Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1996 PES-TR4
Formerly TP115
Relay Performance
Testing
PREPARED BY THE
Power System Relaying Committee
Relaying Practices and Consumer Interface Protection
Subcommittee
J. A. Jodice, Chairman
M. Meisinger, Vice Chairman
C. Renville, Secretary
Relay Performance Testing
Abstracting is permitted with creditto the source. For other copying, reprint, or republication
permission, write to the IEEECopyright Manager, IEEEService Center445 Hoes Lane, P.O
Box 1331,Piscataway, NJ 08855-1331. All rightsreserved. Copyright 1996by The Institute
of Electrical and Electronics Engineers, Inc.
IEEE ServiceCenter
PO Box 1331
445 Hoes Lane
Piscataway, NJ 08855-1331
1-800-678-IEEE
1-908-981-1393
1-908-981-9667 (Fax)
833-233 (Telex)
Relay Performance Testing
RELAY PERFORMANCE TESTING
CONTENTS
1.0 INTRODUCTION , 4
1.1 General 4
1.2 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 4
2.1 General 7
3.1 General 0 8
3.2.1.7 Sine Wave with Controllable Frequency and Rate of Change in Frequency. . . . . . . .. 12
- 1-
3.2.2 DC Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 12
3.4 Integrity 13
3.5 Application 13
4.1 General 13
4.3.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 16
5.1 General 21
6.0 EXAMPLE 22
6.1 Introduction 22
7.0 CONCLUSION 24
- 2-
LIST OF ILLUSTRATIONS
- 3 -
RELAY PERFORMANCE TESTING
1.0 INTRODUCTION which illustrates many test approaches. These examples are
not intended to be test guides. The information is included
1.1 General
to show how one utility applied specific tests to ensure that
The purpose of this report is: relay performance would meet application objectives.
to provide relay users with an understanding of the
1.2 Definitions
strengths and limitations of testing methods used
The primary test methods and test purposes are discussed
for evaluating the performance of protective
in this section.
relays.
to serve as a reference for the development of test 1.2.1 Steady-State Test
plans which determine relay performance and its A steady-state test is used to determine the calibration
suitability for application objectives. point or setting for any measured parameter. Phasor test
'[his material is applicable to a wide variety of relays; it quantities are held stable for a duration much longer than
is not an instructional guide for testing specific types of the operating time of the relay, and are then varied in
relays. increments much smaller than the resolution of the relay.
For the example of an instantaneous overcurrent relay
Various objectives associated with relay performance
where the nominal measuring time is 2 cycles, the duration
testing are identified; means to achieve those objectives are
of stable test quantities (Delta Time) would typically be
described. A discussion of test signals and the equipment
more than 20 cycles. If the relay measuring resolution is 1.0
used to produce them is presented to provide a better
amp, the test current would be varied in increments (Delta
understanding of test methods.
Value) of less than 0.1 amp. Figure 1 shows part of a typical
Most of the discussion in the paper is general, with steady-state test signal. The voltage is maintained constant
non-specific background information. Section 6.0 at the fault value, the current is increased at a rate of Delta
concludes with an example of a comprehensive test plan Value/Delta Time.
- 4-
1.2.2 Power System Simulation Test synchronously switched means that changes in phasor value
Relays are required to respond to the transient (i.e., phase and/or amplitude) from pre-boundary values to
conditions of a disturbed power system. By simulating the post-boundary values occur in all phasors at the same time
signals "seen" by the relay under such conditions, setting with no discemable skew. Power system characteristics such
and response time may be determined. The disturbance as high frequency and de decrement are not represented in
may be simulated in more or less detail by one of the two this test.
following test methods.
For example, three states may represent the pre-fault,
fault, and post-fault power system condition. Additional
1.2.2.1 Dynamic-State Test
states may be used to represent evolving faults.
A dynamic-state test is one in which phasor test
quantities representing multiple power system conditions Figure 2 shows the test signals that might be used in a
are synchronously switched between states. The term dynamic state test; prefault and fault states are shown.
Prefault Fault
State 1 State 2
- 5 -
e) voltage recovery and offsetdue to residual charge 1) voltage transient and chargingcurrent whenlocal
on the series compensating capacitor when HV end closes;
groundingswitch opens; g) return to load when remote breaker closes.
a. b. c. d. e. f. g.
- 6 -
2.0 PURPOSE OF RELAY PERFORMANCE TESTING 2.2 Integrity Testing
There are a number of occasions during the life of a relay
when integrity tests are performed. Acceptance testing upon
2.1 General
receipt is usually the first instance outside the factory.
This section reviews the purposes for both integrity and In-service integrity tests are generally performed on a
application tests [1]. Testing should be complemented by periodic basis, which depends on several factors; the most
thoroughly reviewing both the manufacturers' specifications common include:
and those power system parameters relevant to the relay
application. manufacturers recommendations
operating history of the particular relay type
Evaluating the suitability of a relay for a specific complexity of the protection function
application is the first instance when both integrity and criticality of the protected circuit
application tests may be performed. Integrity tests are maintenance schedule of the protected apparatus
general and verify relay conformance with both
2.3 Application Testing
manufacturer and user acceptance criteria. These are
usually steady-state or limited dynamic-state tests designed Similarly application tests are performed periodically
to examine the performance of all measurements performed during the installed life of a relay. Instances include:
by the relay. Design Verification/Type Testing
Manufacturers employ a multitude of tests to ensure the
The diagnostic quality of integrity and application tests relay is suitable for the application. Design specifications
has improved as advanced test instruments have become and critical performance characteristics are verified at the
available and affordable. Computer automated integrity pre-production phase. Special tests may be performed to
tests examine relay performance more rapidly than manual ensure a particular users application is satisfied. [3]
methods. More extensive integrity and application tests
may be performed, at lower costs. Application tests using Relay Selection
dynamic state and transient simulation methods are being Prior to selecting a relay for a specific protection applica-
applied more frequently during the relay life cycle, tion, its response to expected power system conditions should
improving protection system reliability. be evaluated. A combination of dynamic state and transient
simulation tests may be used, dependingupon the complexity
Application tests are more comprehensive and are of the application. Some utilities have modelled the transient
designed to examine relay performance specific to the behavior of critical circuits, and performed transient simula-
application. Dynamic state and transient simulation tests tion tests prior to purchase; these establish the suitability of
simulate the power system conditions which relays will a particular relay design for the application.
