Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
NO:V7588 SHEET 1 OF 1
END CUSTOMER
CONSULTANT
DRAWING SUB-
WORK ORDER
APPLICABLE CUSTOMER
Sr. No. OF
SERIES
DESCRIPTION FOR PANEL DRG. No.
DRAWING
No. SHEETS
ITEM No.
No.
NOTE: SCH.-SCHEMATIC DRAWING; WRG.-WIRING DRAWING;Z-IF W.O. IS HAVING ONLY ONE SWITCHBOARD; FOR
MULTIPLE SWITCHBOARD ORDER USE LETTER A,B,C..; IN DRG. SUB-SERIES: 10 SERIES STANDS FOR - INCOMER TYPE, 20
SERIES FOR - OUTGOING TYPE, 30 SERIES FOR - BPT TYPE; 40 SERIES FOR - BUS-COUPLER TYPE
DRAWING SERIES: T-TECHNICAL SPECIFICATION; G-GENERAL ARRANGEMENT DRAWING (FRONT VIEW, SIDE VIEW, PANEL
LINEUP & INSTRUMENT LAYOUT) & FOUNDATION PLAN; M-SINGLE LINE DIAGRAM; S-SCHEMATIC DRAWING; B-BILL OF
REV. SUMMARY OF REVISION DRN. CHK. DATE MATERIAL; L-LEGEND; W-WIRING DRAWING; U-BUS-WIRING DIAGRAM; C-BREAKER DRAWING
TECHNICAL SPECIFICATIONS
F F
(A) SYSTEM PARAMETERS (D) CIRCUIT BREAKER
1 RATED VOLTAGE 11000V 1 APPLICABLE STANDARD IS 13118/1991
2 RATED FREQUENCY 50Hz 2 MECHANISM TRIP FREE
3 SYSTEM NEUTRAL EFFECTIVELY EARTHED 3 BREAKING CAPACITY 40 kA AT 11 kV
4 FAULT LEVEL 40 kA 4 SHORT TIME RATING 40 kA FOR 3 SEC
VT7588-Z-00
DRG. NO.
1 CLOSING COIL 24 V DC 4 PANEL SPACE HEATER 230V AC (E) MAIN HORIZONTAL BUSBARS
2 TRIPPING COIL 24 V DC 5 SPR CHARGE MOTOR 230V AC 1 RATED CURRENT 2500A
3 INDICATION CIRCUIT 110 V AC
4 PANEL SHALL BE PAINTED INSIDE AND OUTSIDE WITH SHADE RAL 7035
5 DOOR OPERATED LIMIT SWITCH SHALL BE PROVIDED FOR PANEL ILLUMINATION LAMP. 1 MATERIAL FOR EARTH BUS COPPER
6
C C
B B
CROMPTON GREAVES LTD.
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
PROJECT : GENERAL ARRANGEMENT DRAWING PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
3 FOR 1 PANEL BOARD APPD. PSS 03.09.2016
CONSULTANT : SHEET 1 OF 2
2
TECHNICAL SPECIFICATION THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VT7588-Z-00 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
TABLE FOR WIRE COLOR & WIRE SIZES
VT7588-Z-00
DRG. NO.
RED,YELLOW,BLUE,BLACK
2 PT SECONDARY CIRCUIT 2.5 SQMM.
FOR R,Y,B PH & NEUTRAL
3. WIRE SHALL BE DESIGNATED BY SAME FERRULLE NUMBER AT BOTH OF ITS END, &
FERRULE DENOTATION SHALL BE AS PER TABLE 1V OF IS 375-1963 / IS 5578-*-1984
without prior consent of
4. WIRING SHALL BE DONE WITH 1100 VOLT FRLS GRADE MULTISTRANDED COPPER WIRE
A 5 NAME DATE
PROJECT : GENERAL ARRANGEMENT DRAWING PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
3 FOR 1 PANEL BOARD APPD. PSS 03.09.2016
CONSULTANT : SHEET 2 OF 2
2
WIRING SIZE & COLOR CODE DETAILS THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VT7588-Z-00 REV 0
0
857
700
POWERPACK
CUTOUT IN THE BOTTOM FRAME
386
INSTRUMENT LAYOUT
AS VS
1866
2025
822
SKT
SSW HSW PSW
FOUNDATION VIEW LR TNC
825
53
552
900
180 180
750
2422
2369
2422
2270
40 435
1370
1023
374
803 689
124 1866 32
857
FRONT VIEW 2025
POWER FLOW IC/OG SIDE VIEW
SWGR SR NO. 83415VK NOTES :
