For air at 25oC (Dry bulb) 60% saturated
at 1.01325bar, determine:
0.03166
g = 0.622 = 0.02006kg / kg
1.01325 0.03166
= = 0.6
g
= 0.6 g
= 0.6 0.2006 = 0.01204kg / kg
h = ha + hs
h = 1.005 25 + .01204 2547 = 55.8kJ / kg dryair
Dew point temperature =tg at ps
ps
s = 0.622 = 0.01204
p ps
ps = p
+ .622
0.01204
= 1.01325 = 0.0192bar
0.01204 + 0.622
2
Fix point 4
L1 m& freshair
= = 0.25
L1 + L2 m& aTotal
3
L2
4
2
L1
Fix point ADP and
hence process line
through cooler
L2
4
ADP 2
L1
Draw Room ratio line Sensible =5 x 80 +1233=1633W
Sensible heat load Latent =5 x 140 = 700W
Direction from protractor for
Total heat load Total =2333W
Passes through point 2 Sensible/Total =0.7
3
L2
4
ADP 2
L1
Air enters room on room
ratio line at 20oC
Air leaves cooler at same
as enters room and on
coil process line 3
This fixes points 5 and 1
L2
4
5
ADP 2
1
Air mass flow
m& a (h2 h1 ) = Heat gain = 2.33kW
h2= 50.6kJ/kg
h1= 43.3kJ/kg
2.333
m& a = = 0.319kg / s
(50.6 43.3)
Rate of heat extraction = m& a (h4 h5 )
h4= 63kJ/kg
h5= 36.5kJ/kg
L2
4
5
ADP 2
1