experience during service. Sufficient internal and external
faults should be applied to examine the suitability of the Commissioning/System Testing
relay for the given application. Multiple faults within the Application tests on individual relays minimize the
zone of protection should be applied to examine relay possibility of setting errors. Since protection systems often
sensitivity. Faults outside the protected zone should be comprise several discrete relays, the protection system should
applied to examine selectivity. be tested as a whole to ensure appropriate interaction and
coordination.
A test plan may incorporate a combination of both
Operation Analysis
integrity and application tests. Complexity of both relay
After an unexpected operation, application tests offer
function and application form the criteria for selecting tests.
insight to the probable causes of malfunction. Recent
For example: integrity tests verifying performance of simple
experiences reveal inappropriate interaction between relays
instantaneous overcurrent relays generally include calibra-
to have been the cause of scheme misoperation. A scheme
tion at a defined current and measurement of operate time.
test verifies coordination between relays. Operation of
These tests use sinusoidal steady-state and dynamic-state
associated communications equipment, reclosers, breakers
current, respectively. For applications where power system
and transfer schemes is also verified. Fault and event
currents may not be sinusoidal due to CT performance or
recorder operation may also be confirmed.
system harmonics, experience has shown instantaneous relay
performance varies substantially from that which isexpected During the last few years end-to-end satellite synchro-
[2]. Applying a test current waveform which approximates nized dynamic-state and transient simulation tests have
the magnitude, frequency components, and d.c, offset of the been used to examine overall protection and communica-
protected circuit secondary is recommended to determine tion system operation. These have successfully identified
whether performance is suitable for the application. [2] malfunctions of individual relays in the scheme; of
- 7 -
solid-state relays, and of associated communication equip- Tests should be performed with the relay mounted in the
ment. Failure of circuit breakers to operate properly has manner prescribed by the manufacturer. For electromag-
also been discovered. Application tests are notably netic relays, normal physical orientation of the case
appropriate in the following instances: (vertical, level, etc) should be observed. For relays with
electronic circuitry, the case should be grounded.
To evaluate effects of less than ideal instrument
transformer performance, such as (ct) saturation The burden, and especially the capacitance and induc-
and (cvt) subsidence. tance, of test operation indicators should be low with
relationship to the rating of contact or other output sensing
To evaluate effects of unusual system conditions devices.
such as ferroresonance, harmonic resonances, off
AVOID ERRORS!
nominal frequency, low voltage, loss of stability,
high load, high source to line impedance ratio. Relays are measuring instruments. As with all measuring
instruments the accuracy, resolution, and stability of calibra-
To evaluate the effects of power electronic devices
tion and test signals must exceed (relay) measurement speci-
and their controls, such as static var compensators,
fications. Instability or errors in test signals may cause
variable series compensation, and local HVDC
inaccuracies in settings. Subsequent indeterminate re-
circuits.
sponse to power system disturbances may result.
To evaluate response to unusual conditions such as
evolving faults, slow clearing external faults, and 3.2 Measured Signals
faults with high arc or ground resistance.
3.2.1 AC Signals
3.0 TEST SIGNALS This section reviews the requirements for voltage and
current test signals used for both integrity and application
3.1 General tests. Control of parametric values of frequency, amplitude,
AVOID DAMAGE! and phase angle relationships is presented in terms of relay
measurements. Test source specifications and their effect
Test signals may exceed the continuous rating of the
on test results is also discussed.
relay. Test equipment may be capable of damaging the relay
if carelessly applied; the damage may cause immediate The voltage and current parameters for most relay tests
failure or operation may be slowly degraded. Marginal approximate a power system fault condition. Voltage and
operation followed by failure when called on to operate current amplitudes and phase angle relationships at the
under power system transient conditions is a more serious power system frequency must be independently controlled
event. to simulate the fault phasor relationships.
Persons responsible for designing the test must be For steady-state tests, phasor parameters are slowly
cognizant of relay I 2t specifications, and voltage limitations. changed to determine relay calibration setting. Single phase
Test designers must ensure that those responsible for faults require a change in one parameter, while the
carrying out the tests are aware of the precautions necessary remaining phasors describing the fault remain constant.
to avoid damage or reduction of life. Unnecessary The phasor diagram in Figure 4 shows the constant, (preset)
tampering or adjustment of the relay must be discouraged voltage phasor relationships which describe an A-N Fault
to reduce "adjustment induced" failure. Condition.
VA = VFAULT
- 8-
In the Phasor Diagram of Figure 4, VA is set at the fault (II) represents an incrementing current used to determine
voltage; VB and Vc represent balance. The dotted phasor A-N reach.
