Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Technical Information
ACFM, ICFM & CFM - Actual Cubic Feet per Minute, Inlet Cubic Feet per Minute &
Cubic Feet Per Minute
These terms refer to similar things. They refer to a volume of air (one cubic foot)
at ambient conditions, no matter what those ambient conditions are. Changes in
pressure, temperature or relative humidity (changes in mass) do not change these
ratings. These ratings are, therefore, measures of volume regardless of weight.
Although these terms sound similar, they are as different as gallons and pounds. A gallon
is a measure of volume (like ACFM and ICFM) regardless of the weight of the substance
occupying that gallon. A pound is a measure of weight (like SCFM) without regard to the
volume it occupies.
All positive displacement compressors are rated according to the inlet volume of air they
compress. It does not matter whether the manufacturer calls this number ACFM, ICFM, FAD,
Capacity ACFM or CFM. All of these terms refer to the volume of air entering the compressor.
A manufacturer can play games by measuring these volumes at different points in the compressor
package or under conditions that are different from the actual ambient conditions, but all ratings
refer to the volume of air entering the machine.
If the compressor is going into a process application and mass flow (SCFM) must be
determined, there are a few simple calculations that will allow you to determine the SCFM flow of
a compressor if you know the volume flow rating (CFM), the ambient conditions under which the
compressor must run and the standard to which you must convert. The volume flow rating will
The formula for calculating the correction factor for the effect temperature has on density is:
If the standard temperature is 68oF and the ambient temperature is 90oF, this formula would look
like this:
This tells you that air at 90oF is only 96% as dense as air at 68oF. If you want to calculate
the SCFM capacity of a compressor at this temperature condition, multiply the compressor
volume flow rating by this temperature correction factor. If you know the SCFM requirement
and you are sizing a compressor to operate at 90oF, divide the SCFM requirement by the
temperature correction factor to find the volume flow required.
EXAMPLE:
The customer needs the equivalent mass flow of 400 SCFM where the standard
temperature is 68oF and the ambient temperature is 90oF.
The customer has a 750 ACFM compressor and wants to know its SCFM delivery at
90oF, using a 68oF temperature standard.
The capacity of the compressor did not change. It is still a 750 ACFM compressor. What
changed was the density, or weight, of each cubic foot of air that the compressor pulled in
through the inlet valve.
Another factor that affects air density and must be calculated when converting ACFM to
SCFM is the absolute ambient air pressure. Lower absolute ambient pressure means a lower air
density. The formula for finding the absolute ambient pressure factor is:
If the location of the application is Denver, and the standard being used is 14.69 PSIA, the
formula would be:
This tells you that air at 12.2 PSIA is only 83% as dense as air at 14.69 PSIA. If you want
to calculate the SCFM capacity of a compressor at this pressure condition, multiply the
compressor volume flow rating by this pressure factor. If you know the SCFM requirement and
you are sizing a compressor to operate at 12.2 PSIA., divide the SCFM requirement by the
pressure factor to find the volume flow rate required.
EXAMPLE:
The customer needs the equivalent mass flow of 400 SCFM where the standard
pressure is 14.69 PSIA and the absolute ambient pressure is 12.2 PSIA.
The customer has a 750 ACFM compressor and wants to know its SCFM delivery at
12.2 PSIA, using a 14.69 PSIA standard.
Consult factory if relative humidity must also be factored. The calculations required are
not as simple as those for pressure and temperature.
EXAMPLE:
What is the compression ratio of a machine located at sea level, discharging at 100
PSIG?
What is the compression ratio of a machine located at 5,000 feet above sea level,
discharging at 100 PSIG?
