Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Version V1.0
Revision date October 24, 2012
BOM 31012653
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Electrical Safety
I. Hazardous voltage
Danger
Some components of the power system carry hazardous voltage in operation. Direct contact or indirect contact through
moist objects with these components will result in fatal injury.
Safety rules in the industry must be observed when installing the power system. The installation personnel must
be licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets,
bangles, rings.
When water or moisture is found on the Subrack, turn off the power immediately. In moist environment,
precautions must be taken to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during
installation.
Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance
with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.
II. Tools
Warning
In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.
III. Thunderstorm
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD
Notice
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale
ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from
damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.
V. Short circuit
Danger
During operation, never short the positive and negative poles of the DC distribution unit of the system or the non-grounding
pole and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment
burning and endanger human safety.
Check carefully the polarity of the cable and connection terminal when performing DC live operations.
As the operation space in the DC distribution unit is very tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Insulated tools must be used.
In live operation, keep the arm muscle tense, so that when tool connection is loosened, the free movement of
the human body and tool is reduced to a minimum.
Warning
240VA, hazardous energy, keep off, no bridge connection. This converter contains outputs exceed 240VA, when installing
into end system care must be taken that the output and appropriate wire may not be touched.
Battery
Danger
Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery
connection method.
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent
battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs,
thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
Use special insulated tools.
Use eye protection device, and take preventive measures.
Wear rubber gloves and apron to guard against electrolyte overflow.
In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery
upside down or slanted.
BLVD
The system has battery low voltage disconnection (BLVD) function. BLVD means when the mains fail and
batteries supply power, the controller cuts the load off when the battery voltage drops down to below 43.2V to
prevent over-discharge. The BLVD voltage is settable. Refer to ACU+ User Manual for setting method.
The factory setting is enabling BLVD, which means that if power outage lasts for a long time or the power system
fails, there might be BLVD. Users should classify the loads and connect the priority loads to BLVD routes. For
vital loads, users can disable BLVD of these loads to insure reliability of the power supply.
The method of disabling BLVD is:
Set BLVD Enable item of the controller to N. Refer to ACU+ User Manual for setting method.
Notice
The advantage of enabling BLVD is protecting the batteries from over-discharge when the battery voltage is low. The
disadvantage of enabling BLVD is that when the battery voltage drops down to a certain value, all the loads (including
non-priority loads and priority loads) will be cut off due to battery disconnection.
The advantage of software disabling BLVD is prolonging the power supply of priority loads. The disadvantage is that
software disabling cannot prevent unwanted power failure due to misoperation or power system failure.
Others
I. Sharp object
Warning
When moving equipment by hand, protective gloves should be worn to avoid injury by sharp object.
Notice
Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.
Notice
The signal lines should be bound separately from heavy current and high voltage lines, with binding interval of at least
150mm.
Contents
Chapter 1 Overview
This chapter introduces model description, composition and configuration, and features.
The power system in this manual refers to the NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 series 19
inch subrack power system.
NetSure 501 A 4 1 S 1
Cabinet configuration
Cabinet type: Subrack
Version
The number of the rectifier in the typical power supply
system: 4, If the number ranges between 0 ~ 9, the character
is represented by a number, If the number is larger than 9,
the character isrepresented by a letter, for example: A
represents the number 10, B represents the number 11, and
so on
Region A : Asia- Pacific region
Output power of the rectifier. 501: 1740W ~2000W. 701: 2900W ~5000 W
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
2 Chapter 1 Overview
Positive terminals
Battery MCB
AC input MCB
Load MCB
Rectifier
Monitoring module
Controller
Dummy panel
System configuration
The configurations of the power system are described in Table 1-1.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 1 Overview 3
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
4 Chapter 1 Overview
1.3 Features
The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99.
Wide AC input voltage range: 85V ~ 290V (NetSure 701 A41) or 85Vac ~ 300Vac (NetSure 501 A41 & NetSure
501 A91).
The rectifier uses soft switching technology, raising the system rated efficiency to 91%.
Ultra-low radiation. With advanced EMC design, the rectifier meets international standards such as CE and
NEBS. Both the conducted and radiated interference reach Class B.
The rectifier safety design complies with UL, CE and NEBS standards.
High power density.
Rectifiers are hot pluggable. It takes less than 1min to replace a rectifier.
Two over-voltage protection methods are optional: hardware protection and software protection. The latter one
also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage.
Perfect battery management: The management functions include the LLVD (optional), BLVD, temperature
compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and on-line battery
test, etc.
M221S and M222S support historical alarm record up to 200 and historical record up to 1000. And M820B
supports historical alarm record up to 3000 and historical record up to 60000
10 sets of battery test data records.
Network design: Providing multiple communication ports (such as RS232, modem and dry contacts), which
enables flexible networking and remote monitoring. M820B support the USB communication interface.
Perfect lightning protection at AC side and DC side.
Complete fault protection and fault alarm functions.
NetSure 701 A41-S3, NetSure 701 A41-S5 and NetSure 501 A41-S1 adopt the way of outage for control, This
way effectively prevents the storage battery from deeply discharging after system battery protection drops out
and hence prevents the unattended outdoors and indoors server rooms from the damage due to the deep
discharge.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 5
2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Emerson Network Power Co., Ltd.To inspect the equipment, you should open
the packing case, take out the packing list and check against the packing list that the equipment is correct and
complete. Make sure that the equipment is delivered intact.
Cables
The cable design should meet relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70C temperature
durability. With cable length shorter than 30 meters, the Cross-Sectional Area (CSA) calculation should be based on
2
the current density of 3.5A/mm . The suggested CSA value is no less than the Table 2-1.
Table 2-1 Load cable CSA selection
AC MCB rated current Max. battery current Min. cable CSA Max. cable length
125A 105A 35mm2 50mm2
100A 80A 25mm2 50mm2
63A 50A 16mm2 25mm2
The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. To select the
battery cable CSA, see Table 2-2. Select the DC load cable CSA according to the Table 2-3.
Table 2-2 Battery cable CSA selection
Battery MCB rated current Max. battery current Min. cable CSA Max. cable length (volt drop: 0.5V, with max. CSA)
125A 105A 35mm2 6m
63A 50A 16 mm2 5m
Note:
1. The specs are applicable at ambient temperature of 25C. If the temperature is higher or lower than this, the CSA of the cable
should be increased.
2. The battery cable should reach at least +90C heat durability. It is recommended to use double-insulated copper-core flame
retardant cable as battery cable
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
6 Chapter 2 Installation Instruction
To prevent the air switching capacity is too large, the load overload does not work. Recommended the capacity of the
air switching is up to 1.5 ~ 2 times of the load peak.
The CSA of the system grounding cables should be consistent with the largest power distribution cables. The CSA
2
value is no less than 25mm .
AC and DC power distribution interface definition see Table 2-4.
Table 2-4 AC and DC power distribution interface definition
Connector name Connector specifications Wiring instructions
H type terminal, max. cable CSA 35mm2 (Single-phase power input)
AC input MCB AC power line
H type terminal, max. cable CSA 25mm2 (Three -phase power input)
AC power
Connected to the
distribution Grounding
One M8 bolt, OT type wiring terminal, max. cable CSA 35mm2 grounding bar of the
busbar
equipment room
Battery output H type terminal, max. cable CSA 25mm2 (63A and below) Connected to the battery
MCB H type terminal, max. cable CSA 50mm2 (capacity above 63A) port
DC power Negative H type terminal, max. cable CSA 25mm2 (63A and below) Connected to the users load
distribution output MCB H type terminal, max. cable CSA 50mm2 (capacity above 63A) port
Positive Connected to the users load
Terminal subrack terminal: cable CSA 50mm2
busbar port
Note
1. The cabinet or rack the subrack power supply system installed in must provide fireproof and electric protection casing, or
install in cement or other difficult to burn, at the same time and other combustible materials to keep enough distance.
2. For the convenience of maintenance, users should maintain a clearance of 800mm at the front of the power supply system.
3. Subrack cannot be installed against the wall, it must leave enough space for heat dissipation.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 7
Subrack
power system
M6 screw
M6 screw
Connector
Connector
Battery
bracket
Installed in cabient
Insert the subrack power system to the matching cabinet, as shown in Figure 2-2.
Subrack power
system
The engineering graphics of the subrack power system as shown in Figure 2-3 to Figure 2-8.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
8 Chapter 2 Installation Instruction
445
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 9
265.0
438.5
482.6
Figure 2-8 Installation size of NetSure 701 A41-S5 (unit: mm)
Note
1. Tighten the captive screw of the MFU and DU Panel by the cross head screwdriver when there is no operation.
2. Also tighten the handle of the 501 modules by the cross head screwdriver.
3. Please plug in the new modules or installing a new panel after removing the rectifier module.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
10 Chapter 2 Installation Instruction
Cable-bundling plate
Danger
Take the NetSure 701 A41 power supply system as an example, the position of the terminals are shown in
Figure 2-12.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 11
Note
If the user selects the subrack with AC input terminal, no overcurrent or short circuit protection function, then configuration of
the overcurrent and grounding protection device is required for the subrack upstream. For selection of the detailed protection
device specification, please contact the Emerson local technical support center.
