2. Medium Voltage C.B (1kV to 52kV) 3. High voltage C.B (66kV to 220kV) 4. Extra high voltage (EHV) C.B (300kV to 765kV) 5. Ultra high voltage (UHV) C.B (above 765kV) Based on Location 1. Indoor type 2. Outdoor type Low and Medium voltage switchgears and high voltage gas insulated switchgear(GIS) are categorized as Indoor switchgears. whereas switchgear which has air as an insulating medium i.e Air insulated switchgear(AIS) are categorized as outdoor switchgears. Based on External design (outdoor type C.B) 1. Dead tank type 2. Live tank type Based on medium used for Arc quenching 1. Air-break C.B 2. Oil C.B 3. Air Blast C.B 4. Sulphur hexaflouride (SF6) C.B 5. Vaccum C.B Live Tank - the circuit breaker and the switching unit is located in an insulator bushing which is live at line voltage (or some voltage above ground). Live Tank circuit breakers are cheaper than dead tank and require less space. Dead Tank - the switching unit is located within a metallic container which is kept at earth potential. As the incoming / outgoing conductors are taken through insulated bushings, it is possible to place current transformers on these. (with a Live Tank arrangement this is not possible and separate CTs are required). LIVE TANK CIRCUIT BREAKER 6 DEAD TANK CIRCUIT BREAKER 7 Oil CB are not suitable for heavy current interruption at low voltages due to carbonization of oil. ABCB is quite suitable for high current interruption at low voltage. Air at atmospheric pressure is used as an arc extinguishing medium. Two pair of contacts: Main contacts and Arcing contacts. Main contact carry current when breaker is in closed condition They have low contact resistance. When contacts are opened, main contacts separate first , the arcing contact still remains closed. Therefore the current is shifted from main contact to arcing contact. The arcing contacts separate later on and the arc is drawn between them. Principle of High Resistance is employed for arc interruption. Arc resistance is increased by lengthening, splitting and cooling the arc. The arc length is rapidly increased employing arc runners and arc chutes. The arc moves upward by both electromagnetic and thermal effects.It moves along the arc runner and then it is forced into a chute. It is split by arc splitters. A blow out coil is employed to provide magnetic field to speed up arc movement and to direct the arc into splitters. Available in the voltage range of 400 to 12 kV. Widely used in low and medium voltage system. Extensively used with electric furnace, with large motors requiring frequent starting, in a place where chances of fire hazard exist. Also used in DC circuits upto 12 kV. Compressed air of 20-30 kg/cm2 is employed as an arc quenching medium. Suitable for operating 132kV & above and also been used in 11kV-33kV range for certain application. At present Sf6 C.B is used for 132kV and above, and vaccum CB for 11-33kV so air blast C.B are becoming obsolete. Cheapness and free availability of the interrupting medium, chemical stability and inertness of air. High speed operation Elimination of fire hazard Short and consistent arcing time and therefore, less burning of contacts Less maintenance Suitability for frequent operation Facility for high speed reclosure. An air compressor plant has to be installed and maintained. In residential areas, silencers need to be provided as high level noise is produced when arc intrruption takes place in air blast C.B. Problem of Current chopping Problem of restriking voltage. 2 types of air blast C.B 1. Cross-Blast Circuit Breaker 2. Axial-Blast Circuit Breaker 1. Cross-Blast Circuit Breaker: High pressure blast is directed perpendicularly to the arc for its interruption. The arc is forced into a suitable chute. Sufficient lengthening of arc is obtained, resulting in the introduction of appreciable resistance in the arc itself. Therefore resistance switching is not common in this C.B. Suitable for intrrupting high current (upto 100kA) at comparitively low voltage. High pressure blast of air is directed longitudinally i.e in line with the arc. Suitable for EHV and super high voltage application. This is because interrupting chambers can be fully enclosed in porcelain tubes. Resistance switching is employed to reduce the transient overvoltages. No. of breaks depends upon the system voltage, for ex. 4 at 220kV and 8 at 750kV. It is commissioned for 1100kV system. Types 1. Plain-break Oil Circuit breakers 2. Self-generated Pressure Oil Circuit Breaker a) Plain Explosion pot b) Cross-jet Explosion pot c) Self-compensated Explosion pot 3. Double Break Oil Circuit Breaker. 