Sei sulla pagina 1di 36

The GreenBook

Green your Building with


Airflow Measurement
Breathe Easier!

Indoor Air Quality


Specify thermal dispersion airflow measurement

Thermal Dispersion Airflow Measurement

technology on your high-performance buildings


Breathe easier by improving IAQ. Its not only green, but ensuring the comfort and well-being of the occupants
makes good business sense since the benefits realized from increased productivity can offset the total cost of
energy to operate a building. EBTRON can provide airflow measurement solutions that result in energy efficient

building operation and improved IAQ.

EBTRON manufactures a full line of airflow measurement devices to meet any application requirement and budget.

Take advantage of our more than 25 years of experience in measurement and control. Contact EBTRON or one

of our 80 + independent representatives today. EBTRON will show you how to use airflow measurement devices

to satisfy LEED credit requirements, save energy and help green your building.

LEED is a registered trademark of the U.S. GREEN BUILDING COUNCIL.

Thermal Dispersion Airflow Measurement

1663 HWY. 701 S., Loris, S.C. 29569 Toll Free: 800 2EBTRON (232 8766) Fax: 843 756 1838 Internet: EBTRON.com
The EBTRON Green Book- 3

INTRODUCTION EBTRONs thermal dispersion tech-


nology relates the velocity of the air
NO COMPROMISE DESIGN
Control of HVAC system airflow rates to the power and rise in temperature
is essential for the successful opera- of a heated element in a moving air
Only the highest quality, stable,
tion of high performance buildings. stream. EBTRON uses a precision,
bead-in-glass thermistors are used
bead-in-glass, self-heated thermis-
in our airflow and temperature
Outside air and building pressure are tor as the heated element and another
measuring devices.
fundamental to ASHRAE Standard precision thermistor to measure the
62.1 compliance; a prerequisite for ambient air temperature. Multiple
Waterproof epoxy sensor potting
acceptable indoor air quality (IAQ). sensing points are used to produce an
compounds assure long life of sen-
Outside air for the dilution of con- average velocity for true volumetric
sors, even in the harshest environ-
taminants requires precise monitoring airflow (CFM or L/s). Each sensing
ments.
and control of outside airflow rates point is individually calibrated at up
into the building at each air handling to sixteen points to NIST-traceable
Gold plated interconnects on all
unit. Proper pressurization through airflow standards. Most models in-
critical electrical connections result
control of airflow rates is essential to clude a temperature output signal.
in years of trouble-free operation.
limit moisture development within
Switching power supplies reduce
the building envelope and for tem- Unlike differential pressure flow
heat and energy consumption while
perature and humidity control. rings or crosses that have very little
increasing the life of the devices.
sensitivity at low air velocities and
EBTRON has been a leader producing use percent of full scale accuracy
Electrically isolated output signals
thermal dispersion airflow measure- pressure transducers, the sensitivity
protect circuitry and facilitate inter-
ment products since 1984. Our trained to airflow increases as the flow rate
facing to the host BAS.
application specialists, combined decreases. As a result, accuracy is
with an extensive local representative percent of reading. Greater sensi-
Space-age alloys and high-tech
network, assure your designs meet the tivity results in better accuracy, espe-
plastics result in lightweight de-
performance requirements demanded cially with turn-down, compared to
vices that are cost-effective to ship,
for todays 21st Century buildings. differential pressure-based devices
easy to install and endure the ele-
and vortex shedders. As a result, the
ments that todays HVAC systems
AIRFLOW MEASUREMENT technology is ideal for the measure-
are exposed to.
PRODUCTS ment of the relatively low airflow
rates typically found in most HVAC
FEP plenum rated cables remain
EBTRON airflow measuring devices applications. Long term stability is
strong and pliable, even under the
(AMD) are the result of the Compa- assured by the selection of high qual-
extreme temperatures associated
nys more than 25 years of experience ity thermistors and signal processing
with outdoor air intakes.
manufacturing high-performance components. Unlike pressure-based
thermal dispersion instruments. devices and vortex shedders that fre-
Kynar coated wires are abrasion
AMDs are available to measure in quently require field calibration and
resistant and assure long-life in
ducts or plenums, fan inlets and a auto-zeroing, EBTRON does not rec-
HVAC environments that are sub-
range of specialty applications and ommend periodic calibration of its
ject to continuous vibration.
can interface with any building auto- airflow measuring devices. In fact,
mation system (BAS). there is no auto-zero function in any
EBTRON airflow measuring device.
It simply is not required.
The EBTRON GreenBook - 4

Duct/Plenum Airflow
EBTRON prides itself on manufac- Measurement (-P Sensor Probes)
turing only the highest quality prod-
ucts. Our no-compromise philoso- Duct/plenum probes are ideal for ap-
phy is evident throughout all of our plications requiring out-of-the-box
product lines. accuracy. This type of AMD has the
most predictable performance when
The Advantage product line was installed in accordance to published
originally comprised of two distinct placement guidelines. Duct/plenum
series, the GOLD Series and the mounted AMDs are ideal for sup-
SILVER Series. In 2008 the HY- ply/return (or exhaust) airflow track-
BRID Series, combined key features ing and the direct measurement of
of both. All Advantage products are outside air intake flow rates. Their
complete AMDs that include the versatile probe design allows them
sensor probes and transmitter. As a to be installed after the duct work is
result, no additional transmitters or installed.
transducers are required to interface
with your BAS. This results in single Fan Inlet Airflow Measurement
source responsibility with improved (-F Sensor Probes)
accuracy and lower equipment first-
cost. Transmitters are available with Fan inlet stations are designed to be
traditional analog output signals (0- installed directly in the inlet of cen-
10 VDC/4-20mA) as well as RS-485 trifugal and vane axial fans without
(BACnet MS/TB, BACnet ARC- significantly affecting fan perfor-
NET, Modbus RTU, JCI N2-Bus), mance. This technology is generally
Ethernet (BACnet TCP/IP, Modbus) applied when measurement in ducts
or Lon, all at no additional charge. or plenums is not feasible do to place-
ment limitations or excessive branch
Which Series is best for you? ducts at the AHU.