Absolute Ambient Pressure at 5,000 feet above sea level = 12.2 PSIA
Absolute Discharge Pressure = 100 (Gauge Pressure) + 12.2 Ambient Pressure
Compression Ratio=Absolute Discharge/Absolute Ambient=112.2/12.2 =
9.2 to 1 Compression Ratio
As the compression ratio in a single stage, flooded rotary screw compressor goes up, the
volumetric efficiency of the compressor goes down slightly. For this reason, you will need to use
the following correction factors for determining the volume flow rate (CFM) at various altitudes:
VOLUME FLOW MASS FLOW TOTAL
ALTITUDE CORRECTION CORRECTION CORRECTION
FACTOR FACTOR FACTOR
Mean Sea Level 1 1 1
1000 ft above MSL 0.9984 0.964 0.9625
2000 ft above MSL 0.9969 0.93 0.927
3000 ft above MSL 0.9954 0.896 0.892
4000 ft above MSL 0.994 0.863 0.858
5000 ft above MSL 0.9926 0.832 0.826
6000 ft above MSL 0.9912 0.801 0.794
7000 ft above MSL 0.9899 0.77 0.762
8000 ft above MSL 0.9887 0.743 0.735
9000 ft above MSL 0.9874 0.715 0.706
10000 ft above MSL 0.9862 0.688 0.6785
The thinner air at altitude causes two other things to happen that affect air compressor
packages. First, the actual horsepower required by a particular compressor goes down as the
altitude goes up. This is due to the fact that the air becomes less dense (thinner air requires less
power to compress it) as altitude increases. As the air becomes less dense it also loses some of its
ability to transfer heat. This second effect means that motors lose some of their ability to dissipate
heat and can no longer be run at the rated horsepower levels. At about 7500 feet above MSL, the
motor's available horsepower curve and the compressor's horsepower requirement curve cross.
Either a larger motor will be required, ambient temperatures will have to be maintained below the
motors nameplate temperature rating or shorter motor life will have to be accepted for
installations above 7500 feet.
Altitude also affects the efficiency of the lubricant cooler and aftercooler. Tech data is
based on sea level conditions. The cooler performance degrades with altitude.
In most rotary screw compressors, increasing or decreasing the pressure settings will have
similar effects. The rule of thumb is:
For every 1 PSIG change from rated pressure, the brake horsepower required will
change 0.5% from the rated BHP. Increase the pressure by 10 PSIG and the
BHP will go up 5%. Decrease the pressure by 20 PSIG and the BHP will go
down 10%.
Changes in discharge pressure from the rated pressure of the compressor will result in
changes in the overall compression ratio. These compression ratio changes will cause changes in
the volumetric efficiency of the compressor that will result in changes in capacity. The rule of
thumb is:
For every 10 PSIG change from rated discharge pressure, the CFM capacity of
the compressor will change 0.4% from the rated capacity. Reducing pressure
from 110 PSIG to 100 PSIG will result in a capacity increase of four tenths of one
percent. Increasing the pressure by 10 PSIG will cause a reduction in capacity of
about four tenths of one percent.
It is important to use actual CFM requirements to figure the load level of the compressor.
Do not base power cost calculations on comments like, "About half the time we run at full load
and about half the time we run at 70% of full load." Full load for one machine may not be the
same as full load for another machine. Always determine the exact air requirement in order to
provide the customer with a power cost calculation that approximates his situation.
To find the annual power costs, calculate the cost per hour of operating at the various
anticipated load levels and multiply by the anticipated number of hours that the machine will
operate at those load levels.
4) Estimating additional capacity required to raise system from one pressure to a higher
pressure.
EXAMPLE:
What is the additional capacity required to maintain a 100 PSIG system pressure at sea
level in a system that now operates at 91 PSIG using 500 CFM?
The total BTUs per minute of heat rejected by a rotary screw compressor is equal
to the brake horsepower being used times 42.41. A 100 BHP compressor would
have a total heat load of 4,241 BTU/minute. Of this total, about 8% is rejected
as radiant heat. Of the remaining 92%, about 85% (78.2% of total) is rejected
through the lubricant cooler and about 15% (13.8% of total) is rejected through
the aftercooler.
Control Methods
Load Control--Load / No Load (On-line, Off-line)
One of the earliest control schemes for rotary screw compressors was the simple
adaptation of reciprocating-type controls to the rotary screw compressor. These pressure-based
controls operate within a pressure range of about 10 to 15 PSIG. The compressor will run at full
capacity until the measured system pressure reaches the upper set point of the pressure switch.