Connect the negative cable of the load to the upper terminal of load MCB. Connect the positive cable of the load to
the DC positive busbar, as shown in Figure 2-13.
Note
1. The batteries may have dangerous current. Before connecting the battery cables, the corresponding battery input MCBs or the
battery cell connector must be disconnected to avoid live state of the power system after installation.
2. Be careful not to reverse connect the battery. Otherwise, both the battery and the power system will be damaged!
1. Connect one end of the negative battery cable to the upper terminal of battery MCBs. Connect one end of the
positive battery cable to the DC positive bus bar.
2. Connect copper lugs to the other end of the battery cables. Bind the connecting parts with insulating tape, and put
them beside the battery. Connect the cables to the battery when the DC distribution unit is to be tested. As shown in
Figure 2-14.
Positive terminal
Battery MCB
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
12 Chapter 2 Installation Instruction
There are two user interface board of the power system can optional, respectively the W2453X1 user interface board
and IB2 user interface board. The W2453X1 user interface board is used together with the M221S monitoring unit or
M222S monitoring unit only; and the IB2 user interface board is used together with the M820B monitoring unit only.
At most two user connector boards are allowed in the power supply system. Standard cabinet is only configured with
one user connector board.
With one user connector board configured, the power supply system provides three external digital signal input
interfaces: DI2, DI3, DI4 (DI1 is used for DC SPD alarm. If no DC SPD is configured in the power supply system, DI1
is available) and four dry contact alarm output interfaces: DO1, DO2, DO3, DO4. With two user connector boards
configured, the power supply system provides additional four dry contact alarm output interfaces: DO5, DO6, DO7,
and DO8.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 13
With default settings, when the preceding alarms are generated, the contactors of the corresponding dry contacts
should change their status, that is, the normally-open contactors close, and the normally-closed contactors open. All
the status changes should be verified by a multimeter. After the alarms are removed, the dry contacts should resume.
The default settings of the dry contact alarms can be changed through the controller. The interfaces of the user
connector board are shown in Figure 2-16.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
14 Chapter 2 Installation Instruction
Note
1. J11 and J12 are temperature sensor ports. They are not used here.
2. J2 is I2C interface, and provides the power.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 15
The definition of dry contact function can be set through controller or WEB browser.
The specifications of the dry contact ports are as follows:
Digital inputs: 8-route, opto-isolation, the alarm and high/low level are definable (high level: 20V ~ 60V, low level: less
than 1V).
Digital output: 8-route, relay isolation, maximum: 30Vdc 1A, 125Vac 0.5A; 60W; minimum: 10uA @ 10Vdc, alarm is
definable.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
16 Chapter 3 Installation Testing
This chapter introduces procedures of installation testing. The corresponding safety rules shall be adhered to in the
test.
Installation check
OK Comments
Check all the MCBs and cables. Are their models correct?
Check the bus bar connections, input and output cable connection, and connection between the power
system and the system grounding.
Check the if the number and connections of the batteris are correct. Check the polarity of the battery string
with a voltmeter.
Make sure all the cable connections are firm and reliable.
Startup preparations
OK Comments
Make sure that all the MCB are switched off.
Measure the AC input voltage. Make sure the input voltage is within the allowable range. Umin=___V
Check that the communication and alarm cables are connected to the signal transfer board.
Check that the temperature sensor, if any, has been installed.
Check that the battery string circuit is not closed.
Connect the disconnected batteries to the battery string circuit
Switch off unconnected battery MCBs. Check that the battery signal cables are connected to battery
MCBs reliably, not loosened or suspended
Measure with a voltmeter across the connection points of each battery and make sure that the polarity is Umin=___V
right. For a lead-acid battery with 24 cells, the voltmeter should read 2.0-2.1V/cell or 48-51V/battery. If the
voltage of certain cell is lower than 2.0V, that cell must be replaced.
Check with an ohmmeter that there is no short circuit between the positive & negative distribution bus
bars, or between the positive & negative battery poles
(Note: Pull out all modules before the check and restore them after the check)
Startup
OK Comments
Switch on the system AC input MCB. The green LED on the rectifier will be on and the fan will start
running after a certain delay. The controller will show that the power supply voltage is 53.5V.
Check the system voltage and busbar polarity with a voltmeter. The voltage difference between the
measured value and displayed value should be less than 0.2V.
Start and stop each rectifier of the system by unplugging and inserting each rectifier. Check their output
voltages.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 3 Installation Testing 17
OK Comments
The system model has been set correctly in factory before delivery, check that the setting agrees with
the actual system:
NetSure 701 A41-S148V/SETSet the battery shunt coefficient for175A/25mV
NetSure 701 A41-S2S548V/SETSet the battery shunt coefficient for300A/25mV
NetSure 501 A41-S148V/SETSet the battery shunt coefficient for175A/25mV
NetSure 501 A41-S248V/SETSet the battery shunt coefficient for300A/25mV
NetSure 501 A91-S148V/SETSet the battery shunt coefficient for300A/25mV
The DC over-voltage alarm point has been set correctly in factory before delivery, check that the
setting agrees with the actual system:
Set DC over-voltage alarm: 58V
Check that the parameter SettingAlarm SettingsAlarm mode, check that the mode is set to High
The battery string number set at the controller should be the same as the number actually connected.
(By default: 2)
Set the battery capacity according to the actual capacity of the battery connected to the system.
Default: 300Ah
Configure the temperature coefficient according to the battery manufacturers requirement. Setting
range: 0-500mV/C. By default: 72mV/C. (if no temperature sensor is installed, do not set this
parameter)
Set the charge current limit according to your needs. Setting range: 0.1~0.25C10. (By default: 0.1C10)
Set the controller according to the voltage suggested by the battery supplier.
Floating Charge (FC) voltage range: 42V ~ Boost Charge (BC) voltage. Default: 53.5V.
BC voltage range: FC voltage ~ 58V. By default: 56.4V.
For batteries that do not need BC, set the BC voltage to FC voltage plus 0.1V
Put through the battery MCBs and connect the batteries
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
18 Chapter 3 Installation Testing
OK Comments
with the actual parameters.
For the system configured with temperature sensor, the controller should be able to display the battery
ambient temperature. Hold the probe of the temperature sensor with hand and watch the controller,
which should diplay the change of temperature.
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the
repairing center for fault analysis.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 19
The controller modules of this power system are M221S, M222S and M820B. The M820B control module for details
please refer to the ACU+ User Manual. This chapter introduces the front panel and functional keys briefly, and
expounds screen contents, access method, system controlling, information querying and parameter setting.
After the controller is powered on, the language selection screen will pop up, and the controller is initialized. The
default language is Chinese. After the initialization, the first system information page will appear.
There are backlit LCD display, functional keypad, indicators and positioning pin on the front panel of M500D controller,
as shown in figure 4-1.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
20 Chapter 4 Use Of Controller
MANUAL
Sys Mode: Auto
In Manual
ECO
Disable
CycPeriod: 168h
RectWork: 80%
Rect Limit: 1
System Type:
48V / set
Capacity: 300Ah
LCD Rotation: On
4.2.1 Status
In the screen of MAINMENU, when cursor is at Status, press ENT to go to the status screen:
RECTIFIER 1/3
ID: 02070801232
R48800B00
DC Volt: 53.4V
DC Curr : 0.0A
Curr Limit: 109%
AC Volt: 201V
AC Status: On
DC Status: On
AC Derated : N
Temp Derated : N
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 21
In the status screen, you can move the cursor to Active Alarm, Rectifiers, and History Alarm respectively and press
ENT to check the information of active alarm, rectifiers, and history alarm. The rectifier screen shows the information
of first rectifier, if you want see the information of next rectifier, just press ENT. In screen of Active Alarm, Alarm
1/2, 1/2 means there are 2 active alarms and this screen is displaying the first active alarm. The alarm level and
alarm start time are displayed in the screen
In the screen of History Alarm, the ALARM 001 means this screen is displaying the first history alarm. The alarm
start time and end time are displayed in the screen.
4.2.2 Settings
In the Main Menu screen, move the cursor to the item of Setting and press ENT to enter the Setting menus. Before
you access the Setting menu, the system will require you to enter the password first. Method of entering password:
For example, to enter the password of 640275: Press ENT, and the bit will be highlighted, now you can press or
continuously to enter the numbers from 0 to 9, or enter the letters from a to z or from capital letter A to Z. After
entering 6, press ENT and the cursor will move to the next bit, and in the same way, press or continuously to
enter 4, and you can enter the rest bits 0275 in the same way.