1. THE INSTRUMENT LAYOUT AND HEIGHT SHOWN IS TENTATIVE, SUBJECT TO CHANGE
PANEL NO: P1 DURING DETAILED ENGINEERING STAGE
2. ONLY 10% PANELS SHALL BE OFFERED FOR INSPECTION.
3. PT SHALL BE 1PHASE 3 NOS.
GENERAL ARRANGEMENT DRAWING PVM 03.09.2016
V7588
FOR 6 PANEL BOARD PSS 03.09.2016
1 2
FRONT/SIDE VIEW, INSTRU. LAYOUT
SREX POWER INDIA PVT LTD
NTS VG7588-Z-00 0
0
1866
250 825
FOUNDATION HOLES
40 25
40
386
VG7588-Z-00
100
44
350
857
350
*
100
110 25
DIMENSION OF TRENCH IS MINIMUM
700X386 RECOMMENDED & CROSS CHANNEL WITH
LOCATION OF FOUNDATION BOLT.
M12 TAPPED HOLE TO BE GROUTED FOR
CLAMPING OF REAR SIDE FOUNDATION BOLTS.
250 825
130
110 100
460
GENERAL ARRANGEMENT DRAWING PVM 03.09.2016
V7588
FOUNDATION PLAN PSS 03.09.2016
2 2
SREX POWER INDIA PVT LTD
NTS VG7588-Z-00 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
21 DISTANCE PROTECTION RELAY NORMALLY CLOSED PUSH BUTTON FI1,FI2 INDICATION CIRCUIT FUSES
25 CHECK SYNCHRONIZING RELAY M MOTOR T TRIP CKT HEALTHY TEST PUSH BUTTON MTTB METERING TEST TERMINAL BLOCK FAN1,FAN2 ANNUNCIATION CIRCUIT FUSES
27 UNDER VOLTAGE RELAY CURRENT TRANSFORMER DA DC FAIL ACCEPT PUSH BUTTON RTTB RELAY TEST TERMINAL BLOCK FCA1,FCA2 COMMON ALARM CIRCUIT FUSES
32 DIRECTIONAL POWER RELAY VOLTAGE TRANSFORMER AA AC FAIL ACCEPT PUSH BUTTON FSY1,FSY2 SYNCHRONIZING CIRCUIT FUSES
37 UNDER CURRENT/POWER RELAY THERMOSTAT EPB EMERGENCY PUSH BUTTON ADF AC DC FAIL RELAY (WITH ALARM LOGIC) FAX1,FAX2 AUXILLARY RELAY CKT FUSES
46 NEGATIVE SEQUENCE VOLTAGE RELAY BUZZER/HOOTER PA/PR ACCEPT/RESET PUSH BUTTON DCF DC FAIL RELAY (WITH ALARM LOGIC) FM/LKM FUSE/LINK FOR MOTOR CIRCUIT
VL7588-Z-00
47 NEGATIVE SEQUENCE CURRENT RELAY LAMP PM/PT MUTE/TEST PUSH BUTTON CAR COMMON ALARM SCHEME FH/LKH FUSE/LINK FOR HEATER CIRCUIT
49 THERMAL RELAY SWITCH(TNC,LR,AUTO MANUAL) VSS VOLTAGE SELECTION SCHEME FS/LKS FUSE/LINK FOR SOCKET CIRCUIT
E 50 HIGHSET OVER CURRENT RELAY TOGGLE SWITCH Z OPENS WHEN SPRINGS ARE CHARGED FV1-4 FUSES FOR VOLT SEL SCHEME E
50N HIGHSET EARTH FAULT RELAY COIL ZZ CLOSES WHEN SPRINGS ARE CHARGED SS SURGE SUPPRESSOR MCB MINIATURE CIRCUIT BREAKER
FILE NAME:
51 IDMTL OVER CURRENT RELAY CC CURRENT COIL OF METER LS CLOSES WHEN VCB IS MECH.FREE TO CLOSE LA LIGHTNING ARRESTOR
DRG. NO.