When this set point is reached, a signal is sent to close the inlet valve and relieve some or all of
the pressure in the lubricant separator reservoir. The only air being compressed, at this point, is
air that has leaked around the inlet valve plate. With some controls, this leakage is calibrated so
that an amount of air is always being delivered to the air/lubricant reservoir to maintain enough
positive pressure to ensure proper lubricant circulation. With the inlet valve closed, the
compressor is said to be running unloaded. When the system pressure drops to the lower pressure
set point, a signal is sent to reopen the inlet valve and the compressor is again running fully
loaded. This control can adequately satisfy system demands, if applied to a system designed to
use this type of compressor control. Applying a compressor with this type of control to a system
that has not been specifically designed for it can result in higher than expected energy
consumption, unacceptable fluctuations in system pressure, and lower than expected equipment
life.
Traditionally, published power consumption curves for rotary screw compressors have
simplified the actual operating conditions of this type of control, resulting in an overly optimistic
portrayal of energy requirements. Part-load power requirement calculations were actually based
on the operating characteristics of reciprocating compressors. The traditional method of
calculating power consumption at levels other than full load is to factor the power consumed at
full load and the power consumed at unload as a function of time at each of these load levels. To
find the power consumed at 80% of full load capacity one would multiply the full load
horsepower requirement by .8, the percent of time spent at full load, then multiply the unload
horsepower requirement by .2, the percent of time spent at unload, then add the two numbers
together. Actual screw compressor operation differs from this considerably.
Lubricant-flooded rotary screw compressors must also have controls designed to limit the
amount of lubricant carryover into the downstream air system. When a compressor with load/no
Since reservoir pressure is not instantaneously relieved, horsepower does not immediately
fall to the unloaded level when the inlet valve closes. Tests show that horsepower requirements
typically fall to about 80% of the full load level when the inlet valve closes, and then fall steadily
to the unload power requirement while the compressor is reducing the reservoir pressure. The
actual average horsepower required for a load/no load compressor operating at less than full
capacity is a function of the following factors:
This can be illustrated by using a typical 1000 CFM compressor with a 1000 gallon air
receiver and calculating the horsepower required at various loads. Typical performance for a
machine this size would include: 222 BHP at full load and maximum discharge pressure (110
PSIG); 210.9 BHP at full load and initial load pressure (100 PSIG, 1 PSIG change in pressure
results in 0.5% change in horsepower required); 55.5 BHP at final unloaded level; 177.6 BHP at
initial unloaded level; 60 second reservoir blowdown time; 14.5 PSIA ambient pressure.
The load cycle time at a particular demand level can be calculated from the above
information by using the following formula:
A system demand of 800 CFM will result in a load cycle of 27.7 seconds loaded and 6.9
seconds unloaded, when being supplied by a 1000 CFM compressor with a 1000 gallon air
receiver. The total cycle time to supply a steady 800 CFM demand is 34.6 seconds. With an 80%
(800 CFM) demand, the cycle would start at 100 PSIG. The 1000 CFM compressor would
deliver that amount to
Load/No Load Cycle the 1000 gallon
receiver. 800 CFM
1000 CFM Compressor w/1000 Gal. Receiver would be used to
satisfy the system
230
Final Load Final Load demand and the
220 remaining 200 CFM of
Initial Load Initial Load
210 compressor capacity
200 would be used to raise
190 the receiver pressure
180
from 100 PSIG to 110
PSIG. The
170
Initial Unload Reload Initial Unload
Reload
horsepower required
160 for full load operation
0 10 20 30 40 50 60 70
would be the average
of the initial loaded
Actual BHP Profile Actual Average Theoretical Average
horsepower (210.9)
800 CFM Demand (Figure 1) and the final loaded
horsepower (222), or
216.45.
