Sei sulla pagina 1di 15

Plumbing Calculation

Rev-01

Water Supply Calculation Sheet

Project Title : El- Thani Tower


Building Owner : Shekh Abd. EL Aziz el Thany
Project Location : EL - Dafna
Project City : Doha
Project Co` : Qatar
Client Name : Shekh Abd. EL Aziz el Thany
Company Name : Gulf Consulting Group
Company Phone : 00974 - 4364455
Company E-mail : gcgqatar@qatar.net.qa
Company P.O.Box : 8387
Date of Project : ###
Project Description : 2B + G + 22 Resdintinal and Commerical Building
Code Reference : International Plumping Code
Approving Agency : Qatar Palaning
Designed by : Eng. Ahmed M. Sami
Buliding Lowest Level : 0 m
Building Highest Level : 135 m
Roof and SiteTotal Area : 7135 m2
Storage for Rain Water : 2 Days
Storage for Septic tank : 3 Days
Number of Typical Floors : 16 Floor
Comment :

Prepared By
Gulf Consulting Group
Eng. Ahmed M. Sami
###
Plumbing Calculation
Rev-01
1- Building specification :
so get total building height (static head) 135 m

2- For residential :
No. of bed room in the building : 288 Bed room
No. of person in the room : 2 Person
No of person 576 Person
Assume daily water consumption in L/s/person 180 L/day
Then the total water consumption of building 103.68 m3

3- For commercial center:-


daily water consumption = total area of all commercial floors / 10 m2 per person
* daily water consumption per person
Assumption daily consumption per person in liter/day 70 Liter/Day/Person
Area of total commercial floors 8180 m2
Daily water consumption 57.26 m3

4- For Office Building 8 Hour Shift :-


NO. of Person 0 Person
assume daily water consumption in L/s/person 60 L/day
Daily water consumption 0 m3

5-For Factories 7 Hour Shift :-


NO. of Person 0 Person
assume daily water consumption in L/s/person 60 L/day
Daily water consumption 0 m3

6-For Hotels up to 3 Stars :-


NO. of room 0 room
Assume daily water consumption in L/room 170 L/room
Daily water consumption 0 m3

7-For Hotels up to 4 Stars With All Services :-


NO. of rooms 0 room
Assume daily water consumption in L/room 700 L/room
Daily water consumption 0 m3

8-For Hotels up to 5 Stars With All Services :-


NO. of rooms 0 room
Assume daily water consumption in L/room 1200 L/room
Daily water consumption 0 m3

9-For Car Parking :-


NO. of cars 0 car
Assume daily water consumption in L/car 30 L/car
Daily water consumption 0 m3

10-For Restaurant and Cafes Per Meal :-


NO. of Person 0 Person
Assumed no. of meal per person 1 meal
Assume daily water consumption in L/s/meal 30 L/meal
Daily water consumption 0 m3
11-For Laundry in Hotels Per Bed :-
NO. of Bed 0 Bed
Assume daily water consumption in L/bed 130 L/bed
Daily water consumption 0 m3

12-For Laundry in Hospital Per Bed :-


NO. of Bed 0 Bed
Assume daily water consumption in L/bed 600 L/bed
Daily water consumption 0 m3

13-For School :-
NO. of Student 0 Student
Assume daily water consumption in L/student 75 L/student/day
Daily water consumption 0 m3

14-For Airport :-
NO. of Passenger Per Day 0 Passenger
Assume daily water consumption in L/passenger 20 L/passenger/day
Daily water consumption 0 m3

15-For Meeting Area :-


NO. of person 0 Person
Assume daily water consumption in L/person 10 L/person/day
Daily water consumption 0 m3

16-For Public Building :-


NO. of person 0 Person
Assume daily water consumption in L/person 50 L/person/day
Daily water consumption 0 m3

17-For Camps :-
NO. of person 0 Person
Assume daily water consumption in L/person 75 L/person/day
Daily water consumption 0 m3

18-For Swimming Pools & Shore :-


NO. of person 0 Person
Assume daily water consumption in L/person 40 L/person/day
Daily water consumption 0 m3