ALARM
Alarm Level
Alarm Control BATTERY
DI Setting Basic
LVD
Charge
AC Test
Over Volt: 280V Temp Comp
Under Volt: 180V
PH Fail: 80V DC
AC Input: N Over Volt2: 58.2V
AC PH: 3-PH Over Volt1: 58.5V
Under V1: 45.0V
Under V2: 45.0V
Amb High: 40C
Amb Low: - 5C
RECTIFIER
Position: Disabl
R -Posi: 1-1
SETTINGS
HVSD: 59.0V
Alarm
Default V: 53.5V
Battery
Walk-in On: N
AC
Walk-in T: 8s
DC
Interval T: 0s
Rectifier
Controller AC OverV On: N
Communication ACCurrLim : 30A
CONTROLLER
Lang: English
Tzone: GMT + 08:00
Date: 2009-03 -23
Time: 22:17:18 COMMUNICATION
System Type: Address: 1
48V/1000A CommMode : RS232
DownloadMode:N Protocol: YDN23
Reset PWD: N BaudRate: 9600
Reset Para: N IP/Subnet/Gate:
Oper1PWD: ****** 10.163.210.91
Oper2PWD: ****** 255.255.255.0
AdminPWD: ****** 10.163.210.1
CallbackTime: 3
PhoneNumber:
86010677
86010808
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
22 Chapter 4 Use Of Controller
In the Setting menu, there are 7 items that are Alarm, Rectifier, LVD, AC, DC, Controller and Communication
respectively.
Move the cursor to Rectifier and press ENT, you can configure the following rectifier parameters:
Position: Enable or disable the shelf setting.
R-Posi: rectifier position in shelf.
HVSD: high voltage shut down, rectifier will shut down when its output voltage exceeds this HVSD point.
Default V: rectifier default output voltage.
Walk-in ON: rectifier walk-in function (soft start) is enabled.
Walk-in T: rectifier walk-in time (soft start time).
Interval T: rectifier sequential startup interval.
AC OverV on: rectifier will shutdown when AC input exceeds AC over voltage point.
ACCurrLim: rectifier current limiting value during startup process.
Move the cursor to AC and press ENT, you can configure the following AC parameters:
Over Volt: set the over voltage protection point.
Under Volt: set the under voltage protection point.
PH Fail: set the phase failure voltage point.
AC PH: can set the AC input to 3-phase or single phase (1-PH).
Move the cursor to DC and press ENT, you can configure the following DC parameters:
Over Volt2: set the over voltage protection point2.
Over Volt1: set the over voltage protection point1.
Under V1: set the DC output under voltage point 1.
Under V2: set the DC output under voltage point 2.
AmbHigh: set the high ambient temperature.
AmbLow: set the low ambient temperature.
Move the cursor to Controller and press ENT, you can configure the following controller parameters:
Lang: set the display language of LCD, you can select English or your local language.
Tzone: set the time zone.
Date: set the current date.
Time: set the current time.
System Type: set the system type.
DownloadMode: enter the download mode through serial port.
Reset PWD: Reset the password to default.
Reset Para: Reset parameters to default.
Oper1PWD: set the password of operator 1.
Oper2PWD: set the password of operator 2.
AdminPWD: set the password of administrator.
There are three levels password. Default passwords: 1 for operator1, 2 for operator2, and 640275 for administrator.
Only administrator can transfer to serial and web download mode and reset the password. Operator2 can change the
system type and reset the parameters.
Move the cursor to Alarm and press ENT, you can enter the alarm menus:
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 23
Alarm ENT ALARM LEVEL ENT ALARM LEVEL ENT ALARM LEVEL
Alarm Level Alarm Block SPD fault LFuse Alarm
Alarm Control Severity: Severity: Severity:
DI Setting Observation Alarm Major Alarm Critical Alarm
Out Relay: 0 Out Relay: 0 Out Relay: 6
ALARM CONTROL
Alm Voice: Open
Clear: History
DI SETTINGS
DI NO.: 1
Digital1 Alarm
Active: High
Note:
1. The alarm levels of temperature sensor disconnected alarm and temperature sensor failure alarm, and the
corresponding relay output cannot be set through the LCD. The alarm levels of these two alarms and the
corresponding relay are the same with those of the high temperature alarm setting.
2. If the analog alarm has two levels of alarm thresholds, and if these two alarm thresholds are set to the same value,
then the second level will be cancelled and the first level of the alarm will be displayed in LCD. For example: If the
alarm threshold of high temperature 1 is set to the same with the threshold of high temperature 2, and if this
threshold is set to 40 deg C, then when the temperature exceeds 40 deg C, the system will only issue high
temperature 1 alarm, and will not issue the high temperature 2 alarm.
In the alarm level setting submenu, you can also set the output relay no. for the corresponding alarm.
Alarm control menu
For the submenu of AlmVoice of alarm control menu, you can set it to Open(audible alarm is enabled) or Close (no
audible alarm), and you can also set the time of audible alarm and the time can be 3min, 10min, 1h and 4h.
For the submenu of Block Alarm, you can set Y or N to select whether the alarm should be blocked or not.
For the submenu of Clear, you can select History, ECOFail, Maintain, ShortTest, TestFail ,Rect Lost Rect
Commb and Rect Not respond to clear corresponding alarm.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
24 Chapter 4 Use Of Controller
DI SETTINGS
All the alarms can be configured with No.1 to No.8 alarm contacts. 0 means no alarm dry contacts. All the alarm dry
contacts provide NC (normally closed) or NO (normally opened) output and the default alarm dry contacts are given in
the following table.
Table 4-4 Default alarm dry contact setting
Dry contact No. Default alarm
Dry contact 1 Mains Failure
Dry contact 2 DC Under Volt or DC Over Volt
Dry contact 3 Rectifier alarm
Dry contact 4 LVD2
Dry contact 5 LVD1
Dry contact 6 None
Dry contact 7 None
Dry contact 8 None
Table 3-5 lists the alarms that you can scroll through in the ALARM SETTINGS/ALARM LEVEL menu, and also
shows their factory default Alarm Level and Mapped Output Relay settings.
Table 4-5 Controller Alarms and Factory Default Settings
Default mapped
Alarm name Alarm description Condition Default alarm level
output relay
Alarm Block Alarm Block Alarms are blocked by the LCU+ Observation
Batt Battery middle voltage out of the range of ( bus
Batt Imbalance Major
Imbalance voltage /2) 0.6
SavePowerF Into and out of save power status for 5 times in one
SavePowerFault Major
ault hour
Save Power Save Power Function System is in save power status Observation
AC High AC Voltage High Input phase voltage higher than AC High point Observation
AC Low AC Voltage Low Input phase voltage lower than AC Low point Observation
AC PH Fail AC Phase Fail Input phase fails Observation
Ambient/ Battery temperature higher than
Temp High2 Temperature High 2 Major
Temperature High 2
Ambient/ Battery temperature higher than normal
Temp High1 Temperature High1 Major
operation range
Ambient/ Battery temperature lower than normal
Temp Low Temperature Low Observation
operation range
Batt Over
Battery Over Charge The charging current over the maximum value Observation
Chg
DC Volt System output voltage much higher than float
DC Voltage High+ Critical 2
High+ charge voltage
System output voltage higher than float charge
DC Volt High DC Voltage High Critical 2
voltage
System output voltage slightly lower than float
DC Volt Low DC Voltage Low Critical 2
charge voltage
System output voltage is much lower than float
DC Volt Low- DC Voltage Low- Critical 2
charge voltage
Rect HVSD Rectifier HVSD Rectifier HVSD circuit activated Major 3
The difference between rectifier output current and
Rect average output current larger than 8A (+/-4A), and
Rectifier LoadShare Observation 3
LoadShare the load of the rectifier greater than 10% of its
capacity
The output power of at least one rectifier is derated
Rect Derated Rectifier Derated Observation 3
because of AC undervoltage or overtemperature
Rect Fan
Rectifier Fan Fails Fan of at least one rectifier fails Major 3
Fails
AC input voltage out of the range of 85Vac to
Rect Protect Rectifier Protect Observation 3
295Vac results in at least one rectifier protected
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 25
Default mapped
Alarm name Alarm description Condition Default alarm level
output relay
Serious load sharing alarm (the output current of the
Rect Failure Rectifier Failure rectifier is lower than 1A, and the average load is Critical 3
greater than 10% of the total rectifier capacity)
Rect Rectifier High temperature protection activated in at least one
Major 3
TempHigh Temperature High rectifier
Rect AC Fail Rectifier AC Fail AC input voltage lower than 80Vac Major 3
Rect Comm Rectifier
Rectifier(s) unable to communicate with LCU+ Major 3
Fail Communication Fail
MultiRect
Multi rectifier Alarm Two or more rectifiers have alarms Critical
Alarm
System System has not been maintained within preset
System Maintain None
Maintain maintenance time
Rect Lost Rectifier Lost Rectifier reduction detected Critical
Rect
Rectifier OverLoad Total load current greater than the High Load value Observation
OverLoad
Mains
Mains Failure AC input voltage lower than 80Vac Major 1
Failure
LVD2 LVD2 LVD contactor 2 open due to low battery voltage Critical 4
LVD1 LVD1 LVD contactor 1 open due to low battery voltage Critical 5
Battery discharge test failure (battery voltage is
Batt Test Fail Battery Test Fail Observation
lower than setting value before test time is reached)
The difference between bus voltage and the set
DC Volt Fail DC Voltage Fail Observation
output voltage larger than the set value
Curr The total output current not equal to the sum of the
Current Imbalance Observation
Imbalance battery current and the load current
Batt
Battery Discharge Batteries are discharging Observation
Discharge
Batt Test Battery Test The batteries are testing None
Boost
Boost Charge The batteries are in boost charge state None
Charge
Manual
Manual Mode The system is in manual mode Observation
Mode
SelfDetect
SelfDetect Fail LCU+ detects error in hardware self test Observation
Fail
After battery disconnection/ connection signal is
LVD2Ctrl Fail LVD2 Control Fail sent out, the feedback signal of the contactor is Critical
false
BattFuse
Battery Fuse Fail Battery fuse(s) or circuit breaker(s) open Critical
Fail
LoadFuse
Load Fuse Fail Distribution (load) fuse(s) or circuit breaker(s) open Critical
Fail
Digital4 Digital4 User programmable Major
Digital3 Digital3 User programmable Major
Digital2 Digital2 User programmable Major
Digital1 Digital1 User programmable Major
SPD SPD SPD signal interrupted Major
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
26 Chapter 4 Use Of Controller
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 27
Limit: set the charging current limit. This is the maximum charging current that should be allowed into the battery at
any time, as regards to the nominal capacity of the battery. For example, a value of 0.150C10 means that the
charging current is limited to 15% of the batterys nominal capacity.