VA =ACTION
+I
I
Vc
~\
I \
I \
I \
11 lAB =ACTION
IV \ /
I A /
I /
/
I
I // VAB=V FAULT
I
Vc
Figure 6 Phase-to-Phase Test with Current Action
These simple examples demonstrate amplitude control Dynamic state tests are used to determine the time
requirements for basic steady-state tests. Tests for system response of a relay to a predetermined fault condition. For
disturbances involving additional phases require similar example, run the previously described steady-state test to
control of the involved phasor qualities. determine A-N reach; then perform a dynamic state test to
reveal operate time for the fault condition.
- 9 -
VA = V FAULT
30V~
Vc VB Vc VB
70v 1-240 0 70v 1-120 0 70v 1-240 0 70v 1-120 0
- 10 -
of the waveform, at a point in time. For polyphasesystem and frequency to properly reproduce the system distur-
representation, synchronism between all sources of digital bance. Discussions on sampling frequencies and data
information must be precise to ensure correct phase format may be found in the COMTRADE Standard [4]
relationship. Any amplifying means must similarly provide recommended for anyone considering use of transient
constant or predictable phase shift vs. both load impedance simulation application tests.
VA
IAAQ(l
\TV v V V v
==ooaA!\f\f\f\
v v v C7 V \TV \TV
VB ADAAAAAAAAAAAAAAAAAI
JVVVVVVVVVVVl}VVV\[VVV
\AAAAAAAAAAAAAAAAAAA
VC
VV \[\[V VVvVV\[V \)\[VVVVV ~
11
Df\ f\ f\
12
13
- 11 -
3.2.1.6 Line Synchronized and Self Synchronized Instrument transformer (Cf) saturation, or
Operation (CVT) subsidence, or ferroresonance,
Test signal sources require frequency accuracy and Power system swings or current reversals,
stability in proportion with relay measurement capability.
Typically, quartz crystal based references are used to attain Power transformer ferroresonance,
accuracy of approximately0.01 Hz and stabilityof 50 to 100 Inrush from transformer, reactor, transmission
ppm. line, cable, and shunt capacitor energization,
Some electromechanical relays are susceptible to Effects of nonlinear devices such as surge
electromagnetic fields from generator and distribution arresters, thyristors,spark gaps,and powerdiodes,
busses. These relays may appear to perform incorrectly Circuit breaker current chopping and transient
when tested with signals having independent crystal based recoveryvoltages.
references since these are asynchronousto the local power The precedingitems are not meant to form an exhaustive
system fields. Variations of the relay operating point may list; they give an idea of the variety of transients that must
be observed as the test signal beats with the interfering exist in the test signal which simulates system conditions,
system frequency. This signal is used for transient simulation tests where the
applied test signal represents the faulted power system as
Such relays are in wide serviceso care must be observed
closely as necessary to evaluate proper relay performance.
and interference effects noted. To determine the setting
error due to interfering magnetic fields, run one test in line 3.2.2 DC Signals
synch mode to determine one set of test results. Run a Some relays which measure de quantities are special
second test with phasors reversed 1800 The actual setting purpose devices. DC test signals which examine perform-
is the averagebetween the two results. If the variationfrom ance should be a subject of agreement between the
the average is significant,check the applicationof the relay manufacturer and user. Sincegeneralizationisnot appropri-
in its environment. ate for such specialpurpose relays,they willnot be discussed
further.
3.2.1.7 Sine Wavewith Controllable Frequency and Rate
3.3 Environmental Signals
of Change in Frequency
Manufacturers normally specify applicableenvironmen-
The accuracy and stability of the frequency should be tal standards for whichtheir relays are designed. Users will
some small fraction of the resolutionof the relay.This varies
normally only apply such signals when the manufacturers
from 0.02 Hz for axial turbine synchronizing relays to 0.1 specificationis silent on a particular aspect of performance,
Hertz for general purpose frequency relays. The rate of or for troubleshooting. This document does not address
change should be controllable similarly to that described environmental signals. Other standards and references
above for amplitude control. discuss environmental signals in great depth; they will be
Rate of change in frequency vs. time ranges from 0.01 mentioned briefly here.
Hz/second to tenths of Hz/second depending on power Some of the test instruments used to provide a.c, test
system design. signalsmay be susceptibleto the environmental test signals
when simultaneously applied to the relay. AC test
3.2.1.8 Sine Wavewith Added Harmonic Content instruments should conform to the same environmental test
Control of harmonic frequency, its magnitude and time standards as the relay. Alternately, the test instruments
(phase angle at each harmonic) relationship may be should be evaluated to ensure its performance in the
required. These signals are used for testing relays such as presence of environmental test signals is known.
harmonicallyrestrained differential relays, and tuned relays 3.3.1 Auxiliary DC and DC Interference
such as third harmonic sensing stator ground fault relays.
If a relay requires a de power source, various test signals
Reference [2] discusses the effect of harmonics on relays,
may be applied to the relay's internal dc power supply.
and is particularly useful when designing application tests.
Maximum and minimum de voltage levels may be applied
Commonly required harmonics are 2nd, 3rd ,5th, 7th, 9th,
(with or without superimposed ripple) for verifying
11th, 13th, and 15th. Harmonic frequencies higher than 1
operation under actual measurement conditions, and for
kHz are rarely required in a measured signal.
measuring dc burden [3]. Voltagedips and interruptions of
various magnitudes and duration may be applied to the
3.2.1.9 Sine Wavewith Transient Components power supply [6].
Representing Actual Si~nals From a Power System
These transients may include; 3.3.2 Conducted Electrical Interference
The effect of conducted AC surges and fast transients
Fault or switchinginduced de offset, which appear on any relay terminals are important, and
- 12 -
should be investigated. These signals are applied to all the relay performance should be verified by full transient
terminals except those specifically exempted by the tests, or the results discussed with the manufacturer.
manufacturer's specifications in accordance with the Since they closely simulate actual fault conditions [12]
standard on Surge Withstand Capability [7]. transient tests signals are required to fully assess relay
performance. Transient tests need include only those system
3.3.3 RF Signals and RF Interference conditions relevant to the application.
RF signals from nearby transceivers have interfered with
Harmonic contaminated test signals may also be applied
some electronic relays and also with electromechanical
in some application test plans, particularly where the
relays with solid state electronics. Manufacturers and users
measured signal is also contaminated with harmonics.
are referred to [8] for guidance.
