Sei sulla pagina 1di 60

11

By Denis Mitchell
and Patrick Paultre

Seismic Design

11.1 Introduction..................................................................................... 113


11.2 Seismic Design Considerations ..................................................... 115
11.3 Loading Cases ............................................................................... 115
11.4 Design of a Six-Storey Ductile Moment-Resisting
Frame Building ............................................................................... 116
11.4.1 Description of Building and Loads.................................................. 116
11.4.2 Determination of Design Forces..................................................... 117
11.4.2.1 Gravity Loading .............................................................................. 117
11.4.2.2 Seismic Loading ............................................................................. 118
11.4.3 Deflections, Drift Ratios and Torsional Sensitivity........................ 1112
11.4.4 Design of Ductile Beam................................................................ 1112
11.4.4.1 Determination of Design Moments............................................... 1113
11.4.4.2 Moment Redistribution and Moment Envelopes .......................... 1113
11.4.4.3 Design of Flexural Reinforcement at Critical Sections ................. 1114
11.4.4.4 Design of Transverse Reinforcement in Beams .......................... 1117
11.4.4.5 Checking Extent of Plastic Hinging .............................................. 1119
11.4.4.6 Bar Cut-offs .................................................................................. 1119
11.4.4.7 Splice Details................................................................................ 1119
11.4.5 Design of Interior Ductile Column ................................................ 1121
11.4.5.1 Column End-Actions from Analysis .............................................. 1121
11.4.5.2 Factored Axial Loads and Moments............................................. 1122
11.4.5.3 Preliminary Selection of Column Reinforcement.......................... 1122
11.4.5.4 "Strong Column - Weak Beam" Requirement .............................. 1123
11.4.5.5 Design of Transverse Reinforcement in Column ......................... 1124
11.4.5.6 Splice Details................................................................................ 1128
11.4.6 Design of Interior Beam-Column Joint ......................................... 1128
11.4.6.1 Determination of Factored Forces in Joint ................................... 1128
11.4.6.2 Check Factored Shear Resistance of Joint.................................. 1130
11.4.6.3 Transverse Reinforcement Required in Joint............................... 1130
11.4.6.4 Bond of Beam Bars ...................................................................... 1131
11.5 Analysis of a Ductile Core-Wall Structure .................................... 1131
11.5.1 Description of Building and Loads................................................ 1131
11.5.2 Analysis Assumptions .................................................................. 1132
11.5.3 Seismic Loading ........................................................................... 1132
11.5.3.1 Minimum Lateral Earthquake Force ............................................. 1133
112 Seismic Design

11.5.3.2 Accidental Torsion........................................................................ 1135


11.5.3.3 Degree of Coupling ...................................................................... 1135
11.5.3.4 Check on Structural Irregularity.................................................... 1136
11.5.3.5 Dynamic Analysis ......................................................................... 1136
11.5.3.6 Deflections and Drift Ratios.......................................................... 1140
11.5.4 Design Forces .............................................................................. 1140
11.5.5 Design of Coupling Beams........................................................... 1145
11.5.5.1 Design Forces for Coupling Beams ............................................. 1145
11.5.5.2 Design and Detailing of Coupling Beams..................................... 1146
11.5.5.3 Ductility of Coupling Beams ......................................................... 1147
11.5.6 Design of Ductile Walls ................................................................ 1147
11.5.6.1 Design Forces in E-W Direction ................................................... 1147
11.5.6.2 Design Forces in N-S Direction .................................................... 1149
11.5.6.3 Design of Base of Wall for Flexure and Axial Load...................... 1149
11.5.6.4 Ductility of Walls ........................................................................... 1153
11.5.6.5 Checking Wall Thickness for Stability (Clause 21.6.3) ................ 1153
11.5.6.6 Buckling Prevention Ties for Concentrated Reinforcement
(Clause 21.6.6.9).......................................................................... 1154
11.5.6.7 Design for Shear at Base of Walls (Clause 21.6.9) ..................... 1154
11.5.6.8 Checking Sliding Shear Resistance at Construction Joints
(Clause 21.6.9.4).......................................................................... 1156
11.5.6.9 Determination of Plastic Hinge Region (Clause 21.6.2) ............... 1157
11.5.6.10 Changes in Horizontal Distributed Reinforcement Over the
Height of the Walls (Clause 21.6.5) ............................................. 1157
11.5.6.11 Changes in Vertical Distributed Reinforcement Over the
Height of the Walls (Clause 21.6.5) ............................................. 1158
11.5.6.12 Changes in Concentrated Vertical Reinforcement Over the
Height of the Walls (Clause 21.6.6) ............................................. 1158
11.5.7 Frame Members Not Considered Part of the SFRS .................... 1158
11.5.7.1 Slab-Column Connections (Clause 21.12.3) ................................ 1158
11.5.7.2 Check on Design And Detailing of Columns (Clause 21.12)........ 1159
11.5.8 Comparisons With the Design Using the 1994 CSA Standard .... 1159
11.5.9 References ................................................................................... 1159
CAC Concrete Design Handbook 113

11.1 Introduction
The 2005 National Building Code of Canada (NBCC) gives the minimum lateral earthquake
force for the equivalent static force procedure as:

S (Ta ) M v I E W S (2.0 )M v I E W
V =
Rd Ro Rd Ro

and for a Seismic Force Resisting System (SFRS) with an R d equal to or greater than 1.5 ,
2 S (0.2)IEW
V need not be taken greater than
3 Rd Ro
where:
S (Ta ) = design spectral response acceleration, expressed as a ratio to gravitational
acceleration for a period of Ta
Mv = factor to account for higher mode effect on base shear
IE = earthquake importance factor for the structure
Ta = fundamental period of vibration of the building in seconds in the direction under
consideration
W = dead load, plus 25% of the design snow load, plus 60% of storage load and the full
contents of any tanks. Minimum partition load need not exceed 0.5 kPa
Rd = ductility-related force modification factor that reflects the capability of a structure to
dissipate energy through inelastic behaviour
Ro = overstrength-related force modification factor that accounts for the dependable
portion of reserve strength in a structure.
The designer chooses the type of SFRS, with the corresponding force modification factors,
R d and R o . The values of R d and R o are a function of the type of lateral load resisting system
and the manner in which the structural members are designed and detailed. Table 11.1 provides
a guide for the required design and detailing provisions of CSA Standard A23.3 associated with
the corresponding factors, R d and R o .
114 Seismic Design

Table 11.1 Design and Detailing Provisions Required for Different Reinforced Concrete
Structural Systems and Corresponding R d and R o Factors
Type of SFRS Rd Ro Summary of design and detailing requirements in CSA
A23.3-04
Ductile 4.0 1.7 Beams capable of flexural hinging with shear failure and
moment bar buckling avoided. Beams and columns must satisfy
resisting ductile detailing requirements. Columns properly
frames confined and stronger than beams. Joints properly
confined and stronger than beams.
Moderately 2.5 1.4 Beams and columns must satisfy detailing requirements
ductile for moderate ductility. Beams and columns to have
moment minimum shear strengths. Joints must satisfy moderate
resisting ductility detailing requirements and must be capable of
frames transmitting shears from beam hinging.
Ductile 4.0 1.7 At least 66% of base overturning moment resisted by
coupled walls wall system must be carried by axial tension and
compression in coupled walls. Coupling beams to have
ductile detailing and be capable of flexural hinging or
resist loads with diagonal reinforcement (shear failure
and bar buckling avoided). Walls must have minimum
resistance to permit attainment of nominal strength in
coupling beams and minimum ductility level.
Ductile 3.5 1.7 Coupling beams to have ductile detailing and be
partially capable of flexural hinging or resist loads with diagonal
coupled walls reinforcement (shear failure and bar buckling avoided).
Walls must have minimum resistance to permit
attainment of nominal strength in coupling beams and
minimum ductility level.
3.5 1.6 Walls must be capable of flexural yielding without local
Ductile
instability, shear failure or bar buckling. Walls must
shearwalls
satisfy ductile detailing and ductility requirements.
Moderately 2.0 1.4 Walls must satisfy detailing and ductility requirements
ductile for moderate ductility. Walls must have minimum shear
shearwalls strength.
Conventional 1.5 1.3 Beams and columns must have factored resistances
construction: greater than or equal to factored loads. Columns and
Moment beams must satisfy minimum detailing requirements for
resisting conventional construction. Closely spaced hoops
frames required in columns unless factored resistance of
columns greater than factored resistance of beams or if
R d R o = 1.0 .
Conventional 1.5 1.3 Walls must have factored resistances greater than or
construction: equal to factored loads. Factored shear resistance must
Shearwalls exceed shear corresponding to factored flexural
resistance or shear corresponding to R d R o = 1.0 .
Walls must satisfy minimum detailing requirements for
conventional construction.
Other 1.0 1.0
SFRS(s)
CAC Concrete Design Handbook 115

11.2 Seismic Design Considerations


Seismic design is concerned not only with providing the required strength but also with
providing minimum levels of ductility and choosing appropriate structural systems. These goals
may be achieved by:
(i) choosing structural systems which are as symmetrical as possible in plan and as
uniform as possible in elevation (minimizing structural irregularities);
(ii) designing the primary lateral load resisting structural components so that desirable
energy dissipating systems will form (e.g., "weak-beam strong-column");
(iii) detailing the energy dissipating regions of the primary lateral load resisting components
to ensure that substantial inelastic deformations can be achieved without significant
loss of strength, and
(iv) ensuring that secondary members which are not part of the lateral load resisting system
can maintain their gravity load carrying capacity as they undergo the required lateral
deformations.
In the design of ductile members it is necessary to determine the hierarchy of strengths of
different members. To ensure that certain hierarchy of strengths are achieved the CSA Standard
defines "probable", "nominal" and "factored" resistances. Table 11.2 summarizes the various
types of flexural resistances used in the CSA Standard and suggests approximate relationships
between these resistances.
Table 11.2 Factored, Nominal and Probable Moment Resistances
Type of flexural Calculated Where used Approximate
resistance using relationships for
flexure
M r = factored c = 0.65 All members must
resistance s = 0.85 satisfy M r M f
M n = nominal c = 1.0 To ensure columns M n 1.2M r
resistance s = 1.0 stronger than beams
M p = probable c = 1.0 M p 1.47M r
resistance s = 1.0
fs = 1.25f y
Note: the relationship between M n and M r for the case of flexure and axial load depends on the
level of axial load

11.3 Loading Cases


For loading combinations including earthquake, the factored load combinations shall include:
Principal loads:
1.0D + 1.0E

and either of the following combinations of principal and companion loads:


1) For storage occupancies, equipment areas and service rooms:
1.0D + 1.0E + 1.0L + 0.25S

2) For other occupancies:


1.0D + 1.0E + 0.5L + 0.25S
116 Seismic Design

11.4 Design of a Six-Storey Ductile Moment-Resisting Frame


Building
11.4.1 Description of Building and Loads

The six-storey reinforced concrete frame building shown in Fig. 11.1 is located in Vancouver
and is to be designed as a ductile moment resisting frame structure. The six-storey reinforced
concrete office building has 7 - 6 m bays in the N-S direction and 3 bays in the E-W direction which
consist of 2 - 9 m office bays and a central 6 m corridor bay.
The interior columns are all 500 x 500 mm while the exterior columns are 450 x 450 mm.
The one-way slab floor system consists of a slab 110 mm thick spanning in the E-W direction
supported by beams in the N-S direction. The secondary beams supporting the slab are 300 mm
wide x 350 mm deep (from top of slab to bottom of beam). The beams of both the N-S and E-W
frames are 400 mm wide x 600 mm deep for the first three storeys and 400 x 550 mm for the top
three storeys.

Material Properties
Concrete: normal density concrete with f c = 30 MPa
Reinforcement: f y = 400 MPa

Live loads
Floor live loads:
2
2.4 kN/m on typical office floors
2
4.8 kN/m on 6 m wide corridor bay

Roof load
2
2.2 kN/m snow load, accounting for parapets and equipment projections
2
1.6 kN/m mechanical services loading in 6 m wide strip over corridor bay

Dead loads
3
self-weight of reinforced concrete members calculated as 24 kN/m
2
1.0 kN/m partition loading on all floors
2
0.5 kN/m mechanical services loading on all floors
2
0.5 kN/m roofing

Wind loading
2
1.84 kN/m net lateral pressure for top 4 storeys
2
1.75 kN/m net lateral pressure for bottom 2 storeys

The fire-resistance rating of the building is assumed to be 1 hour.


