Sei sulla pagina 1di 57

ABB Xiamen Electrical Controlgear CO., Ltd.

Sectos SF6 Load Break Switch

ABB Group
February 3, 2012 | Slide 1
Sectos Load Break Switch
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 2
ABB Xiamen Electrical Controlgear Co., Ltd.

JV Contact Signing Date: Sep. 9, 2001


CNXEC Total Investment: 8.6MUSD
Shareholders:
ABB (China) Limited 80%
Xiamen Mechanical & Electrical Group Co., LTD. 20%

ABB Group
February 3, 2012 | Slide 3
ABB local companies stand for quality in China

Heilongjiang

Jilin

Liaoning

Gansu Neimenggu

Xinjiang
Beijing

Hebei
Qinghai Ningxia Tianjin
Shanxi

Shanxi
Shandong
Henan
Xizang
Jiangsu
Sichuan Anhui
Hubei
Chongqing Shanghai
Zhejiang
Jiangxi
Hunan
Guizhou
Fujian

Yunn
an
Guangxi Guangdong Taiwan

Hong Kong

Hainan

ABB Group
February 3, 2012 | Slide 4
ABB Xiamen Electrical Controlgear Co., Ltd.
Advanced Production Line

ABB Group
February 3, 2012 | Slide 5
ABB Xiamen Electrical Controlgear Co., Ltd.
All Series of MV Outdoor Products

Outdoor product groups Quality/Certificates


Sectos SF6 load break switch ISO 9001:2000
PVB vacuum circuit breaker OHSAS18001
OHB SF6 circuit breaker Xiamen New Hi-Tech Enterprise
Fuse cutout Xiamen Leading Industrial
Enterprise
NPS switch-disconnector
DCD disconnector
Distribution automation

ABB Group
February 3, 2012 | Slide 6
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 7
Sectos Load Breaking Switch
Application

Type ABB Offering Open & close Open & close Close a Open a fault
a feeder under load fault

Air break switch NPS Yes Yes Yes No

SF6 Load break switch / Sectos Yes Yes Yes No


sectionalizer
Recloser OVR Yes Yes Yes Yes

ABB Group
February 3, 2012 | Slide 8
Sectos Load Breaking Switch
Overview

Sectos load breaking switch offers the following features:


Complete sealed stainless steel tank
2-position(ON - OFF) or 3-position(ON - OFF - EARTH)
Reliable spiral spring operation mechanism with light
reflecting and clear position indicator
Stable gas density switch with a temperature
compensated gauge
Mechanical manual locking device or low gas locking
device
Multiple mounting modes
Complete feeder automation ready solution
Easily upgraded from manual to motor operation
ABB controls with communication capabilities

ABB Group
February 3, 2012 | Slide 10
Sectos Load Breaking Switch
Installed in more than 40 countries

Finland
Norway Sweden
United Lithuania
Kingdom Poland
USA France Hungary China
Spain Croatia Slovenia
Greece
Morocco Iran Thailand
Egypt Vietnam
Algeria Israel Jordan
Honduras Saudi
Tunisia India
Senegal Philippines
Arabia
Ecuador Malaysia
Brazil
Peru Indonesia
Bolivia Tanzania

Chile
Australia
Argentina South Africa
New Zealand

ABB Group
February 3, 2012 | Slide 12
Sectos Load Breaking Switch
NXB and NXBD

NXB NXBD
Two-way load break switch Three-way load break switch
Three-position: ON / OFF /EARTH Three-position: ON / OFF /EARTH

ABB Group
February 3, 2012 | Slide 13
Sectos Load Breaking Switch
NXB and NXBD

NXB NXBD
Rated voltage 12-24 kV 12-24 kV
Rated current 630 A 630 A
Number of breaking operation C - O 400 400
Short time withstand current (4 sec) 20 kA 20 kA
Peak withstand current 50 kA 50 kA