Environmental test signals may be applied in application
3.3.4 Non Electrical Influencing Factors test plans, particularly where the manufacturer's specifica-
Altitude, temperature, humidity, and seismic shock are tion is silent about an environmental factor which may be
other influencing factors on relay performance [9]. These present in an application.
factors are not discussed here. 4.0 TEST EQUIPMENT
- 13 -
Today, computer based electronic simulators of various test quantities. Variacs can be utilized in single phase, three
types have become available, and are used in increasing phase open delta or three phase wye configuration. They
numbers by utilities and manufacturers alike. The most modify the mains potential, producing a source of variable
basic playback simulators use records of actual faults from voltage. Outputs are not isolated from the power mains and
DFR or system waveform information produced by are a shock hazard. Relay inputs must be connected
mathematical models. Real time digital simulators provide appropriately to prevent incorrect signal paths. Variacs can
the interactive flexibility of analog model power systems. be a source of undesired harmonics.
They compute initial, balanced system conditions and the
changes in system conditions due to disturbances, all in real Variacs are also utilized as an integral extension ofeither
time, e.g.: protection system response modifies the system the load box or the phase shifter to vary the voltage or
parameters and conditions are re-computed in real time. current test quantities.
- 14 -
Multi Ratio Load Resistors
Variac Transf.
Tap Select
Variable
Resistor
L..----(O
Output Terminals
The output voltage from a special three-phase induction Internal alarm systems eliminate use of external
motor with a balanced and symmetrical rotor (primary) and meters
stator (secondary) windings provides continuously variable Electronic relay test instruments produce sine waveforms
phase relationships with respect to its input. of voltage and current at appropriate levelsfor testing relays.
Typical voltage and current maximums are 300V rms and
A six-phase to three-phase tapped transformer, tap 35A rms, at power ratings range up to 100 VA. Higher
changing switches and a variac also provide variable phase powered current sources for high current tests on
angle output voltages with respect to its input. Tap selection electro-mechanical relays are rated around 150A and 500
provides coarse selection of phase angle; the variac is used VA.
for fine tuning.
Advanced functions provided by newer digital designs
include synchronous switchingof phasors for dynamic-state
4.3 Electronic Test Instruments tests and playback of waveforms from external digital files
for transient simulation tests. Use of external frequency
4.3.1 Common Characteristics references from satellites allows synchronization of
Common characteristics of electronic instruments remotely located test instruments for in-situ end-to-end
designed specifically for protection testing include: tests on relays. D.C. coupled feedback amplifiers offer
reproduction of the d.c, transient component of fault
Internally generated sine wave reference waveforms. P.C. based programs for steady-state, dynamic
Variable frequency operation and transient test methods are in general use; automated
Direct digital control of voltage, current, phase integrity testing for periodic maintenance testing is a
angle, and frequency common application.
- 15 -
EXTERNAL REFERENCE
MAINS
POWER INPUT
~ PHASE
LOCKED
VARIABLE DIGITALDIVIDER
LOOP
FREQUENCY
REFERENCE (GPS ETC.)
FREQUENCY REFERENCE
---------------
DIGITAL
ANALOG
OUTPUT
SAMPLE
CLOCK
WAVEFORM GENERATION
ERROR - - - - - - - - - - - - - - - - - - - - --
ALARM ~
___ --~__t ERROR DETECTION \V
-------
FEEDBACK
.......- .....----<
CONVERTIBLE
ANALOG VOLTAGE
INPUT CURRENT
DIRECTCOUPLED
OUTPUTSTAGE
CONDITIONING
AMPLIFIER
TRANSFORMER
COUPLED
CURRENT
OUTPUTSTAGE
TRANSFORMER
COUPLED
VOLTAGE
OUTPUTSTAGE
- 16 -
For sinewave generation, 3600 sine co-efficients are output causedby changesin the load impedanceor the line
stored in memory, in this example; one value is stored for powersupply. The output is monitored by error detection
every0.1, from 0 to 359.9.The address counter wraps circuits and an alarm issoundedifthe output containsampli-
around afterevery3600 counts and returns to the start point tude or total harmonic distortion errors exceeding test in-
to produce a continuous waveform. Phase control is strument specifications.
achieved byoffsetting the start point of the address counter.
The phase angleisset by front panel controlsor byexternal 4.4 Transient Simulators
computercontrol. Sincephasecontrol iscompletely digital, Descriptions of the designs and operationalcharacteris-
thisdesign does not create phase errors when the sinewave ticsof the three mostprevalentformsof transientsimulator
frequency is changed. available today are included in this section.