When the receiver pressure reached 110 PSIG, the compressor closed the inlet valve and
began to relieve the separator reservoir pressure. For this machine, it takes 60 seconds for the
reservoir pressure to drop to its design point. During that 60 seconds, the horsepower will drop
steadily from the initial unloaded requirement (177.6) to the final unloaded requirement (55.5).
The compressor, however, is only running unloaded for 6.9 seconds at a time and never reaches
its final unloaded reservoir pressure. Falling at the rate of 2.035 BHP/second, unloaded
Using a larger air receiver will lengthen the load an unload times and will make the
unloading transition period a smaller percentage of the overall cycle time, improving the
horsepower required to run at a particular load level. Figure 2 shows power consumption at
various load levels with different receiver sizes. At a 50% load level, actual performance with a
1000 gallon receiver is about 40% higher than typical published performance. Increasing the
receiver size ten fold results in improved performance, but actual horsepower required at 50%
load is still 12 % higher
than published numbers
Load/No Load Power Curves would indicate. In
order to reach the
At Various Load Levels
theoretical performance
230 curve, the reservoir
210
blowdown period must
190
be an insignificant
percentage of the total
170
w/1,000 Gal. Rec. unloaded cycle time.
150
w/10,000 Gal. Rec.
130
Typical Published Perf. In multiple machine
110 applications, the
90 number of machines is
70 limited by the maximum
50 acceptable system
0 200 400 600 800 1000
pressure variation.
Each load/no load
1000 CFM Compressor (Figure 2) machine has to be set
with its upper and
lower pressure points at
least 2 PSIG different from the next closest compressor. Staggered in such a manner,
compressors added to a system designed originally to operate between 100 and 110 PSIG would
either have to waste horsepower to compress to higher than required pressures, or operate at a
lower than desired operating pressure. With five machines in such a system, plant air pressures
would have to drop to 92 PSIG before the final machine was instructed to run fully loaded.
Load/No Load controls rely on a constant swing in discharge air pressure of about 10
PSIG. This constant fluctuation is undesirable in most applications because air device efficiency
changes between 1% and 1.4% for each pound of supply pressure change. In applications that
have small storage capacities, load/no load controls produce rapid pressure fluctuations and
excessive inlet valve wear. Modulation control addresses both of those issues by providing a
constant system pressure with minimal valve movement at any given system demand. Power
consumption does not, however, decline with increased air receiver capacity as it does with
load/no load controls. Because reduced demand produces higher pressure at a reduced flow rate,
modulating compressors usually have lower lubricant carryover than comparable load/no load
compressors.
Load/no load controls require the lower pressure set point to be adjusted to the minimum
system pressure required. This type of control will operate the compressor at full capacity until
the pressure is 10 PSIG above this minimum point. Operation at this upper point requires about
5% more horsepower than operation at the lower (system design) pressure. Modulating
compressors start at the same minimum system pressure requirement and only exceed that
pressure if demand is less than capacity. This gives modulating compressors a power advantage
over load/no load compressors when system pressure rises.
The horsepower required to compress a gas is a function of the mass and compression
ratio. Increasing system pressure triggers the inlet valve to reduce the inlet flow, resulting in
reduced suction pressure. As the discharge pressure rises, suction pressure drops and the number
of compression ratios increases. Because the number of compression ratios increases as the mass
flow drops, part load operation of modulating compressors requires a significant percentage of
their full load power requirement. Figure 3 illustrates the power required by modulating
compressors at various load levels. It is only slightly better than a load/no load compressor with a
receiver sized at one gallon of storage per CFM of compressor capacity. Note that the shape of
the curve and the rate of decline is almost identical to the load/no load curve using one gallon of
storage per CFM of capacity. The advantage is in where the curve starts. Modulating controls
Modulating
compressors running in multiple machine applications are subject to the same limits on numbers of
machines as load/no load compressors. All modulating machines in a multiple machine application
may be running at less than full load at the same time. While this results in a very steady plant air
pressure, it is not a very efficient use of power.
