate and then fit a new PRD.
device has operated 6.2 Twisted/blocked 6.2.1 Check for free passage through hose.
(water ejected from flexible shower hose. Replace hose if necessary and then fit new PRD.
PRD tube).
6.3 Showerhead 6.3.1 Fit new PRD. Commission unit with
not removed while showerhead removed.
commissioning.
In the unlikely event of a fault occurring please contact Triton Customer Service.
Do not remove the shower from the installation.
27
Opal
28
Opal
29
Service Policy Triton Standard Guarantee
In the event of a complaint occurring, the following Triton guarantee this product against all
procedure should be followed: mechanical and electrical defects arising from faulty
1 Telephone Customer Service on workmanship or materials for a period of two years
0870 067 3333 (0845 762 6591 in Scotland and for domestic use only, from the date of purchase,
in Northern Ireland), having available the model provided that it has been installed by a competent
number and power rating of the product, together person in full accordance with the
with the date of purchase. fitting instructions.
2 Triton Customer Service will be able to confirm
whether the fault can be rectified by either the Any part found to be defective during this
provision of a replacement part or a site visit guarantee period we undertake to repair or replace
from a qualified Triton service engineer. at our option without charge so long as it has been
3 If a service call is required the unit must be fully properly maintained and operated in accordance
installed for the call to be booked and the date with the operating instructions, and has not been
confirmed. In order to speed up your request, subject to misuse or damage.
please have your postcode available when This product must not be taken apart, modified or
booking a service call. repaired except by a person authorised by Triton.
4 It is essential that you or an appointed representa- This guarantee applies only to products installed
tive (who must be a person of 18 years of age or within the United Kingdom and does not apply to
more) is present during the service engineer's visit products used commercially. This guarantee does
and receipt of purchase is shown. not affect your statutory rights.
5 A charge will be made in the event of an aborted
service call by you but not by us, or where a call What is not covered:
under the terms of guarantee has been booked and 1 Breakdown due to: a) use other than domestic
the failure is not product related (i.e. scaling and fur- use by you or your resident family;
ring, incorrect water pressure, pressure relief device b) wilful act or neglect; c) any malfunction
operation, electrical installation faults). resulting from the incorrect use or quality of
6 If the product is no longer covered by the electricity, gas or water or incorrect setting of
guarantee, a charge will be made for the site controls; d) faulty installation.
visit and for any parts supplied. 2 Repair costs for damage caused by foreign
7 Service charges are based on the account being objects or substances.
settled when work is complete, the engineer 3 Total loss of the product due to non-availability
will then request payment for the invoice. If this of parts.
is not made to the service engineer or settled
within ten working days, an administration 4 Compensation for loss of use of the product or
charge will be added. consequential loss of any kind.
5 Call out charges where no fault has been found
Replacement Parts Policy
with the appliance.
Availability: It is the policy of Triton to maintain
6 The cost of repair or replacement of pressure relief
availability of parts for the current range of
devices, showerheads, hoses, riser rails and/or wall
products for supply after the guarantee has
brackets, isolating switches, electrical cable, fuses
expired. Stocks of spare parts will be maintained
and/or circuit breakers or any other accessories
for the duration of the products manufacture and
installed at the same time.
for a period of five years thereafter.
7 The cost of routine maintenance, adjustments,
In the event of a spare part not being available a
overhaul modifications or loss or damage arising
substitute part will be supplied.
therefrom, including the cost of repairing
Payment: The following payment methods can be damage, breakdown, malfunction caused by
used to obtain spare parts: corrosion, furring, pipe scaling, limescale, system
1 By post, pre-payment of pro forma invoice by debris or frost.
cheque or money order.
2 By telephone, quoting credit card (MasterCard
or Visa) details. Customer Service: % 0870 067 3333
3 By website order, www.tritonshowers.co.uk Scottish and Northern Ireland
Customer Service: %
0845 762 6591
Triton Showers
Triton Road
Trade Installer Hotline: %
0870 067 3767
Fax: 0870 067 3334
Nuneaton
Warwickshire CV11 4NR www.tritonshowers.co.uk
Triton is a division of Norcros Group (Holdings) Limited E mail: technical@tritonshowers.co.uk
Extended Warranty AVAILABLE NOW. Call 0870 067 3333 for more details.
TRITON reserve the right to change product specification without prior notice. E&OA. TRITON SHOWERS 2008