Transientsimulators accurately representthe steadystate
When reproducing transient waveforms, the stored
and the transientpowersystem waveform. Earlysimulators
coefficients are those of the desiredwave. Coefficients may
were analog, and used scaleddownor electronicmodelsof
represent any digital number within memory depth
power system elements. These model power systems tend
(typically 16 bits) and any number of samples within
to be large and expensive and have been confined to
memorycapability. The clockfrequency isset to the desired
manufacturers, larger utilities, and research laboratories.
samplereproductionrate; the addresscounterruns through
a sampleset once, then stops. UsingEMTP data at 10J,lSec. Playback digital simulators using off-line EMTP
per sample for example, a transient event of one second solutions and conditioning amplifiers allow stored digital
requires 100,000 samples or 1666/1667 samples per 60 Hz waveforms to be fed to relays. These simulators are less
cycle. costly and smallerthan the ModelPowerSystem (MPS), but
cannot acceptinput from the device under test and interact.
The numerical output of the waveform memory drives a The MPS has the advantage of runningin real time and can
digital to analog converter(DAC)providing instantaneous be used in an interactive mode with the device under test.
analogvalues for each co-efficient. The sequentialsamples
producethe desiredwave at a smallsignal referencevoltage, Real time digital simulators are nowavailable. Running
typically around 10volts peak. That referencewave is fed EMTP in real time with parallel processing computers
into a multiplying digital to analogconverter, (XDAC). This which driveconditioning amplifiers, combines the smallsize
scales the sinewave amplitude according to the digital value of the playback simulator with the real time interactive
set by the front panel controlsor externalcomputercontrol. capability of the MPS. They are more expensive than
When the XDAC is set to full scale, scaled amplitude is playback simulators.
equal to the reference wave amplitude. The analogoutput 4.4.1 Analog Simulators
signal drives poweramplifiers to attain VAlevels suitableto
Lowand high power analogsimulators or MPSutilizing
drive relay inputs.
lumped parameter models have been used to simulate
Amplification and Output Stages power systems for many years. These provide analog
waveforms fortestingrelays understeadystate and transient
The smallsignal output from the waveform generator is conditions. The lowpower MPS requirespowercondition-
amplified by negative feedback amplifiers to produce ing amplifiers. These convert the signals to levels suitable
relaying level voltages and currents.
for driving the relayunder test. Amplifiers are described in
Because relays contain saturating electromechanical Section 4.5. The highpowerMPS operates at signal levels
components, the amplitude and phase of the relayburden which allow direct connection between the MPS and the
can change by orders of magnitude. This mandates relayunder test. See Figure 11.[14]
amplifier stability under rapidly changing load impedance. The MPS provides facilities for representationof all the
The amplifiers maybe voltage, current,or convertible types important elements of a power system.[14] These include
capable of being switched between voltage and current transmission lines, shunt reactors, series compensation
modes. capacitors, circuit breakers, and generation sources. cr
The amplifier output is fed to the output terminals byan and CVT models are also available. Fault location, fault
output stagewhich conditions the feedback, and rangecon- type and point-on-wave fault initiation are controllable to
trol relays. Transformer coupledsources include a variable research wide ranges of power system operation.
ratio output transformer. This maximizes amplifier power Relayoperation and the MPS waveforms are measured
transfer to the load by impedance matching. DC coupled and recorded to provide information describing how the
sources drive the relay directly. Feedback is derived from relaywould performon the actualpowersystem. The MPS
a current shunt for current sources and from a resistorfor usesac contactorsto simulatecircuitbreakers;these maybe
voltage sources. Negative feedback around the amplifier operated from the trip contacts of the relay or recloser
compares the output withthe input,correcting errors in the where appropriate.
- 17 -
"LOW
ANALOG MODEL POWER
.........
.........
CONDITIONING
I---
~~ I
"
USER INTERFACE --. MONITORING
EQUIPMENT
- 18 -
~,
D/A CONVERSION
REAL TIME SYSTEM .......... ......... RELAY SYSTEM UNDER
SIMULATOR ...... AND CONDITIONING ....... TEST
AMPLIFIERS
~~
- 19 -
Identifying coefficients on various waveforms at extension as well, if reclose functions are involved in the test
which protection timing begins plan.
In the event that tests using actual DFR records are
Converting files to binary for downloading to
insufficient to establish relay performance, complementary
waveform memory
EMTP studies will be required. Power system and relay
Storing test results application experience will dictate the level of complexity
required for playback simulators.
For DFR and EMTP files, extending the prefault data
period is an important editing function. Sufficient prefault In comparison to todays real time simulators and model
is required to allow relays to normalize operation before power systems, the off-line EMTP runs can represent very
disturbances are applied. Post-fault periods may require complex power systems.
"
USER INTERFACE "
MONITORING
EQUIPMENT
Current sources must be capable of ranges from 10 per Minimal specifications for power conditioning amplifiers:
unit up to a maximum of 50 per unit for some power systems. Amplifier performance must conform to the require-
Typical 20 per unit, SA secondary current values are: ments of both the relay burden, and the simulation quality.
20 x f2 x SA = 141A pk. Higher DFR sampling rates and typical, 50J..Ls per sample
EMTP calculations place significant burdens on amplifier
- 20 -
design. Amplifiers formerly suitable for use with analog 5.0 TEST METHODS
model power systems have less dynamic range and
5.1 General
frequency response than required by today's simulators.