When utility companies began raising electricity costs and started penalizing users with
high demands, instead of discounting costs when demands increased, compressor manufacturers
looked for more efficient ways to control rotary screw compressors at part load. Rotor length
control was developed to allow a compressor to match its output to the system demand without
the penalty of increasing compression ratios. By controlling the effective length of the rotor
compression area, inlet pressure can remain steady and compression ratios fairly constant over the
upper 50% of the compressor's capacity. This method of reducing mass flow without increasing
compression ratios provides a distinct power advantage when operating at part load. Several
methods of controlling the effective length of rotors are currently in production. Although all
types offer better efficiencies at some point in their part load operating range than modulating
controls or load/no load controls, the design and manufacture of each type of rotor length control
has both operating and efficiency differences.
The turn valve and the spiral valve are of essentially the same design. Each type is based
on a patent issued to Mike Herschler, John Shoop and Robert Anderson, who were working for
Rev.3.15.97 Tech Info -12
Back to TOC
_________Quincy Rotary Screw Sales Manual____________
Gardner-Denver at the time. The companies that manufacture these designs use different control
methods, but the mechanics of controlling the effective length of the compression area are the
same with both valves. Both designs incorporate a number of ports in the low pressure inlet end
of the rotor housing, near where the two rotor bores meet. These ports are as deep as the housing
is thick. Below these ports is a cylindrical shaped valve with a spiral cut groove that either seals
the port or opens to a cavity that connects to the inlet air passageway. Because these ports are
located at the start of the compression cycle and pressure is very low, opening the port, even a
small amount, prevents compression from beginning until the rotor tips pass the partition in the
rotor bore casting that separates the ports. This effectively reduces the trapped volume of air to
compressed and reduces the horsepower required.
Closing the ports creates a clearance pocket in the rotor bore. As the tip of the rotor
passes over this pocket, some of the air being compressed slips around the tip of the rotor and
passes from an area of higher pressure to an area of lower pressure. This hurts the efficiency at
load levels above 50%, when compression is taking place in the part of the rotor bore that
contains these pockets. Typically, this efficiency loss is about four percent, according to one of
the co-inventers and verified by test results. A compressor with a turn or spiral valve will either
use more power to make the same air as the identical compressor without pockets or it will
produce less air at the same horsepower. Figure 4 illustrates typical power consumption and
CFM production for this type of control. To deliver 1000 CFM, the compressor starts at a higher
horsepower level than the other control methods. Below 900 CFM, the turn/spiral valve uses less
horsepower per CFM than modulation or either of the load/no load scenarios.
For multiple machine applications, both designs use a pressure deadband type of
control. Each machine
must initially be set to
Turn Valve Power Curve operate with a two or
At Various Load Levels (100 PSIG System Req.) three pound
differential between
225 compressors. One
205
control scheme uses a
timer to close the gap
185 between machines if
165 air usage remains
steady over a
145
predetermined period
125 of time. Another
500 600 700 800 900 1000 control method uses
the same logic used to
Inlet Modulation L/NL w/1000 Gal control load/no load
L/NL w/10000 Gal Turn/Spiral Valve
and modulating
machines. Both
1000 CFM Compressor (Figure 4)
control methods allow
individual machines to
control their own
Quincy Compressor developed the curved lift valve method of effective rotor length
control to overcome the efficiency losses associated with what the turn valve patent refers to as
"...the unavoidable unswept volume formed by the auxiliary ports which open into the compressor
working chambers." Instead of operating a valve that required "auxiliary ports", Quincy took
advantage of our state-of-the-art machining capabilities and designed a system of valves that are
machined in place while the rotor bores are being cut. The actual faces of the valves are
dimensionally identical to the rotor bore and have no "unswept volume" that would reduce
volumetric efficiency (see Power$ync option brochure for illustration). This rotor length control
design is the only
one in use on air
Curved Lift Valve Power Curve compressors that
maintains the full
At Various Load Levels (100 PSIG System Req.)
efficiency of solid
rotor bores.