Over: set the over boost charging current. This is the charging current, as regards to the nominal capacity of the
battery, at which an over current alarm will be initiated if this current is reached. For example, a value of 0.300C10
means that when the charging current reaches 30% of the batterys nominal capacity, an alarm will be extended.
AutoBoost: An Automatic Boost is started when one of the following conditions is reached.
-Enable: Use this submenu to enable or disable auto boost charging.
-Curr: This is the battery discharge current, as regards to the nominal capacity of the battery, above which an
Automatic Boost is started, when the Automatic Boost function is enabled. For example, a value of 0.060C10 means
that an Automatic Boost is started if the battery current is greater than 6% of the batterys nominal capacity.
-Cap: This is the remaining battery capacity under which (less than) an Automatic Boost is started when the
Automatic Boost function is enabled.
CycBoost
-Enable: Use this submenu to enable or disable cyclic boost charging.
-Period: Use this submenu to set cyclic boost charging period. This is the interval, in hours, between the boost
cycles.
-Time: Use this submenu to set cyclic boost charging time. This is the duration of each cycle for the Cyclic Boost
when this function is enabled.
Const Boost
-Curr: Use this submenu to set constant boost charging current.
-Time: Use this submenu to set constant boost charging time.
BoostLimitTime: Use this submenu to set boost charging time limit beyond which boost charge will be stopped.
Move cursor to Test, you can configure the following parameters:
End Test: A Battery Test is interrupted when one of the following conditions is reached.
-Volt: This is the end of test voltage level for each battery test.
-Time: This is the maximum duration, in minutes, for each battery test.
-Cap: This is the remaining battery capacity, as regards to the nominal capacity of the battery, at which a Battery Test
will be interrupted. For example, a value of 0.700C10 means that when the charging current reaches 70% of the
batterys nominal capacity, the battery test is interrupted.
Cyc Test: Displays whether the time (on specific dates) battery test function is enabled (Y) or not (N). During a Timed
Battery Test, the output voltage of the rectifiers is reduced so that the batteries power the load. If the batteries fail, the
rectifiers power the load.
Short Test: A short test is a short duration battery discharge test used to verify that parallel batteries are discharging
equally. If the discharge current difference between the two batteries exceeds a preset level (default is 10 A), a Short
Test Fault alarm is generated.
-Enable: Displays whether the short (at specific intervals) battery test function is enabled (Y) or not (N).
-Alarm: Displays the battery current difference at which an alarm will be extended.
-Time: Displays the interval, in hours, between short battery tests.
-Duration: Displays the duration, in minutes, of each short battery test.
ConCurr Test: A Constant Current test is a battery discharge test done at constant current. The controller will
automatically adjust the rectifiers to maintain the battery discharge current at the preset value.
-Enable: Displays whether the constant current battery test function is enabled (Y) or not (N).
-Current: Displays the stable test current.
Move cursor to TEMP COMP, you can configure the following parameters:
Center Temp: Displays the temperature, in C, at which the system operates at normal voltage levels.
Temp 1: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None)
in position No. 1, and if there is one, whether it is used for battery or ambient temperature measurements.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
28 Chapter 4 Use Of Controller
Temp 2: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None)
in position No. 2, and if there is one, whether it is used for battery or ambient temperature measurements.
Coeff: Displays the temperature compensation slope or rate of change per C above or below the normal operation
level selected in the second line. This value is expressed in millivolt per C per string (mV/C/str). For example, for a
rate of change of 72mV/C/str in a 24-cell, 48 V nominal, battery string, the rate of change is 3 mV per cell.
4.2.3 Manual
In the Main Menu, move the cursor to Manual and press ENT to enter Manual control menu:
Change to 'Manual' from 'Auto'
MAIN MENU MANUAL MANUAL
Status ENT Sys Mode: Auto Start: Float
Settings In Manual LVD1: Reconn
Manual LVD2: Reconn
ECO RectTrim : 53.5V
Quick Settings RectLimit : 121%
In the manual screen, you can perform the following manual control operations:
Start: To start float or boost charging or battery test.
LVD1: To reconnect or disconnect LVD1 contactor.
LVD2: To reconnect or disconnect LVD2 contactor.
RectTrim: To adjust the rectifier output voltage.
RectLimit: To adjust the rectifier current limiting point.
4.2.4 ECO
In the Main Menu, move the cursor to ECO and press ENT to enter ECO menu:
In the Main Menu, move the cursor to Quick Setting and press ENT to enter Quick Setting menu:
MAIN MENU
ENT System Type:
Status 48V / 1000A
Settings Capacity: 300Ah
Manual LCD Rotation: On
ECO
Quick Settings
In the Quick Setting screen, you set the system type and system capacity, as well as the parameters (current, voltage)
of load shunts and battery shunts.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 29
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
30 Chapter 4 Use Of Controller
Available Settings
Components Name Default setting Unit
Low limit High limit
Load shunt Yes / No No /
LVD1 Enabled Disabled / Enabled Disabled /
Disabled
LVD2 enabled Disabled /
LVD /Enabled
LVD1 voltage 40 60 43.2 V
LVD2 voltage 40 60 43.2 V
Over voltage alarm point 0 500866 280485 V
AC unit Under voltage alarm point 0 500866 180304 V
Phase failure alarm point 0 500866 80255 %
IP address 0-255 192.168.1.2 /
Subnet code 0-255 255.255.255.0 /
Default gateway 0-255 192.168.1.1 /
Local address 1 255 1 /
Port type RS232/Modem/ETH RS232 /
Communication Baud rate 1200/2400/4800/9600 9600
parameters Protocol YDN23/EEM/RSOC/SOCTPE YDN23 /
Alarm call-back enabled Yes / No No /
Call back times 0 10 3
Call back number 1
Call back number 2
Call back number 3
Language English / Chinese English
Display time zone GMT+08:00
System date
System time
Restore default configurations Yes / No No
Controller
Set rotating screens Horizontal/Vertical Horizontal
parameters
48V/set, 48V/1000A,
48V/500A, 48V/300A,
System type 48V/100A, 24V/set, 48V/set
24V/1000A, 24V/500A,
24V/300A and 24V/100A
Procedure
Note
This procedure needs to be performed only when the controller is connected to an Internet and the User has set that
the access to the Internet needs to be made through proxy. If the controller is connected Internet and the user
computer is connected to the Internet, the user cannot disable the proxy, otherwise he will have no access to the
controller.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 31
2. Select Internet Options from the Tools menu. The Internet Options window opens. In the Internet Options
window, select the Connections tab.
3. Click on the LAN Settings... button. The following window opens. In the LAN Settings window, uncheck the proxy
box and click OK.
Procedure
In Internet Explorer, enter the IP address programmed into the controller and press ENTER. The following WEB
Interface window opens. Enter a valid User Name and Password, and then click OK. By default, there are two User
Name and Password combinations, one is admin and 640275, the other is operator and 1. The username of
admin has the highest authority and the username operator has no authority for uploading and downloading
configuration files.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
32 Chapter 4 Use Of Controller
After entering a valid User Name and Password, and clicking OK; the homepage window opens.
The homepage window is divided into three areas: System Information, Parameter Settings and Control Functions,
and Upload/Download Files.
System information
At the top of homepage, System Information is displayed, such as System Voltage, System Load, MA/CA Number,
OA Number, Battery Mode, Site Name, HW Version, and SW Version.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 33
Battery Test: To disable or enable the periodical battery test function. This setting has no effect on the short
test.
Current Limitation: To disable or enable the battery charging current limitation function.