4. Bulk oil and Minimum Oil Circuit Breaker. It has a fixed and moving contact immersed in oil. When contacts separate there is a severe arc which decomposes the oil into gases. The gas obtained is mainly hydrogen The volume of gases produced is about 1000 times that of oil decomposed. Hence, the oil is pushed away from arc and the gaseous medium surrounds arc. The arc quenching factors are as follows: 1. Elongation of the arc 2. Formation of gaseous medium in between the fixed and moving contact. 3. Turbulent motion of the oil, resulting from the gases passing through it. Employed for low current interruption at comparatively low voltages. Used on low voltage dc circuits and low voltage ac distribution circuits. At higher voltages its size become large.so it requires large amount of oil. Can be used upto 11kV with an interrupting capacity upto 250 MVA. Arc energy is utilised to generate a high pressure in a chamber known as explosion pot or pressure chamber or arc controlling device. Contacts are enclosed within pot. Pot is made of insulating material and it is placed in the tank It has high interrupting capacity. Arcing time is reduced. Since the pressure is developed by the arc itself, it depends upon the magnitude of current. Simplest form of an explosion pot. When the moving contact separates a severe arc is formed .The oil is decomposed and gas is produced. It generates high pressure within the pot The high pressure causes turbulent flow of streams of gas into the arc resulting in arc extinction. If arc extinction doesnt occur in pot it occurs immediately after moving contact leaves the pot, due to high velocity axial blast of the gas which is released through the throat. Also known as axial extinction pot. Not suitable for breaking heavy currents. Suitable for interruption of medium range current. suitable for high current interruptions. Arc splitters are used. When moving contact is separated from the fixed contact an arc is formed. It is pushed into arc splitters and finally it extinguishes. It is combination of Plain jet and cross jet explosion pot. Its upper portion is cross-explosion pot and lower portion a plain explosion pot. On heavy currents the rate of gas generation is very high and consequently the pressure produced is very high, the pot operates as cross explosion pot. When current is low, the pressure is also low in the beginning , the arc is extinguished by plain explosion pot action. It is used for high speed arc interruption, particularly at low currents. It employs an immediate contact b/w fixed and moving contact. When the moving contact separates, the immediate contact also follows it. The arc first appears b/w fixed contact and immediate contact. soon after the immediate contact stops and a second arc appears b/w immediate contact and moving contact. The second arc is extinguished quickly by employing gas pressure and oil momentum developed by the first arc. In bulk oil C.B oil performs 2 functions. It acts as an arc extinguishing medium and it also serves as insulation b/w live terminals and earth. The tank is earthed. Its main drawback is that it requires a huge amount of oil at higher voltages. Due to this very reason it is not used at higher voltages. Advantage: the protective CT can be acommodated on the bushings instead of being supplied as separated piece of apparatus. In minimum Oil C.B container is made of porcelain or other insulating material. Consist of 2 sections : upper chamber and lower chamber. Upper chamber an arc control device, fixed and a moving contact. Lower chamber- acts as an insulating support and contains operating mechanism. Both chambers are filled with oil and are physically separated. Available in the voltage range of 3.3kV to 420kV. No. of interrupter units contained in a tank depends upon the fault current to be interrupted, and the system voltage. Up to 11kV, MOCB employs 1 interrupter per phase, 2 per phase at 132kV and 6 per phase at 275kV. Low Oil circuit Breakers Operation When the contacts are separated in oil, arc is formed. The heat of arc decomposes oil and gases are formed. These gases expand due to heating of the arc. The gas flowing near the contact zone cause cooling and splitting of the arc and the arc gets extinguished. 36