225
Figure 5 shows
205 that the slope of
the turn/spiral
185
valve and curved
165 lift curve are very
similar. The
145
primary difference
125 is that the curved
500 600 700 800 900 1000
lift valve efficiency
improvement
Inlet Modulation L/NL w/1000 Gal L/NL w/10000 Gal allows it to make
Turn/Spiral Valve Curved Lift Valves the same CFM as
the turn/spiral
1000 CFM Compressor (Figure 5) valve at a lower
initial horsepower.
Quincy Compressor and a major VFD manufacturer were involved in a joint study of the
feasibility of using variable frequency drive to control compressor capacity prior to Quincy's
development of the curved lift valve concept of capacity control. Initial results looked very
promising. It appeared that this type of control would be more efficient than any other method of
reducing the power required to operate at less than full load. Quincy was very interested in this
because it required no new airend design and no major package design changes. Unfortunately,
there is one major drawback to this method of control.
Variable frequency drives work by converting 60 Hertz current to direct current and then
reconverting it to the proper frequency required to turn the drive motor at the desired speed. This
conversion uses an additional 4% to 6% more energy. If the actual motor horsepower (kW) is
charted, it outperforms all other forms of capacity control. If, however, the power required to
make the
conversion is
Variable Frequency Drive Power Curve added back
to the motor
At Various Load Levels (100 PSIG System Req.) power, VFD
fails to
220 outperform
the turn
200
valve in the
180 upper 20%
of its
160
operating
140 range and
fails to
120
500 600 700 800 900 1000 outperform
the curved
lift valve in
Inlet Modulation L/NL w/1000 Gal L/NL w/10000 Gal
the upper
Turn/Spiral Valve Curved Lift Valves VFD
40% of its
operating
1000 CFM Compressor (Figure 6) range. For
compressors
that lack a turn valve or curved lift valve feature, and are being used in applications that do not
require the full capacity of the compressor, installing a VFD will improve part load efficiency
when compared to modulating-type controls.
Another issue that must be considered when evaluating the potential benefit of a VFD is
the operating speed of the airend. Rotary screw compressor efficiency changes with changes in
RPM. The efficiency of a given size and design of airend is governed, in part, by the tip speed of
the rotors. Tip speed is the speed, in meters per second, that the outside perimeter of a given
rotor is traveling. Efficiency remains relatively constant through a range of speeds, but falls off
Controlling multiple machines offers the largest opportunity for energy savings.
Pressure-based controls are offered by all compressor manufacturers. Only Quincy offers an
OEM, flow-based controller for multiple compressor installations. The controller is Power$ync.
In multiple machine applications it is not uncommon for the energy savings afforded by
Power$ync to pay back the entire conversion from competitive machines in less than two years.
The compressor in the fourth position would be set to run 15 PSIG higher than the system
pressure requirement just to make the pressure-based control work properly. This uses about
7.5% more horsepower than the compressor in position 1. Controls that use pressure transducers
and microprocessors can narrow the gap between compressors to about 2 PSIG, but that creates
problems. A wide gap between machines will result in fewer machines running to meet a
particular demand, but higher operating pressures will offset the savings and add to the artificial
demand. Leaks and unregulated air use will consume more CFM at higher pressures, adding to
the system demand. A narrow gap between machines keeps the artificial demand to a minimum,
but more machines will be running at part load to satisfy a particular demand.
To illustrate how this works, consider the following application that has three demand
levels; 1600 CFM, 2500 CFM and 5000 CFM. Assume that, with a 5000 CFM maximum
demand, the customer uses five 1000 CFM compressors. These compressors are set to have a 10
PSIG modulation range and the modulation ranges are set two PSIG apart. Also assume that all
the inlet valves are working perfectly and a change in pressure of one PSIG will result in a 10%
change in capacity.
A more efficient control method is one that allows a mix of compressor sizes that can
supply demand with machines running at full, or nearly full load. Power$ync accomplishes this
with flexible scheduling and sequencing. With Power$ync, only one machine at a time trim to
match demand.