Boost Charge: To disable or enable the periodical battery boost charging function. This setting has no effect on
auto boost charging.
LVD1 Level, LVD2 Level: To set the low voltage disconnection point.
Under Voltage Level 1, Under Voltage Level 2: To set the under voltage point.
System Volt: To set the system voltage.
Boost Volt: To set the battery boost charging voltage.
NMS1 IP, NMS2 IP: To set the IP address of SNMP
Remote1 IP, Remote2 IP: To set the IP address of EEM protocol.
TCP IP address: To set the IP address of TCP IP protocol.
Upload/download files
1. Procedure
1) To upload a configuration file, click the Upload button. The following window opens. Click the Save button.
2) The following window opens. Navigate to where you want the file to be saved. Click the Save button.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
34 Chapter 4 Use Of Controller
After the upload is completed, the system will pop up a window to prompt the user that the upload is successful:
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 35
Then click Download button, the system will pop up a window requiring you to confirm:
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
36 Chapter 4 Use Of Controller
Click OK, the system will prompt you that the download is successful:
In the above screen, you can click Back to the Homepage to return to the Homepage.
Administrator can click Go to Firmware Download Mode to enter Bootloader download interface.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 37
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
38 Chapter 4 Use Of Controller
Here we can see there are 4 options, choose 1 to download the application program, choose 2 to download the
configuration data, choose 3 to upload the data configuration file, choose 4 to execute the application program.
1. Method of downloading the application program:
1) Press 1 on the keyboard, enter the surface of download;
2) Choose Transfer->Send File, select the .bin file you want to download;
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Controller 39
4) After the file downloading is completed successfully, the following interface pops up:
2. Method of downloading the configuration data: Similar to the download of application program, will not be
introduced here;
3. Method of uploading the data configuration file:
1) Press 3 on the keyboard, enter the interface of uploading files:
2) Choose Transfer->Receive File to select the position in which you save the file
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
40 Chapter 4 Use Of Controller
Figure 4-30 Select the position in which you save the file
4) After the file downloading is completed successfully, the following interface pops up.
You can also press "4" on the keyboard to execute the application.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Alarm Handling 41
This chapter describes the handling of alarms, as well as the preventive maintenance of the system during system
daily operation.
The maintenance personnel must have adequate knowledge about the power system.
Note
1. The maintenance must be conducted under the guidance of related safety regulations.
2. Only the trained personnel with adequate knowledge about the power system can maintain the inner part of the subrack.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
42 Chapter 6 Alarm Handling
Run indicator
Protection indicator Run indicator
Fault indicator Protection indicator
R48-3200 Fault indicator
R48-1800
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Alarm Handling 43
Monitoring module
Symptom Causes Handling method
alarms
Protection
Check whether the communication cable is in
indicator Rect Not Respond Rectifier communication interrupted
normal connection
blinks(yellow)
Reset the rectifier. If the protection is triggered
Rect HVSD Rectifier over-voltage
again, replace the rectifier
Two or more recitifiers have the same ID
Rect Failure Contact Emerson for maintenance
number
Fault indictor
Check whether the rectifier communication is
on (red)
Serious current sharing imbalance, normal. If not, check whether the
Rect Failure 501 series modle: current imbalance > 3%; communication cable is in normal connection.
701 series modle: current imbalance > 5% If the communication is normal while the
protection indicator is on, replace the rectifier
Fault indicator
Rect Fan Fails Fan fault Replace the fan
blinks (red)
.
Figure 5-2 Disassembling the front panel
Replacing rectifier
Except replacing the fan, it is recommended not to repair any other part of the module. When faulty, the module
should be replaced, not repaired. See the following procedures to replace the rectifier.
1. Take a new rectifier and check it for any damage from transport.
2. Loosen the fixing screw of the handle of the R48-1800A rectifier with a Phillips screwdriver. Pull out the faulty
rectifier from the rack by grabbing its handle.
Be careful with the rectifier just pulled out from the system, as it could be very hot due to long-term operation. Do not
let it slip away and get damaged.
3. By holding the rectifier handle, push the new rectifier into the slot just vacated and make sure the connection is
good. After a brief delay, the rectifier run indicator will turn on and the fan will start running.
4. Check whether the new rectifier works normally. You should make sure that:
1) The controller recognizes the new rectifier.
2) The new rectifier shares current with other rectifiers.
3) When this new rectifier is pulled out, there is a corresponding alarm and the controller displays the alarm.
If the new rectifier passes all the above tests, the replacement is a success.
5. Push the handle back into the front panel to fix the rectifier with the positioning pin. Fix the fixing screw of the
handle of the R48-1800 rectifier with a Phillips screwdriver.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
44 Appendix 1 Technical And Engineering Data
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 1 Technical And Engineering Data 45
Parameter
Parameter Description
category
AC input under-voltage protection point Default: 80 5Vac, configurable through controller
AC input alarm
AC input under-voltage protection Default: 95 5Vac, 10Vac higher than the AC input under-voltage
and protection
recovery point alarm point
DC output over-voltage alarm point Default: -58.0 0.2Vdc, configurable through controller
DC output alarm Default: -57.5 0.2Vdc, 0.5Vdc lower than the over-voltage alarm
DC output over-voltage recovery point
and protection point
DC output under-voltage alarm point Default: -45.0 0.2Vdc, configurable through controller
Default: -45.5 0.2Vdc, 0.5Vdc higher than the under-voltage alarm
DC output under-voltage recovery point
point
DC output alarm
DC output over-voltage proteciton point Default: -59.0 0.2Vdc, configurable through controller
and protection
LLVD Default: -44.0 0.2Vdc, configurable through controller
BLVD Default: -43.2 0.2Vdc, configurable through controller
The rectifiers can work in parallel and share the current. The
Current sharing
unbalanceness is better than 5%
R48-1800AR48-2000R48-2000e:
176Vac input, The rectifier outputs max.power: 100%
85Vac input, The rectifier outputs max. power: 40%
80Vac input, The rectifier low pressure power off
R48-3200R48-2900UR48-3500eR48-3200e
176Vac input, The rectifier outputs 100% power
120Vac input, The rectifier outputs 50% power
Derate by input (at 45C)
85Vac input, The rectifier outputs 18.75% power
80Vac input, The rectifier low pressure power off
R48-4000e:
207Vac input, The rectifier outputs 100% power
120Vac input, The rectifier outputs 2200W power
85Vac input, The rectifier outputs 1500W power
80Vac input, The rectifier low pressure power off
Output voltage can rise slowly upon rectifier start up. The rise time
Output delay
is configurable
Fan speed adjustable Rectifier fan speed can be set to half or full speed
Rectifier
The rectifier provides over-voltage hardware and software
protection. The hardware protection point is 59.5V 0.5V, and it
requires manual resetting to restore operation. The software
protection point is between 56V and 59V (0.5V above output
voltage, 59V by default), and can be set through the controller
There are two software protection modes, which can be selected
through the software at the host:
1. Lock out at the first over-voltage
Once the output voltage reaches protection point, the rectifier will
Over-voltage protection shut off and hold that state. It requires manual resetting to restore
the operation
2. Lock out at the second over-voltage
When the output voltage reaches the software protection point, the
rectifier will shutdown, and restart automatically after 5 seconds. If
the over-voltage happens again within a set time (default: 5min.
Configurable through controller), the rectifier will shut off and hold
that state. It requires manual resetting to restore the operation
Manual resetting: Resetting can be done manually through the
controller, or by removing the rectifier from system
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
46 Appendix 1 Technical And Engineering Data
Parameter
Parameter Description
category
R48-1800A:
Temperature below 45C, outputs full power
Temperature above 45C, there will be linear derating, that is:
At 55C, output power is 1,600W
At 65C, output power is 1,500W
At 75C, output power is 800W
At 80C, output power is 0
R48-2000R48-2000e:
Starts at -40C; Temperature below 45C, outputs full power
Temperature above 45C, there will be linear derating, that is:
At 55C, output power is 1,750W
At 65C, output power is 1,600W
At 70C, output power is 800W
At 75C, output power is 0
R48-3200e:
At the ambient temperature of:
Below 45C, outputs full power: 3,000W
Above 45C, there will be linear derating, that is:
At 55C, output power 2,400W
At 60C, output power 1,500W
At 65C, output power: 0
R48-3200:
Starts at -40C; Temperature below 45C, outputs power is 3200W.
Rectifier Temperature derating Temperature above 45C, there will be linear derating, that is:
At 65C, output power is 2,320W
At 70C, output power is 1,450W
At 75C, output power is 0
R48-2900U:
Starts at -40C; Temperature below 45C, outputs power is 2900W.
Temperature above 45C, there will be linear derating, that is:
At 55C, output power is 2,320W
At 60C, output power is 1,450W
At 65C, output power is 0
R48-3500e:
Starts at -40C; Temperature below 45C, outputs power is 3500W.
Temperature above 45C, there will be linear derating, that is:
At 50C, output power is 3200W;
At 55C, output power is 2900W;
At 65C, output power is 2320W;
At 70C, output power is 1450W.