Previoussectionsof thispaper havediscussed varioustest
Frequency response, output amplitude range and signals and test equipment that are available to the relay
accuracy are well known criteria. They conform to engineer for both integrity and application testing. This
specifications and standards for instrument transformers section is a general discussion of how that information may
and with power system performance. As noted previously, be used to plan effective integrity and application tests.
peak voltampere rating must be considered in light of both
It should be recognized that protective relays come in a
per-unit simulation values and relay burden.
wide variety of complexities, from simple single quantity
Amplifier stability under widely changing relay burdens overcurrent functions to complete distance protection
has been mentioned. Load power factors from unity to schemes: therefore this paper is not a comprehensiveguide
nearlyzero lead and zero laghavebeen observedand should on relay testing. Section 6 of this paper includes examples
be considered limits for amplifier specifications. Stability of integrity and application tests and should help illustrate
under rapidly changing signal conditions should also be test protocols.
consideredwhen specifying amplifiers. Large signalslewing
Care is required in applicationof multiphase test signals
rates of a few amperes per microsecond are commonly
to ensure accuracy of the test signal. For instance, the
observed in EMTP simulations. A change in peak current
voltagesduring a phase-to-phase fault maybe simulatedby
from -7A pk (SA RMS), to 210A pk is based on 140 A pk
applying twophase to neutral phasors withthe proper phase
at 20EU. plus 70A pk(50% offset). Toaccommodatea fully
relationship.
offsetcurrent signal,twice the peak current of a symmetrical
signal is required. The slewing rate is approximately In cases when the phase-to-phase voltage is low, very
0.5NJ..Ls (2l7NlOOJ..Ls). Lightning strikes represent smallerrors in the phase relationshipof the twotest phasors
thousands of amps per J..ls in primary current - requiring will cause large errors in the magnitude of the test voltage.
slewing rates of tens of amperes per J..lS secondary current. On a 120volt system, a phase fault with a source to fault
impedance ratio of 10 to 1 would result in a faulted
phase-to-phase voltageof 12volts. In a wyeconnected test
Voltage amplifiers systemthe phase-to-phase fault voltagewouldbe produced
by two phasors with equal magnitude of 35 .157Vdisplaced
Input voltagerange + 10Vpeak (high impedance
source) -- by 9.83 0 A total phase difference error of plus 10 (10.83 0 )
would result in a phase-to-phase to voltage of 12.6 V, a
Output voltage range.::!:. 300V peak voltage error of + 5%. A phase angle error of 0.50
Power output: 75 - 150 VA rms (150 - 300 VA producing12.3 voltsisa 2.5%error. Duringsuch tests,direct
peak) application of a phase-to-phase signal is preferable if
possible.
Frequency response (small signal) de to 10 kHz
+ 3dB For any given test, the relay engineer must decide what
type of input signals and what type of test equipment are
Noise -80 dB of full scale required. In some cases, compromise may be necessary
Transfer Gain Error @ nominal frequency.::!:. 1% because of practical considerations such as test equipment
availability. In the choiceof input signals, the engineer must
Common Mode rejection -60 dB of full scale be guided by his experience and knowledge of both the
power system and the relay.[18]
Current amplifiers
Input voltagerange.::!:. 10Vpeak (high impedance In many cases,the test will be similar to those suggested
source) by the relay manufacturer. For these tests, decisions are
generally straightforward, depending primarily upon what
Output current range.::!:. 160A peak equipment is available to meet the manufacturer's require-
Power output 0.5 - 3kVA rms (1- 6kVApeak) ments. If, for example, the test involves verificationof the
time curves on a time overcurrent relay, the engineer may
Frequency response (smallsignal)de to 10kHz + conclude that steady-state current signals will produce the
3dB -- desired results. This choice will allow the use of several
different types of test equipment.
Noise -80 dB of full scale
However, when a relay is being tested for a specific
Transfer Gain Error @ nominal frequency... 1%
application, or as the result of some specific power system
Common Mode rejection -60 dB of full scale condition,the manufacturer's instructionbook method may
- 21 -
not be sufficient. Recent examples haveproven the need for electronic test sources as well. However, the user must
simulation tests on overcurrent relays, one in an industrial ensure that the test connections and phasor relationshipsof
protection circuitwith highlydistorted waveforms, another the electronicinstrument duplicate those of the passivetest
where an instantaneous element was driven by a saturated equipment.
CI: For these tests the relay engineer must determine the
appropriate inputs and test equipment. Since all relaysare 5.3 Application Test Methods
applied on power systems, a power system simulator will When current and voltage signals representative of
generallyprovide proper current and voltageinputs for any actual power system conditions are desired, some form of
type of test. However, power system simulation tests are power system modeling is required. If dynamic state
usually expensive and time consuming. simulation provides an adequate level of simulation, load
and fault phasor values can be calculated using traditional
Between these two extremes are many other tests of
principlesor a computer based fault study program.
varying degrees of complexity. The selection of the input
signals and the type of test equipment is not directly If more realistictransient simulation is required, it may
dependent upon whether the test is an integrity test or an be possibleto obtain actual disturbance data from a digital
application test, but rather on how close to actual power fault recorder. Otherwise computer modelling with
system signals the test signal must be. Since many relays programs similar to EMTP are required. Transient
filter out all components except the fundamental from the simulation waveforms may be stored in either analog or
measured signal, dynamic state simulation is a powerful digital form. These may be played back to the relays at a
method of application testing, but it has some important later time. Analog power systems may also be used. The
limitations.[10] type of model is often determined by what means are
available.
The improper representation of transition from
one state to another can sometimes cause In a playbacksimulator,the relaycannot interact directly
incorrect relayoperation, especially in high speed with the power systemsimulation. When the relay issuesa
relays. trip output, since there are no circuit breakers in the
pre-recorded simulationto respond, there is no interaction.