Series selection is based on the type Application Specific Airflow


of sensor probe, application, interface Measurement
requirements and budget.
EBTRON manufactures application
What sensor probe should you use? specific AMDs for small ducts, class-
room unit ventilators and desiccant
AMD sensor probe selection is de- wheel energy recovery ventilators.
pendent on your application. Consult
EBTRON or your local representa-
tive for application engineering and
product selection support. AMD sen-
sor probes are available for the fol-
lowing measurement applications:
The EBTRON Green Book- 5

Sensor Probe Compatibility GOLD HYBRID SILVER


Max Sensors 16 4 2
Max Probes (dependent of sensor type) 4 4 2
User Interface
16 Character Alpha-numeric LCD Display
Display Individual Sensor Airflow & Temperature
Push-button User Interface
Dip Switch User Interface
EB-Link Infra-red Interface to PDA
BAS Interface
Linear 0-10 VDC/4-20mA (isolated from main circuit)
Linear 0-10 VDC/4-20mA (isolated from 24 VAC)
RS-485 (BACnet ARCNET)
RS-485 (BACnet MS/TP, Modus RTU, JCI-N2-Bus)
RS-485 View Individual Sensor Values
Ethernet (BACnet-Ethernet, BACnet-IP, Modbus TCP, TCP/IP)
LonWorks Free Topology Interface
Special Functions
Field Cal Wizard
Live or Coefficient Digital Offset/Gain Adjustment
Digital Gain Adjustment Control
Output Rate of Change Dampening Filter
Variable Output Integration
Low Limit Airflow Cutoff
Velocity Weighted Temperature Output
Transmitter Circuitry and Construction
Gold Cable Receptacle Pins
Circular DIN Receptacle
Switching Power Supply
UL Listed
The EBTRON GreenBook - 6

LEED CERTIFICATION
EBTRON CAN HELP YOU ACHIEVE LEED CERTIFICATION
Based on LEED 2009 for New Con-
struction, Schools and Core & Shell.
Airflow measurement can be invaluable when designing for LEED certifica-
tion. A single AMD can have a cascading effect on multiple LEED points.
Todays society is keenly interested
One credit in particular, IEQ Credit 1, provides one point for measuring out-
in developing and supporting the
side air intake flow rates to all low occupant density spaces Credits that can
green initiative. EBTRON products
be impacted by the use of EBTRON AMDs include:
can help in obtaining a number of
LEED points, either directly or in-
EA Prerequisite 1 Fundamental Commissioning
directly, and are an essential compo-
nent of any green, high performance EA Prerequisite 2 Minimum Energy Performance
building.
EA Credit 1 Optimize Energy Performance
Measurement for monitoring and/or
control is a prerequisite for the effec- EA Credit 3 Enhanced Commissioning
tive and efficient operation of todays
high performance buildings. Failure EA Credit 5/5.1/5.2 Measurement, Verification & Submetering
to provide measurement devices for
monitoring and control of critical IEQ Prerequisite 1 Minimum IAQ Performance
building systems can result in reduced
IEQ Prerequisite 2- Environmental Tobacco Smoke Control
energy efficiency, occupant health
and building longevity. IEQ Prerequisite 3- Minimum Acoustical Performance

EBTRON products can make a differ- IEQ Credit 1 Outdoor Air Delivery Monitoring
ence in a buildings performance.
IEQ Credit 2 Increased Ventilation
EA Prerequisite 1 Fundamental
Commissioning IEQ Credit 3/3.1/3.2 - Construction IAQ Management Plan - Construction
and Occupancy
Prerequisite 1 in Energy and Atmo-
sphere (EA) requires that a building IEQ Credit 5 Indoor Chemical & Pollutant Source Control
has a commissioning authority and
plan. That plan shall provide a means IEQ Credit 6/6.2 Controllability of Systems - Thermal Comfort
to verify the installation and perfor-
IEQ Credit 7/7.1/7.2 - Thermal Comfort - Design & Verification
mance of the systems to be commis-
sioned. IEQ Credit 9 - Enhance Acoustical Performance

The HVAC system is one of the pri- IEQ Credit 10- Mold Prevention
mary energy-related systems that re-
quire commissioning. A number of ID Credit 1 - Innovation in Design
parameters verifying the performance
of this system can be documented us-
ing EBTRON products.
The EBTRON Green Book- 7

Permanently installed EBTRON b. Verify the operation of dampers Minimum Outside Air Control
airflow/temperature monitors can and actuators.
verify that the building performance EBTRONs duct or plenum AMDs
meets the Owners Project Require- 3. Verification of performance: are essential for the control of mini-
ments (OPR) and the Basis of Design mum outdoor air flow rates. On most
(BOD). These techniques improve a. Verify energy consumption us- systems, intake flow rates will vary
quality control by eliminating field ing both the airflow rate and dramatically as a result of damper
measurement error while providing temperature from the AMD. hysteresis, transient wind pressure,
permanent documentation of critical stack effect and changes in mixed
b. Verify design supply airflow
parameters. In addition, permanently air plenum pressure (VAV systems).
rates at each air handler, floor
mounted AMDs can result in more Simply resetting a damper or outside
and/or zone.
cost effective monitoring (faster, air fan to the same minimum position/
more frequent intervals) and can be c. Verify design discharge air tem- speed may not result in maintenance
used for additional functions, such as perature of heating/cooling coils of the desired setpoint. EBTRON
control to improve building operation when AMDs are installed down- testing has shown that the intake error
(and obtain additional LEED points). stream of coils. associated with any one of these fac-
Commissioning can be achieved us- tors can result in intake fluctuations
ing AMDs as follows: d. Validate coil performance by in- in excess of 30%. Cumulative errors
dicating the velocity and/or tem- are even greater. These uncertainties
1. Balancing: perature profiles downstream of are not properly taken into account in
coils. most building energy models and as
a. Set fan sheaves to obtain design a result buildings may not perform
flow rates of fan systems. e. Verify minimum and maxi- as well as model predictions. The
mum outside airflow rates are uncertainties are real, and significant
b.
Set variable frequency drive achieved during operation. benefits can be realized by monitoring
maximum and minimum speeds. and controlling minimum outside air
f.
Verify pressurization at each intake levels on ALL systems, regard-
c. Balance energy recovery ventila- specified pressure compartment less of model predictions.
tor intake and exhaust flow rates (i.e. building, floor, zone, etc.)
for proper ventilation and pres- by monitoring airflow supply/ Improved Air-side Economizer
sure control. return or supply/exhaust differ- Control
entials.
d. Set damper minimum/maximum
positions on modulating damp- ASHRAE 90.1-2007 requires modu-
EA Prerequisite 2 Minimum Energy
ers or set fixed damper positions lating air-side economizers. Con-
Performance
on manual damper systems. trol of air-side economizers is often
very poor since most strategies rely
Prerequisite 2 requires establishment
2. Verification of equipment opera- solely on damper position and reset
of the minimum level of energy effi-
tion: to achieve the desired mixed air or
ciency for the buildings and systems
supply air temperature setpoint. Poor
a. Verify the operation of fans, mo- to reduce the environmental and eco-
control results in lower energy effi-
tors, belts and variable frequen- nomic impact of excessive energy use
ciency. Economizer performance can
cy drives. via Whole Building Energy Simula-
be significantly improved by resetting
tion or the applicable ASHRAE Pre-
the outside air intake setpoint between
scriptive Compliance Path.
the minimum and maximum outside
The EBTRON GreenBook - 8