19-For Mosque :-
NO. of person 0 Person
Assume daily water consumption in L/person 30 L/person/day
Daily water consumption 0 m3

20-For Public Toilet Per Unit :-


NO. of toilet Unit 0 Unit
Assume daily water consumption in L/toilet 120 L/toilet
Daily water consumption 0 m3
21-For Public Urinal :-
NO. of urinal 0 urinal
Assume daily water consumption in L/urinal 40 L/urinal
Daily water consumption 0 m3

22-For Public Lavatory :-


NO. of Lavatory 0 Lavatory
Assume daily water consumption in L/Lavatory 60 L/lavatory
Daily water consumption 0 m3

23-For Public Shower :-


NO. of showers 0 Lavatory
Assume daily water consumption in L/shower 560 L/shower
Daily water consumption 0 m3

24-For Public Slaughterhouse :-


NO. of Caw 0 Caw
Assume daily water consumption in L/caw 400 L/caw
Daily water consumption 0 m3

25-For Commercial Laundry Per Kg of Clothes :-


NO. of Kg 0 kg
Assume daily water consumption in L/kg 35 L/kg
Daily water consumption 0 m3

26-For Farms :-
No. of Caws 0 caw
No. of Calf 0 calf
No. of goats & sheep 0 goat & sheep
No. of horses 0 horses
No. of egg Chicken 0 Chicken
No. of turkey Chicken 0 Chicken
No. of ducks 0 duck
No. of camel 0 Camel
Daily water consumption 0 m3

27- Irrigation water consumption calculations


water consumption for irrigation changed according to kind of planters exists
no. of palm trees 2 Unit
no. of spreading 5 Unit
no of evergreen 9 Unit
area of grass 5 m2
get daily water consumption for irrigation 0.56 m3
OR
Insert Total Green Area for The Building 100 m2
Assume 1 cm of water per 1 m2
Daily water consumption 1 m3
Daily Domestic Water Consumption :-
water consumption per day for the building 162 m3

Daily Irrigation Water Consumption:-


water consumption per day for the building 1 m3

Total Daily Water Consumption For the Building :-


total consumption of water per day 163 m3
muliplay the water consumption in 10% safety f 179 m3

Total Rain Water Holding Tank


Rain water per 1 day 143 m3
Rain water storage capacity 2 days

Under Ground or Ground Water Tank


the storage capacity for 2 days 359 m3

Roof Water Tank Capacity


the storage will be for 1 day 179 m3

Rain Water Holding Tank


the storage will be fo2 day 286 m3

Septic Tank
the storage will be fo3 day 458 m3
Table of total fixtures

ENTER NO. OF UNIT ACCORDING TO FIXTURE TYPE PRIVATE OR PUBLIC

Fixture type : private

Total
FIXTURES / POINT NO. B3 B2 B1 G.F. F.F 2nd.F 3rd F 4th F. 5th F 6th F TYP. F
fixtures
Water closet (flush valve) 1 1 1 1 1 1 1 1 1 1 26 426
Water closet (flush tank) 0 0 0 0 0 0 0 0 0 0 0
Water Bidet 0 1 0 0 0 0 0 0 0 0 16 257
Hose for W.C 0 1 0 0 0 0 0 0 0 0 1
Lavatory (& H.B.) 0 0 0 0 0 0 0 0 0 0 26 416
Kitchen sink 0 1 0 0 0 0 0 0 0 0 16 257
Service sink office,ect 0 0 0 0 0 0 0 0 0 0 0
Shower 1 1 1 1 1 1 1 1 1 1 10 170
Bath tub 0 0 0 0 0 0 0 0 0 0 6 96
Dishwashing machine 0 0 0 0 0 0 0 0 0 0 10 160
Laundry 8 Ib 6 0 0 0 0 0 0 0 0 0 10 166
Laundry 16 Ib 0 1 0 0 0 0 0 0 0 0 1
Ablution (Public) 0 0 0 0 0 0 0 0 0 0 0
Urinal (1" flush valve) 0 0 0 0 0 0 0 0 0 0 0
Urinal (3/4" flush valve) 0 1 0 0 0 0 0 0 0 0 1
Urinal (flush tank) 0 0 0 0 0 0 0 0 0 0 0
Drinking fountain 3/8 in 0 0 0 0 0 0 0 0 0 0 0
SUM 1951