51N IDMTL EARTH FAULT RELAY PC PRESSURE COIL OF METER TNC BREAKER CONTROL SWITCH LLI LINE LINE INDICATOR TS CONTACTOR SENSING TEST POSITION
51S SENSITIVE EARTH FAULT RELAY (52a)VCB OPERATED NO CONTACT LR LOCAL REMOTE SWITCH ANN ANNUNCIATOR CS CONTACTOR SENSING SERVICE POSITION
51G STAND-BY EARTH FAULT RELAY (52b)VCB OPERATED NC CONTACT SS SYNCHRONIZING SELECT SWITCH HCA HOOTER FOR COMMON ALARM CLS CONTACTOR SENSING SERVICE /TEST POSITION
52S SERIES TRIP COIL HSW/PSW TOGGLE SWITCH FOR HEATER/PANEL LAMP TH THERMOSTAT 98O AUX CONTACTOR FOR 59 RELAY CONT MULT
79 AUTO RECLOSING RELAY
80 DC SUPPLY SUPERVISION RELAY PL PLUG & SOCKET SSW TOGGLE SWITCH FOR SOCKET T1,T2... TIMER
81U UNDER FREQUENCY RELAY RCB REAR CABLE BOX DS DOOR SWITCH R1,R2... RESISTOR CTX CURRENT TRANSDUCER
81O OVER FREQUENCY RELAY SCB SIDE CABLE BOX AMS AUTO MANUAL SELECTOR SWITCH VTX VOLTAGE TRANSDUCER
85 PILOT WIRE RECEIVER RELAY FR,FY,FB PT SECONDARY(Y SIDE) FUSES KWX KW TRANSDUCER
86 MASTER TRIP(LOCK OUT) RELAY CT CURRENT TRANSFORMER AM ANALOG/DIGITAL AMMETER F1,F2 PT SECONDARY(V SIDE) FUSES KVARX KVAR TRANSDUCER
C 94 ANTI PUMPING RELAY VT VOLTAGE TRANSFORMER VM ANALOG/DIGITAL VOLTMETER FC1,FC2 CLOSING CIRCUIT FUSES TEMX TEMPERATURE TRANSDUCER C
95 TRIP CKT. SUPERVISION RELAY CBCT CORE BALANCED CURRENT.TRANSFORMER HZ FREQUENCY METER FT1,FT2 TRIPPING CIRCUIT FUSES
98 CONTACTOR ICT INTERPOSING CURRENT TRANSFORMER KW WATT METER
NOTES
KVAR REACTIVE VOLT AMP METER
R BREAKER ON INDICATION(RED) KVA VOLT AMP METER
1. THESE ARE THE FREQUENTLY USED ABBREVIATIONS AS PER CGL STANDARD DRAWINGS
TERMINAL BLOCK FOR CT WIRE
2. REFERENCES IEV-440 , IS-5578, IEC-60050
TERMINAL BLOCK FOR WITHIN PANEL WIRE G BREAKER OFF INDICATION(GREEN) PF POWER FACTOR METER
TERMINAL BLOCK FOR WITHIN BOARD WIRE A AUTO TRIP INDICATION(AMBER) KWH WATTHOUR METER
TERMINAL BLOCK FOR REMOTE FEEDBACK W TRIP CKT HEALTHY INDICATION(WHITE) TVM TRIVECTOR METER
HRC FUSE B SPRING CHARGED INDICATION (BLUE) MDC MAXIMUM DEMAND CONTROLLER
LINK SP SERVICE POSITION INDICATION (AMBER) LM LOAD MANAGER
B B
PLUG AND SOCKET TP TEST POSITION INDICATION (CLEAR) MFM MULTIFUNCTION METER
DF DC FAIL INDICATION(CLEAR) RUN HOUR METER
CROMPTON GREAVES LTD.
BP
NORMALLY OPEN PUSH BUTTON BF BREAKER FAIL INDICATION(RED)
SMI SEMAPHORE INDICATOR
A 5 NAME DATE
PROJECT : LEGEND SHEET PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
APPD. PSS 03.09.2016
3
CONSULTANT : SHEET 1 OF 1
2
THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VL7588-Z-00 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
VS7588-Z-11
E E
FILE NAME:
DRG. NO.
C C
B B
CROMPTON GREAVES LTD.
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
PROJECT : SCHEMATIC DIAGRAM FOR PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
3
IC CUM OG PANEL APPD. PSS 03.09.2016
CONSULTANT : SHEET 1 OF 4
2
TITLE PAGE THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7588-Z-11 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
R
Y
F
B
SCB SUITABLE FOR ** F
2x1Cx630Sq.mm XLPE CABLE/PH VCB SPARE CONTACTS
2 3
TB1 PL VCB52 PL TB1
VCB52 138 U01 17 7a 8a 18 U02 139
2500A 3 OVERCURRENT +
4 5 6 1 EARTH FAULT RELAY-CGI14N
TB1 PL VCB52 PL TB1
VS7588-Z-11
C70 10 12
51 50
2S3 C10 116
TB1 PL VCB52 PL TB1
BURDEN/A.CL:15VA/5P10
C71
CT3
CTS- 3 NOs
ET
D D
1S3 D10 107 D70
BURDEN/A.CL:15VA/CL-0.5
YELLOW BP
AMMETER SELECTOR DIGITAL
P1
ET 1 2
SWITCH AMMETER TO INDICATION CIRCUIT
BLUE
VT1 VM
FR
A 1A n E10 119 E10 1 2 E11
E72 V1 VN
R 1
N VS
120
FY
E30 E30 1 2 E31 E71
VT2 Y 2
A 1A n DIGITAL
E50 121 E50 1 FB 2 E51 10A
B N B VOLTMETER B
E70 122 E70
VT3 VOLTMETER
CROMPTON GREAVES LTD.
E90
All information contained in this document
A 1A n SELECTOR SWITCH
is confidential and should not be used
N ET
without prior consent of
ET
1 PHASE FEEDER CONNECTED VTs
INCOMER NOTE:
VTR : 11000V/R3 // 110V/R3
FIXED TYPE VTs FOR HIGHER CT RATIO SHORT & EARTH
RCB SUITABLE FOR ** 100VA/CL 0.5 ** CUSTOMER TO SPECIFY CABLE SIZE AT THE TIME OF DRG APPROVAL
C10 C30 C50, ,D10 D30 D50 INSTEAD OF
2x1Cx630Sq.mm XLPE CABLE/PH C13 C33 C53 ,D13 D33 D53,
A 5 NAME DATE
PROJECT : SCHEMATIC DIAGRAM FOR PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
3
IC CUM OG PANEL APPD. PSS 03.09.2016
CONSULTANT : SHEET 2 OF 4
2
POWER CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7588-Z-11 REV 0
1 2 3 4 5 6 7 8 9 10
0
J1
J2
REV
94
J3
16 VCB52
VS7588-Z-11
DRG. NO.
5150
26 25 AUX SUPPLY OF 3 OC+EF RELAY
+ -
1 2 K1 1 A 1 2 K3 30 1a 2a c d 31 K2 2 1
6A 6A
5150 TRIPPING COIL TRIPPING
16 17 CIRCUIT
COMMON TRIP
130 129
C FUTURE TRIP C
E50
E30
AUTO TRIP
All information contained in this document
is confidential and should not be used
PL LSS PL SP AMBER
L1 2 1 2 3 L9 1 2
without prior consent of
TITLE
3 IC CUM OG PANEL APPD. PSS 03.09.2016
CONSULTANT : SHEET 3 OF 4
2
DC CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7588-Z-11 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
134
PP
1 3 J1 131
POWER J1
PACK
I/P O/P
2 4 J2 132
VS7588-Z-11
J2
230V AC
1 3 24V DC
E E
MCB2
16A
FILE NAME:
2 4
DRG. NO.
H4
H3
A1 A2
ZZ PL B
21 H7 1 2
SPRING CHARGED INDICATION
BLUE
FH HSW TH HE1 LKH
1 2 H21 1 2 H23 1 2 H25 135 H25 1 2 H22 136 H22 2 1
C 2A C
DS LMP
137 H21 1 2 DOOR OPERATED LIMIT SWITCH H27 1 2
AM
12 13 AUXILIARY SUPPLY FOR DIG. AMMETER
+ -
VM
12 13 AUXILIARY SUPPLY FOR DIG. VOLTMETER
+ -
B 3 PIN SOCKET B
SKT
CROMPTON GREAVES LTD.
All information contained in this document
is confidential and should not be used
FS SSW LKS
1 2 H31 1 2 H33 P N H32 2 1
without prior consent of
10A
90 E
ET
A 5 NAME DATE
PROJECT : SCHEMATIC DIAGRAM FOR PVM 03.09.2016
W.O.NO. V7588
4 DRN.
OWNER:
TITLE
3 IC CUM OG PANEL APPD. PSS 03.09.2016
CONSULTANT : SHEET 4 OF 4
2
AC CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER : SREX POWER INDIA PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7588-Z-11 REV 0
B-SHEET FOR W. O. : V7588 REV - 0
B-SHEET NO : VB7588-Z-00
CUSTOMER : SREX POWER INDIA PVT LTD
PREPARED BY : PVM
APPROVED BY : PSS
DATE : 03.09.16
PANEL QTY 1 FOR 1 SET
IT TAG DESCRIPTION IC TOTAL
IND. LAMPS LED TYPE MAKE:AS PER CGL STANDARD
COLOUR VOLTAGE PURPOSE
A1 R RED 110V AC VCB ON 1 1
A2 G GREEN 110V AC VCB OFF 1 1
A3 B BLUE 230V AC SPR. CHR. INDICATION 1 1
A4 A AMBER 110V AC AUTO TRIP 1 1
A5 W WHITE 24V DC TRIP CKT HEALTHY 1 1
A6 RP RED 110 V AC R PHASE HEALTHY 1 1
A7 YP YELLOW 110 V AC Y PHASE HEALTHY 1 1
A8 BP BLUE 110 V AC B PHASE HEALTHY 1 1
A9 SP AMBER 110V AC SERVICE POSITION IND 1 1
A10 TP CLEAR 110V AC TEST POSITION IND 1 1
A21 TH THERMOSTAT 1 1
A24 TIMER 1 1
PURPOSE: FOR SPRING CHARGING MOTOR CKT
CONTROL VOLTAGE: 230V AC
A25 PP POWERPACK 1 1
RATING: 230V AC-24V DC
CT & PT
CT1 CT1 11kV EPOXY CASTED CURRENT TRANSFORMER 3 3
CT2 CTR - 2000-1000/5+5 A
CT3 STR - 40 kA/ 3SEC
CORE1- (5A)-15VA/0.5
CORE2 - (5A) - 15VA/5P10
CT SEC - ON P1 SIDE
MAKE- CGL/SILKANS/SGELECTRICALS/EQUIVALENT
VT VT VOLTAGE TRANSFORMER 3 3
RATIO : 11000/110 1PH FIXED TYPE VT
WDG:100VA/CL0.5
CONNECTION - STAR-STAR
EPOXY RESIN CAST , FEEDER CONNECTED
MAKE:CGL/SILKAAN/KAPPA/ECS
VOLTAGE FACTOR - 1.2 CONT 1.5 FOR 30 SEC
RELAYS
R1 5150 3 OC + 1 EF RELAY 1 1
DESIGNATION OF RELAY-CGI 14C
NUMERICAL COMMUNICABLE FP IDMTL+INST 3O/C+1E/F RELAY
FLUSH MOUNTING TYPE
OVER CURRENT IDMTL SETTING 5% TO 200% OF CT SECONDARY
EARTH FAULT IDMTL SETTING 5% TO 200% OF CT SECONDARY
INSTANTANIOUS O/C SETTING 50-1600% IN STEP OF 1%
METERS
M1 AM DIGITAL AMMETER
MAKE - ELMEASURE / RISHABH/EQUI
FLUSH MTG.
CT SEC: 5A
CT RATIO:2000-1000/5A 1 1
AUX VOLTAGE - 80-230 VAC
ACC. CLASS:0.5
M2 VM DIGITAL VOLTMETER 1 1
AUX.SUPPL : 230V AC
VTR - 11KV/110
ACC CLASS: CL 0.5
MTG : FLUSH
MAKE - ELMEASURE / RISHABH/EQUI
NOTE: ALL SWITCHES CONTACTORS MCBs, LAMPs SHALL BE AS PER CGL STANDARD