air intake flow rates. This can be Units are often oversized and require requisite 2 and can be applied to EA
achieved on systems with full size or adjustment in the field. On desiccant Credit 1.
min./max dampers using EBTRONs wheel ERVs, filters load on the intake
duct or plenum AMDs. This strategy side faster than they do on the exhaust Proper selection of AMDs at the
results in more stable temperature side. The imbalance in filter loading zone level on VAV systems is another
control while assuring that minimum results in decreased intake flow rates area where real-world performance
intake rates are met and never ex- when compared to the exhaust. EBT- improvements can be realized. EB-
ceeded. Proper economizer tempera- RON manufactures desiccant wheel TRONs ELF-D thermal dispersion
ture control is analogous to VAV box ERV intake/exhaust airflow measure- AMD and EBTRONs STA102-T
space temperature control on pressure ment stations designed to solve this thermal dispersion AMD for small
independent systems that reset the problem. ducts can allow for lower supply
flow setpoint rather than the damper airflow rates, hence lower duct stat-
position directly to improve space EA Credit 1 Optimize Energy ic pressures (less fan horsepower).
temperature control and assure mini- Performance Equally important, improved sensor
mum and maximum ventilation rates. accuracy at maximum turndown can
Implementing this strategy allows for EA Credit 1 provides up to 21 points significantly reduce reheat when com-
sequencing of dampers, which results for increasing the buildings level of pared to pneumatic flow technology
in lower pressure drop of AHU damp- efficiency above the baseline prereq- that is typically used in VAV terminal
ers, hence less fan energy. The inte- uisite. boxes. It is not improbable for tradi-
gral temperature output can be used tional terminal box flow technology
for high limit shutoff control in areas The proper selection of AMDs for to result in 20% or more error with
where use of dry-bulb temperature is both monitoring and control can have turndown when the uncertainty of the
acceptable. When supply and return a significant impact on the overall DDC pressure sensor is considered.
(and/or exhaust) airflow measure- energy performance of a building
ment is added, net building pressure compared to baseline values. Un- EA Credit 3 Enhanced
will also be maintained. The velocity fortunately, it is difficult to ascertain Commissioning
weighted temperature feature on all the actual performance of many of
GOLD and HYBRID transmitters can todays systems and sensors in real- EA Credit 3 requires additional verifi-
improve supply or mixed air tempera- world installations. As a result, the cation after initial system verification
ture measurement accuracy compared benefit of using high-performance required in EA Prerequisite 1.
to traditional serpentine sensors and AMDs is not always obvious to engi-
should be utilized whenever possible. neers and owners. The permanently mounted sensors
and monitors discussed in EA Pre-
Increased Efficiency of Exhaust Air HVAC energy efficiency can be sig- requisite 1 Fundamental Commis-
Energy Recovery Ventilators (ERV) nificantly improved by accurately sioning can also be used as part of a
monitoring key airflow rates, such as long-term continuous commission-
ERV energy performance (and proper outside air intake flow rates or by as- ing plan.
building pressure) requires that in- suring that air-side energy recovery
take and exhaust rates are properly systems are properly balanced and op- EBTRON AMDs are designed with
balanced. As with any outside air erating at maximum efficiency. Mini- high quality components and are not
system, flow rates are significantly mum outside air control, improved subject to drift. Interface flexibility
influenced by wind and stack pres- air-side economizer performance and allows for fast and accurate measure-
sures as well as mixed air plenum increase energy efficiency on ERVs is ment, independent of the BAS.
pressure variations on VAV systems. discussed in the section for EA Pre-
The EBTRON Green Book- 9

EA Credit 5/5.1/5.2 Measurement, ing/room pressure monitors to cases will significantly under or over
Verification & Submetering verify the integrity of the building ventilate the space.
envelope, seals and partitions.
EA Credit 5/5.1/5.2 requires ongo- The industry trend on high occupant
ing accountability of building energy IEQ Prerequisite 1 Minimum IAQ density spaces is to use CO2 based
consumption over time. Performance DCV. Although the concept of re-
setting the ventilation rates based on
The concept of installing measure- Prerequisite 1 in Indoor Environmen- CO2 levels is attractive, the technique
ment equipment for monitoring pur- tal Quality (IEQ) requires that build- is prone to numerous errors that re-
poses is often overlooked. In many ings meet the minimum requirements sult from steady-state assumptions
buildings, monitoring for control of the Ventilation Rate Procedure and measurement error. LEED pro-
is only a subset of the sensors that (VRP) of ASHRAE Standard 62.1- vides a point for the use of standalone
should be installed so that the over- 2007. CO2 sensors in high occupant density
all performance of the building can be spaces while requiring compliance
monitored and maintained over time. The VRP is very clear; it specifies with ASHRAE 62.1-2007. Unfortu-
Some examples of where EBTRON breathing zone outside air VENTILA- nately, CO2 DCV alone will not meet
monitoring devices could be benefi- TION RATES based on space type, the requirements of 62.1-2007.
cial over time are as follows: occupancy and area.
Improved CO2 methods can estimate
Monitor outside airflow rates on Low occupant density spaces, such the population using AMDs installed
fixed minimum and DCV sys- as offices or other spaces having an in the outside air intake and at each
tems with duct or plenum AMDs occupant density less than 25 people zone (mutlit-zone systems). However,
to make sure that minimum intake per 1,000 square feet, have minimal the uncertainties of CO2 based mea-
flow rates are maintained and DCV changes in the specified outside air surement may not meet the intent of
systems do not drive intake flow ventilation rate with typical changes Standard 62.1 or LEED. More accu-
rates above design maximums (i.e. in occupancy. Low occupant den- rate methods to count the population
fully occupied levels) or below sity spaces should have a duct or will improve DCV performance and
minimum levels affecting occupant plenum AMD installed in each out- include turnstiles, or electronic coun-
health or building pressure. Moni- side air intake. Minimum ventilation ters such as EBTRONs thermal oc-
toring also provides a method to rates should be calculated using the cupancy counter.
verify that damper actuators, link- guidelines of the ASHRAE 62.1 Us-
age, etc. have not malfunctioned. ers Manual and maintained during IEQ Prerequisite 2- Environmental
occupied periods. LEED provides Tobacco Smoke Control
Monitoring for tenant submetering for an additional credit for the direct
provides a process for corrective measurement of outside air intake Prerequisite 2 is designed to minimize
action if energy savings are not be- flow rates in IEQ Credit 1 Outdoor exposure of the building occupants
ing met. Air Delivery Monitoring. Demand and its components to Environmental
controlled ventilation (DCV) meth- Tobacco Smoke (ETS).
Monitor supply airflow rates to ods using CO2 based reset should BE
detect filter loading, belt slippage/ AVOIDED on low occupant density If Option 2 is chosen, designated
breakage, etc. spaces. The uncertainty associated smoking rooms/areas must have a
with CO2 DCV, especially at low oc- dedicated exhaust system to maintain
Monitor bleed airflow across cupant densities, cannot assure com- proper pressurization and isolation of
critical pressure zones with build- pliance with the Standard and in most ETS.
The EBTRON GreenBook - 10