Fixture type : public

Total
FIXTURES / POINT NO. B3 B2 B1 G.F. F.F 2nd.F 3rd F 4th F. 5th F 6th F TYP. F
fixtures
Water closet (flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Water closet (flush tank) 1 0 0 0 0 0 0 0 0 0 0 1
Water Bidet 1 0 0 0 0 0 0 0 0 0 0 1
Hose for W.C 1 3 0 0 0 0 0 0 0 0 0 4
Lavatory (& H.B.) 1 0 0 0 0 0 0 0 0 0 0 1
Kitchen sink 1 0 3 0 0 0 0 0 0 0 0 4
Service sink office,ect 1 0 3 0 0 0 0 0 0 0 0 4
Shower 1 0 0 3 0 0 0 0 0 0 0 4
Bath tub 1 3 0 0 0 0 0 0 0 0 0 4
Dishwashing machine 1 0 0 0 0 0 0 0 0 0 0 1
Laundry 8 Ib 1 0 0 0 0 0 0 0 0 0 0 1
Laundry 16 Ib 1 0 0 0 0 0 0 0 0 0 0 1
Ablution (Public) 1 3 0 0 0 0 0 0 0 0 0 4
Urinal (1" flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Urinal (3/4" flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Urinal (flush tank) 1 2 2 0 0 0 0 0 0 0 0 5
Drinking fountain 3/8 in 1 0 0 0 0 0 0 0 0 0 0 1
SUM 39
A B C D E F G H I J
1 Pump will Calculated according to the type of project
2
3 Put ( X ) Beside The Type of Project
4
5 Appartemen x Hotels & Club Hospital
6
7 School Office Industerial
8
9 Put ( X ) Beside The Type of Heater Used
10
11 Individual Heaters Don`t Mark 2 Point
12
13 x Centeral Heater
14
15 Total length of water pipe for lift pump from ground to roof water tank 176 m
30 No. of Lift Pump To be Used = 3 Duty + 1 StandBy
31 No. of Boster Pump To be Used = 5 Duty + 1 StandBy
32
33 Lift Pump Selection
34 Pump Flow 160 GPM
35 Pump Head 283 PSI
36 Pump HP 45 HP
37 No. of Pumps 3 Duty + 1 StandBy
38
39 Boster Pump Selection
43 Pump Flow 81 GPM
44 Pump Head 35 PSI
45 Pump HP 3 HP
46 No. of Pumps 5 Duty + 1 StandBy
47
48 Pressure Vessel
49 Volume of Vessel 568 Liters
50
51
Filter will Calculated According to it's Location :-

Put ( X ) Beside The Type of Project

Ground Floor x Roof Floor g

No. of Filters Will be used = 3 No.


Enter Total Length of Pipe From Main Tank To Filteration= 10 m
Level Difference From Ground Tamk To Filteration Tank = 2 m
Enter Total Volume of Receving Water tank = 40 m3
No. of Pumps Will Be Used = 2 Duty + 1 StandBy

Filter Selection
Filter Capacity 58 GPM
Filter Working Pressure 22 Psi
No. of Filters 3 Unit
Maximum Losses in Filter 15 Psi
Filteration Pump Capcity 88 GPM
Filteration Pump Head 26.4 Psi
Irrigation Pump Selection

Put ( X ) Beside The Type of Irrigation

Manual Syste x Automatic system

Insert No. of Irrigation Pump Will be Used 1 Duty 1 StandBy


Enter Total Time to Finish Manual Irrigation = 3 Hours
Enter Difference in Head Between Pump & Irrigation Line 0.3 m
Enter Total Lengh Of Irrigation Pipe = 80 m

Irrigation Pump Selection :-


Pump Capacity 1.5 GPM
Pump Head 50 Psi
Pump HP 0.08 HP
Pumps 1 Duty, 1 StandBy
Pressure vesel 85 Liters