At 75C, output power is 0
R48-4000e:
Starts at -40C; Temperature below 50C, outputs power is 4000W.
Temperature above 45C, there will be linear derating, that is:
At 55C, output power is 3500W;
At 65C, output power is 3000W;
At 75C, output power is 2400W
Conducted emission
Class A EN55022
Radiated emission
Voltage fluctuation and flash Class A EN61000-3-11
Immunity to EFT Level 4 EN/IEC 61000-4-4
EMC
Immunity to ESD Level 3 EN/IEC 61000-4-2
Immunity to surges Level 4 EN/IEC 61000-4-5
Immunity to radiation Level 2 EN/IEC 61000-4-3
Immunity to conduction Level 2 EN/IEC 61000-4-6
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 1 Technical And Engineering Data 47
Parameter
Parameter Description
category
The AC input side can withstand five times of simulated lightning
voltage of 5Kv at 10/700s, for the positive and negative polarities
Lightning respectively. It can withstand five times of simulated lightning surge
protection At AC side current of 20Ka at 8/20s, for the positive and negative polarities
features respectively. The test interval is not smaller than 1 minute. It can
also withstand one event of simulated lightning surge current of
40Ka at 8/20s
Safety regulation IEC60950-1:2001
Acoustic noise 60db (A) (When the ambient temperature is lower than25)
At temperature of 15C ~ 35C and relative humidity not bigger than
90%RH, apply a test voltage of 500Vdc. The insulation resistances
Insulation resistance
between AC circuit and earth, DC circuit and earth, and AC and DC
circuits are all not less than 10M
(Remove the SPD, controller and rectifiers from the system before
the test.) AC loop to DC loop can withstand 50Hz.
Others
DC circuit to earth: 50Hz, 2,500Vac; or 3535Vdc;
AC to DC circuits: 50Hz, 1,000Vac; or 1414Vdc;
Insulation strength
Assistant circuit (not directly connected to the host circuit): 50Hz,
500Vac
For all the three tests above, there should be no breakdown or
flashover within 1min, with leakage current not bigger than 10Ma;
MTBF > 200,000hr
ROHS Compliant with R5 requirement
NetSure 501 A41-S1/S2: 483 360 223
Maximum dimensions NetSure 501 A91-S1: 483 360 445
of the subracks NetSure 701 A41-S1/S2/S3/S5: 483 360 267
NetSure 701 A41-S4: 483 360 400.5
Dimensions
Monitoring module
(mm)(WDH) 85 85 287
M501D/ M500D
R48-1800A, R48-2000, R48-2000e: 87.9 85.3 272
Rectifier R48-3200e, R48-3200, R48-2900U, R48-3500e: 132.3 88 294
Mechanical
R48-4000e:132.3 88 294
Subrack (without
rectifiers and 25
controller)
Weight (kg) Monitoring module
< 0.8
M501D/M500D
R48-1800A, R48-2000, R48-2000e 2.0
Rectifier
R48-3200, R48-2900U, R48-3200, R48-3500e, R48-4000e 3.5
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
48 Appendix 2 Installation Instruction Of Battery Rack
Packing list
Figure 1 Accessory
Installation procedures
1. Installation procedures of two-layer battery rack
1) Install accessory 1 and accessory 2 according to Figure 2 (a).
2) Install accessory 3 according to Figure 2 (b).
Accessory 1
Accessory 3
Accessory 2
(a) (b)
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 2 Installation Instruction Of Battery Rack 49
Accessory 4
Accessory 2
Accessory 4
Accessory 2
(a) (b)
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
50 Appendix 2 Installation Instruction Of Battery Rack
Packing list
Figure 5 Accessory
Installation procedures
1. Install accessory 1 and accessory 2 according to Figure 6 (a).
2. Install accessory 3 according to Figure 6 (b).
Accessory 2
Accessory 1 Accessory 3
(a) (b)
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 2 Installation Instruction Of Battery Rack 51
Accessory 2
Accessory 4
1. Fix the battery rack to the ground according to the installation dimensions shown in Figure 8. The fixing bolts are
accessories.
575
600 480
600
Figure 8 Installation dimensions (unit: mm)
2. Fix the subrack power system onto the top of the battery rack. Refer to 2.3 Mechanical Installation.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 52
0V
W81+W82
7-29 8-QF18
1 8-QF17 1
2 2
Three-phase AC input
PL 1
B QFA
L1 L2 L3 N
TO MFU unit PL busbar 1 3 5 7
25-N/26-N/27-N/228-N/29-N
Controller motherboard switch 7
M221S Front view MFU door connected ground 2 4 6 8
21-N/22-N/23-N/24-N
9-BUS+-2 W80 W80 9-BUS+-1W80
22-L/25-L/28-L
23-L/26-L/29-L
21-L/24-L/27-L
W80 X7-2
8-NPL-QFD
X6-1 X5-1
13-J8-1
13-J8-3
13-J8-5
13-J8-2
8-PL-QFD
13-J7-1
11-2
11-1
W02
W01 W01W01
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 1
User interface board 1 13
Module subrack Rear view
24-CAN+
24-CAN-
W2453X1
13-J8-8
8-QFB1-1
8-QFB2-1
13-J8-7
13-J8-4
13-J7-2
8-PL-1
9-BUS+-1
13-J8-6
8-B--1
10-1
10-2
6
Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
W2453X1
4- 4+ 2- 2+ DO4 DO2
3- 3+ 1- 1+ DO3 DO1
24 23 22 21
W80 W80 H4 H3 H2 H1
X3-2
W80 W80 W80 W80 W80
W80 L
W01 L
W01 L
W01 L
W01
W02 W02 W02 W02
N N N N
X3-1
PE PE PE PE
J3
P W04 P W04 P W04 P W04 7-4 7-2
MFU DC power
8 12 W05
wiring diagram
Rear top view
J4
MFU
9
J6 1
2 3
1
2 3
1
2 3
1
2 3
5 4 5
6
4 5
6
4 5
6
4 5
6
TO the user BUS+
protective
PE
0V 1 8 12
earth J8 J7
1 2 W80
2 1 7-35/7-47/7-49/7-50 W80
3 9-2 5-3 W07 2 X5-1/X6-1 W80
4 29
H9
28
H8
27
H7
26
H6
25
H5
L
W01 L
W01 L
W01 L
W01 L
W01
W80+W81+W82 To the positive Busbar N
W02 N
W02 N
W02 N
W02 N
W02
7-29 P
PE
W04 P
PE
W04 P
PE
W04 P
PE
W04 P
PE
W04
1 1 1 1
QFD16
QFD1
QFD3
QFD2
W80
2 2 2 2 1
2 3
1
2 3
1
2 3
1
2 3
1
2 3
7-28
7-30
4 5 4 5 4 5 4 5 4 5
PL 6 6 6 6 6
TO DU unit PL bar 12
KM2
W80 1 1
QFB1
W80
QFB2
7-39
7-31 PL
7-41
W80 10
7-46 1 RB 2 2
1 2
W05
15-J7 2 2 1
1 8-B-
7-22
7-20
7-44
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 53
18
M34C3C1
W06
DCSPD
13-J3-1+
15
13-J3-1-
J2 J1 M2433X2
12-1 1 7-39
12-2 2
1
8-PL-1 2 7-41
3 J3 J1 J2 J4
J5 J6 J7
PE v+ v-
8-PL-2
5-2
9-2
W06 W06 W06
Controller motherboard switch 7
M221S Front view
9-BUS+-1 W80
W80 W80
X6-1 X5-1 W80 W80 W80 W80 W80 W80
9-BUS+-1
13-J8-1
13-J8-3
13-J8-5
13-J8-2
13-J7-1
18-J1-2
18-J1-1
8-PL-1
X7-2
11-2
11-1
User interface board 1 13
W2453X1
W2453X1
4- 4+ 2- 2+ DO4 DO2
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
3- 3+ 1- 1+ DO3 DO1