EBTRON generally does not recom- being in accordance with the require-
IEQ Credit 1 Outdoor Air Deliv-
mend direct pressure control of fans ments of ASHRAE Standard 62.1-
ery Monitoring (1 Point)
or dampers. However, in the interest 2007.
of limiting overall costs, EBTRON
Provide a direct outdoor airflow
recommends that the following pres- Mechanically Ventilated Systems
measurement device capable of
sure control method be used to main-
measuring the minimum outdoor air
tain proper pressurization of smoking Low Occupant Density Spaces (under
intake flow rate with an accuracy
rooms/areas: 25 people per 1,000 sq.ft.):
of +/-15% of the design minimum
outside air as specified by ASHRAE
Install a bleed airflow room pres- IEQ Credit 1 awards 1 point for in-
Standard 62.1-2007. Generate an
sure monitor between the smoking stallation of a direct airflow measure-
alarm if the rates are not within tol-
room and adjacent area. ment device capable of measuring the
erance.
minimum outdoor air intake flow with
Install an automatic door closer on an accuracy of +/- 15% of the design
the entry door to the smoking room. minimum outdoor air rate as defined Standard since CO2 levels, at best,
by ASHRAE 62.1-2007, for all me- can estimate the amount of outdoor
Control the exhaust fan speed using chanical ventilation systems where air entering a space, per person. CO2
a variable frequency drive (VFD) 20% or more of the design supply must be combined with direct outdoor
and maintain at least 0.02 inches of airflow serves non-densely occupied airflow measurement on all systems,
water gauge negative pressure with spaces. The airflow measurement de- and accurate zone airflow measure-
respect to the adjacent area. vice should be capable of generating ment on multi-zone systems to assure
an alarm when the airflow values vary compliance with the Standard.
IEQ Prerequisite 3 - Minimum
by more than 10% from the design
Acoustical Performance IEQ Credit 2 Increased Ventilation
values.
(Schools only)
This requirement can easily be IEQ Credit 2 is designed to improve
IEQ Prerequisite 3 is designed to en- IAQ by providing at least 30% more
achieved by using any EBTRON
sure that classrooms are sufficiently breathing zone outdoor air than re-
duct or plenum probe (GTx116-P,
quiet to permit effective communica- quired by ASHRAE Standard 62.1-
HTx104-P). Proper model selection is
tion. 2007.
based on the size of the intake, budget
constraints and the desired installed
HVAC energy efficiency can be sig- Breathing zone outdoor air is directly
accuracy of the system
nificantly improved by accurately related to occupant productivity and
monitoring key airflow rates and health. When the cost of operating a
High Occupant Density Spaces
improved efficiency can result in re- facility takes into account the cost of
(greater than or equal to 25 people per
duced fan speeds and size and there- employee salaries, it becomes obvi-
1,000 sq.ft.):
fore, reduced noise. ous that productivity and health are
Monitor CO2 levels within all high
occupant density spaces. important criteria when evaluating the
IEQ Credit 1 Outdoor Air Delivery overall performance of a building.
Monitoring
Changes to ASHRAE Standard 62.1
in 2004 resulted in variable ventila- Typical employee costs, including
IEQ Credit 1 is designed to provide salaries and benefits, are up to 50
tion rates, per person, with changes
ventilation system monitoring to help times the cost of energy to operate a
in occupancy. As a result, a single
sustain occupant comfort and well- building. A 2% increase in productiv-
CO2 setpoint can no longer meet the
The EBTRON Green Book- 11

ity on an individual having an annual vices can be used as either permanent In addition to proper filtration, chemi-
salary of $50,000 would equate to a monitors or be removed and used on cals and hazardous particulates must
$1,000 benefit per year to an end-user. subsequent projects. be contained within boundaries as a
The 2% increase is conservative. An result of proper, compartmentalized
increase in outdoor air at the breath- IEQ Credit 3.2 Construction pressure control. Compartmental-
ing zone from 17 cfm to 22.1 cfm IAQ Management Plan - Before ized pressure control is most effec-
(based on the 30% increase required Occupancy tively accomplished by volumetric
to meet IEQ Credit 2 and default val- airflow control and/or tracking using
ues for office space in Standard 62.1) IEQ Credit 3.2 is designed to reduce accurate AMDs. Validation can be
will cost the end-user between $2 and indoor air quality problems resulting accomplished by monitoring pressure
$10 per year per person, depending from the construction/renovation pro- between critical pressure zones with
on the cost to condition the additional cess prior to occupancy. bleed airflow sensors.
outside air. Clearly, there is a signifi-
cant benefit to all by fulfilling the re- Option 1 Flush-out IEQ Credit 6/6.2 Controllability of
quirements of this credit. Systems
Requires that a total air volume of
Airflow measurement is a prerequi- 14,000 cu.ft. of outside air per sq.ft. IEQ Credit 6/6.2 requires that a high
site for ensuring that ventilation rates (while maintaining 60 F and rela- level of thermal comfort control be
specified by ASHRAE Standard 62.1 tive humidity no higher than 60%) of provided to individual occupants or
are delivered to the breathing zone in floor area is provided to flush-out con- groups of occupants sharing spaces.
both low and high occupant density taminants. This volume of air can be If local thermal comfort adjustments
spaces. provided prior to occupancy or during made by the occupants result in
occupancy during a flush-out pe- changes to the supply ventilation rates
IEQ Credit 3/3.1 Construction IAQ riod as specified by the requirement. to the space, a cascading effect on
Management - During Construction system performance will result with-
By installing AMDs to meet the re- out proper monitoring and control.
IEQ Credit 3/3.1 is designed to reduce quirements of IEQ Prerequisite 1 and On VAV systems, this is generally
IAQ problems resulting during the IEQ Credit 1 you will already have understood (although often ignored).
construction/renovation processes. provided the instrumentation required However, many other systems will
to meet this credit if the flush-out will also have significant changes in sys-
Pathway interruption requires that the be accomplished using the existing tem performance. Examples of such
work area is negatively pressurized to HVAC system. Simply use the out- systems include: under-floor systems
minimize the migration of construc- side air AMD to totalize the volume with manually adjusted floor diffus-
tion site contaminants. Depending on of air provided during the flush-out ers, constant volume systems that al-
the type(s) of systems used in the con- periods until the required air volume low for local changes in supply flow
struction and occupied zones, the use is achieved. rates to adjust space temperature and
of AMDs to provide compartmental- cycling heat pump systems without a
ized pressure control is essential. IEQ Credit 5 Indoor Chemical & dedicated outside air system.
Pollutant Source Control
In addition, verification of proper On these systems, changes in the
pressurization between construction IEQ Credit 5 is designed to minimize space temperature setpoint that
and occupied zones can be accom- the exposure of building occupants to change supply airflow rates will alter
plished by using one of EBTRONs hazardous particulates and chemical the breathing zone outdoor air. It may
bleed airflow sensors. These de- pollutants. also affect coil performance, building
The EBTRON GreenBook - 12

pressure and humidity control. As Zone air: Supply registers only Return air: When combined with
a result, the following airflow rates operate effectively over a specified supply airflow measurement, re-
should be monitored and controlled: range of airflow rates. EBTRON turn airflow measurement can be
AMDs can drastically improve used for airflow tracking to assure
Outdoor air intakes: Intake flow zone flow performance and thermal proper building pressure control, a
rates will change with changes in comfort by limiting minimum and prerequisite for proper space tem-
supply air volume if not monitored maximum supply flow rates and perature and humidity control.
and controlled as a result of chang- setting alarms when applicable.
ing pressures in the mixing box. Zone air: Supply diffusers only
Uncontrolled intake flow rates can IEQ Credit 7/7.1 and 7.2 Thermal operate effectively over a specified
result in the inability of the system Comfort Design/Verification range of airflow rates. On VAV
to maintain space temperature and systems, measurement error (drift,
humidity as a result of too much IEQ Credits 7/7.1 and 7.2 require that low flow uncertainty) from tradi-
outside air (insufficient capacity to a high level of thermal comfort be tional pneumatic airflow measure-
handle the latent load) or too little provided for the occupants. ment devices cannot assure that
outside air (uncontrolled infiltra- the optimal range of flows are de-
tion of high dew point outside air When it comes to thermal comfort, livered, thus resulting in very poor
through the building envelope). proper control of airflow rates is an diffuser performance and thermal
essential prerequisite. Generally, air- comfort. EBTRON AMDs can
Supply air: Supply airflow rates flow rates cannot be properly main- drastically improve VAV zone flow
affect a systems ability to provide tained during operation without moni- performance. As an added benefit,
proper temperature and humidity toring and feedback control. accurate, thermal dispersion zone
control. Systems that allow oc- airflow measurement can also re-
cupant control of supply airflow The critical airflow rates that should duce wasted reheat, lower supply
rates to modify space temperature be monitored and/or controlled to as- airflow rates at the box (lower duct
should, at a minimum, include sup- sure proper thermal comfort are as static pressure) and improve DCV
ply airflow measurement high and follows: performance.
low limit alarms.
Outdoor air intakes: Uncontrolled IEQ Credit 9 - Enhanced Acoustical
Return (or exhaust) air: If supply intake flow rates can result in the Performance (Schools)
airflow rates are varied, building inability for the system to maintain IEQ Credit 9 is designed to provide
pressurization could be affected space temperature and humidity classrooms that are quiet to allow for
since the supply/return or supply/ as a result of too much outside air effective communication.
exhaust differential flow rate is (insufficient capacity to handle the HVAC energy efficiency can be sig-
directly related to building/space latent load) or too little outside air nificantly improved by accurately
pressure. When combined with (uncontrolled infiltration of high monitoring key airflow rates and
supply airflow measurement, return dew point outside air through the improved efficiency can result in re-
(or exhaust) airflow measurement building envelope). duced fan speeds and size and there-
can be used for airflow tracking fore, reduced noise.
to assure proper building pressure Supply air: Improper airflow rates
control, a prerequisite for proper will result in poor coil performance
space temperature and humidity and discharge air temperature/hu-
control. midity control.
The EBTRON Green Book- 13

IEQ Credit 10 - Mold Prevention The VRP specifies breathing zone For low occupant density, multi-zone
(Schools) outside air based on space use, floor spaces, the minimum outside airflow
area and occupancy and the optimal rates should be set to maintain or ex-
IEQ Credit 10 is designed to reduce design is dependent on whether the ceed the minimum requirements spec-
the potential presence of mold in system is single or multi-zone and ified by the VRP of ASHRAE Stan-
schools through preventative design low or high occupant density. dard 62.1. ASHRAE provides an easy
and construction. Single Zone, low occupant density to use Microsoft Excel spreadsheet
for the determination of minimum
Accurately monitoring and control- Low occupant density spaces typi- ventilation rates with the ASHRAE
ling key airflow rates can result in cally have occupancy levels greater 62.1-2007 Users Manual, available
proper building pressurization which than 70% of the maximum expected for sale from ASHRAE.
could prevent the infiltration of mois- occupancy. For a typical office space,
ture into the building envelope there- a reduction in occupancy of approxi- On multi-zone systems, the percent-
by reducing the potential for mold mately 30% will only result in a de- age of outdoor air required from zone
growth and water damage. crease in the required outside air of to zone will typically vary as a result
10%. The outside air reduction of of varying thermal loads between
ASHRAE STANDARD 62.1-2007 10% is well under the uncertainty of zones. As a result, there will be at
most DCV techniques, therefore elim- least one zone that requires more out-
ASHRAE 62.1 2007, Ventilation for inating the application of DCV on this door air as a percentage of the supply
Acceptable Indoor air Quality, is the type application. air than the others. This is known as
industry standard defining ventilation the critical zone.
rates of outside air required to pro- For low occupant density, single zone
vide acceptable IAQ. The Standard spaces, the minimum outdoor airflow Critical zone fractions that are con-
has two procedures, the VRP and the rates should be set to maintain or ex- siderably higher than surrounding
IAQ Procedure, which engineers and ceed the minimum requirements spec- zones can have a dramatic impact on
building owners must select only one ified by the VRP of ASHRAE Stan- minimum ventilation rate required.
for compliance. The IMC, 2006 & dard 62.1 for the maximum expected This is especially true on multi-zone,
2009 LEED and many local codes occupancy. Note that the maximum mixed occupant density spaces hav-
reference the VRP for compliance. expected occupancy for a spaces cur- ing small, variable occupancy con-
Both the VRP and IAQ Procedure rent use may be less than the design ference rooms. When one zone has
specify ventilation rates for IAQ. occupancy of the space. a disproportionately high critical zone
fraction, consideration for increasing
Because the IAQ Procedure has many Install a permanently mounted, EB- the supply flow rate, providing recir-
subjective components, the use of the TRON duct or plenum AMD in the culated plenum air or a installing a
VRP is typically recommended by minimum outdoor air intake to moni- dedicated outdoor air system to the
EBTRON. However, the IAQ Pro- tor and/or control minimum outdoor zone should be considered.
cedure can be extremely useful when airflow rates.
used in conjunction with the VRP on Multi-zone, low occupant density On some buildings, calculating the
contaminants that are present and de- minimum ventilation rate based on
tectable in buildings above threshold As is the case with low occupant den- seasonal load changes may result in
limits. However, when this is done, sity single zone systems, there is little some savings on minimum ventila-
the minimum ventilation rates speci- benefit of implementing DCV on this tion rates.
fied by the VRP must be maintained. type of system.
The EBTRON GreenBook - 14

Install a permanently mounted, EB- CO2-Based DCV


THINK OUTSIDE THE BOX
TRON duct or plenum AMD in the
minimum outdoor air intake to moni- Changes implemented in 2003 to the
The VRP requires that the applica-
tor and/or control minimum out air- VRP by addendum n redefined how
tion/use, floor area, supply airflow
flow rates. CO2 DCV could be used for compli-
and occupancy of each zone be
ance. CO2 levels do not directly in-
known to determine the ventilation
Single Zone, high occupant density dicate population as many incorrectly
rate required to satisfy the standard
assume. At best, CO2 levels indicate
in real-time.
High occupant density spaces typi- the rate that outdoor air is entering a
cally, but not always, have significant space per person (OA cfm/person).
Dont forget to take advantage of the
changes in occupancy throughout the
counting systems that may already
day. When an occupancy change re- One method to use CO2 is to monitor
be in place in your facility when
sults in a reduction of the required the differential CO2 (CO2) level be-
selecting a DCV system. Direct
outdoor airflow rate by more than tween the outside and interior space.
counting has far less uncertainty
10%, there is motivation to use some Assuming steady-state and the default
than CO2 based strategies. Several
type of DCV strategy to reduce en- CO2 production rate, typically that for
examples of counting systems that
ergy consumption. office work, the CO2 level has a cor-
may present but not part of your
responding outside airflow rate for a
DCV strategy include the following:
DCV is compelling, but not always given population (a transient-state
effective, as a result of uncertain- model can also be applied). Reset
Computer logons of employees at
ties in the technique used to estimate the outdoor air setpoint to the calcu-
their workstation
changes in occupancy. The following lated setpoint between minimum and
methods may be used for DCV. Care design maximum population values. Turnstile counters in arenas, the-
should be taken when implementing By resetting the outdoor air setpoint atres, etc.
any of these strategies and one should in this manner, the control system
not forget that the core mission in can adjust to changes in population. Electronic time card systems
providing outdoor air is to improve This method can be simplified using
occupant satisfaction and well-being. the straight-line approximation sug- Video imaging counters for oc-
EBTRON has developed an ASHRAE gested by Stanke. Regardless of the cupancy monitoring in large gath-
62.1 BACnet DCV Calculator that method used, one should exercise ex- ering areas (casinos, exhibition
can calculate the setpoint required treme caution in relying on CO2 DCV halls, etc.)
for compliance with any of the DCV for Standard compliance since the
methods indicated below, thus elimi- uncertainty of this DCV technique is
nating overhead required making the extreme and not generally understood
cumbersome calculations by the host by most users. In many cases CO2-
control system. based DCV will under or over venti-
late by more than 50%.
In all cases, install a permanently
mounted, EBTRON duct or plenum Another method uses the CO2 level
AMD, in the minimum outdoor air between the supply air and zone. This
intake to control minimum outdoor differential is generally very small
airflow rates. and sensor error becomes a significant
factor. To minimize sensor error, a
single sensor with sampling capabili-
The EBTRON Green Book- 15

ties should be used to sample both the occupancy. On single zone systems, One method uses zone CO2 levels and
supply and space CO2. This method this technique will set the outside air airflow measurement to estimate the
uses the steady-state (or transient- intake setpoint to fully occupied con- population of each zone (or at least of
state) model and the supply airflow ditions. This technique should be critical zones). Once the population
rate to the space to estimate the popu- avoided if the space will be occupied is known for each space, the ventila-
lation. frequently by a one or two people dur- tion rates specified by the Standard
ing unoccupied periods (example: for mutli-zone recirculating systems
Direct Occupancy Count DCV a teacher stays in a classroom much can be established and the correct out-
of the day when the students are not door air setpoint be maintained based
Direct occupancy counting systems, present). on zone occupancy, zone floor area
such as electro/mechanical turnstiles, and zone supply airflow rates. As
thermal and video imaging sensors Multi-zone, high occupant density with all methods relying on CO2 lev-
and other IR devices are a much els, there is considerable uncertainty
more reliable method for DCV than There is also often justification to re- in the population estimates as a result
its CO2-based counterpart. On sin- duce the outside airflow rate below of steady-state assumptions, CO2 pro-
gle zone systems, the breathing zone design occupancy conditions on mul- duction level and CO2 measurement
outdoor air is calculated by adding a tiple zone systems. However, meet- error.
fixed floor component to the variable ing ASHRAE Standard 62.1 speci-
occupancy component. Following fied ventilation rates is not as straight As with high occupant density, single
VRP procedures, the corresponding forward since the fraction of outdoor zone systems the differential CO2
outdoor air setpoint can be easily cal- air in the supply air required to sat- (CO2) level between the supply air
culated and reset. isfy each zone will differ from space and zone could also be used to esti-
to space. mate the occupancy of each zone us-
Scheduling DCV ing a single, sampling sensor.
In all cases, install a permanently
The use of occupancy/time schedules mounted, EBTRON duct or plenum Direct Occupancy Count DCV
can be an effective method for DCV. AMD, in the minimum outdoor air
On single zone systems, the breath- intake to control minimum outdoor Direct occupancy counting systems
ing zone outside air is calculated by airflow rates. is perhaps the best method for DVC.
adding a fixed floor component to Once the population is known for
the scheduled occupancy component. CO2-Based DCV each space, the ventilation rates speci-
Following VRP procedures, the cor- fied by the Standard for mutli-zone re-
responding outdoor air setpoints can Multi-zone conditions complicate circulating systems can be established
be easily calculated and reset using a CO2 DCV application. Many either and the correct outdoor air setpoint be
time schedule. ignore the multi-zone requirements of maintained based on zone occupancy,
ASHRAE 62.1-2007 and treat multi- zone floor area and zone supply air-
Binary (occupied/unoccupied) DCV ple zones as a large single zone or use flow rates.
a zone CO2 sensor to reset zone sup-
Binary detection of occupancy is ben- ply airflow rates and provide reheat.
eficial when spaces operate at near Treating multiple zones as a single
design occupancy levels (70% or zone does not meet the requirements
greater) when occupied. In most cas- of Standard 62.1 and zone reset will
es, a simple IR or combination IR/ul- result in wasted reheat.
trasonic detector is used to determine
The EBTRON GreenBook - 16

Scheduling DCV Binary (occupied/unoccupied) DCV can be modified to use a ventilation


matrix based on design occupancy
The use of occupancy/time schedules Binary detection of occupancy is and load if the space will be occupied
can be an effective method for DCV. beneficial when spaces operate at frequently by a one or two people dur-
The ventilation rates specified by the near design occupancy levels (70% ing unoccupied periods (see previ-
Standard for mutli-zone recirculat- or greater) when occupied. In most ous page).
ing systems can be estimated and the cases, a simple IR motion detector
correct outdoor air setpoint be main- or combination IR/ultrasonic detec-
tained based on scheduled zone occu- tor is used to determine occupancy.
pancy, zone floor area and zone sup- The ventilation rates specified by the
ply airflow rates. Standard for mutli-zone recirculat-
ing systems can be established and an
approximate outdoor air setpoint be
maintained based on maximum zone
occupancy, zone floor area and zone
supply airflow rates. This technique

LOW-RISK BINARY OCCUPANCY DETECTION DCV

The setpoint matrix below was established using ASHRAE 62.1-2007 guidelines on a three room classroom based on
all occupancy combinations of either full occupancy (35) or zero occupancy. Binary sensors placed in each classroom
would set the outside airflow rate to the outside air setpoint listed in the table (bottom left).

The actual outside air required for a given set of population and load conditions is listed in the table as OA Required
(bottom right). The actual outside air delivered is listed as OA Provided. Note that in all cases, the classrooms were
adequately ventilated. Although the maximum demand controlled reductions was not achieved, this technique would
never have placed the students at risk (our core goal?) as is possible with CO2 DCV techniques.

Setpoint Matrix
Actual Conditions
Rm. 1 Rm. 2 Rm.3 OA
Status Status Status Setpoint Rm. 1 Rm. 2 Rm. 3 OA OA
Pop. Pop. Pop. Provided Required
OCC OCC OCC 1410
33 28 34 1410 1322
OCC OCC UNOCC 1035
33 28 1 1410 1037
OCC UNOCC OCC 1035
33 3 1 1410 817
UNOCC OCC OCC 1035
2 3 1 1410 425
OCC UNOCC UNOCC 605
33 28 0 1305 946
UNOCC OCC UNOCC 605
33 0 0 605 578
UNOCC UNOCC OCC 605
0 0 0 0 0
UNOCC UNOCC UNOCC 0
The EBTRON Green Book- 17

CV/VAV
Supply fan only, minimum OA mode

OA

AMD MD

OA SA

MD

RA

NOTES:

1. Modulate OA and RA dampers in sequence to maintain min. OA.


2. OA=Qp

COMMENTS:

1. If OA is greater than desired Q p, system requires exhaust or relief.


2. Not recommended for DCV since building pressure will vary consid-
erably with changes in OA.
The EBTRON GreenBook - 18

CV/VAV
Supply fan with constant exhaust or relief fan, minimum OA mode

EX

OA

AMD MD

OA SA

MD

RA

NOTES:

1. Modulate OA and RA dampers in sequence to maintain min. OA.


2. Use air balance measurement or permanently mounted AMD for con-
stant volume exhausts (i.e. toilets).
3. OA-EX=QP
4. Not recommended for DCV since building pressure will vary con-
siderably with changes in OA and here is no provision for exhaust
airflow reset.
The EBTRON Green Book- 19

CV/VAV
Supply fan with variable exhaust or relief fan, minimum OA mode

EX

AMD

QP

OA

AMD MD

OA SA

MD

RA

NOTES:

1. Modulate OA and RA dampers in sequence to maintain min OA.


2. OA-EX=QP
3. Modulate EX fan to maintain QP
4. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below lowest EX flow.

Do not allow QP to over-pressurize the building when DCV OA


requirements are high.
The EBTRON GreenBook - 20

CV/VAV
Supply fan with variable exhaust or relief fan, modulating economizer

EX

AMD

QP

Reset OA setpoint
OA

AMD MD CW TS

OA SA

MD

RA

NOTES:

1. Modulate OA, RA dampers and then cooling coil in sequence to reset OA


setpoint to maintain supply air temperature.
2. OA setpoint must not fall below minimum required for IAQ /ventilation.
3. OA-EX=QP.
4 .Modulate EX fan to maintain QP.
5. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below lowest EX flow.

Do not allow QP to over-pressurize the building when DCV require-


ments are high.
The EBTRON Green Book- 21

CV/VAV
Supply/Return fan system, minimum OA mode (no relief at AHU)

Toilet
EX

OA

AMD MD

OA SA

MD

RA

NOTES:

1. Modulate OA damper, RA fan and RA damper in sequence to main-


tain minimum. OA.
2. OA-EX=Qp

COMMENTS:

1. If OA is greater than desired Qp, system requires exhaust or relief.


2. Not recommended for DCV since building pressure will vary consid-
erably with changes in OA.
The EBTRON GreenBook - 22

CV/VAV
Supply/Return fan system, minimum OA mode (active relief at AHU)

Toilet
EX

OA

AMD
AMD MD

OA SA

2 MD
Pos QP AMD

RE RA

OPEN
BS

Optional

NOTES:

1. Modulate OA and RA dampers in sequence to maintain minimum OA.


2. SA-(RA+EX)=QP.
3. Modulate RA fan to maintain QP.
4. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below EX flow.

Do not allow QP to over-pressurize the building when DCV OA


requirements are high.
The EBTRON Green Book- 23

CV/VAV
Supply/Return fan system, modulating economizer

Toilet
EX

Reset OA setpoint
OA

AMD
AMD MD CW TS

OA SA
Assume ERV, if present,
is totally bypassed on this MD
2
system. Pos QP AMD

RE RA

OPEN
BS

Optional

NOTES:

1. Modulate OA - RA dampers and then cooling coil in sequence to reset


OA setpoint to maintain supply air temperature.
2. OA setpoint must not fall below minimum required for IAQ.
3. SA-(RA+EX)=QP exercised when applying DCV.
4. Modulate RA fan to maintain QP.
5. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below lowest EX flow.

Do not allow QP to building when DCV requirements are high.


The EBTRON GreenBook - 24

CV/VAV
Supply/Relief fan system, minimum OA mode (no relief at AHU)

Toilet
EX

OA

AMD MD

OA SA

2 MD
Pos

RE RA
CLOSED

NOTES:

1. Modulate OA damper, RA fan and RA damper (Relief fan and Recir-


culation damper) in sequence to maintain minimum OA.
2. OA-EX=QP.

COMMENTS:

1. If OA is greater than desired QP , system requires exhaust or relief.


2. Not recommended for DCV since building pressure will vary consid-
erably with changes in OA.
The EBTRON Green Book- 25

CV/VAV
Supply/Relief fan system, minimum OA mode (active relief at AHU)

Toilet
EX

OA

AMD
AMD MD

OA SA

2 MD
Pos AMD

RE RA
OPEN
QP

NOTES:

1. Modulate OA and RA dampers in sequence to maintain min OA.


2. S A-(RA+EX)=QP .
3. Modulate RE fan to maintain QP .
4. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below EX flow.

Do not allow QP to over-pressurize the building when DCV OA


requirements are high.
The EBTRON GreenBook - 26

CV/VAV
Supply/Relief fan system, modulating economizer

Toilet
EX

Reset OA setpoint
OA

AMD
AMD MD CW TS

OA SA

2 MD
Pos AMD

RE RA
OPEN
QP

NOTES:

1. Modulate OA and RA dampers then cooling coil in sequence to reset


OA setpoint to maintain supply air temperature.
2. OA setpoint must not fall below minimum required for IAQ.
3. SA-(RA+EX)=QP
4. Modulate RE fan to maintain QP .
5. Caution should be exercised when applying DCV.
Do not allow OA setpoint to fall below lowest EX flow.

Do not allow QP to over-pressurize the building when DCV re-


quirements are high.
The EBTRON Green Book- 27

CV/VAV
Single Supply/Return serving multi-floor system, minimum OA mode (no relief at AHU)

T o ile t
EX

AMD

SA1
Q P1
OA

AMD MD SA Fan SP MD AMD

T o ile t
EX
RA1
OA
MD

SA2
AMD
R A F an SP

RA2

MD AMD

NOTES: Q P2

1. Modulate SA and RA fans to maintain duct static (w/reset)


2. Modulate OA and RA dampers in sequence to maintain total OA.
3. SA-(RA+EX)=QP at each zone.
4. Modulate RA floor dampers to maintain QP for each floor.
COMMENTS:
1. This method compensates stack effect on tight floor to floor construc-
tion, and without vertical path for stack flow (i.e. open stairwell, atri-
um and some elevator shafts).
The EBTRON GreenBook - 28

CV/VAV
Single Supply/Return or Supply/Relief serving multi-floor system, minimum OA mode (active relief at AHU)
T o ile t
EX

AMD

SA1
Q P1
OA

AMD MD SA Fan SP MD AMD

T o ile t
EX
RA1
OA
2 MD
P os

RE
SA2
OPEN AMD
R A F an SP
BS

R ecom m en ded
RA2

MD AMD

NOTES: Q P2

1. Modulate SA and RA (or RE) fans to maintain duct static (w/reset).


2. Modulate OA and RA dampers in sequence to maintain total OA.
3. SA-(RA+EX)=QP at each zone.
4. Modulate RA floor dampers to maintain QP for each floor.

COMMENTS:

1. This method compensates stack effect on tight floor to floor construc-


tion, and without vertical path for stack flow (i.e. open stairwell, atri-
um and some elevator shafts).
The EBTRON Green Book- 29

CV/VAV
Single Supply/Return or Supply/Relief serving multi-floor system, modulating economizer
T o ile t
EX

AMD

R eset O A s etpoint SA1


Q P1
OA

AMD MD CW T S SA Fan SP MD AMD

T o ile t
EX
RA1
OA
2 MD
P os

RE
SA2
OPEN AMD
R A F an SP
BS

R ecom m en ded
RA2

MD AMD

Q P2
NOTES:

1. Modulate OA and RA dampers then cooling coil in sequence to reset


OA setpoint to maintain supply air temperature.
2. Modulate SA and RA (or RE) fans to maintain duct static (w/reset).
3. SA-(RA+EX)=QP at each zone.
4. Modulate RA floor dampers to maintain QP for each floor.

COMMENTS:

1. This method compensates stack effect on tight floor to floor construc-


tion, and without vertical path for stack flow (i.e. open stairwell, atri-
um and some elevator shafts).
The EBTRON GreenBook - 30

CV/VAV
Systems with minimum OA ERV, minimum OA mode

OA AMD

SA
OA

EX

AMD RA
QP

If there is no bypass on ERV, se-


lect an EBTRON HTx104-E for
OA/EX measurement at the desic-
cant wheel.

NOTES:

1. Modulate ERV OA fan to maintain min. OA.


2. OA-EX=QP
3. Modulate ERV EX fan to maintain QP .

COMMENTS:

1. Active control is required to compensate for filter loading, stack, and


mixed air plenum pressure (VAV) effects and to partially compensate
for wind, on forced makeup or ERV fan system.
The EBTRON Green Book- 31

CV (multiple AHUs)
Systems with single minimum OA ERV, minimum OA mode

BD

OA1 SA1

BD

OA AMD EX1
RA1

OA
BD

EX
SA2
OA2
AMD
QP
BD

EX2 RA2

NOTES:

1. Modulate ERV OA fan to maintain min. OA.


2. OA-EX=QP
3. Use air balance measurement or permanently mounted AMD to man-
ually balance OA and EX at each AHU zone.
4. Modulate ERV EX fan to maintain QP

COMMENTS:

1. Active control is required to compensate for filter loading, wind and


stack pressure effects on forced makeup or ERV fan system.
2. Do not use manual adjustment to AHU zones on cycling fan systems.
The EBTRON GreenBook - 32

VAV (multiple AHUs) [low-rise only]


Systems with single minimum OA ERV, minimum OA mode

OA1

AMD MD

OA1 SA1

BD

OAFan SP
EX1
RA1

OA

EX
SA2
AMD
OA2
AMD MD
QP

OA2

EX2 RA2

BD

NOTES:

1. Modulate ERV OA fan to maintain duct static pressure (w/reset).


2. Modulate OA dampers to maintain AHU OA at each zone.
3. OA-EX=QP
4. NOT BEST METHOD: Use air balance measurement or permanently
mounted AMD to manually balance OA and EX at each AHU zone.
5. Modulate ERV EX fan to maintain overall QP

COMMENTS:

1. Active control is required to compensate for filter loading, wind, stack and
mixed air plenum pressure (VAV) effects on forced makeup or ERV fan
system.
The EBTRON Green Book- 33

CV/VAV (multiple AHUs or FCUs)


[low or high-rise]
Systems with single minimum OA ERV, minimum OA mode

OA1

AMD MD

OA1 SA1
Q P1

MD AMD

O A F an SP
EX1
RA1

OA

EX
SA2
OA2
EX Fan SP AMD MD

OA2

EX2 RA2

MD AMD

Q P2
NOTES:

1. Modulate ERV OA and EX fans to maintain duct static (w/reset).


2. Modulate OA dampers to maintain AHU OA at each zone.
3. OA-EX=QP at each zone.
4. BEST METHOD: Modulate AHU EX dampers to maintain QP at each
zone.

COMMENTS:

1. This method compensates for all external and system pressure effects.
The EBTRON GreenBook - 34

CV/VAV (multiple AHUs or FCUs)


[low or high-rise]
Systems with single bypass ERV, modulating economizer

R eset O A 1 setpo int


OA1

AMD MD CW TS

OA1
SA1
Q P1

MD AMD

B yp a ss O A F an SP EX1
OA RA1
R eset O A 2 setpo int

CW TS

SA2
B yp a ss OA2
EX EX Fan SP AMD MD

OA2

EX2 RA2

MD AMD

Q P2

NOTES:

1. Modulate ERV OA and EX fans to maintain duct static (w/reset).


2. Modulate OA damper then cooling coil at each zone in sequence to
reset zone OA setpoint to maintain supply air temperature.
3. OA-EX=QP at each zone.
4. Modulate AHU EX dampers to maintain QP at each zone.

COMMENTS:

1. This method compensates for all external and system pressure effects.
Stop Blowing Money!

Energy Conservation
Specify for your high-performance buildings

Thermal Dispersion Airflow Measurement

Continuously verify system performance Improve economizer stability


Optimize outside airflow delivery Balance energy recovery ventilators
Maintain building pressure Reduce fan energy
Improve thermal comfort Minimize wasted reheat

EBTRON manufactures a full line of airflow measurement devices to meet any application requirement and
budget. Take advantage of our more than 25 years of experience in measurement and control. Contact EBTRON
or one of our 80 + independent representatives today. EBTRON will show you how to use airflow measurement
devices to satisfy LEED credit requirements, save energy and help green your building.

LEED is a registered trademark of the U.S. GREEN BUILDING COUNCIL.

Thermal Dispersion Airflow Measurement

1663 HWY. 701 S., Loris, S.C. 29569 Toll Free: 800 2EBTRON (232 8766) Fax: 843 756 1838 Internet: EBTRON.com
LEED with

Thermal Dispersion Airflow Measurement

LEED Certification
IEQ Credit 1 (1 Point) Outdoor Air Delivery Monitoring
Provide a direct outdoor airflow measurement device capable of
measuring the minimum outdoor air intake flow rate
LEED 2009 Rating System- NC/EB/CS/HC/SC

EBTRONs thermal dispersion airflow measurement devices are ideal for the measurement of the lower airflow
rates and challenging placement conditions associated with outdoor air intakes. EBTRON manufactures a full
line of airflow measurement devices to meet any application requirement and budget. Take advantage of our more
than 27 years of experience in measurement and control. Contact EBTRON or one of our 80 + independent


representatives today. EBTRON will show you how to use airflow measurement devices to satisfy LEED credit
requirements, save energy and help green your building.
LEED is a registered trademark of the U.S. GREEN BUILDING COUNCIL

Thermal Dispersion Airflow Measurement

1663 HWY. 701 S., Loris, S.C. 29569 Toll Free: 800 2EBTRON (232 8766) Fax: 843 756 1838 Internet: EBTRON.com

The Ebtron GreenBook_R2A

Potrebbero piacerti anche