CAC Concrete Design Handbook 117

Fig. 11.1 Six-storey structure located in Vancouver

11.4.2 Determination of Design Forces


11.4.2.1 Gravity Loading

To determine the member forces, the structure was analyzed using ETABS. To make
allowances for cracking, member stiffnesses were assumed to be 0.4 of the gross I for all beams
as required by CSA A23.3. To account for the influence of the axial load level on the column
stiffnesses, average estimated cracked moments of inertia of 0.6 and 0.7 of I g were used for the
columns in the top three storeys and bottom three storeys, respectively (Clause 21.2.5.2). The
analysis models and the gravity loading are illustrated in Fig. 11.2.
118 Seismic Design

To illustrate the requirements for the design of a ductile moment-resisting frame,


components of a typical interior E-W frame will be designed in the following examples.

Fig. 11.2 Unfactored loading cases considered in design of typical interior frame

11.4.2.2 Seismic Loading


Minimum Lateral Earthquake Force
The structure is located in Vancouver and is founded on very dense soil and soft rock.
Therefore the site classification is C and the acceleration-based and velocity-based site coefficients
are Fa = 1.0 and Fv = 1.0 , respectively.
The seismic response factor, S, is dependent on the fundamental period, T, of the structure.
The 5% damped spectral response accelerations, Sa (0.2) , Sa (0.5 ) , Sa (1.0 ) and Sa (2.0 ) are 0.94,
0.64, 0.33 and 0.17, respectively. The design spectral response accelerations are given by the
product of the site coefficients and S a as shown in Fig. 11.3.

Figure 11.3 Design spectral response acceleration

The empirical fundamental lateral period, Ta , for concrete moment frames is given by:

Ta = 0.075hn3 / 4 = 0.075 21.9 3 / 4 = 0.759 s


CAC Concrete Design Handbook 119

The calculated period for this structure, using the computer program ETABS is 1.35 s. The
value of the fundamental lateral period cannot be taken greater than 1.5 0.759 = 1.139 , and
hence use Ta = 1.14 s. The corresponding value of S (Ta ) is 0.308 (see Fig. 11.3).
For this office building, the earthquake importance factor, I E = 1.0 . The values of M v and
J depend on the ratio of Sa (0.2) / Sa (2.0 ) = 0.94 / 0.17 = 5.53 and the value of Ta . For this case
M v = 1.0 and J = 1.0 .
For this ductile moment resisting frame structure R d = 4.0 and R o = 1.7 . Hence the seismic
base shear, V, is:
S (Ta ) Mv IEW 0.308 1.0 1.0 W
V = = = 0.0453W
Rd Ro 4.0 1.7

S (2.0 ) Mv I EW 0.17 1.0 1.0 W


Vmin = = = 0.025W
Rd Ro 4.0 1.7

2 S (0.2)IEW 2 0.94 1.0 W


Vmax = = = 0.092W
3 Rd Ro 3 4.0 1.7

For this structure, W = 44,765 kN.


Hence, V = 0.0453W = 0.0453 44,765 = 2026 kN.
The portion of V concentrated at the top of the building is
Ft = 0.07Ta V = 0.07 1.139 2026.1 = 161.5 kN, but need not be taken greater
than 0.25V = 0.25 2026.1 = 506.5 kN.
The calculations of the seismic lateral forces at each floor level are summarized in Table
11.3.

Table 11.3 Lateral Load Calculations for Each Floor Level


Floor hx , Wx , hxW x , Fx , Vx , Tx ,
m kN kNm kN kN kNm
6 roof 21.90 7457 163,308 696 0 2953
5 18.25 7365 134,411 440 696 1866
4 14.60 7365 107,529 352 1,135 1493
3 10.95 7526 82,410 270 1,487 1144
2 7.30 7526 54,940 180 1,757 763
1 3.65 7526 27,470 90 1,936 381
0 0.00 - - 0 2,026
Total - 44,765 570,068 2,026 - 8601

Accidental Torsion
The 3-D model shown in Fig. 11.4 was used to calculate accidental torsional effects by
applying the lateral forces Fx (see Table 11.3) at an accidental eccentricity of 0.1D nx , where
Dnx is the plan dimension of the building at level x, perpendicular to the direction of seismic
loading. This gives an accidental torsional eccentricity of 4.245 m, from the centre of mass (same
as centre of rigidity) for loading in the E-W direction. The resulting floor torques, T x , are given in
Table 11.3.
1110 Seismic Design

Dynamic Analysis
This symmetrical structure has no structural irregularities in the vertical or horizontal
directions and in addition is not sensitive to torsion (see Section 11.4.3). Therefore, In accordance
with NBCC a dynamic analysis is not required. However, a dynamic analysis was carried to
determine the lateral period of vibration (see above). This dynamic analysis was also used to
determine the design forces for the members and to estimate the lateral displacements. The
purpose of carrying out a dynamic analysis in this example is to illustrate the approach required
and to obtain a more realistic design force distribution.
The first step is to determine Ve from a linear dynamic analysis. The design base shear
Vd is obtained from:
Ve
Vd = IE
Rd Ro
However for this regular structure, Vd shall not be taken less than 0.8V .
All forces and deflections obtained from the linear dynamic analysis are scaled by the factor
Vd / Ve to obtain the design values. However, in order to obtain realistic values of anticipated
deflections and drifts, the design values need to be multiplied by R d R o / I E .
Fig. 11.4 shows the 3-D model for the dynamic analysis, using ETABS. In the analysis, rigid
end offsets were used to simulate the dimensions of the joints and rigid diaphragms were
assumed. The total mass for each floor was concentrated at the centre of mass (coincident with
the centre of rigidity for this structure). To account for sway effects (P-Delta) the ETABS program
option, accounting for second order effects by the addition of the so-called geometric stiffness,
which is a function of the compression forces in the columns from gravity loads, was used. These
compressive forces were obtained from the consistent loading case of 1.0D + 0.5L + 0.25S , with
live load reduction factors.
The first three lateral modes in the E-W direction are shown in Fig. 11.5, together with the
associated periods of vibration and the modal participating mass ratios. Note that the sum of
these ratios is 96.9% of the total mass and hence exceeds the minimum required ratio of 90% of
the total mass (NBCC). Spectral modal superposition, using SRSS for the first three modes in the
E-W direction was used to determine all forces and deformations.
CAC Concrete Design Handbook 1111

Figure 11.4 3-D Model used for dynamic analysis

Mode 1 Mode 2 Mode 3


T = 1.349 T = 0.453 T = 0.250
MPMR = 0.82 MPMR = 0.11 MPMR = 0.04

Figure 11.5 Mode shapes, corresponding lateral periods of vibration and modal
participating mass ratios

The base shear determined by dynamic analysis is Ve = 10690 kN.

Therefore:
10690
Vd = 1.0 = 1572 kN
4.0 1.7
However for this regular building Vd shall not be taken less than 0.8V = 0.8 2026 .1 = 1620.9 kN.
Hence, all forces and deflections obtained from the dynamic analysis shall be multiplied by
Vd / Ve = 1620 .9 / 10690 = 0.152 .
1112 Seismic Design

11.4.3 Deflections, Drift Ratios and Torsional Sensitivity


The deflections obtained from the dynamic analysis need to be multiplied by the factor 0.152
to account for the total anticipated displacements, including the inelastic effects. It is necessary to
multiply these deflections by the factor R d R o / I E to obtain the design values. Note that the
deflections obtained from dynamic analysis include P-Delta effects. The deflections arising from
accidental torsional eccentricity shall be added to the deflections from the dynamic analysis.
To determine if the structure is sensitive to torsion, the value of B x is determined from the
maximum and average displacements of the structure at level x in the E-W and N-S directions.
The maximum value, B , of the B x values is at the first floor level for loading in the E-W direction
(an average displacement of 5.1 mm and a maximum displacement of 6.8 mm), giving:
6.8
B = max = = 1.35
ave 5.1
Because B is less than 1.7, the structure is not sensitive to torsion.
The maximum interstorey drift ratio occurs in Frames 1 and 8 in the second storey for the E-
W direction of loading. From the dynamic analysis the maximum interstorey drift ratio is 0.0015
and the interstorey drift ratio from accidental torsion at this level is 0.0007, for a maximum
interstorey drift ratio of 0.0022. Therefore the anticipated interstorey drift ratio, including inelastic
effects is 0.0022 4.0 1.7 / 1.0 = 0.0146 . This anticipated maximum interstorey drift ratio is less
than the NBCC limit of 0.025.

11.4.4 Design of Ductile Beam


To illustrate the procedures involved in designing a beam in a ductile moment-resisting
frame, a typical first storey interior beam will be designed below. For illustration purposes frame 2
will be designed. This frame, although it has a smaller torsional shear than frame 1, will require
more reinforcement than frame 1 because it carries larger dead and live loads. The details of the
beam and column framing are given in Fig. 11.6.

Fig. 11.6 Typical beam and column framing


CAC Concrete Design Handbook 1113

11.4.4.1 Determination of Design Moments


The moments in the beams resulting from dead load, D, live load, L, and earthquake loading,
E, as determined from frame analyses, are in Fig. 11.7. Note that the moments are given at the
face of the columns. Since most of the gravity loading in beams AB, BC and CD is introduced at
the locations of the secondary beams, the small uniformly distributed loading has been
approximated by additional concentrated loads at the secondary beam locations.

Fig. 11.7 Loading cases on typical interior beam at second floor level

Table 11.4 gives the unfactored moments at critical locations and also gives the factored moment
combinations which need to be considered.

11.4.4.2 Moment Redistribution and Moment Envelopes


Instead of designing each of the critical sections for the maximum factored moments given in
Table 11.4, moment redistribution will be used to reduce some of the maximum design moments.
Since the beams in a ductile moment-resisting frame structure are designed and detailed to
exhibit considerable ductility the maximum redistribution of 20%, permitted by Clause 9.2.4, will be
used.
While it is possible to redistribute the earthquake moments, care must be exercised to
ensure that the total column shears in any one storey remain unchanged after redistribution. A
simpler approach is to redistribute only the dead load and live load moments.
In order to reduce the magnitude of the negative moments at location BA, the dead and live
load support moments are reduced at this location by the maximum permitted amount (20%). The
positive moments in span AB are increased by the appropriate amounts. The resulting moments
are summarized in Table 11.5.
1114 Seismic Design

Table 11.4 Moments at Critical Locations (kNm) Before Redistribution

AB a b BA BC c
D -167 +119 +105 -206 -104 +29
L -66 +50 +45 -90 -79 +41
Accidental Torsion 30 11 9 28 41 15
E without accidental 98 36 30 92 131 48
torsion
E with accidental 128 47 39 120 172 63
torsion
1.25D+1.5L -308 +224 +199 -393 -249 +98
1.0D+1.0E -39 +166 +144 -86 +68 +92
1.0D-1.0E -295 +72 +66 -326 -276 -34
1.0D+0.5L+1.0E -72 +191 +167 -131 +29 +112
1.0D+0.5L-1.0E -328 +97 +88 -371 -316 -13
Note: controlling load combinations shown in bold

Table 11.5 Moments at Critical Locations (kNm) after Redistribution

AB a b BA BC c
D -167 +132 +133 -165 -104 +29
L -66 +56 +57 -72 -79 +41
Accidental Torsion 30 11 9 28 41 15
E without accidental 98 36 30 92 131 48
torsion
E with accidental 128 47 39 120 172 63
torsion
1.25D+1.5L -308 +249 +252 -314 -249 +98
1.0D+1.0E -39 +180 +172 -45 +68 +92
1.0D-1.0E -295 +85 +94 -284 -276 -34
1.0D+0.5L+1.0E -72 +208 +201 -81 +29 +112
1.0D+0.5L-1.0E -328 +113 +122 -320 -316 -13
Note: controlling load combinations shown in bold

It is noted that, after redistribution, earthquake loading governs at all negative moment
sections at the second floor level.

11.4.4.3 Design of Flexural Reinforcement at Critical Sections


Top bars at column faces
In deciding on the appropriate top reinforcement, note that Clause 21.5.5.6 limits the
diameter, db, passing through the joint to l j / 24 for this normal density concrete structure and
uncoated bars. Thus for this case the maximum diameter of beam bars passing through the
interior columns is 500 / 24 = 21 mm. Hence the maximum beam bar size is 20M.
At column A, a factored moment resistance of at least 328 kNm is required. Assuming a
flexural lever arm of 0.75h = 0.75 0.600 = 0.450 m, the required area of top bars would be
328 1000 / (0.450 0.85 400 ) = 2144 mm . If it is assumed that slab reinforcement within a
2

distance of 3hf from the sides of the beam is effective, then 410M bars in the slab are effective.
CAC Concrete Design Handbook 1115

It is assumed that these 10M bars in the flange are effective under reversed cyclic loading even
though there is no anti-buckling reinforcement for these bars. Note that larger bars may not be
2
effective. The additional reinforcement required is then 1744 mm . Note that it is unwise to be too
conservative when designing the top reinforcement since beam shears, joint shears, column
moments and column shears are all increased if the flexural capacity at the end of the beam is
increased.
Let us try an arrangement of 620M bars as shown in Fig. 11.8. Keeping in mind that the
positive moment resistance of the beam needs to be at least one-half of the negative moment
resistance, try using 420M bars on the bottom of the beam.

Fig. 11.8 Beam cross section near column face

Accounting for the presence of the compression reinforcement, the depth of compression, c,
is found to be 92 mm and the factored negative moment resistance is 359 kNm. Hence the
moment capacity is satisfactory.
The required minimum top and bottom reinforcement, As ,min , from Clause 21.3.2.1 is:
2 2
As ,min = 1.4bw d / f y = 1.4 400 527 / 400 = 738 mm 1200 mm O.K.

The maximum reinforcement permitted is:


2 2
0.025bw d = 0.025 400 527 = 5270 mm 2200 mm O.K.

Note that in choosing the arrangement of the beam bars at column faces the following
factors must be considered:
(a) the need to restrain the longitudinal bars from buckling by providing lateral restraint in the
form of hoops and ties.
(b) the need to pass the beam bars through the column cage, and
(c) the need to provide adequate space between top bars to permit placement and vibration of
concrete.
Since the magnitudes of the negative moment resistances required at column faces AB, BA
and BC are all about the same, we will use the same reinforcing arrangement at these three
locations.
1116 Seismic Design

Bottom bars for positive moment regions

Span BC:
For span BC, the effective compressive flange width is 1600 mm (see Clause 10.3.3). For
2
420M bars ( As = 1200 mm ), M r at the column face, accounting for the large amount of top
reinforcement, is 229 kNm which is larger than one half of 359 kNm (i.e., M r at column face
2
where As = 2200 mm ).
As 420M bottom bars are provided at column faces AB, BA and BC, use 420M bars in
span BC. The positive moment resistance M r is 229 kNm in the midspan regions of span BC.
As 229 kNm exceeds 112 kNm (Table 11.5), 4-20M bars will be satisfactory.

Span AB:
For span AB, the effective compressive flange width is 2200 mm (see Clause 10.3.3). For
M r 252 kNm (Table 11.5) try 6- 20M bottom bars. Neglecting the top reinforcement, the depth
of the equivalent rectangular stress block is 18 mm and M r = 315 kNm (see Fig. 11.9).
Accounting for the large amount of top reinforcement, the positive moment M r at the column face
is 246 kNm.

Fig. 11.9 Positive and negative moment capacities of beam


CAC Concrete Design Handbook 1117

11.4.4.4 Design of Transverse Reinforcement in Beams


Shear requirements
Determine the shears corresponding to the development of flexural hinging at both ends of
the beam. For the chosen reinforcement at the beam ends the probable moment resistances are:

(i) Probable negative moment resistance, M pr

Using a strain compatibility approach to calculate M pr results in a depth of compression,

c = 95 mm, a stress block depth of 85 mm and M pr = 528 kNm (see Fig. 11.9). Note that the
probable moment resistance of the beams can be estimated by multiplying M r by the ratio
-
1.25 / 0.85 = 1.47 . In this case M pr would be 359 1.47 = 528 kNm. This simple approach is
sufficiently accurate for design purposes.
+
(ii) Probable positive moment resistance, M pr
The factored moment resistance at the ends in span BC is 229 kNm and hence we can
+
estimate the probable moment resistance as M pr = 1.47 229 = 337 kNm. Similarly, the
probable moment resistance at the ends of span AB is 1.47 246 = 362 kNm.
(iii) Determine factored shears
The shear diagrams shown in Fig. 11.10 are drawn for lateral forces acting in the west
direction. For lateral forces acting in the east direction the shear diagrams will be "mirror images"
of those shown (e.g., the shear at B would be 234 kN).

Fig. 11.10 Determinaton of shears corresponding to flexural hinging


1118 Seismic Design

Using = 45 and = 0 gives (Clause 21.3.4.2):


Vr = s Av f y d v / s

At the column faces the transverse reinforcement consists of 410M legs, hence
2
Av = 400 mm .

At the ends A and B the required spacing for shear is:


0.85 400 400 0.9 527
s= = 276 mm
234 1000
At the ends B and C the required spacing for shear is:
234
s= 276 = 247 mm.
262
2
If 2-legged 10M stirrups are used as transverse reinforcement ( Av = 200 mm ) the required
spacings in the middle regions of beams AB and BC are 344 mm and 228 mm, respectively.
Other shear design requirements:
(i) Maximum shear (Clause 11.3.3)
Vr ,max = 0.25 c f c bw d v = 0.25 0.65 30 400 0.9 527 = 925 kN

(ii) Minimum amount of stirrups (Clause 11.2.8.2):


for 4 stirrup legs:
Av f y 400 x 400
s = = 1217 mm
0.06 f c bw 0.06 30 x 400

for 2 stirrup legs:


s 608 mm
(iii) Spacing limits (Clause 11.3.8.3):
Since V f < 0.125 c f c bw d v = 0.125 x 0.65 X 30 x 400 x 0.9 527 = 462 kN

Then s max = 600 mm or 0.7d v = 0.7 0.9 527 = 332 mm.

Note that near the ends of the beams the stirrup spacing required for shear cannot exceed
276 and 247 mm for spans AB and BC, respectively.

"Anti-buckling requirements (Clause 21.3.3.2)


Hoops to prevent buckling of longitudinal bars are required over a length of 2d from the face
of the columns. The spacing of the hoops shall not exceed:
(i) d / 4 = 527 / 4 = 132 mm
(ii) 8d bl = 8 20 = 160 mm
(iii) 24d bh = 24 10 = 240 mm
(iv) 300 mm
Note that the 4-legged arrangement of transverse reinforcement satisfies Clause 21.3.3.3.
Hence use a spacing of 130 mm for 4-legged hoops over a length of at least
2d = 2 527 = 1054 mm.
CAC Concrete Design Handbook 1119

11.4.4.5 Checking Extent of Plastic Hinging


The moment diagrams corresponding to plastic hinging at both ends of beams AB and BC
are shown in Fig. 11.10. Hinging can spread over a distance of about 3.43 m from the face of
column B in beam AB. Since the earthquake loading can reverse, provide 4-legged hoop
reinforcement spaced at 130 mm as shown in Fig. 11.11. The bottom 4-20M bars can only be
spliced near midspan of the beam (Clause 21.3.2.3). Therefore, to satisfy the maximum spacing
requirements of Clause 21.3.2.3 for regions of lap splices, provide 2-legged hoops spaced at 100
mm in the middle region of beam AB (see Fig. 11.11). For span BC, provide 4-legged hoops at a
spacing of 130 mm over a distance of 2d (1054 mm) from the column faces. Outside of these
regions, the provision of 2-legged hoops at a spacing of 100 mm satisfies both the shear
requirements and the confinement requirements for lap splices (see Fig. 11.11).

11.4.4.6 Bar Cut-offs


The locations of bar cut-offs are determined from the moment diagrams corresponding to the
formation of plastic hinges at the ends of the beams. The theoretical cut-off location is located at
a distance of 1.51 m from the face of the column (see Fig. 11.10). From Clause 12.10.4 it is
required to provide an embedment length beyond the theoretical cut-off point of at least d or 12db.
Hence the minimum length required is 1510 + d = 1510 + 527 = 2037 mm. Continue the 620M
top bars a distance of 3 m from the column face such that the bars are terminated in a region of
lower shear. For span BC, extend the 6-20M top bars a distance of 2.0 m from the face of the
column.

11.4.4.7 Splice Details


Flexural reinforcement cannot be spliced within a distance of 2d from the column face nor
within a distance d from of a potential plastic hinge location (Clause 21.3.2.3). In evaluating cut-
off locations, d was taken as 527 mm.
In determining locations of bar cut-offs and splices we will consider the moment diagram
corresponding to the formation of hinges at the ends of the beams (see Fig. 11.10). The splices
for the top bars will be located in a region of the beam where the bars are predicted to remain in
compression. However, as it is required to have a minimum negative and positive moment
resistance at the face of the joint (Clause 21.3.2.2) the splice length will be calculated as for a
tension splice.
(a) Splicing of the 220M "continuous" top bars
The required minimum moment capacity along the length of the beam (Clause 21.3.2.2) is
0.25 359 = 90 kNm. M r for 2-20M top bars is 175 kNm. Hence for the classification of
tension lap splices in accordance with Clause 12.15.2 (As provided)/ As required) is
175 / 90 = 1.94 . Hence Class B splices are required. The development length l d for these top
bars from Table 12-1 is:
fy 400
l d = 0.45k 1k 2 k 3 k 4 d b = 0.45 1.3 1 1 0.8 20 = 684 mm
f c 30
Thus the splice length is 1.3 684 = 890 mm.

(b) Splicing of the 420M "continuous" bars


The development length for these bottom bars is:
fy 400
ld = 0.45k 1k 2 k 3 k 4 d b = 0.45 1 1 1 0.8 20 = 526 mm
f c 30
1120 Seismic Design

Thus the splice length is 1.3 526 = 684 mm.

The details of the reinforcement in the beam are illustrated in Fig. 11.11.

Fig. 11.11 Reinforcement details in beams


CAC Concrete Design Handbook 1121

11.4.5 Design of Interior Ductile Column


To illustrate the procedures involved in designing a column in a ductile moment resisting
frame a typical first storey interior column in Frame 2 or 7 of the building described in Section 11.4
will be designed. The column that will be designed is shown in Fig. 11.12.

Fig. 11.12 Beam-column framing

11.4.5.1 Column End-Actions from Analysis


The column end actions obtained from analysis are summarized in Table 11.6. The
earthquake forces given are those for lateral seismic forces acting in the E-W direction. For the
live load values, pattern loading and live load reduction values were considered.
Table 11.6 Column End Actions
PD PL PE MD ML ME VD VL VE
kN kN kN kNm kNm kNm kN kN kN
nd
2 floor bottom 1598 486 106 +41 +28 147 +20 +13 92
of column
st
1 floor top of 1704 556 137 -53 -37 112 +28 +19 94
column
st
1 floor bottom of 1704 556 137 +32 +22 183 +28 +19 94
column
1122 Seismic Design

11.4.5.2 Factored Axial Loads and Moments


The column must be designed to resist the appropriate combinations of axial load and
moment. From Table 11.6, it is evident that the factored moments at the base of the column will
be larger than that at the top.
For the base of the column at the ground floor level the factored axial load and moment
combinations are given in Table 11.7.

Table 11.7 Factored Axial Load and Moments at Column Bases

Case 1 Case 2 Case 3 Case 4 Case 5


1.25D 1.0D 1.0D 1.0D+0.5L 1.0D+0.5L
+1.5L +1.0E -1.0E +1.0E -1.0E

Pf -2964 -1841 -1567 -2119 -1845


kN

Mf +73 +216 -151 +226 -140


kNm

Note that for this member Ag fc / 10 = (500 500 ) 30 / 10 = 750 kN. As Pf exceeds this
value, the requirements of Clause 21.4 apply (Clause 21.4.1.1).

11.4.5.3 Preliminary Selection of Column Reinforcement


In selecting the column bars, recall that the diameter of these bars must satisfy the
requirements that d b l j / 24 = 600 / 24 = 25 mm (Clause 21.5.5.6) for this normal density
concrete and for uncoated bars. Hence the maximum bar size is 25M. Try using 8-25M bars as
shown in Fig. 11.13.

Fig. 11.13 Column reinforcement details


2
For this arrangement of reinforcement Ast = 8 500 = 4000 mm . From Clause 21.4.3.1
2
the minimum area of longitudinal steel is 0.01 500 500 = 2500 mm and the maximum area of
longitudinal steel outside of lap splice regions (assuming lap splicing with an equal area of steel)
2
is 0.03 500 500 = 7500 mm . Hence this steel arrangement satisfies these requirements.
CAC Concrete Design Handbook 1123

Checking Column Capacity


The axial load-moment interaction diagram for the chosen column section is shown in Fig.
11.14. It can be seen that the column has adequate capacity to resist the various combinations of
Pf and M f which occur at the base of the column.

Fig. 11.14 Pr - M r interaction diagram for column section

Although there is a considerable excess of moment capacity in the column, this additional
capacity is needed at the top of the column in order to ensure that the columns are stronger than
the beams (see below).

11.4.5.4 "Strong Column - Weak Beam" Requirement


The flexural capacity of the columns must exceed the flexural capacity of the beams so that

M nc M pb

Hence it is necessary to first determine the probable resistances of the beams framing into the
column.
1124 Seismic Design

(a) Probable negative moment resistance, M pb

Note that the probable resistance, M pb , can be approximated as
1.47M r = 1.47 359 = 528 kNm. This simple approach is sufficiently accurate for design
purposes as can be seen from Fig. 11.9.
+
(b) Nominal positive moment resistance, M pb
+
M pb = 1.47 246 = 362 kNm.

(c) Determination of M nc

To determine M nc for a particular loading case we need to calculate the nominal moment
resistance of the column above and below the beam-column joint. The lowest flexural resistance
will occur at either the highest or lowest axial load, that is, load cases 3 and 4 need to be
investigated (load case 1 does not involve lateral load). The axial load corresponding to cases 3
and 4 are given in Fig. 11.15 along with the column nominal moment resistances corresponding to
these axial loads (from the P-M interaction diagram).

Fig. 11.15 Capacity design of columns and factored loads on column

Thus the requirement that M nc M pb is satisfied. Note that for simplicity the above
calculations have neglected the influence of the beam and column shears acting at the joint faces.

11.4.5.5 Design of Transverse Reinforcement in Column


Shear requirements
The column must have a factored shear resistance, Vr, which exceeds the column shear
corresponding to the probable moment resistance in the beams and which exceeds the shear
CAC Concrete Design Handbook 1125

forces due to factored loads (Clause 21.4.5.1). From Table 11.6, load case 4 (1.0D + 0.5L + 1.0E )
gives the maximum factored shear of 132 kN.
The moment at the top of the column corresponding to the development of the probable
moment resistances of the beams may be estimated from:

( +
M c = M pr
+ M pr)
Kc
= (362 + 528 )
1 / 3.05
= 445 kNm
Kc 2 1 / 3.05

However since we are designing a ground storey column a different approach is required at
the base of this column. It is assumed that the column frames into a substructure that is
considerably stronger and stiffer than the column and hence the possibility of hinging at the
column base must be accounted for. To ensure adequate column shear capacity, it is necessary
to determine the maximum probable moment resistance corresponding to all axial loads.
Because the axial loads for all the seismic load cases are close to the balanced axial load level,
the moment at the base of the column will be taken as the probable moment resistance
corresponding to the balanced loading conditions (i.e., the highest probable moment resistance
possible). The calculations involved in determining this moment resistance are summarized in
Fig. 11.16.

Fig. 11.16 Determination of factored shear strength in ground storey column


1126 Seismic Design

The column actions which will correspond to the formation of hinges in the beams at the top
of the column and the formation of a hinge at the base of the column are shown in Fig. 11.16.
From Clause 21.4.5.2 the shear carried by the concrete is determined with values of and
taken from Clause 11 but limited to a maximum of 0.10 and a minimum of 45, respectively.
For this column containing greater than minimum amounts of transverse reinforcement and
subjected to axial compression, Clause 11.3.6.3 applies, but the limits for and given above
control. The shear resistance attributed to the concrete, assuming that d v = 0.72h , is:

Vc = c f c bw d v = 0.65 0.10 30 500 0.72 500 = 64.1 kN

The required Vs is equal to 359 64.1 = 294.9 kN. Using the transverse reinforcement
arrangement shown in Fig. 11.13 with square and diamond shaped hoops, the effective area of
( ) 2
shear reinforcement is Av = 2 + 2 cos 45 o 100 = 3.41 100 = 341 mm . Hence, the required
stirrup spacing can be found from Equation (11-7) as:
s Av f y d v cot 0.85 341 400 0.72 500 cot 45 o
s= = = 142 mm
Vs 294.9 1000

Since Vf of 359 kN is less than 0.125 c fcbw d v = 439 kN, then from Clause 11.3.8.1, the
maximum spacing of the shear reinforcement is the smaller of 0.7 0.72 500 = 252 mm or
600 mm.
In order to satisfy the minimum shear reinforcement requirements of Clause 11.2.8.2, the
maximum spacing of the 10M stirrups is:
Av f y 341 400
s= = = 830 mm
0.06 f c bw 0.06 30 500

Therefore for shear a spacing of 142 mm controls.

(b) Confinement requirements


Since the column under consideration is at the base of the structure confinement
reinforcement must be provided over the full height of the column (Clause 21.4.4.6).
From Clause 21.4.4.2, the total cross-sectional area of rectangular hoop reinforcement
depends on the following factors:
nl 8
kn = = = 1.33
nl 2 8 2

( ) ( )
Po = 1fc Ag Ast + fy Ast = 0.805 30 500 2 4000 + 400 4000 = 7541 kN
k p = Pf / Po = 2119 / 7541 = 0.281
Hence, the total area of confinement reinforcement is:
Ag f c 500 2 30
Ash = 0.2k n k p shc = 0.2 1.33 0.281 2
420s = 3.34s
Ach f yh 420 400
but not less than:
f c 30
Ash = 0.09shc = 0.09 420 s = 2.84s
f yh 400
2
For Ash = 341 mm , s = 341 / 3.34 = 102 mm.
CAC Concrete Design Handbook 1127

From Clause 21.4.4.3 the spacing of the hoops shall not exceed:
(i) h / 4 = 500 / 4 = 125 mm
(ii) 6d b = 6 25 = 150 mm

(iii) s x = 100 + (350 hx ) / 3 = 100 + (350 187.5 ) / 3 = 154 mm

Hence use 10M hoops at 100 mm centres as shown in Fig. 11.17. The chosen arrangement
of hoops and longitudinal reinforcement also satisfies Clauses 21.4.4.4 and 7.6.5. The details of
the first-storey column reinforcement are given in Fig. 11.17.

Fig. 11.17 Details of reinforcement in first-storey column


1128 Seismic Design

11.4.5.6 Splice Details


We will splice the column bars at mid-height of the column with tension lap splices in
accordance with Clause 21.4.3.2. The development length, l d , can be found from Table 12-1 as:
fy 400
l d = 0.45k 1k 2 k 3 k 4 d b = 0.45 1 1 1 1 25 = 822 mm
f c 30
Provide a lap length of 1.3l d = 1.3 822 = 1068 mm (see Fig. 11.17).

11.4.6 Design of Interior Beam-Column Joint


To illustrate the procedures involved in designing a beam-column joint in a ductile moment-
resisting frame, an interior joint in the structure described in Section 11.4 will be designed. A
description of the joint details is given in Fig. 11.18.

Fig. 11.18 Geometry of interior beam-column joint

11.4.6.1 Determination of Factored Forces in Joint


In accordance with Clause 21.5.1.2, assume that the tensile force in the beam reinforcement
is 1.25 As f y .
CAC Concrete Design Handbook 1129

To estimate the corresponding shear, Vcol , in the column above the joint, assume that
flexural hinging occurs in the beams at the first and second storey levels. The calculations are
summarized in Fig. 11.19.

Fig. 11.19 Determination of factored shear resistance in joint


1130 Seismic Design

11.4.6.2 Check Factored Shear Resistance of Joint


Since four equal depth beams frame into the joint and each covers more than 3/4 of each
face of the joint, the joint is considered to be externally confined (Clause 21.5.4.1). Hence the
factored shear resistance of the joint is taken as:
V r = 2.2 c f c A j = 2.2 0.65 30 500 500 = 1958 kN
As the design shear in the joint of 1408 kN is less than 1958 kN, the shear resistance of the
joint is adequate.

11.4.6.3 Transverse Reinforcement Required in Joint


As the joint is framed by four equal depth beams which provide confinement, only one-half of
the confinement steel required for the column is required through the joint (Clause 21.5.2.2). The
spacing required for confinement in the joint is therefore 200 mm. However the spacing limits of
Clause 21.4.4.3 control ( s max = h / 4 = 125 mm). Hence provide 3 sets of 10M hoops between
the flexural bars in the beams as shown in Fig. 11.20.

Fig. 11.20 Details of joint reinforcement


CAC Concrete Design Handbook 1131

11.4.6.4 Bond of beam Bars


As the beam bars pass through the joint their bond characteristics are checked by the
requirement in Clause 21.5.5.6 that the bar diameters be not greater than
l j / 24 = 500 / 24 = 21 mm (normal density concrete and uncoated bars). Since this exceeds the
actual bar diameter of 20 mm this requirement is met.

11.5 Analysis of a Ductile Core-Wall Structure


11.5.1 Description of Building and Loads
The twelve-storey reinforced concrete building shown in Fig. 11.21 is located in Montreal and is
founded on stiff soil.

Fig. 11.21 Plan and elevation of twelve-storey office building


1132 Seismic Design

The twelve-storey reinforced concrete office building has a centrally located elevator core.
Each floor consists of a 200 mm thick flat plate with 6 m interior spans and 5.5 m end spans. The
columns are all 550 x 550 mm and the thickness of the core wall components 400 mm. The 400
mm thick wall thickness was initially chosen such that it exceeds l u / 14 = 4650 / 14 = 332 mm
(Clause 21.6.3). This value is checked in Section 11.5.6.5. The core wall measures 6.4 m by 8.4
m, outside to outside of the walls. Two 400 mm wide x 900 mm deep coupling beams connect the
two C-shaped walls at the ceiling level of each floor. The core walls extend one storey above the
th th
roof at the 12 floor level forming an elevator penthouse at the 13 floor level. The slab has a 100
mm overhang.

Material Properties
Concrete: normal density concrete with fc = 30 MPa
Reinforcement: f y = 400 MPa

Gravity and Wind Loadings


2
Floor live load: 2.4 kN/m on typical office floors
2
4.8 kN/m on 12 m by 12 m corridor area around core
2
Roof load: 2.2 kN/m full snow load
2
1.6 kN/m mechanical services loading in 6 m wide strip over corridor bay
3
Dead loads: self-weight of members calculated at 24 kN/m
2
1.0 kN/m partition loading on all floors
2
0.5 kN/m ceiling and mechanical services loading on all floors
2
0.5 kN/m roofing
2
Wind loading: varies from 1.1 to 1.37 kN/m net lateral pressure over the height of the building

The building is to be designed with a fire-resistance rating of 2 hours.

11.5.2 Analysis Assumptions


To determine the forces in the walls and the coupling beams and the periods of vibration, the
three-dimensional core wall system was analyzed using ETABS. To make allowances for
cracking, member stiffnesses were based on effective properties equal to 0.25I g for the moment
of inertia and 0.45 Ag for the shear area for all diagonally reinforced coupling beams as required
by Clause 21.2.5.2.1. The walls were modeled with an effective flexural stiffness of 0.7EI g and an
effective axial stiffness of 0.7EAg , determined as a function of the axial loading at the base of the
walls (see Clause 21.2.5.2.1).

11.5.3 Seismic loading


For the force modification factors, Rd and Ro , we will assume that the core-wall system will
take 100% of the lateral loads as allowed by the NBCC. In the N-S direction we will design and
detail the walls as ductile shear walls and hence Rd = 3.5 and Ro = 1.6 . In the E-W direction we
will design and detail the coupling beams and walls as a ductile coupled wall system and hence
Rd = 4.0 and Ro = 1.7 . In order for the E-W direction to qualify as a ductile coupled wall system
we must check the degree of coupling as determined by analysis of the structure.
CAC Concrete Design Handbook 1133

11.5.3.1 Minimum Lateral Earthquake Force


The structure is located in Montreal and is founded on stiff soil. Therefore the site
classification is D. The acceleration-based site coefficient Fa = 1.124 and the velocity-based site
coefficient Fv = 1.360 . The seismic response factor, S (Ta ) , is dependent on the fundamental
period, Ta , of the structure. The 5% damped spectral response accelerations, Sa (T ) , for Montreal
are given in Table 11.8. Table 11.8 also gives the design spectral response accelerations, S (T ) ,
obtained from the product of the site coefficients and S a as shown in Fig. 11.22.

Table 11.8 Spectral response accelerations and design spectral response accelerations

T 0.2 T = 0.5 T = 1.0 T = 2.0 T 4.0


Sa (T ) 0.69 0.34 0.14 0.048 0.024

S (T ) 0.776 0.462 0.190 0.065 0.033

Figure 11.22 Design spectral response acceleration

The empirical fundamental lateral period, Ta , for this shear wall structure in the N-S and E-W
directions, is given by:
Ta = 0.05hn3 / 4 = 0.05 45.0 3 / 4 = 0.869 s

N-S Direction
The calculated period for this structure in the N-S direction, using the computer program
ETABS, is 1.83 s. Note that a 3-D model including the walls, the slabs and the columns was also
analysed and resulted in a period of 1.75 s. Because this period is within 15% of the periods of the
walls alone, then a period of 1.83 s was used.
The value of the fundamental lateral period cannot be taken greater than 2 0.869 = 1.74 and
hence use Ta = 1.74 s. From linear interpolation, S (Ta ) = 0.0981 (see Fig. 11.22).
The values of M v and J depend on the ratio of Sa (0.2) / Sa (2.0 ) = 0.69 / 0.048 = 14.4 and the
value of Ta . It is necessary to interpolate the value of S (Ta ) Mv and the value of J between periods of
1.0 and 2.0 s and 0.5 and 2.0 s, respectively. This interpolation results in S (Ta ) Mv = 0.170 ,
Mv = 1.736 and J = 0.505 .
1134 Seismic Design

This office building has an earthquake importance factor, I E = 1.0 . For this ductile shear wall
Rd = 3.5 and Ro = 1.6 .
Hence the seismic base shear, V, is:
S (Ta ) Mv IEW 0.0981 1.736 1.0 W
V = = = 0.0304W
Rd Ro 3.5 1.6

S (2.0 ) Mv I EW 0.0653 2.5 1.0 W


Vmin = = = 0.0291W
Rd Ro 3.5 1.6

2 S (0.2)IEW 2 0.7756 1.0 W


Vmax = = = 0.0923W
3 Rd Ro 3 3.5 1.6

For this structure, W = 90590 kN.


Hence V = 0.0304W = 0.0304 90590 = 2756 kN.
The portion of V concentrated at the top of the building is
Ft = 0.07TaV = 0.07 1.737 2755.6 = 335 kN, but need not be taken greater than
0.25V = 0.25 2755.6 = 688.9 kN.
The calculations of the seismic lateral forces at each floor level are summarized in Table
11.9.

E-W Direction
The calculated period for this structure in the E-W direction, using the computer program
ETABS is 1.72 s. It is noted that this period may be used because the period for the full 3-D
structure (walls, slabs and columns) is within 15% of this value. The value of the fundamental
lateral period cannot be taken greater than 2 0.869 = 1.74 and hence use Ta = 1.72 s. From
linear interpolation, S (Ta ) = 0.101 (see Fig. 11.22).
It is necessary to interpolate the value of S (Ta ) Mv and the value of J between periods of 1.0
and 2.0 s and 0.5 and 2.0 s, respectively. This interpolation results in S (Ta ) Mv = 0.110 ,
Mv = 1.093 and J = 0.757 .
For the ductile coupled wall system in the E-W direction Rd = 4.0 and Ro = 1.7 .
Hence the seismic base shear, V, is:
S (Ta )Mv IEW 0.101 1.093 1.0 W
V = = = 0.0162W
Rd Ro 4.0 1.7

S (2.0 ) Mv I EW 0.065 1.2 1.0 W


Vmin = = = 0.0115W
Rd Ro 4.0 1.7

2 S (0.2)IEW 2 0.776 1.0 W


Vmax = = = 0.0760W
3 R d Ro 3 4.0 1.7

For this structure W = 90590 kN.


Hence V = 0.0162W = 0.0162 90590 = 1466 kN.
The portion of V concentrated at the top of the building is
Ft = 0.07TaV = 0.07 1.72 1466 = 176.2 kN, but need not be taken greater than
0.25V = 0.25 1466 = 366.5 kN.
CAC Concrete Design Handbook 1135

The calculations of the seismic lateral forces at each floor level using the equivalent static
force procedure are summarized in Table 11.9. The weight of the penthouse has been included
at the roof level.

Table 11.9 Lateral Load Calculations for Each Floor Level

Floor hi , Wi , hi Wi , N-S E-W


m kN kNm Fx Tx Fx Tx
12 45.00 8154 366930 727.1 2163 385.1 1146
11 41.35 7467 308761 329.8 981 175.8 523
10 37.70 7467 281506 300.7 895 160.3 477
9 34.05 7467 254251 271.6 808 144.7 431
8 30.40 7467 226997 242.5 721 129.2 384
7 26.75 7467 199742 213.4 635 113.7 338
6 23.10 7467 172488 184.3 548 98.2 292
5 19.45 7467 145233 155.2 462 82.7 246
4 15.80 7467 117979 126.0 375 67.2 200
3 12.15 7467 90724 96.9 288 51.7 154
2 8.50 7467 63470 67.8 202 36.1 108
1 4.85 7766 37665 40.2 120 21.4 64
0
Total 90590 2265745 2756 8198 1466 4362

11.5.3.2 Accidental Torsion


The 3-D model shown in Fig. 11.23 was used to calculate accidental torsional effects by
applying the lateral forces Fx (see Table 11.9) at an accidental eccentricity of 0.1Dnx , where
Dnx is the plan dimension of the building at level x, perpendicular to the direction of seismic
loading. This gives an accidental torsional eccentricity of 2.975 m, from the centre of mass (same
as centre of rigidity) for loading in the N-S and E-W directions. The values of Tx are given in
Table 11.9.
The structure was analysed with a 3-D model of the core-wall structure for both wind and
seismic loading, with and without eccentricity. In these analyses the participation of the flat plate
and columns was neglected.

11.5.3.3 Degree of Coupling


In the calculations of the base shear it was assumed that there was sufficient coupling of the
walls in the E-W direction to qualify this wall system as a ductile coupled wall system rather than a
partially coupled wall system. To check the degree of coupling by the wall system in the E-W
direction, the base overturning moment resisted by axial tension and compression forces in the
walls (resulting from shear in the coupling beams), divided by the total base overturning moment
is determined. Although the design forces were obtained from dynamic analysis, it is not
1136 Seismic Design

appropriate to use these values to determine the degree of coupling because the values obtained
from modal combination (e.g., SRSS or CQC) does not satisfy static equilibrium. The degree of
coupling was determined using static analysis with the Fx forces from the equivalent static force
procedure, giving:

Tl 5513 6.5
= = 0.74
M1 + M 2 + Tl 2 6400 + 5513 6.5

where
T = axial tension and compression acting at centroid of coupled walls
l = distance between centroids of coupled walls, equal to 6.5 m for this example

The degree of coupling is 74%, which is exceeds the minimum limit for ductile coupled walls of
66%. Hence Rd = 4.0 and Ro = 1.7 , as assumed above.

11.5.3.4 Check on Structural Irregularity


To determine if the structure is sensitive to torsion, the values of B need to be determined at
all levels from the maximum and average displacements of the structure at in the E-W and N-S
directions. The maximum value, B (determined at the extreme points of the structure), in the N-S
direction occurs in the first storey, with a displacement due to accidental torsion of 1.04 mm and a
displacement due to Fx of 1.30 mm. Hence:

max 1.04 + 1.30


B= = = 1.80
ave 1.30

Because B is greater than 1.7, the structure is sensitive to torsion and hence is designated as
irregular. The maximum value of B in the E-W direction occurs in the first storey and is 1.66.
Note that a 3-D analysis of the structure, including the columns and slabs as well as the
actual mass distributions indicates that the first and fourth modes of vibration are torsional with
periods of 1.89 and 0.54 s, respectively. This confirms that the structure is indeed torsionally
sensitive.
This design example illustrates the steps necessary to design this common type of structure,
that is torsionally sensitive.

11.5.3.5 Dynamic Analysis


The NBCC requires that the Dynamic Analysis Procedure be used except that the Equivalent
Static Force Procedure may be used for structures that meet any one of the three conditions in
parts (a), (b) and (c) of Clause 4.1.8.7. For this building, the term I E FaSa (0.2 ) is greater than 0.35
and hence the condition in part (a) is not satisfied. The presence of the structural irregularity due
to torsion sensitivity means that the Equivalent Static Force Procedure cannot be used (part (b) of
4.1.8.7). Part (c) of 4.1.8.7 is also not satisfied. Accordingly, the Equivalent Static Force
Procedure is not permitted as an alternative to the Dynamic Analysis Procedure for this example
building. The first step is to determine Ve from a linear dynamic analysis. The design base shear
Vd is obtained from:

Ve
Vd = IE
Rd Ro
CAC Concrete Design Handbook 1137

Because this is an irregular structure, that requires dynamic analysis (NBCC 4.1.8.7), Vd shall not
be taken less than 1.0V rather than 0.8V , permitted for a regular structure.
All forces and deflections obtained from the linear dynamic analysis are scaled by the factor
Vd / Ve to obtain the design values. However, in order to obtain realistic values of anticipated
deflections and drifts, the design values need to be multiplied by R d R o / I E .
Fig. 11.23 shows the 3-D ETABS model that considers only the core wall system (SFRS) and
is used for the dynamic analysis. The second model used is the entire structure including the
frame members not considered part of the SFRS (columns and the slabs) to check the ductility
and strength of these members subjected to seismically induced deformations. The total mass for
each floor was concentrated at the centre of mass (same as centre of rigidity for this example)
and rigid diaphragms were assumed at each floor level. Sway effects (P-Delta) were included
using the ETABS program option. For this analysis, compressive loads on the walls were obtained
from the consistent loading case of 1.0D + 0.5L + 0.25S , with live load reduction factors.
The first three lateral modes in the N-S and E-W directions are shown in Fig. 11.24, together
with the associated periods of vibration and the modal participating mass ratios. Note that the sum
of these ratios is 94.9% and 93.8% of the total mass in the N-S and E-W directions, respectively.
These ratios exceed the minimum required ratio of 90% of the total mass (NBCC). Spectral modal
superposition, using SRSS for the first three modes in the both directions was used to determine
all forces and deformations.
The base shear in the N-S direction determined by dynamic analysis is Ve = 14159 kN.
Therefore:
1.0
Vd = 14159 = 2528 kN
3.5 1.6

However for this irregular building Vd shall not be taken less than V = 2755.6 kN. Hence, all
forces and deflections obtained from the dynamic analysis shall be multiplied
byVd / Ve = 2755.6 / 14159 = 0.195 in the N-S direction.
The base shear in the E-W direction determined by dynamic analysis is Ve = 11021 kN.
Therefore:

1.0
Vd = 11021 = 1621 kN
4.0 1.7

However for this irregular building Vd shall not be taken less than V = 1466.1kN. Hence, all
forces and deflections obtained from the dynamic analysis shall be multiplied by
Vd / Ve = 1621 / 11021 = 0.147 in the E-W direction.
1138 Seismic Design

Figure 11.23 3-D Model used for dynamic analysis


CAC Concrete Design Handbook 1139

Mode 1 Mode 2 Mode 3


T = 1.830 T = 0.339 T = 0.143
MPMR = 0.67 MPMR = 0.22 MPMR = 0.07

(a) N-S direction

Mode 1 Mode 2 Mode 3


T = 1.717 T = 0.435 T = 0.199
MPMR = 0.72 MPMR = 0.17 MPMR = 0.05

(b) E-W direction

Figure 11.24 Mode shapes, corresponding lateral periods of vibration and modal
participating mass ratios in the N-S and E-W directions
1140 Seismic Design

11.5.3.6 Deflections and Drift Ratios


The deflections obtained from the dynamic analysis are multiplied by the factor 0.195 in the
N-S direction and 0.147 in the E-W direction. To account for the total anticipated displacements,
including the inelastic effects it is necessary to multiply these deflections by the factor R d R o / I E
Vd Rd Ro
to obtain the design values. Note that the factor is equal to 1.0 unless Vd is controlled
Ve I E
by the value of V , as in the N-S direction in this example (see 11.5.3.5). The deflections obtained
from dynamic analysis include P-Delta effects. The deflections arising from accidental torsional
eccentricity are added to the deflections from the dynamic analysis.
The maximum total interstorey drift in the N-S direction occurs in the eighth storey. From the
dynamic analysis the interstorey drift in this storey is 0.00060 and the interstorey drift from
accidental torsion at this level is 0.00041, for a maximum interstorey drift of 0.0010. Therefore the
anticipated interstorey drift, including inelastic effects, is 0.0010 3.5 1.6 / 1.0 = 0.0056 .
Similarly the maximum anticipated interstorey drift in the E-W direction is 0.0047. These
anticipated maximum interstorey drift ratios are less than the NBCC limit of 0.025.

11.5.4 Design Forces


The results from the 3-D analyses for both seismic and wind loading are summarized in
Tables 11.10, 11.11, 11.12 and 11.13. It is noted that for wind loading, the case with eccentric
wind loading does not govern. Table 11.10 gives the forces from seismic loading analysis in the
N-S direction, without and with accidental torsion effects.
Table 11.11 gives the forces from seismic loading analysis in the E-W direction, without
accidental torsion effects.
Table 11.12 gives the forces from accidental torsion due to seismic loading analysis in the E-
W direction. It is noted that accidental torsion is resisted by shear flow around the components of
the C-shaped walls and by shear in the coupling beams. The accidental torsion does not create
any global moments, axial loads or shears in the C-shaped walls, but results in local moments,
axial loads and shears in the component parts, AB, BC and CD (see Fig. 11.27).
CAC Concrete Design Handbook 1141

Table 11.10 Results of Seismic Loading Analyses (1.0E) in N-S direction for one wall,
including accidental torsion

Storey Wall moment Wall moment Wall shear Wall shear


without with without with
torsion, torsion, torsion, torsion,
kNm kNm kN kN
13 top 0 492 0 114
13 bot 0 907 0 114
12 top 0 1503 406 509
12 bot 1484 2611 406 509
11 top 1484 3297 605 787
11 bot 3689 4839 605 787
10 top 3689 5623 647 898
10 bot 6022 7040 647 898
9 top 6022 7922 589 902
9 bot 8037 8797 589 902
8 top 8037 9767 518 886
8 bot 9504 9890 518 886
7 top 9504 10931 515 934
7 bot 10391 10494 515 934
6 top 10391 11375 596 1062
6 bot 10831 11548 596 1062
5 top 10831 11212 738 1249
5 bot 11097 12582 738 1249
4 top 11097 11514 923 1478
4 bot 11647 14090 923 1478
3 top 11647 13107 1119 1719
3 bot 13033 16685 1119 1719
2 top 13033 15859 1283 1943
2 bot 15567 20803 1283 1943
1 top 15567 20210 1378 2057
1 bot 20396 28332 1378 2057
1142 Seismic Design

Table 11.11 Results of Seismic Loading Analyses (1.0E) in E-W direction (Coupled Wall)
for one wall

Storey Wall Wall Wall Coupling Coupling


moment, axial shear, beam beam
kNm load, kN shear shear with
kN without torsion,
torsion, kN
kN
13 top 452 139 0 69.6 113.0
13 bot 452 139 0
12 top 1078 332 252 96.3 149.0
12 bot 309 332 252
11 top 1086 596 390 132.2 192.8
11 bot 618 596 390
10 top 945 913 441 159.5 228.9
10 bot 1135 913 441
9 top 1019 1251 438 173.6 251.6
9 bot 1515 1251 438
8 top 1280 1583 430 179.3 265.1
8 bot 1720 1583 430
7 top 1527 1895 440 184.6 276.7
7 bot 1815 1895 440
6 top 1708 2188 466 194.6 290.7
6 bot 1859 2188 466
5 top 1826 2469 508 210.2 307.4
5 bot 1860 2469 508
4 top 1820 2753 581 228.9 323.3
4 bot 1889 2753 581
3 top 1597 3047 678 242.9 329.8
3 bot 2205 3047 678
2 top 1303 3341 764 237.3 310.4
2 bot 3090 3341 764
1 top 1957 3588 810 191.8 244.3
1 bot 5577 3588 810
CAC Concrete Design Handbook 1143

Table 11.12 Local forces due to accidental torsion (1.0E) in E-W direction (Coupled Wall
Direction) in different components of C-shaped wall

Wall component AB or CD ( ) Wall component BC ( )


Storey 3.2 m long segments 6.4 m long segment
Moment, Axial Shear, Moment, Axial Shear,
kNm load, kN kNm load, kN
kN kN
13 top 90.4 -58.0 -36.9 -81.1 0.0 58.2
13 bot -44.4 -58.0 -36.9 131.3 0.0 58.2
12 top 115.0 -94.9 -55.3 232.9 0.0 -55.6
12 bot -86.8 -94.9 -55.3 30.2 0.0 -55.6
11 top 142.0 -106.4 -70.0 330.6 0.0 -97.9
11 bot -113.5 -106.4 -70.0 -26.6 0.0 -97.9
10 top 168.2 -105.9 -84.5 398.0 0.0 -134.7
10 bot -140.2 -105.9 -84.5 -93.7 0.0 -134.7
9 top 191.0 -95.3 -97.8 442.9 0.0 -167.7
9 bot -165.9 -95.3 -97.8 -169.1 0.0 -167.7
8 top 209.9 -75.6 -109.4 468.1 0.0 -197.3
8 bot -189.6 -75.6 -109.4 -252.1 0.0 -197.3
7 top 224.2 -47.1 -119.1 475.1 0.0 -224.4
7 bot -210.6 -47.1 -119.1 -343.8 0.0 -224.4
6 top 233.2 -9.0 -126.5 464.1 0.0 -249.4
6 bot -228.4 -9.0 -126.5 -446.1 0.0 -249.4
5 top 235.9 40.1 -131.0 433.9 0.0 -273.0
5 bot -242.4 40.1 -131.0 -562.7 0.0 -273.0
4 top 231.0 102.9 -132.3 382.1 0.0 -296.3
4 bot -251.8 102.9 -132.3 -699.3 0.0 -296.3
3 top 217.2 183.4 -129.8 304.9 0.0 -319.7
3 bot -256.7 183.4 -129.8 -861.8 0.0 -319.7
2 top 189.4 286.1 -118.7 190.8 0.0 -350.8
2 bot -243.9 286.1 -118.7 -1089.6 0.0 -350.8
1 top 221.8 457.3 -120.2 248.5 0.0 -359.1
1 bot -361.0 457.3 -120.2 -1493.1 0.0 -359.1
1144 Seismic Design

Table 11.13 Results of Wind Loading Analyses (1.4W)

N-S E-W Direction


Storey Direction (Coupled Wall Direction)
Wall Wall Wall axial Coupling beam
moment, moment, load, shear,
kNm kNm kN kN
13 top 0 159 49 24.5
13 bot 0 159 49
12 top -74 444 119 38.9
12 bot 122 178 119
11 top 47 633 241 64.4
11 bot 577 72 241
10 top 503 735 426 95.7
10 bot 1287 -84 426
9 top 1212 800 679 128.8
9 bot 2263 -281 679
8 top 2190 827 1001 162.5
8 bot 3498 -508 1001
7 top 3427 819 1391 195.5
7 bot 4990 -767 1391
6 top 4923 770 1845 227.0
6 bot 6734 -1060 1845
5 top 6672 665 2358 255.5
5 bot 8726 -1402 2358
4 top 8670 473 2918 278.3
4 bot 10962 -1823 2918
3 top 10915 130 3504 290.5
3 bot 13433 -2385 3504
2 top 13396 -496 4073 281.5
2 bot 16161 -3233 4073
1 top 16136 -1669 4546 233.3
1 bot 20087 -5599 4546

The design forces for both seismic and wind loading are given in Fig. 11.25. The distribution
of wall moments for wind loading is typical for a coupled wall system. The distribution of wall
moments for seismic loading was obtained from modal combinations (SRSS) and therefore the
moments obtained are absolute values.
CAC Concrete Design Handbook 1145

Fig. 11.25 Results of analyses for seismic and wind loading

11.5.5 Design of Coupling Beams


11.5.5.1 Design Forces for Coupling Beams
The maximum coupling beam shear due to factored wind loading is 290.5 kN and due to
earthquake effects (including accidental torsion) is 329.8 kN. Hence the seismic loading case
governs the design of the coupling beams. These maximum shears occur in the coupling beams
in the third storey (see Tables 11.11 and 11.13).
In designing the coupling beams we can account for redistribution of moments between the
beams and hence the factored shear resistance required for earthquake loading would be the
sum of the shears in the coupling beams divided by the number of coupling beams. This would
require a factored shear resistance of 3283 / 13 = 252.5 kN for seismic loading.
The coupling beams have a depth of 900 mm and a clear span of 2000 mm and hence
satisfy the dimensional limitation that the depth must not be greater than twice the clear span
(Clause 21.6.8.5). The ductile coupling beams must be designed with diagonal reinforcement,
rather than longitudinal bars and vertical hoops, because the clear span of each beam is not equal
to or greater than four times the effective depth (see Clauses 21.6.8.6 and 21.3.1.1).
Since the design torsions arise only from accidental torsional eccentricity, which can act in
either direction, the same coupling design forces and beam details will be used on the north and
south sides of the core wall.
1146 Seismic Design

11.5.5.2 Design and detailing of coupling beams


Fig. 11.26 shows the details of the diagonal reinforcement in a coupling beam. From the
geometry of the reinforcement, the angle between the centroidal axis of one set of diagonal
bars and the horizontal is 19.4.

Fig. 11.26 Coupling beam reinforcing details

If 4-20M bars are provided in each set of diagonal bars then the factored shear resistance is:
Vr = 2s As fy sin = 2 0.85 4 300 400 sin 19.4 = 271.0 kN
If this reinforcement is placed in the lower storeys, then a moment redistribution of 17.8%
would be required in the coupling beam with maximum moment due to seismic loading and 6.7%
redistribution would be required for wind loading. Clause 9.2.4 permits a moment redistribution up
to 20%.
The diagonal reinforcement must have closely spaced hoops as required in Clause 21.6.8.7
with a maximum spacing given by the smaller of:
(a) 6d bl = 6 20 = 120 mm
(b) 24d bh = 24 10 = 240 mm
(c) 100 mm
CAC Concrete Design Handbook 1147

Hence use 10M hoops spaced at 100 mm.


The diagonal reinforcement must extend into the wall at each end a minimum distance of
1.5l d = 1.5 526 = 789 mm. Hence use an embedment length of 800 mm. In addition to the
diagonal reinforcement, provide minimum transverse and longitudinal reinforcement, as shown in
Fig. 11.26, but only in the clear span of the beam.
Although a designer might choose to use the same coupling beams details, with 4-20M
diagonal bars, over the full height of this building, reducing the amount of reinforcement in the
coupling beams near the top of the structure is advantageous whenever possible. This approach
is illustrated below.
If the reinforcement in the coupling beams is reduced to 4-15M near the top of the structure,
then the factored resistance per beam is:
Vr = 2s As fy sin = 2 0.85 4 200 400 sin 19.4 = 180.7 kN.
The beams with 4-15M bars would require a hoop spacing of 90 mm.
Provide coupling beams with 4-20M bars for storeys 1 to 11 and beams with 4-15M bars for
the top two coupling beams. This arrangement gives a total shear capacity of the 13 beams of:

V r = 11 271.0 + 2 180.7 = 3342 kN

This shear resistance of the thirteen coupling beams exceeds the required shear resistance of
3283 kN.
Hence provide diagonally reinforced coupling beams with 4-20M for the first 11 storeys and
beams with 4-15M diagonal bars for the top two coupling beams.

11.5.5.3 Ductility of coupling beams


The inelastic rotational capacity of the coupling beams must be greater than the rotational
demand. The rotational demand is given by (Clause 21.6.8.4):
f Rd Ro l cg 0.019 4.0 1.7 6.5
id = = = 0.0093
hw lu 45.0 2.0
The rotational capacity of diagonally reinforced coupling beams (Clause 21.6.8.4) is 0.04.
Hence the coupling beams have sufficient ductility.

11.5.6 Design of Ductile Walls


11.5.6.1 Design Forces in E-W Direction
The design forces in the walls are determined from a capacity design approach. It is desired
that the walls be strong enough such that flexural hinging occurs in the coupling beams, which are
the primary energy dissipators of the structural system. In order to determine the design forces in
the walls we will consider a push-over type of loading on the coupled wall system. For this
analysis it is required that the factored resistance of the walls be at least equal to the moment
corresponding to the development of flexural hinging in the beams.
The push-over approach used for this twelve-storey coupled wall structure provides a
conservative design approach to the requirements of Clause 21.6.8.12. For taller coupled wall
structures the provisions of Clause 21.6.8.12 should be used.
The nominal shear resistance, Vn , for the coupling beam containing 4-20M diagonal
reinforcing bars is:
Vn = 2s As f y sin = 2 1.0 1200 400 sin 19.4 = 318.9 kN
Similarly the nominal resistance for the beams containing the 4-15M bars is 212.6 kN.
1148 Seismic Design

In order to satisfy the capacity design requirement, the factored wall moments will be
increased at each level x by the factor bx , determined as:

bx =
V n

V f

where:
V n = sum of the shears corresponding to the nominal flexural resistance of coupling
beams above level x
V f = sum of factored shears above level x

The beam overstrength factors, cumulative dead and live loads and the factored axial loads
and factored moments in each wall multiplied by bx are shown on Table 11.14. The values of

V f are taken as the wall axial loads given in Table 11.14, since the axial load wall is the sum of
the shears in the coupling beams.

Table 11.14 Coupling Beam Overstrength Factors and Dead and Live Loads per Wall
Storey Vn , Vf , bx PD , PL , Pn , bx M1 ,
kN kN kN kN kN kNm
13 top 212.6 113.0 1.88 -945 0 425 851
13 bot -945 0 425 851
12 top 212.6 149.0 1.62 -1701 -196 850 1750
12 bot -1701 -196 850 501
11 top 318.9 192.8 1.64 -2457 -394 1488 1777
11 bot -2457 -394 1488 1012
10 top 318.9 228.9 1.55 -3213 -513 2126 1469
10 bot -3213 -513 2126 1765
9 top 318.9 251.6 1.48 -3969 -621 2764 1506
9 bot -3969 -621 2764 2239
8 top 318.9 265.1 1.42 -4725 -725 3402 1814
8 bot -4725 -725 3402 2438
7 top 318.9 276.7 1.37 -5481 -825 4039 2088
7 bot -5481 -825 4039 2483
6 top 318.9 290.7 1.32 -6237 -924 4677 2259
6 bot -6237 -924 4677 2459
5 top 318.9 307.4 1.28 -6993 -1020 5315 2338
5 bot -6993 -1020 5315 2382
4 top 318.9 323.3 1.24 7749 1115 5953 2259
4 bot 7749 1115 5953 2344
3 top 318.9 329.8 1.21 8506 1208 6591 1929
3 bot 8506 1208 6591 2664
2 top 318.9 310.4 1.19 9262 1301 7228 1550
2 bot 9262 1301 7228 3676
1 top 318.9 244.3 1.20 9797 1393 7866 2345
1 bot 9797 1393 7866 6682
CAC Concrete Design Handbook 1149

The required moment capacity at the base of each wall, given in Table 11.14, is 6682 kNm
for seismic loading without accidental torsion. It is noted that the required moment at the base of
each wall due to wind (see Table 11.13) is 5599 kNm. Hence the seismic capacity design
requirements control the design.
From Table 11.14, the minimum axial force at the base of the "tension wall" corresponding to
development of flexural hinges in the coupling beams is:
Ps + Pn = 9797 + 7866 = 1931 kN, that is a compressive load.
The maximum axial force at the base of the "compression wall" corresponding to
development of flexural hinges in the coupling beams is:
Ps + Pn = 9797 0.5 1393 7866 = 18360 kN.
To account for the local forces (see Table 11.12) from accidental torsion a simplified
approach will be taken. Although the axial loads and moments on parts AB and CD have opposite
signs it will be assumed that the C-shaped wall is subjected to an additional axial load of twice the
axial tension or compression acting on segments AB or CD and an additional moment of twice the
moment acting in these segments. For example, at the base of the structure the additional axial
load for design is 2 457 = 914 kN and the additional moment is 2 361 = 722 kNm.

11.5.6.2 Design Forces in N-S Direction


From Tables 11.10 and 11.13, the base moment in each wall due to lateral seismic loading is
28332 kNm (including accidental torsion) and the base moment due to factored wind loading is
20087 kNm, respectively. Hence, for flexural design in the N-S direction, the earthquake loading
controls. The corresponding axial load for the two walls is
2(PD + 0.5PL ) = 2( 9797 0.5 1393 ) = 2 10494 = 20988 kN.

11.5.6.3 Design of base of wall for flexure and axial load


Preliminary choice of vertical reinforcement
(a) Minimum area of concentrated reinforcement (Clause 21.6.6.4)
In the 3.2 m long walls in the E-W direction:
2
As = 0.0015 bw l w = 0.0015 400 3200 = 1920 mm
2
Therefore try 425M bars ( As = 2000 mm ) as concentrated reinforcement at one end of the 3.2
m long wall (segments AB and CD).
In the 6.4 m long wall (segment BC) in the N-S direction
2
As = 0.0015 bw l w = 0.0015 400 6400 = 3840 mm
For the case of flanged walls, concentrated reinforcement at the ends of the effective flanges
may supply up to one half of the required minimum wall web concentrated reinforcement (Clause
21.6.6.5). Hence the required concentrated reinforcement at the web-flange intersection is
2
0.5 3840 = 1920 mm . Hence try 4-25M at the intersection of the two walls.
Outside the plastic hinge regions, only two-thirds of this area of the concentrated
reinforcement is required.
Provide a clear cover for the hoops of 40 mm, resulting in a clear cover of 50 mm for the
main vertical reinforcement in the wall, as required for a two-hour fire-resistance rating.
In regions of plastic hinging, the uniformly distributed horizontal reinforcement must be
anchored within the region of concentrated reinforcement to develop 1.25f y (Clause 21.6.5.5).
1150 Seismic Design

The development length required for the 10M bars, using the simplified equation in Clause
12.2.3 is:
1.25fy 500
l d = 0.45k1k 2 k 3 k 4 d b = 0.45 1 1 1 0.8 10 = 329 mm
fc 30
The length provided in the region of concentrated reinforcement (see Fig. 11.27) is 320 mm.
With the significant cover provided on the bars and the additional confinement provided in this
region of concentrated reinforcement, the development length can be shown to be less than 320
mm using Eq. 12-1 in Clause 12.2.2. Hence, the hoop configuration shown in Fig. 11.27 is
adequate.

(b) Maximum area of concentrated reinforcement (Clause 21.6.4.3)


Clause 21.6.4.3 limits the reinforcement ratio, including regions with lap splices, to 0.06.
With the layout of the 4-25M bars at the ends of the flanges and at the web-flange junctions, as
shown in Fig. 11.27, the percentage of steel equals (4 500 ) / (400 400 ) = 0.0125 . This
arrangement allows for lap splicing of the reinforcement without exceeding the limit of 0.06.

Fig. 11.27 Details of reinforcement in walls.

At the base of the walls the spacing of the horizontal distributed reinforcement must be decreased
to 120 mm in component BC and to 150 mm in components AB and CD (see Section 11.5.6.7).

(c) Maximum bar diameters (Clause 21.6.4.4)


In the 400 mm thick walls, the maximum diameter of reinforcement is 400 / 10 = 40 mm.
CAC Concrete Design Handbook 1151

(d) Distributed reinforcement (Clauses 21.6.5)


In the plastic hinge region, the spacing of the distributed reinforcement must not exceed
300 mm in each direction. Outside of this region, the maximum spacing is 450 mm. The
distributed reinforcement ratio must be greater than 0.0025 in each direction.
In the 400 mm thick wall elements, the maximum spacing, assuming two curtains of 10M
reinforcing bars is (2 100 ) / (0.0025 400 ) = 200 mm. Hence, at the base of the walls, use 2
curtains of 10M bars at 200 mm spacing in the horizontal and vertical directions.
In the regions of plastic hinging, two curtains of reinforcement must be provided in the N-S
direction if the design shear in one wall exceeds (Clause 21.6.5.3):
0.18c fc Acv = 0.18 0.65 30 400 6400 = 1641 kN.
Two curtains of reinforcement must be provided in the E-W direction if the design shear in
one wall exceeds:
0.18c fc Acv = 0.18 0.65 30 800 3200 = 1641 kN.

Calculation of M r at base of walls

The factored moment resistances for different loading cases were determined using the
stress block factors of Clause 10.1.7, strain compatibility and a maximum concrete compressive
strain of 0.0035. Table 11.15 summarizes the results.

Table 11.15 Predicted Factored Moment Resistances and Depths of Compression per Wall
at the base (Global wall forces)
Load Case Nf Mf Nr Mr c
kN kNm kN kNm mm
E-W (1 C-shaped wall)
tension
1.0D + 1.0E -1931 6682 -1931 15058 493
wall
compression 1.0D + 1.0E -17663 6682 -17663 21773 226
wall 1.0D + 0.5L + 1.0E -18360 6682 -18360 22280 233
N-S (per wall)
1.0D + 1.0E -9797 28332 -9797 49058 290
1.0D + 0.5L + 1.0E -10494 28332 -10494 51097 303

The required moment capacity in the E-W direction from analysis is 6682 kNm per wall. As
can be seen from Table 11.15, the tension wall has a factored moment resistance of
15058 kNm, while the compression wall has a factored moment resistance of 22280 kNm.
Hence the factored flexural resistance exceeds the required factored moment. Figure 11.28
illustrates the moment resistances for the walls in the E-W direction.
It is noted that the total forces in the E-W tension wall, including global (Table 11.15) and
local (Table 11.12) forces at its base is:
N f = 1931 + 914 = 1017 kN and M f = 6682 + 722 = 7405 kNm.
For this level of axial load the factored moment resistance is 13385 kNm. Hence the wall
strength is adequate for both global and local forces. It can be shown, in a similar way, that the
factored resistance of the compression wall is adequate for global and local forces.
Clause 21.6.8.8 requires that the walls at each end of a coupling beam be designed so that
the factored moment resistance of the wall about its centroid, calculated using axial loads Ps + Pn ,
1152 Seismic Design

exceeds the moment corresponding to the nominal resistance of the coupling beam. This
requirement will be satisfied at all the different levels of the structure because the push-over
analysis summarized in Table 11.14 already considers the attainment of the nominal resistances
of the coupling beams over the entire height of the structure. Hence all of the design moments
and axial forces correspond to these conditions.
In the N-S direction, the factored moment resistance for both load cases significantly
exceeds the required moment (see Table 11.15 and Fig. 11.29).

Fig. 11.28 Factored moment resistances of ductile coupled walls (E-W direction)

Fig. 11.29 Factored moment resistance of ductile shear walls (N-S direction)
CAC Concrete Design Handbook 1153

11.5.6.4 Ductility of walls


E-W Direction - Ductile Coupled Walls (Clause 21.6.8)

For ductile coupled walls, the inelastic rotational demand id is taken as:

f Ro Rd 0.019 1.7 4.0


id = = = 0.0029 0.004
hw 45.0
The inelastic rotational capacity ic , taking l w as the length of the coupled wall system
(Clause 21.6.8.3) and assuming cu = 0.0035 is:

l 0.0035 8.4
ic = cu w 0.002 = 0.002 = 0.0278 0.025
2c 2 0 . 493
Because the rotational capacity of 0.025 exceeds the rotational demand of 0.004, sufficient
ductility is provided.

N-S Direction - Ductile Shear Walls (Clause 21.6.7)


For ductile shear walls, the ratio of the nominal flexural resistance to the factored flexural
resistance, M f , at the base is 1.95 and hence the inelastic rotational demand id is taken as:

id =
( f Ro Rd
f w ) (0.028 1.6 3.5 0.028 1.95 )
= = 0.0024 0.004
l 6.4
hw w 45.0
2 2
The inelastic rotational capacity ic , assuming cu = 0.0035 is:

cu l w 0.0035 6.4
ic = 0.002 = 0.002 = 0.0350 0.025
2c 2 0.303
Because the rotational capacity of 0.025 exceeds the rotational demand of 0.004, sufficient
ductility is provided.

Confinement of concentrated reinforcement (Clause 21.6.7.3)


Because the inelastic rotational capacities of the walls in the E-W and N-S directions were
determined using cu = 0.0035 , it is not necessary to check the confinement requirements of
Clause 21.6.7.4 for the concentrated reinforcement in the walls.

11.5.6.5 Checking wall thickness for stability (Clause 21.6.3)


Clause 21.6.3 requires a wall thickness of l u / 10 in those parts of a wall that, under factored
vertical and lateral loads, are more than half way from the neutral axis to the compression face of
the wall section.
The 3200 mm long portions of the E-W "tension wall" may be considered as simple
rectangular wall elements as shown in Fig. 11.28 with a neutral axis depth of 493 mm. Since the
neutral axis depth is less than 4bw = 4 400 = 1600 mm and is less than
0.3l w = 0.3 3200 = 960 mm, the l u / 10 limit need not apply (see Clause 21.6.3.4). According
to Clause 21.6.3.2 the wall thickness in the plastic hinge region must not be less
than l u / 14 = 4650 / 14 = 332 mm. Hence the wall thickness of 400 mm is adequate.
1154 Seismic Design

For the 6400 mm long portion of the E-W "compression wall", it is noted that
c / 2 = 233 / 2 = 117 mm, which is less than the wall thickness, and furthermore, the wall is
laterally supported at its ends by the 3200 mm wall portions. Hence, this portion of the wall need
not have a thickness of l u / 10 (see Clause 21.6.3.5).
For stability considerations for the wall loaded in the N-S direction, the value of
c / 2 = 303 / 2 = 152 mm is smaller than the 400 mm thickness of the flanges. Therefore the
400 mm wall dimension is adequate and the width of the flange of 3200 mm, greatly exceeds
l u / 5 (see Clause 21.6.3.5).
Therefore all of the stability requirements are satisfied.

11.5.6.6 Buckling prevention ties for concentrated reinforcement


(Clause 21.6.6.9)
The concentrated reinforcement should have buckling prevention ties in accordance with
Clause 7.6 and the ties must be detailed as hoops (Clause 21.6.6.9). In plastic hinge regions, the
hoop spacing shall not exceed:
(i) 6d bl = 6 25 = 150 mm
(ii) 24d bh = 24 10 = 240 mm
(iii) one-half the wall thickness = 400 / 2 = 200 mm.
Hence provide 10M hoops at a spacing of 150 mm as shown in Fig. 11.27.

11.5.6.7 Design for shear at base of walls (Clause 21.6.9)


The walls must be designed to resist the shear corresponding to the formation of plastic
hinges at their bases (Clause 21.6.9.1).

Determine probable moment resistances of walls


In order to determine the probable moment resistances of the walls, axial load-moment
calculations were carried out with c = s = 1.0 and using an equivalent "yield" strength of steel
of 1.25fy . In the E-W direction, we only need to determine the probable moment resistance of the
"compression wall" subjected to an axial load corresponding to 1.0E + 1.0D + 0.5L , since it results
in the larger resistance. From calculations, the probable moment resistance of the wall, M pw , is
26235 kNm in the E-W direction and 60679 kNm per wall in the N-S direction.
It is assumed that earthquake loading causes plastic hinging at the base of the walls.
Assuming that the ratio of the shear to moment at the base of a wall remains constant as the
moment increases to the probable resistance, the shear at the base as the wall develops a plastic
hinge will be:
M pw
V = Vf
Mf

N-S direction:
M pw 60679
V = Vf = 2057 = 4406 kN
Mf 28332
In calculating the shear capacity of the wall, the effective shear depth d v is taken as
0.9d = 0.9 6200 = 5580 mm, but need not be taken less than 0.8l w = 0.8 6400 = 5120 mm
(Clause 21.6.9.3).
CAC Concrete Design Handbook 1155

In the region of expected plastic hinging, at the base of the wall, the inelastic rotational
demand id is less than 0.005 and hence the factored shear demand cannot exceed:
0.15c fcbw d v = 0.15 0.65 30 400 5120 = 5990 kN
The factored shear demand of 4406 kN is less than this upper limit.
Because the inelastic rotational demand id is less than 0.005, the factored shear resistance
is calculated using = 0.18 . The axial load on the tension wall is -10494 kN (compression). This
axial load is less than: 0.1fc Ag = 0.1 30 (3200 800 + 5600 400 ) = 14400 kN.
Hence is taken as 45 (Clause 21.6.9.6). The factored shear resistance (Clauses 11.3.4
and 11.3.5), assuming pairs of 10M bars at 120 mm spacing is:
s Av f y d v cot
Vr = c f c bw d v +
s
0.85 200 400 5580 cot 45 o
= 0.65 0.18 30 400 5580 +
120
= 1430 + 3162 = 4592 kN
Hence the shear resistance is adequate with pairs of 10M horizontal bars spaced at 120 mm.
It is noted that the accidental torsion causes shear in segments AB and CD. This shear, due
to accidental torsion, must be considered in design, accounting for the fact that the critical flange
will be in tension and have large flexural cracks due to the attainment of plastic hinging for loading
in the N-S direction. A method to check the shear resistance of these segments, accounting for
large cracks and possible redistribution of shear resisting torsion, is described in the calculations
below for loading in the E-W direction.

E-W direction:
In the E-W direction it is necessary to first determine the shear from seismic loading and
include accidental torsion effects. The shear at the base without accidental torsion is
810 / 2 = 405 kN in segment AB. The analysis including accidental torsion indicates a shear force
of 120 kN on wall segments AB and CD (see Table 11.12). In accordance with Clause 21.6.8.13 it
may be necessary to redistribute the shear force of 359 kN in the segment BC because under
plastic hinging this wall segment will experience large tensile strains and cracks. If the torsion
arising from this 359 kN force is redistributed to wall segments AB and CD, then an additional
shear force will be necessary. This additional shear force is:
8.0 8.0
VAB = VBC = 359 = 479 kN in two segments
6.0 6.0
Hence the total shear in segment AB is 405 + 120 + 479 / 2 = 765 kN.
In lieu of redistributing the torsional shear from wall segment BC, a more detailed analysis
will be conducted (Clause 21.6.8.13). Wall component BC is lightly loaded in shear but must resist
the shear with large cracks in this tension wall. In order to determine the shear resistance under
these conditions the dowel action resistance will be determined, considering the resistance of
the reinforcement only. From Paulay and Priestley (1992) the dowel resistance can be taken as:
Vr = 0.25 s Av f y = 0.25 0.85 27 200 400 = 459 kN.

Because this resistance exceeds the shear force of 359 kN, redistribution of the shear from the
tension wall BC to wall AB is not necessary. Hence the total shear in segment AB is
405 + 120 = 525 kN.
1156 Seismic Design

The design shear for segment AB, including torsional effects is:
M pw 26235
V = Vf = 525 = 1860 kN
Mf 6682 + 722

For segment CD, the shear from accidental torsion acts in the opposite direction from that in
segment AB. Hence the total shear for segment CD is 405 120 = 285 kN. This results in a
design shear for this segment of:
M pw 26235
V = Vf = 285 = 1010 kN.
Mf 6682 + 722

Segments AB and CD must both be designed for the larger shear of 1860 kN because the
accidental torsion can reverse.
In calculating the shear capacity of the wall, in accordance with Clause 21.6.9.3, we will
assume an effective shear depth, dv = 0.8l w = 0.8 3200 = 2560 mm.
In the region of expected plastic hinging, at the base of the wall, the inelastic rotational
demand id is less than 0.005 and hence the factored shear demand in one segment cannot
exceed:
0.15c fcbw dv = 0.15 0.65 30 400 2560 = 2995 kN

The factored shear demand of 1860 kN is less than this upper limit.
Because the inelastic rotational demand id is less than 0.005, the factored shear resistance
is calculated using = 0.18 . The axial load on the tension wall is -1017 kN. This axial load is less
than: 0.1fc Ag = 0.1 30 (3200 800 + 5600 400 ) = 14400 kN.
Hence is taken as 45 (Clause 21.6.9.6). The factored shear resistance (Clauses 11.3.4
and 11.3.5) for wall segment AB at the base with pairs of 10M bars at a spacing of 150 mm is:
s Av f y d v cot
Vr = c f c bw d v +
s
0.85 200 400 2560cot 45 o
= 0.65 0.18 30 400 2560 +
150
= 656 + 1161 = 1817 kN

Segment AB is overstressed by only 2%, while segment BC is very lightly loaded and hence
a portion can be redistributed to this segment. Hence the shear strength in the E-W direction is
adequate with 2-10M bars at 150 mm spacing.
Extend the 10M horizontal reinforcement into the confined core of the region of concentrated
reinforcement as close to the outside surface of the walls as cover will permit (see Fig 11.27 and
Section 11.5.6.3).

11.5.6.8 Checking sliding shear resistance at construction joints


(Clause 21.6.9.4)
In accordance with Clause 21.6.9.4, we must check the sliding shear resistance of the
construction joints. Since the vertical uniformly distributed reinforcement is constant over the
height of the walls, the most critical situation is at the base of the walls.
CAC Concrete Design Handbook 1157

N-S direction:
In the N-S direction, the required shear strength is 4406 kN per wall. If the construction joint
is intentionally roughened, the factored shear stress resistance from Clauses 11.5.1 and 11.5.2 is:
N
v r = c c + v fy +
Ag

9797 1000
= 0.65 0.50 + 1.0 0.0025 400 +
800 3200 + 400 5600
= 2.302 MPa

Hence, the sliding shear resistance is: 2.302 Acv = 2.302 400 6400 = 5893 kN

Since the sliding shear resistance exceeds the shear corresponding to plastic hinging, sliding
shear will be prevented.

E-W direction:
In the E-W direction, the required shear strength of segment AB is 1860 kN. It will be
assumed that the net compressive axial load is acting on the segments AB and CD (the segment
BC is in tension). If the construction joint is intentionally roughened, the factored shear stress
resistance from Clause 11.5 is:
N
v r = c c + v f y +
Ag

1931 1000
= 0.65 0.50 + 1.0 0.0025 400 +
800 3200
= 1.465 MPa

Hence, the sliding shear resistance of segment AB is:


1.465 Acv = 1.465 400 3200 = 1875 kN.

The sliding shear resistance is adequate.

11.5.6.9 Determination of plastic hinge region (Clause 21.6.2)


As the wall cross sectional dimensions remain constant over the 48.65 m height of the wall
and provided that the main flexural reinforcement is appropriately curtailed, only one plastic hinge
region will form, near the base of the walls. The height over which plastic hinging could take place
from the base of the wall is governed by the longer, N-S, wall (Clause 21.6.2.2) and is taken as
1.5 6.4 = 9.6 m. Therefore detail the first three storeys as plastic hinge regions.

11.5.6.10 Changes in horizontal distributed reinforcement over the height


of the walls (Clause 21.6.5)
The maximum spacing of the 210M horizontal bars, outside of the plastic hinge region is
200 mm, since the minimum reinforcement ratio of 0.0025 must be satisfied. Therefore use 2 -
10M bars at 200 mm spacing above the plastic hinge region.
1158 Seismic Design

11.5.6.11 Changes in Vertical distributed reinforcement over the height of


the walls (Clause 21.6.5)
Once again, the minimum reinforcement ratio of 0.0025 governs the selection of vertical
distributed reinforcement. Hence use 2-10M bars at 200 mm spacing over the entire height of the
wall.

11.5.6.12 Changes in concentrated vertical reinforcement over the height


of the walls (Clause 21.6.6)
The minimum area of concentrated reinforcement which can be used outside the plastic
hinge region is 0.001bw l w (Clause 21.6.6.3). At one end of the 3200 mm long wall, the minimum
2
amount of concentrated reinforcement is 0.001 400 3200 = 1280 mm . Similarly, the minimum
amount of concentrated reinforcement required at the intersection of the wall components is
2
2560 1280 = 1280 mm (Clause 21.6.6.5).
Note that in deciding on the changes to the concentrated reinforcement over the height of the
structure, it is necessary to ensure that the factored moment resistance at each floor level is
sufficient to develop the plastic hinging at the base of the structure. This check should be made
with due consideration for the effect of lap splices in the reinforcement. An example of the
calculations necessary to ensure adequate flexural strength is given in Reference 1.

11.5.7 Frame Members Not Considered Part of the SFRS


Clause 21.12 provides design requirements for members that are not considered part of the
seismic force resisting system. The shear walls and coupled wall system were designed to take
100% of the seismic loading effects. The slabs and the columns must be checked to determine if
the levels of ductility and strength of these important vertical load carrying members are sufficient.

11.5.7.1 Slab-column connections (Clause 21.12.3)


The reduction factor, RE , on two-way slab shear stress is a function of the interstorey drift.
th
The maximum drifts at the extremities of the structure including torsional effects is 0.00565 (8
th
storey) in the N-S direction and 0.0047 (8 storey) in the E-W direction. Hence the reduction
factor is:
0.85 0.85
0.005 0.005
RE = = = 0.901
i 0.00565

Interior slab-column connection:


For an interior slab-column connection, the gravity load two-way shear stress (excluding
shear from unbalanced loading and determined using the seismic load
combinations (1.0D + 0.5L ) can be determined for a first interior columns location as follows:

( )
Vf = [1.0(4.8 + 1.5 ) + 0.5(2.4 )] 5.75 6.0 0.712 = 255 kN

A clear cover of 25 mm and 15M top bars are assumed for the slab.
The corresponding shear stress is:
Vf 255 1000
vf = = = 0.561 MPa
bo d 4 (550 + 160 ) 160
CAC Concrete Design Handbook 1159

The limiting shear stress obtained by multiplying RE by the two-way shear stress for this
square column from Clause 13.3.4.1 is:

v c = 0.38c fc RE = 0.38 0.65 30 0.901 = 1.219 MPa

Hence, no shear reinforcement is required.

Corner slab-column connection:


Applying the same principles to a corner slab-column connection gives a factored shear of:

( )
Vf = [1.0(4.8 + 1.5 ) + 0.5(2.4 )] 3.125 2 0.73 2 = 69.2 kN

Vf 69.2 1000
vf = = = 0.296 MPa
bo d 2 (100 + 550 + 160 / 2) 160

The limiting shear stress obtained by multiplying RE by the one-way shear stress for this
corner column from Clause 13.3.6 and 11.3.6.2 is:

v c = 0.21c fc RE = 0.21 0.65 30 0.901 = 0.674 MPa

Hence, no shear reinforcement is required.

11.5.7.2 Check on design and detailing of columns (Clause 21.12)


Clauses 21.12.1 to 21.12.2 provide detailed requirements for the columns which are not
considered part of the seismic force resisting system. Minimum design and detailing requirements
must be applied or the columns must be analyzed to determine if the factored moments in the
columns exceed their nominal resistances when the structure is deformed laterally to the design
displacements.

11.5.8 Comparisons with the Design Using the 1994 CSA Standard
The structure designed in this chapter is the same structure designed in Reference 2, except
that the structure designed in this chapter was for a foundation on soil of site Class D (stiff soil),
whereas the structure in Reference 2 was for the same structure founded on rock. In addition,
900 mm deep diagonally reinforced coupling beams were used, instead of 600 mm deep coupling
beams with conventional reinforcement. It is noted that, for this structure, the design force levels
using the 2005 NBCC are somewhat lower than those using the 1995 NBCC.

11.5.9 References
1. Mitchell, D. and Collins, M.P., "Chapter 11 - Seismic Design", Concrete Design Handbook,
Canadian Portland Cement Association, Ottawa, 1985, pp. 11-1 11-31.
2. Mitchell, D., Paultre, P. and Collins, M.P., "Chapter 11 - Seismic Design", Concrete Design
Handbook, Cement Association of Canada, Ottawa, 1995, pp. 11-1 11-33.
3. Paulay, T., Priestley, M.J.N., Seismic Design of Reinforced Concrete and Masonry
Buildings, John Wiley and Sons, NY, 1992, 744p.
1160 Seismic Design

Potrebbero piacerti anche