The effectof non fundamental frequency compo- (See Figure 13)
nents such as harmonics is not included. It is
important to includethese effectsin manyapplica- In a real time system, relay outputs can cause a change
tion tests. Somerelayssuchasharmonicrestrained in the power system model, such as opening the circuit
transformer differential relays require harmonics breaker when the relay operates. This is a "closed loop"
forproper operation. Manyrelayscanbe adversely system as shown in the block diagram of Figures 11 and 12.
affectedbyharmonicsand other non fundamental The majority of real time simulators use an analog model
frequencysignals; suchsignalsshouldbe present in of the powersystem. This maybe a lowpower modelwhich
the test if they are present in the application. requires current and voltage amplifiers. In high power
However, dynamic state simulation tests may be modelsthe current and voltageoutputs can drive the relays
useful to explore the expanded characteristicof a directly without interposing conditioning amplifiers (see
cross polarized mho or compensator relay in a Figure 11). Recent advances in digital power system
timely and complete fashion.[19,20] simulation have led to the development of real time digital
simulation. This allows the relay to modify the simulation
5.2 Integrity Test Methods parameters (see Fig. 12).
The basis for most integrity testing on protective relays
will be the manufacturers' recommended methods for the 6.0 EXAMPLE
relay. These tests are designed to verify that the relay is 6.1 Introduction
functioningproperly,and that the correctsettingshavebeen
A Canadian utility was consideringapplication of a new
applied.Generally,these are steady-state tests,but dynamic
typeof multifunctiongenerator protection relayon some of
state tests are sometimesused for checkingtimingand relay
its hydraulicgenerators. A test program was developed to
memory action. determine whether the relay would be suitable for general
In some instancesthe user maydesireto includedifferent application on such generators. The relay generally
methods in the integrity test plan for a particular performed satisfactorily, but some operations that were not
application. These additional tests may be steady state, apparent from the manufacturer's specification were
dynamic state, or transient in nature. discovered.
In many instances the test equipment used in the The relay is capable of operating in two modes:
manufacturers literature is passive (load boxes, variacs, and fundamental frequency measurement, and total rms
phase shifters). The same tests may be performed using measurement. In the fundamental mode, all harmonicsare
- 22 -
filtered out. In the total rms mode, the rms value of the 3. Checkeffectof frequencyvariationof input signalfrom
signal, including the effect of all harmonics is measured. 30 Hz to 120Hz. (SS Freq.)
Tests were made with the relay in both modes. Voltage and Current Measuring Elements - Steady-State
An overview of the test program is presented. Details of Performance
numbers of tests at different settings are not included. 1. For allmeasuringelements,checkthe accuracy at min.,
These data will vary depending on the relay being tested, reference and max. settings. Also check reset ratio.
and purpose of the tests. It will be noted that a largevariety Use pure 60 Hz sine wave signals. (SS)
of tests are included in the following program because the
2. For all measuring elements, check the effect of har-
relay is being tested for general application. monic contamination on the accuracy. Use 60 Hz sine
wavewith 20% third harmonic at variousphase angles
6.2 Sample Test Plan with respect to the fundamental. Run checksin funda-
TEST PROGRAM FOR A MULTIFUNCTION mental and total rms modes. (SS Harm.)
GENERATOR PROTECTION RELAY 3. For allelements,checkthe effectof frequencyvariation
General on accuracy. Use a pure sine waveover a range of fre-
quencies from 30 Hz to 120 Hz. Run checks in funda-
1. For internal timing functions, check accuracy at mini- mental and total rms modes. (SS Freq.)
mum, reference, and maximum settings. Check over-
shoot (inertia) to determine whether signalspersisting 4. For all timed elements, check the accuracy of timers.
(TIME)
for marginally shorter duration than the timer setting
can still cause undesirable outputs. 5. Check the relationship between elements which con-
trol other elements internally. For example, the volt-
2. In allcases,observeand report on contact chatter when
age controlled overcurrent function is not allowed to
test signal approaches operating point.
start until the voltageis depressedbelowa settable lev-
3. Sixdifferent typesof testshavebeen identified; theyare el. Does lowvoltageon anyone phase allowall over-
abbreviated as follows: current functionsto start, or does only the overcurrent
element on the associated phase start?
SS Steady-state 60 Hz tests. Unless otherwise Current Measuring Elements - Dynamic Performance
indicated, this test should be applied using
the fundamental frequency measuringmeth- 1. Check the dynamic performance of the inverse time
od of the relay. overcurrent element. Does it emulate the integrating
actionof an electromechanical inductiondiscwhen the
fault current changes? (Dynamic)
TIME Steady-state timing tests.
2. Check operating time of instantaneous overcurrent
SS Harm. Steady-state tests with harmonics superim- elements. Check effect of presence or absence of pre-
fault load. (Dynamic).
posed on the fundamental frequency signal.
Voltage and Current Measuring Elements - Transient
SS Freq. steady-state tests at variable frequencies. Performance
1. Checkthe effectof transient decomponent on accuracy
Dynamic Dynamicstate simulationsof faultconditions of instantaneous overcurrent elements. Run checksin
using 60 Hz test signals. fundamental and total rms modes. (EMTP)
2. Check the effect of ct saturation on time and instanta-
EMTP Transient tests using data derived from neousovercurrentelements. Run checksin fundamen-
EMTP or other similar simulator. tal and total rms modes. (EMTP)
AID Converter Accuracy 3. Check the response of peak overvoltage elements to
1. Using the indication facility, check the accuracy of all distorted waveforms present during simulated ferrore-
sonant conditions. (EMTP)
voltage and current input functions (magnitude and
angle). Use accurateexternalmeters to checksignalin- Frequency Elements
puts. Checkallvoltageinputsat three points, (1.0~ ref.