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Single-phase AC input(SPD)
24-CAN+
24-CAN-
8-QFB2-2
8-QFB3-2
8-QFB4-2
8-QFB1-2
9-BUS+-1
8-PL-1
13-J8-8
10-1
10-2
13-J8-4
13-J8-7
13-J7-2
13-J8-6
3 2 1
W06 15-J4-1
J3
QFA2 SPD1 QFA
X10-2 W03
W80 W80 W06 15-J4-2 X10-1 W03
W80 12
3-4
1-4
X3-2
L N
J4
W80 W80 LO NO
W80 J6 1 3 N 1 3
W80
1 8 12
J8 J7 2 4 PE L
2 4
2-N
W03
1-2
W80 W03
MFU DC power 3-2 2-N
wiring diagram
8 W03
W03 W03
MFU Rear top view Conneted earthing terminal
21-N/24-N
21-L/24-L
23-N
22-N
22-L
23-L
5 9
PE BUS+ W01 W02
TO the user protective 0V
earth
1 2
W06 15-J5 W06 15-J6 7-47/7-49/7-50 W80
2 3 9-2 Module subrack Rear view
5-3 W07 1 12-1 W84
2-PE W03 6 TO MFU unit PL busbar To the positive busbar of the MFU
To the positive Busbar Shelf 1
W80 W80 24 23 22 21
7-27 7-29 H4 H3 H2 H1
L
W01 L
W01 L
W01 L
W01
1 1 1 1 1 1 W02 W 02 W02 W02
QFD6
QFD5
QFD4
QFD3
QFD2
QFD1
11
N N N N
X3-1
PE PE PE PE
2 2 KM1
W80 2 2 2 2
P W04 P W04 P W04 P W04 7-4 7-2
W80
W05
7-45
7-43
PL NPL
2 3 2 3 2 3 2 3
1 1 1 1
W80
18-J2-3 2 1
4 5 4 5 4 5 4 5
7-26
7-24
6 6 6 6
7-31 NPL
7-46
W80 7-35 1 12 W84
KM2 W80
9-BUS+-1
W06 1 1
18-J2-1
W80
QFB1
QFB2
18-J2-2
15-J7 2
PL 10 2 2
RB
2 1
1 8-B-
2 1
7-22
7-20
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 54
W80
Door connected ground
8-NPL-QFD
X12-2
Controller motherboard switch
8-QFB1-1
8-PL-QFD
W80 W80 W80
11-1
11-2
7
M820B
51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99
52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100
12-1
12-2
8-QFB2-1
W80 W80 User interface board 1
9-BUS+-2 W80 9-BUS+-1 W80
W80 X9
X6-1 X5-1
W80
J6 J7 J8 J9
13-J2-1
13-J2-4
13-J2-3
8-PL-1
13
IB2
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Single-phase AC input
24-CAN+
24-CAN-
J3 J4 J5
8-PL-1
13-J2-2
9-BUS+-1
8-B--1
10-1
10-2
1
QFA
W80 W80
X3-2
W80 W80 W80 J2 L N
W80 4 3 J11 J12 1 3
2 1
MFU DC power
wiring diagram
8
MFU Rear top view W80
2 4
5 9
PE BUS+
0V
1
2
21-N/24-N
21-L/24-L
2 1 7-35/7-47/7-49/7-50 W80
3 9-2 5-3 W07
22-L
23-N
23-L
22-N
2 X5-1/X6-1 W80
4 3 W01 W02
1 1 1 1
QFD4
QFD3
QFD2
QFD1
24 23 22 21
1 1 1 1 11 H4 H3 H2 H1
QFD8
QFD7
QFD6
QFD5
KM1
2 2 2 2 W01 W01 W01 W01
2 2 2 2 W80 W80 L L L L
NPL
7-79
7-81
4 5 4 5 4 5 4 5
W80 7-46 6 6 6 6
1 12
W80 KM2 W80 1 1
QFB2
QFB1
2
7-80
7-82
PL 10 2 2
RB
1 2
1 8-B-
2 1
7-22
7-20
7-44
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 55
Three-phases AC input
1
QFA
L1 L2 L3 N
1 3 5 7
21-N/22-N/23-N
X7-2
9-BUS+-2 W80 W80 9-BUS+-1 W80
W80
21-L
22-L
23-L
X6-1 X5-1 W80
13-J8-1
W02
13-J8-3
13-J8-5
13-J8-2
13-J7-1
W80 W80 W80W80
8-NPL-QFD
8-PL-QFD
W01 W01 W01
12-2
12-1
11-2
11-1
8-PL-1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
13
W2453X1
Module subrack
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 6 TO MFU unit PL busbar To the positive busbar of the MFU
Shelf 1
24-CAN+
W2453X1
4- 4+ 2- 2+ DO4 DO2
24-CAN-
8-QFB1-1
3- 3+ 1- 1+ DO3 DO1
13-J8-8
23 22 21
13-J8-7
13-J8-4
13-J7-2
8-PL-1
8-QFB2-1
9-BUS+-1
8-B--1
13-J8-6
10-1
10-2
H3 H2 H1
1 1 1
-48V
W80W80
X3-2 W80 W80 7-2 X3-1
W80 W80
J3
W80
W80 10 10 10
0V 7-4 W05
12 W04 W04 W04
J4
PE PE PE
J6 W02 W02 W02
N N N
MFU DC power
wiring diagram
8 1 8 12 W01 W01 W01
MFU Rear top view J8 J7
L L L
W80
5 9
PE BUS+
TO the user protective 0V
earth 1
2
2 1 7-35/7-47/7-49/7-50 W80
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80
3
To the positive Busbar
W80+W81+W82 W80+W81+W82
7-29 7-27
11
1 1 1 1 1
QFD5
QFD4
QFD2
QFD1
KM1
QFD3
W80 W80
7-45
7-43
2 2 2 2 2
PL NPL W80
2 1
7-28
7-30
W80 7-31
W80
NPL
7-46
1
12
KM2 W80 1 1
QFB2
QFB1
W80
7-39
7-41
2
PL 10 2 2
RB
1 2
1 8-B-
2 1
7-22
7-20
7-44
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 56
8-NPL-QFD
13-J8-1
13-J8-3
13-J8-5
13-J8-2
13-J7-1
W80
8-PL-QFD
W80 W80
8-PL-1
11-2
11-1
Three-phases AC input
1
QFA
User interface board 1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 13
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 W2453X1
L1 L2 L3 N
1 3 5 7
24-CAN+
24-CAN-
W2453X1
4- 4+ 2- 2+ DO4 DO2
13-J8-8
13-J8-4
13-J8-6
13-J8-7
13-J7-2
8-QFB1-1
9-BUS+-1
8-QFB2-1
10-1
8-PL-1
10-2
8-B--1
3- 3+ 1- 1+ DO3 DO1
W80 W80 2 4 6 8
21-N/22-N/23-N/24-N
X3-2
W80 W80 W80 W80 W80
J4 J3
21-L/24/L
W80
12
22-L
23-L
J6
MFU DC power
wiring diagram 8 Rear top view 1 8 12 W01 W01W01 W02
MFU 5 9 J8 J7
PE BUS+ W80
TO the user protective 0V Module subrack
earth 1
2 6
Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
2 1 7-35/7-47/7-49/7-50 W80
4 3 9-2 5-3 W07 24 23 22 21
H4 H3 H2 H1
2 X5-1/X6-1 W80 1 1 1 1
-48V
3
W80+W81+W82
7-29 7-2 X3-1
1 1 1 1 To the positive Busbar
QFD12
QFD2
QFD1
QFD3
10 10 10 10
0V 7-4 W05
2 2 2 2 W04 W04 W04 W04
PE PE PE PE
PL W02 W02 W02 W02
N N N N
W80 L W01 L W01 L W01 L W01
7-28
W80 7-31 7-30
W80 7-46
1 12
W80 KM2 W80 1 1
QFB2
QFB1
7-41
2
7-39
PL 10 2 2
RB
1 2
1 8-B-
2 1
7-22
7-20
7-44
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 57
18
M34C3C1
J2 J1
12-1 1 7-39 W06
DCSPD
13-J3-1+
13-J3-1-
W84 12-2 1 15
8-PL-1
2
2 7-41 W84 M2433X2
3
J3 J1 J2 J4
J5 J6 J7
PE v+ v-
8-PL-2
5-2
9-2
W06 W06 W06
User interface board 1 13
W2453X1
W2453X1
4- 4+ 2- 2+ DO4 DO2
3- 3+ 1- 1+ DO3 DO1
Door connected ground
Controller motherboard switch 7
M221S Front view
J4 J3
W06 15-J4-1
9-BUS+-2 W80 W80 9-BUS+-1 W80 W06 15-J4-2 Single-phase AC input
W80
X6-1 X5-1
X7-2
W84 W84 W80W80
12
J6
13-J8-1
13-J8-3
13-J8-5
13-J8-2
13-J7-1
8-NPL-QFD
18-J1-2
18-J1-1
8-PL-QFD
11-2
11-1
W80 3 2 1
QFA2 SPD1 QFA
12
8-PL-1
1 8 W03
X10-1 W03
J8 J7
3-4
1-4
LO NO L N
W80 1 3 N 1 3
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
PE
L
2 4 2 4
24-CAN+
24-CAN-
2-N
13-J8-8
8-PL-1
13-J8-7
8-QFB2-1
8-QFB1-1
13-J8-4
13-J8-6
9-BUS+-1
13-J7-2
W03
1-2
10-1
10-2
W03
5-4 3-2 2-N
X10-2 W03W03 W03
W80 W80 W80
X3-2
21-N/24-N
W80
21-L/24-L
W80 W80
W80
23-N
22-N
22-L
23-L
W01 W02
MFU DC power
wiring diagram
8
MFU Rear top view
Module subrack
5 9
BUS+ 6 TO MFU unit PL busbar To the positive busbar of the MFU
PE 0V
Shelf 1
TO the user protective
24 23 22 21
earth 1 H4 H3 H2 H1
2 1 1 1 1
-48V
15-J6 2 W06 15-J6 1 7-35/7-47/7-49/7-50
W06 W80
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80 7-2 X3-1