Single-stage compressors compress air from a given inlet pressure to the final discharge
pressure in one step or stage. With this type of compressor, the overall compression ratio and the
compression ratio per stage are equal. Compressing sea level air to 100 PSIG (14.7 PSIA to
114.7 PSIA) results in an overall compression ratio of 7.8 to 1.
Two-stage compressors compress air from a given inlet pressure to the final discharge
pressure in two steps or stages. The first stage takes a given volume from the absolute inlet
pressure to an intermediate pressure. The second stage takes a volume at the intermediate
pressure and compresses it to the final discharge pressure. While the overall compression ratio
remains the same, regardless of the number of stages, the compression ratio per stage for a
two-stage compressor is the square root of the overall compression ratio. Compressing from sea
level to 100 PSIG yields an ideal compression ratio per stage of 2.793. The first stage would
raise the absolute pressure from 14.7 PSIA to 41.06 PSIA, 14.7 PSIA times 2.793. The second
stage would take the air at 41.06 PSIA and compress it to 114.7 PSIA. The power savings of
two-stage compression is due to the fact that the total compression ratio for this example is the
sum of the compression ratios per stage, or 5.586. Since power required to compress a gas is a
function of the total compression ratios and the mass flow, single-stage compression, with its
higher total compression ratio would require more power than a two-stage compressor
compressing the same volume of mass. That is the way things work...in theory.
The ideal compression ratio per stage assumes several things. There must be perfect
intercooling, the inlet temperature to each stage must be the same. Each stage must be sized and
ported exactly. The compressor must run at a single design point or be able to vary the volume of
both stages. In fluid-flooded, two-stage rotary screw compressors intercooling is not possible.
To cool the air stream between stages would result in water condensation that would immediately
mix with the lubricating fluid as it entered the second stage. Some cooling fluid is usually injected
between the stages, but it does not cool the interstage temperature to the ambient temperature.
Sizing and porting each stage is done for operation at full load. Move away from full load and
today's two-stage screws drop efficiency fast.
There are two primary control schemes for two-stage, flooded screws on the market
today. First is simple inlet modulation. An inlet valve on the first stage responds to increasing
system pressure by restricting the inlet flow. Second is variable displacement (spiral valve). This
method also controls only the first stage flow. Neither method addresses second stage capacity.
At full load, both types of compressors are operating with inlet valves wide open and have
near ambient pressure entering the rotor housing. As system pressure rises, the modulating
control will start to close the inlet valve, resulting in decreased pressure at the rotor face. If the
system requires 75% of the compressor's capacity, the inlet valve will restrict flow to the point
that the absolute pressure at the rotor face is 75% of ambient. At sea level, that would mean that
the pressure at the inlet to the rotors would be 11.03 PSIA instead of 14.7 PSIA. The first stage
would still compress this air 2.793 times and would discharge the air at 30.79 PSIA. Assuming
that the system pressure had risen a couple of pounds in order to signal the machine to modulate,
Rev.3.15.97 Tech Info -19
Back to TOC
_________Quincy Rotary Screw Sales Manual____________
the second stage would now be compressing from 30.79 PSIA to 116.7 PSIA. This would result
in a second stage compression ratio of 3.8. The total compression ratio is the sum of the two
stages, 2.79 + 3.8, or 6.59. This increase in total compression ratio offsets the decrease in mass
flow and makes part-load performance follow a standard modulating power curve.
Using a variable displacement airend on the first stage improves part-load performance
only slightly. The gas laws dictate that the fixed displacement second stage will draw the
interstage pressure down to the exact same level as in the modulating example when running at
less than full load. The same number of molecules occupying the same volume will result in the
same pressure. This means that the second stage compression ratio will be the same as the
modulating machine's second stage. The first stage compression ratio will drop because the
interstage pressure has dropped. The inlet valve remains open to the 14.7 PSIA ambient pressure
and it only has to compress up to 30.79 PSIA. In practice, exactly matching the first stage's
built-in pressure ratio to the interstage pressure at various load levels does not happen. If the
airend was designed to optimize full load performance, it is probably doing some
over-compression at part load.