Making current (kA / operations) 50kA / 5 31.5kA / 10 50kA / 5 31.5kA / 10

Mechanical endurance C-O


Main switch 5000 5000
Earthing switch 2000 2000
Creepage distance 620/960 mm 620/960 mm
Two-way load break switch Yes -
Three-way load break switch - Yes

ABB Group
February 3, 2012 | Slide 14
Sectos Load Breaking Switch
NXBD

NXBD: double NXB


3-way switch disconnector
Has all the features and functions of NXB
Especial useful for loop power supply
1 input + 2 outputs or 2 inputs + 1 output

switched switched switched switched


way no.1 way no.2 way no.1 2 way no.2
1 2 1
3 3
tapped way tapped way

Two-position 3-way Three-position 3-way


switch types NXBD__A_ switch types NXBD__C_
ABB Group
February 3, 2012 | Slide 15
Sectos Load Breaking Switch
NXBD

Before After

NXBD application cases: Tlby station outside Vaasa,


Finland
All 4 motors of the two NXBD are all controlled from the
same RTU (REC523 in the control box).

ABB Group
February 3, 2012 | Slide 16
Sectos Load Breaking Switch
NXA

Hook stick lever


Operation housing
IP67

Clear, reflectible
indicator

Gas filling
valve Silicone rubber
insulator

3 mm stainless steel tank NXA

ABB Group
February 3, 2012 | Slide 17
Sectos Load Breaking Switch
NXA

NXA NXA

Rated voltage 24 kV 36 kV

400 A
Rated current 630 A
630 A

400
Number of breaking operation C - O 400
50

Short time withstand current (3 sec) 16 kA 12.5 kA

Peak withstand current 40 kA 31.5 kA

Making current (kA / operations) 40kA / 5 31.5kA / 3

Mechanical endurance C- O 5000 5000

Creepage distance 960 mm 1440 mm

Two position switch ON / OFF Yes Yes

ABB Group
February 3, 2012 | Slide 18
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 19
Main Components of Sectos
Tank

3mm stainless steel


Laser cutting and robot welding
Special fire-proof material at bottom
Silicon rubber insulator

ABB Group
February 3, 2012 | Slide 20
Sectos- Complete sealed stainless steel tank
Sectos
Cost Type Formula Cost

Material Cost of SF6 $0 $0


Refilling Labor Cost $0 $0

Total = $0

Others
Cost Type Formula Cost
Material Cost of SF6 $100.00 $100.00
Refilling Labor Cost 1wokrs*4hours*$80/hour $320.00

Total = $420.00

Value
Complete sealed stainless steel tank, the leakage is 0.15% per year, much lower then the
competitors.
The prediction lifetime of the Sectos is more than 30 years. During 30 years, refilling SF6 is
unneeded.

ABB Group
February 3, 2012 | Slide 21
Main Components of Sectos
Contact system

Contact material: copper


with silver-plating.
Short time withstand
current: 20kA / 4 seconds.
Making current: 50kA / 5
times
Effective arc extinction by
cooling plate
Large clearance between
open contact gaps

ABB Group
February 3, 2012 | Slide 22
Main Components of Sectos
Earthing Switch

Integrated earthing switch


for NXB & NXBD type
Earthing Switch for safety
maintenance
Close-open-earthing
operations sequence, Only
earthing the switch when
Sectos is opened
Mechanical endurance
2000 CO
Earthing switch is only
operated by manual
operation

ABB Group
February 3, 2012 | Slide 23
Sectos- Integrated earthing switch
Sectos
Cost Type Formula Cost

Material Cost Earthing Switch type NXB_ES* $150.00


Labor Cost No Installation Labor cost $0.00

Total = $150.00

Others
Cost Type Formula Cost

Material Cost Earthing Switch $280.00

Labor Cost 2 workers x 4 hrs x $80 / hour $640.00

Total = $920.00
*Sectos NXB and NXBD available with integrated earthing switch, no need external
earthing switch

Value
labor and time saving
Cost saving for customer

ABB Group
February 3, 2012 | Slide 24
Main Components of Sectos
Operation Mechanism

Reliable manual and motor operation mechanism.


Independent spiral spring operation mechanism
Easy to be upgraded from manual operation to motor
operation at site

ABB Group
February 3, 2012 | Slide 25
Sectos- Easily upgrade from manual to motor type
Sectos
Cost Type Formula Cost

Material Cost $400.00 $400.00


Replacement Labor Cost 1 worker*1hour*$80/hour $80.00

Total = $480.00

Others
Cost Type Formula Cost
Material Cost* $2,800.00 $2,800.00
Replacement Labor Cost 2wokrs*4hours*$80/hour $640.00

Total = $3,440.00
* When upgrade from manual to motor operation, no need to change the whole unit

Value
Easily upgrade
Lower cost for customer

ABB Group
February 3, 2012 | Slide 26
Main Components of Sectos
Position Indicator

Large position indicator


symbols
Reflective colours
The reliable indication of
the device meets the
design and testing of IEC
129 A2

ABB Group
February 3, 2012 | Slide 28
Main Components of Sectos
Gas Pressure Indicators

Temperature compensated gas density switch and gauge


Gas density switch: gas-low alarm will be active and sent
by the relay when the gas pressure is below 1.2bar
Gas gauge: under the tank, with large indication symbols.

ABB Group
February 3, 2012 | Slide 29
Main Components of Sectos
Gas Pressure Locking Devices

Optional gas-low locking device and manual locking device.


Gas-low locking device will lockout the switch when gas
pressure is below 1.1bar for the safety consideration
The switch will be completely lockout when manual locking
device is active. Both remote control and local control will
be blocked to prevent the unauthorized operation

ABB Group
February 3, 2012 | Slide 30
Main Components of Sectos
Measurement Input Signals

Ring type current transformer


Installed around the bushings for protection and monitoring
Easily to be installed and replaced.
Service conditions: -40...+40 .
Ith/Idyn: 20/50 kA.
Accuracy: IEC Class 0.5 and 10P25.

Traditional VT
12, 24 and 36 kV outdoor
75, 110 and 200 kV BIL
Material: HCEP

ABB Group
February 3, 2012 | Slide 31
Main Components of Sectos
Measurement Input Signals

Voltage sensor and Combi sensor


Safe, compact design and wide dynamic range.
With 3 voltage sensors and 3 Combi sensors, we provide 6
voltage inputs and 3 current inputs.

ABB Group
February 3, 2012 | Slide 32
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 34
Installation & Operation
Three Mounting types

Above crossarm

Below crossarm

Mounted on pole directly

ABB Group
February 3, 2012 | Slide 35
Installation & Operation
Examples

ABB Group
February 3, 2012 | Slide 36
Installation & Operation
Examples

ABB Group
February 3, 2012 | Slide 37
Installation & Operation
Examples

ABB Group
February 3, 2012 | Slide 38
Sectos- Easy to install
c

Sectos
Cost Type Formula Cost
Installation Labor Cost 2wokrs*4hours*$80/hour $640.00

Total = $640.00

Others
Cost Type Formula Cost
Installation Labor Cost 2wokrs*8hours*$80/hour $1280.00

Total = $1280.00

Value
NXB manual type with insulator is 82kg.
The competitors are more than 90kg, even 100kg.

ABB Group
February 3, 2012 | Slide 39
Installation & Operation
Manual Operation

Three-position
Mechanism
Operate by down rod Operate by hook stick
ABB Group
February 3, 2012 | Slide 40
Installation & Operation
Motor Operation

Motor Up Motor Down


ABB Group
February 3, 2012 | Slide 41
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 42
Feeder Automation
Drivers

Request for improvement of the quality of the power supply


less and shorter outages and improved voltage quality
Need to improve the operational efficiency through
improved tools for the network operators and the field crews
Need to utilize the distribution network / improve the economy
utilize the network more efficiently (transfer of active power)/
minimize the network losses
minimize the amount of energy not supplied
Provide improved safety for the utility personnel
less need to travel to places difficult to reach
less need to work in dangerous environments
Normally a combination of the above

ABB Group
February 3, 2012 | Slide 43
Feeder Automation
Current-Count-OVR+A2.exe
Automatic sectionalizer - example
Permanent fault, needs 3 reclosing shots
Sectionalizer settings: Counts to trip = 2

FAULT TRIP
1ST RECLOSE 2ND RECLOSE 3RD RECLOSE
TRIP TRIP

Current

Shot 1 Shot 2 Shot 3


Circuit CLOSE
Breaker OPEN
Position
(Recloser)
CLOSE

Disconnector OPEN
Position time
(Sectionalizer)
COUNT TO TRIP = 1 COUNT TO TRIP = 0
FAULT DISAPPEARS
ABB Group
February 3, 2012 | Slide 44
DURING 3RD SHOT
Feeder Automation
Categories

Local Feeder Automation


the operation of the field device is initiated locally, based
on measurements at the point of the field device.
Distributed Feeder Automation FTU or substation
centered
the field devices along the feeder are cooperating to locate
and isolate the fault (FTU centered) or the operation of the
field devices are controlled from the substation (substation
centered)
Centralized Feeder Automation
the field devices are communicating with the overall
SCADA and DMS system. Operation of the field devices
are initiated from the central system.
Various combinations of Centralized, Distributed and
Local

ABB Group
February 3, 2012 | Slide 45
Feeder Automation
Control Options: REC 501 and REC 523

REC 501
FA schemes where measurements are not needed
Control one or two objects
Integrated temperature compensated battery charger
REC 501 Control and
Monitoring Terminal Condition monitoring: SF6 pressure, battery condition,
operation counter, internal self-supervision, etc.

REC 523
Remote Monitoring and Control unit for advanced FA
schemes including measurements and control
Capable of controlling several objects in the same
REC 523 Control and
Monitoring Unit
network node.

ABB Group
February 3, 2012 | Slide 46
Feeder Automation
Control Options: REC 523

Measurement Condition monitoring


phase currents and phase control circuit supervision
tophasevoltages circuit breaker / disconnector condition
REC523
residual current and voltage monitoring
active and reactive power SF6 pressure of primary equipment
active and reactive energy battery condition monitoring
demand values of current battery deep discharge protection
and power operation counter for primary equipment
frequency internal selfsupervision of the unit
power factor
harmonics
Network
Control
Center
temperature Control
battery voltage two to four objects
disturbance and event external heater
recording integrated temperaturecompensated
charger
Communication protocols
SPA
LON
IEC870-5-101
Modbus
DNP 3.0
ABB Group
February 3, 2012 | Slide 47
Feeder Automation
Control Options: REC 523 (continued)

Network
Protection and fault indication capabilities
Control
Center
Auto-reclose function (5 shots)
Phase discontinuity protection
Directional earth-fault protection; two stages
(low-set and high set)
Three-phase directional overcurrent
REC 523
protection, two stages (low-set and high-set)
Three-phase transformer inrush and motor
start-up current detector
Non-directional earth-fault protection; two
stages (low-set and high-set)
Three-phase non-directional overcurrent
protection, two stages (low-set and high-set)
Three-phase undervoltage protection; two
stages (low-set and high-set)
Circuit breaker failure protection
ABB Group
February 3, 2012 | Slide 48
Feeder Automation
REC 523 binary inputs and outputs
Digital inputs
15 pieces
wide input range 18265 Vdc
Digital outputs
9 pieces
included two power outputs
Analog inputs
9 sensors
CTs and VTs
Other integrated functions
temperature compensated
battery charger
+12V outlet for communication
device
Built-in thermostat
IRF relay

ABB Group
February 3, 2012 | Slide 49
Feeder Automation
REC523 - LED display

21 freely configurable LED


Switching states
Fault Indicating
Alarms
etc.

4 different states:
blank
slow blinking
fast blinking
continuously on

Based on IEC 61131-3


programming

ABB Group
February 3, 2012 | Slide 50
Feeder Automation
REC523 - Communication possibilities

Power and
distribution line
carrier
DLM100 DLM100

REC 523
Network Radio
Radio systems modem
Control
Centre GSM/GPRS

Electrical telecommunication
Cables (PSTN, Leased Line)
A
Fibre optic cables

Radio link systems

ABB Group
February 3, 2012 | Slide 51
Feeder Automation
Features of control cabinet
Remote monitoring and control of
Ring Main Units (RMUs) and Pole
mounted switches
Control unit REC 523
IP55 stainless steel enclosure
Remote monitoring and control
Fault indication and information
Communication
Contactor logic and local control push-
buttons
Batteries
Temperature compensated battery
charger
Outlet +12 Vdc for communication
device
Heater or dryer resistor
MCBs
AC outlet
Overvoltage protection

ABB Group
February 3, 2012 | Slide 52
Feeder Automation
Sectos Solution
Suitable for many feeder automation
applications for MV overhead lines
Remote monitoring and control of
pole-mounted switches and
disconnectors
Remotely controllable air
insulated switches and
disconnectors Remote monitoring
and control of Ring Main Units
(RMUs) and Pole mounted
switches
Current based sectionalizer
Current and voltage based
sectionalizer
Closed ring protection scheme
for distribution networks
Current based sectionalizer Engineering documentation supplied
Application description
Principle connection diagram
Configurations downloaded in factory
ABB Group
February 3, 2012 | Slide 53
Feeder Automation
Sectos Solution

Solution: current-count
Location: Blida - Algeria
Product: NXA36
Order: 355 units
Commissioning: April 2002

Solution: voltage-time
Location: Guizhou, China
Product: NXB12
Order: 50 units
Commissioning: July 2005

ABB Group
February 3, 2012 | Slide 54
Feeder Automation
Conclusion

There is an urgent need for Feeder Automation


Increased demands on the utilities (Power Quality)
Less resources available
Increasing efficiency demands
The payback time is short
The deregulation schemes start to stipulate fines for interruptions
Packaged solutions a benefit
Defined and tested functionality
Short installation and commissioning time
Feeder Automation provide a great possibility for the
utilities to improve customer service and efficiency

ABB Group
February 3, 2012 | Slide 55
Content

ABB Overview
Sectos Load Breaking Switch
Main Components of Sectos
Installation and Operation
Feeder Automation
Quality Control
Summary

ABB Group
February 3, 2012 | Slide 56
Quality Control
Sectos

Partial Discharges Test

Robot Welding

Sandblasting

ABB Group
February 3, 2012 | Slide 57
Quality Control
Sectos

Gas Leakage Detection


Helium gas leakage detection (the
molecular weight of Helium is
1/36.5 of SF6).
SF6 leakage rate: <0.15% per year.

Final Test

ABB Group
February 3, 2012 | Slide 58
Sectos- Less maintenance
c

Sectos
Cost Type Formula Cost

Material Cost $0 $0
Maintenance Labor Cost $0 $0

Total = $0

Other air switch every 5 years


Cost Type Formula Cost
Material Cost Air switch $1,400.00
Maintenance Labor Cost 2wokrs*8hours*$80/hour $1,280.00

Total = $2,680.00

Value
Almost Free maintain
For long term, air switch needs to be replace every 5 years. Sectos SF6 load break switch
can last 30~40 years

ABB Group
February 3, 2012 | Slide 59
Summary

Completely sealed stainless steel tank (Leakage<0.15% per year)


ABB patent spiral spring operation mechanism with clear indicator
Reliable, stable gas density switch and gauge with temperature
compensation
Gas-low locking device or manual locking device as options
Easily upgrading from manual to motor operation
Safe, compact design and wide dynamic range of the sensor
solution
Powerful relay REC523 with strongly logic function
Full options for Sectionalizer: Current-count and Voltage-time

ABB Group
February 3, 2012 | Slide 60
ABB Group
February 3, 2012 | Slide 61