2-PE W03 3
12-1
W84 To the positive Busbar 10 10 10 10
0V 7-4 W05
W80 W80 W04 W04 W04 W04
PE PE PE PE
7-29 7-27 W02 W02 W02 W02
N N N N
1 1 1 1 1 1 1 1
QFD12
QFD11
QFD10
QFD9
QFD8
QFD2
QFD1
QFD3
PL NPL
W80
W84 18-J2-3 2 1
7-28
7-30
W80 7-31
NPL
W80 7-46 W84
1 W84 12 W84
9-BUS+-3
1 1
18-J2-1
QFB2
QFB1
2
PL 10 2 2
RB
1 2
1 8-B- 2 1
7-22
7-20
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 58
DU 17
DU
0V
MFU
W81+W82
7-60
1 1 1 1 1 1
8-QF8
8-QF7
8-QF6
8-QF5
8-QF4
8-QF3
2 2 2 2 2 2
PL NPL
8-PL-QFD
TO MFU unit PL busbar To the positive busbar of the MFU
8-QFB1-1
W80 W80 W80
11-1
11-2
Three-phases AC input
51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 1
QFA
52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100
L1 L2 L3 N
12-1
12-1
8-QFB2-1
J6 J7 J8 J9
X9
X4-2 X5-1 W80 13
13-J2-1
13-J2-4
21-L/24-L
8-PL-1
IB2
13-J2-3
21-N
22-N
23-N
24-N
22-L
23-L
W01 W01 W01 W02
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
J3 J4 J5
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
24-CAN+
24-CAN-
9-BUS+-1
8-PL-1
Module subrack
13-J2-2
8-B--1
10-1
10-2
6
W80W80 J2 Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
X3-2 W80W80
4 3 J11 J12 24 23 22 21
2 1 H4 H3 H2 H1
W80 1 1 1 1
W80 -48V
W80
MFU DC power 8 7-2 X3-1
wiring diagram MFU Rear top view 9
5
PE BUS+ 10 10 10 10
0V 7-4 W05
TO the user protective 0V W04 PE
W04
PE
W04 PE
W04
earth PE
1 W02 W02 W02 W02
2 N N N N
2 1 7-35/7-47/7-49/7-50 W80 W01 L W01 W01 L W01
L
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80
L
3
W80 W80
7-59 7-60
1 1 1 1 1 1
QFD18
QFD11
QFD10
QFD9
QFD1
QFD2
11 DU NPL
KM1
2 2 2 2 2 2
W80 W80
7-79
7-81
PL NPL
W80
2 1
7-56
7-55
DU PL
NPL
QFB1
W80
7-80
7-82
10 2 2
2 RB
1 2
PL
1 8-B-
2 1
7-22
7-20
7-44
W80 W80
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 59
18
M34C3C1
J2 J1
12-1 1 7-39 DCSPD
W06
13-J3-1+
13-J3-1-
W84 12-2 1 15
8-PL-1
2
2 7-41 W84 M2433X2
3
J3 J1 J2 J4
J5 J6 J7
PE v+ v-
8-PL-2
9-2
5-2
W06 W06
W06
User interface board 1 13
W2453X1
4- 4+ 2- 2+ DO4 DO2
W2453X1
3- 3+ 1- 1+ DO3 DO1
Controller motherboard switch 7
M221S Front view
J4 J3
W06 15-J4-1
9-BUS+-2 W80 9-BUS+-1 W80 W06 15-J4-2
W80
X6-1 X5-1
W80 W84 W84 W80 W80
12
J6
13-J8-1
13-J8-3
X7-2
13-J8-5
13-J8-2
13-J7-1
18-J1-2
18-J1-1
8-NPL-QFD
11-2
11-1
W80
8-PL-QFD
3 2 1
8-PL-1
1 8 12 QFA2
W03 SPD1 QFA
J8 J7 X10-1 W03
3-4
1-4
LO NO L N
W80 1 3 N 1 3
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
PE L
24-CAN+
2 4 2 4
24-CAN-
13-J8-8
13-J8-4
13-J8-7
8-PL-1
13-J7-2
9-BUS+-1
8-QFB2-1
8-QFB1-1
13-J8-6
2-N
10-1
10-2
1-2
W03 W03
X10-2 5-4 3-2 2-N
W80 W80 W03 W03 W03
W80
X3-2
21-N/24-N
W80
21-L/24-L
W80 W80
22-N
23-N
25-N
W80
22-L
25-L
23-L
MFU DC power W07 W01 W02W07
wiring diagram
8
MFU Rear top view
9 Module subrack
5
PE BUS+ 6 TO MFU unit PL busbar To the positive busbar of the MFU
TO the user protective 0V Shelf 1
earth
1 24
H4
23
H3
22
H2
21
H1 -48V 25
H5
2 W08
W06 15-J6 1 1 1 1 1
QFD8
QFD7
QFD6
QFD2
QFD1
QFD9
QFD3
PL NPL
W80
W84 18-J2-3 2 1
7-28
7-30
12
15-J7 W84
18-J2-1
KM2
18-J2-2
W06 1 1
QFB2
QFB1
2
10 2 2
PL
RB
1 2
1 B- 2 1
7-22
7-20
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 60
User interface
board
PD1 W2453X1
User-defined ST1 MB
AC Output Temperature Sensor Controller QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD6
H1 KMD1
LLVD Contactor
Mains Input QFD7
H2
QFA1
N PL
W34C3C1
QFD10
L
PD2
H3
PE
RS1
H5 QFB1
Battery 1
QFB2
Battery 2 Positive Busbar
CAN
DC SPD
SPD2
M2433X2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 61
PD1
W2453X1
User-defined
AC Output
ST1 MB
Temperature Sensor
QFD1
No
C M221S or
Lo ST2
Class C SPD M222S
SPD1 QFA2 NPL
Temperature Sensor
Optional QFD4
H1 KMD1
LLVD Contactor
Mains Input QFD5
H2
QFA1
N W34C3C1 PL
QFD6
L
PE H3
KMD2
BLVD Contactor
H4
RS1
CAN 1
QFB1
Battery 1
2
QFB2 Positive Busbar
Battery 2
DC SPD
SPD2
M2433X2
1
AC Distribution Unit -48V
0V DC Distribution Unit 1
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 62
User interface
board
PD1
M A4 C5U3 1
ST1 MB
Temperature Sensor Contoller QFD1
M820B
ST2
Tem perature Sensor NPL
Op tional
QFD4
H1 KMD1
LLVD Contactor
Mains Input QFD5
H2
QFA1 PL
N
QFD8
L
H3
PE
KMD2 BLVD Contactor
H4
RS1
CAN
QFB1 Battery 1
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 63
User interface
board
PD1
W2453X1
ST1 MB
Temperature Sensor
Controller
QFD1
M221S or
ST2
M222S
Temperature Sensor
NPL
Optional QFD4
H1 KMD1
LLVD Contactor
Mains Input
H2
QFA1 QFD5
N PL
W
V H3
U
PE
KMD2
BLVD Contactor
CAN
RS1
QFB1
Battery 1
QFB2 Positive Busbar
Battery 2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 64
User interface
board
PD1
W2453X1
ST1 MB
Temperature Sensor Controller
M221S or
ST2
M222S
Temperature Sensor
Optional
H1
PE
KMD2
H4 BLVD Contactor
RS1
CAN
QFB1
Battery 1
QFB2 Positive Busbar
Battery 2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 65
User interface
board
PD1
W2453X1
User-defined
AC Output
ST1 MB
Temperature Sensor Controller
QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD8
H1 KMD1
LLVD Contactor
Mains Input QFD9
H2
QFA1
N PL
W34C3C1
QFD12
L
PD2
H3
PE
KMD2
BLVD Contactor
H4
RS1
CAN
QFB1
Battery 1
QFB2
Battery 2 Positive Busbar
DC SPD SPD2
M2433X2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 66
User interface
board
PD1
MA4C5U31
ST1 MB
Temperature Sensor Controller QFD11
QFD1
M820B
ST2
Temperature Sensor NPL NPL
Optional
QFD4 QFD14
H1 KMD1
LLVD Contactor
Mains Input QFD5
H2 QFD15
QFA1
N PL
PL
QFD10
W QFD18
V H3
U
PE
KMD2 BLVD Contactor
H4
RS1
CAN QFB1
Battery 1
QFB2 Positive Busbar Positive Busbar
Battery 2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 67
User interface
board
PD1 W2453X1
User-defined ST1 MB
AC Output Temperature Sensor Controller QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD6
H1 KMD1
LLVD Contactor
Mains Input QFD7
H2
QFA1
N PL
W34C3C1
QFD10
L
PD2
H3
PE
RS1
H5 QFB1
Battery 1
QFB2
Battery 2 Positive Busbar
CAN
DC SPD
SPD2
M2433X2
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
68 Appendix 5 Glossary
Appendix 5 Glossary
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual