GROUNDING TRANSFORMER AND
RESISTOR
FOR GENERATOR
1.0 CONNECTION
Legend :
(1) GSU Transformer
(2) Surge Arrestor
(3) Power Cable/Bus duct
(4) Generator
(5) Neutral Grounding Transformer
(6) Neutral Grounding Resistor
(7) Voltage relay for grounding detector
2.0 DATA FOR CALCULATION symbol unit value
(a) Generator capacitance to ground per phase Cg f 0.21
(b) Surge protection capacitance per phase Cs f 0.25
(c) Capacitance of transformer busduct and generator Cbt f 0.15
transformer to ground per phase
Total capacitance to ground per phase, C = (Cg + Cs + Cbt) = 0.61 f
(d) Generator Line to Line voltage, VL-L = 11 kV
(e) NG transformer Secondary voltage = 220 V
(f) Rated Frequency, f = 50 Hz
CALCULATION SHEET FOR NEUTRAL
GROUNDING TRANSFORMER AND
RESISTOR
FOR GENERATOR PAGE 3 OF 4
-
Fault current (Zero phase sequence current) , IF = 3 x (1/Xc) x (VL-L / 3) = 3.65 Amp
The capacity of neutral grounding transformer has been considered equal to 3 times the
capacitive kVA as calculated above to account for 10 % voltage variation & to avoid
excessive magnetic inrush and the capacity is applied on basis of 1 minute rating.
Accordingly,
Frequency, f = 50 Hz
The kW loss in secondary resistor during the ground fault will be equal to the capacitive
kVA.
Therefore,
Secondary resistor R = (Capacitive kVA x 1000) / Ir2 = 0.69596 Ohm 0.696 Ohm
Further, final value of Current capacity of resistor (IR) has been increased 10 % to account
for max. 10 % voltage variation,
Therefore,
Duty = 1 Minute