V and max. V). Check allcurrent inputsat three points, 1. Check accuracy of functions. Use 60 Hz sine wavesig-
(0.lA, 5 A and max. available current, keepingin mind nal. Check trip output maintained when frequency
the rating of the relay input circuits). (SS) raised to 120Hz. (SS Freq.)
- 23 -
4. Check whether trip timing is affected by application of 79. Reconnect Time Delay
ramped frequency change or step frequency change. (2
1. This function will not normally be used, but will be
Dynamic)
tested for completeness. Check timer accuracy. Check
5. Apply third harmonic distortion such that there is more how function is initiated and blocked. (TIME)
than one zero crossing per fundamental frequency System Tests
cycle, and check whether measuring accuracy is re-
tained. (SS Harm.) 1. Test the operation of the device with a variety of simul-
taneous and near simultaneous faults.
6. Check response to EMTP simulations of ferroresonant 2. Simulate application of overcurrent and coincident un-
conditions. (EMTP) dervoltage conditions. Set test conditions so that the
inverse time overcurrent element is expected to oper-
7. Check accuracy of timers. (TIME)
ate just before undervoltage, and vice versa. (Dynamic)
Negative Sequence Overcurrent Element. 3. Simulate application of single phase current such that
inverse time overcurrent function will operate just be-
1. Check whether accuracy is affected by use of single fore negative sequence, and vice versa. (Dynamic)
phase current (12 = (1/3)applied current) or balanced
three phase current rotating with negative phase se- 4. Simulate application of overfrequency and overvoltage
quence. conditions such that RMS overvoltage, Peak overvol-
tage, and overfrequency functions all operate near si-
2. Check accuracy of pickup. (SS) multaneously. (Dynamic)
- 24 -
capable of doing full transient simulation tests. Analog 9. ANSI/IEEE C37.90-1989 "Standard for Relays and
simulators are the traditional means of transient testing and Relay Systems Associated With Electrical Power Appa-
they are still widely used in laboratories and factories. Play ratus"
back digital simulators are now being widely used in the field 10. C. F: Henville and J. A. Jodice "Discover Relay Design
and workshop for "open loop" transient tests. Real time and Application Problems with Pseudo Transient
digital system simulators will allow relay users the ability to Tests", IEEE Transactions on Power Delivery, October
do complete "closed loop" application tests in their own 1991,p.p.1438-1443
premises. When the power system is properly modeled, and
11. G. E. Alexander, E J. Lerley, and R. Ryan, "Compara-
test equipment is properly used, virtually any proposed tive Testing Using Digital Simulation and an Analog
application can be comprehensively studied by the relay Model Power System", a paper presented at the Doble
user or manufacturer. It is important to completely ProTesT Users Group Conference, 1990
understand the signals that will be presented to the relay in
12. M. Kezunovic, et al "DYNA TEST Simulator for Relay
its intended application, when devising a test plan to
Testing, Part II: Performance Evaluation" IEEE PES
examine relay performance.
Winter Meeting, February 1991
REFERENCES 13. LA. Thiem, "The Effect of Waveform Distortion on
1. A Survey of Relay Test Practices, 1991 Results, IEEE Overcurrent Relay Calibration", 49th Annual Interna-
Power System Relaying Committee Report, IEEE/ tional Conference Doble Clients, Boston, MA, 1982
PES 1994 Winter Meeting, NY, NY, 94WM137-0 14. "General Electric Model Power System", GE publica-
PWRD tion GER-3225
2. IEEE/PSRC Working Group, "Sine-wave Distortions 15. EG. McLaren et al. '~Real Time Digital Simulator for
in Power Systems and the Impact of Protective Relay- Testing Relays.", IEEE Trans. PWRD, Vol. 7, No.1,
ing", IEEE Report 84TH 0155- 6PWR January 1992.
3. CIGRE SC 34 "Guide on Evaluation of Characteristics 16. M. Kezunovic et aI, "Transients Computation for Relay
and Performance of Power System Protection Relays Testing in Real Time", IEEE Trans. Pwrd., Vol. 9, No.
and Protective Systems" 3, pp. 1298-1307, July 1994
4. ANSI/IEEE C37.111, Common Format for Transient 17. J. Esztergalyos, J. Nordstrom, L Short, K. Martin,
Data Exchange (COMTRADE) "Digital Model Power System", IEEE Computer
5. IEEE Std. 519: IEEE Recommended Practices & Re- Applications in Power, Vol. 3, No.3, July, 1990, p. 19
quirernents for Harmonic Control in Electric Power 18. K. H. Engelhardt, "Dynamic Performance Testing of
Systems Mho Relay Memory Action", 1982 Western Protective
6. C. F Henville "Type Testing of Distance Relays" 14th Relay Conference, Spokane, WA
Annual Western Protective Relay Conference, Spo- 19. W O. Kennedy, B. 1. Gruel, C. H. Shih, L. Yee, "Five
kane, WA October 1987
Years Experience with a New Method of Field Testing
7. ANSI C37.90.1-1989 "Standard Surge Withstand Ca- Cross and Quadrature Polarized Mho Distance Re-
pability (SWC) Tests for Protective Relays and Relay lays", IEEE/PES Winter Meeting February 1987
Systems"
20. R. Ryan, 'Automatic Testing and Plotting of Protective
8. ANSI/IEEE C37.90.2-1995 "Trial-Use Standard With- Relay Polarized Mho Characteristics", 59th Annual In-
stand Capability of Relay Systems to Radiated Electro- ternational Conference of Doble Clients, Boston, MA,
magnetic Interference from Transceivers" 1991
- 25 -