Watting For Automatic System Calculation


Individual Water Heater Selection For Each Bath :-

Calculation Will be According to Type of The Building & Fixture Unit Methods:-

PUT ( X ) Beside Your Type of The Place:-

Appartement House Hospital x Industerial

Club Hotels Office Building

Private residence School YMCA

GYM

Fixture QTY Demand Total Gallon/Hr


private lav. 0 2 0
public lav. 1 6 6
bathtub 1 20 20
dishwasher 1 100 100
foot basin 1 3 3
kitchen sink 0 20 0
laundry 0 28 0
pantry sink 0 10 0
shower 0 75 0
service sink 0 20 0
hydrotherapentic shower 0 400 0
hubbard bath 0 600 0
leg bath 0 100 0
arm bath 0 35 0
sitz bath 0 30 0
continuous flow bath 0 165 0
circular wash sink 0 20 0
semicircular wash sink 0 10 0

Water Heater Selection :-


Heater Storage Capacity = 80 Liters
Heater Power = 2 KW
Sump Pit will size according to The Drainage of Fixture Unit in
1st & 2nd Basement + The Drainage from Kitchen + Drainage of Laundries

No. of Laundry in Basement = 10 Unit


No. of Person Will Served by Restaurant = 200 Person
No. of Cars In Basement = 100 Car
Time Required to Empty the Sum pit = 10 min
Sum pit Depth = 2 m
Difference from low level and high level = 7 m
Total length for Pressure pipe = 10 m

Submersible Pump & Sump Pit Capacity


Sump Pit Volume = 1.3 m3
Sump Pit Dimension = 0.8 m X 0.8 m X 2 m
Submersible Pump Capacity = 2.2 Litters / Sec
Submersible Pump Head = 15 m
Submersible Pump HP = 1 HP
Individual Water Heater Selection For Each Bath :-

Calculation Will be According to Type of The Building & Fixture Unit Methods:-

PUT ( X ) Beside Your Type of The Place:-

Appartement Hou x Hospital Industerial

Club Hotels Office Building

Private residence School YMCA

GYM

PUT ( X ) Beside Your Type of The Pipe:-

Insulated Pipes Non-Insulated Pipes x

PUT ( X ) Beside Your Type of The Pipe:-

Sch-40 x Brass K-Copper


Copper

Fixture QTY Demand Total Gallon/Hr

private lav. 90 2 180


public lav. 15 4 60
bathtub 30 20 600
dishwasher 10 15 150
foot basin 20 3 60
kitchen sink 60 10 600
laundry 15 20 300
pantry sink 20 5 100
shower 30 30 900
service sink 2 20 40
hydrotherapentic shower 0 0 0
hubbard bath 0 0 0
leg bath 0 0 0
arm bath 0 0 0
sitz bath 0 0 0
continuous flow bath 0 0 0
circular wash sink 0 0 0
semicircular wash sink 0 0 0
2990
DEMAND FACTOR 0.3
Probable Maximum Demand 897
Heater or coil Capacity 897
STORAGE CAPACITY Factor 1.25
Storage Tank Capacity GALLO 1121.25

Insert Pipe Length For Supply Network as We Don`t Know the Return Pipe Size

Pipe Diameter Length in meter Q loss


Length of 1/2 " pipe 400 14000
Length of 3/4 " pipe 120 5160
Length of 1 " pipe 300 15900
Length of 1-1/4 " pipe 232 15080
Length of 1-1/2 " pipe 132 9636
Length of 2 " pipe 120 10920
Length of 2-1/2 " pipe 105 11340
Length of 3 " pipe 100 12900
Length of 4 " pipe 100 16300
Length of 5" pipe 100 19900
Length of 6 " pipe 130 30290
Length of 8 " pipe 150 44850
Total Heat loss From Supply Pipes 206276

Total Farther Pipe length Supply & Return = 120 m

Conclusion for Centeral Water System

Heat or coil Capacity 897 Gallon / Hour


Storage Tank Capacity 1121.3 Gallon

Circulation Pump Selection : -

Pump Flow 35 GPM


Pump Head 8 Psi
Pump HP 0.3 HP

Potrebbero piacerti anche