The full load efficiency of a two-stage compressor with a spiral valve first stage will be
less that a comparable fixed displacement or curved lift valve compressor. Just as with
single-stage turn and spiral valve compressors, the cast-in ports in the bottom of the rotor housing
act as leak paths around the tips of the rotors. Sullair does not acknowledge this loss of efficiency
in either single-stage or two-stage literature.
Controllers for multiple machine installations of two-stage compressors are the same ones
used for single-stage compressors. They use a pressure-based logic that relies on deadbands to
stagger identically sized compressors. Any full load power savings can quickly evaporate with
several compressors running at less than full load.
Using the multiple machine example from a few pages earlier we can compare the
operating costs of a two-stage Ingersoll-Rand system to a Quincy Power$ync system. With the
Ingersoll system, one would need one 200 HP, 1100 CFM, 100 PSIG machine and four 200 HP,
990 CFM, 125 PSIG machines. Calculating the reduced horsepower required by the 125 PSIG
compressors running from 102 to 108 PSIG full load results in the following BHP consumption
levels:
Demand 2-Stage BHP Power$ync BHP Savings w/Power$ync
5000 CFM 1,012 1,063 <51>
2500 CFM 866.4 532.9 333.5
1600 CFM 669.2 344.1 325.1
Applying the same duty cycle and the same power costs as the previous example, the Quincy
Power$ync system would save over $61,000.00 per year, when compared to Ingersoll's
two-stage offering. ALWAYS look at the total system performance, not just one machine at one
operating point.
If, in the above example, the BHP listed for the 750 CFM compressor was 163, then the BHP
required at the 600 CFM level (80% of full load) would be 163 x .9577 or 156.1 BHP.
This is approximate flow based on 100% coefficient of flow. Sharp edged orifices may
flow as little as 65% of this amount and smooth, well-rounded orifices may flow as much as 97%
of the listed amount.
Hazardous Classifications (Quincy does not provide any equipment suitable for operation in an
area classified as hazardous.)
Class Ratings - Defines the type of hazardous substance in the surrounding atmosphere.
Class I defines an area in which the atmosphere contains flammable gases or vapors emitted by
liquids.
Class II defines an area in which the atmosphere contains conductive, carbon based, and
combustible dusts.
Class III defines an area in which the atmosphere contains ignitable fibrous materials.
Group Ratings - Defines the type of hazardous substance by its explosive rating based on
other known substances in descending order, from Class I, Group A to Class II, Group G.
Group A-D refer to atmospheres containing Class I gases, vapors and liquids.
Group E-G refer to atmospheres containing Class II conductive, carbon based, and combustible
dusts.
Division Ratings - Defines the degree of hazard by determining the hazardous substance's
expected concentration in the surrounding atmosphere.
Conversion Tables
TO CONVERT: INTO: MULTIPLY BY:
atmospheres torr 760
atmospheres cms of HG 76
atmospheres ft of water 33.9
atmospheres in of Hg 29.92
atmospheres kgs per sq meter 10,332
atmospheres millimeters of Hg 760
atmospheres pounds per square inch 14.7
atmospheres tons per square ft 1,058
bars atmospheres 0.987
bars pounds per square inch 14.5
British Thermal Units ft-pounds 777.6
British Thermal Units kilowatt-hours 2.929 x 10-4
BTU per minute watts 17.57
cm of mercury torr 10
cm of mercury atmospheres 0.01316
cm of mercury feet of water 0.4461
cm of mercury kgs per sq meter 136
cm of mercury pounds per sq ft 27.84
cm of mercury pounds per sq in 0.1934
cubic centimeters cubic feet 3.531 x 10-5
cubic centimeters cubic inches 6.102 x 10-2
cubic centimeters cubic meters 10-5
cubic feet cubic centimeters 2.832 x 104
cubic feet cubic inches 1,728
cubic feet cubic meters 0.02832
cubic feet cubic yards 0.03704
cubic feet gallons 7.481
cubic feet pounds of water 62.4
cubic feet per minute cubic cms per sec 471.9
cubic inches cubic centimeters 16.39
cubic inches cubic feet 5.787 x 10-4