Sei sulla pagina 1di 1

PT PLN (Persero)

Spesifikasi Material Transmisi Utama (MTU)

6.7. Spesifikasi PHBTM Bus VT/LA


PT PLN (Persero)
TECHNICAL PARTICULAR AND GUARANTEE
PHBTM BUS VT/LA

NO. DESCRIPTION UNIT REQUIRED

A. 20 KV SWITCHGEAR
1 Manufacturer to be mentioned
2 Type to be mentioned
3 Type of designation (tempat pemasangan dan konfigurasi busbar) Indoor metal clad and single busbar
4 Standard IEC 62271-200
5 Rated voltage (Ur) kV 24
6 Rated lightning impuls withstand voltage (Up) kV 125
7 Rated power frequency withstand voltage (Ud) kV 50
8 Rated frequency Hz 50
9 Rated normal current
- Main busbar A
- VT/LA busbar A
10 Rated short-time withstand current ( I k ) kA 25
11 Rated duration of short circuit sec. 3
12 Rated peak withstand current ( I p ) kA 2,5 x I k
13 Degrees of protection (IP) Minimum IP 4X
14 Insulation medium air
15 Busbar system :
Material Copper with heatshrink
Main busbar at upper side mm2 to be mentioned
Terminal for Busbar Cable at lower side mm2 to be mentioned
Earthing busbar mm2 to be mentioned
16 Number of phase busbar 3
17 Auxiliary supply
Rated supply voltage of closing and opening devices Vdc 110
Rated supply voltage of control circuit (aux, relay) Vdc 110
Rated supply voltage of auxiliary (heater) Vac 230
18 Loss of service continuity catagory (LSC) LSC2B
19 Internal arc classification (IAC) kA-1sec AFLR 25
20 Minimum thickness of steel sheet :
- front panel for relay, energy meter and others mounted mm 2.5
- other section mm refer to IAC complied
21 Dimension of switchgear cubicle :
- width mm to be mentioned
- depth mm to be mentioned
- height mm to be mentioned
22 Heater with temperature control set to be mentioned (power and range temperature)

B. 20 KV VOLTAGE TRANSFORMER
1 Manufacturer to be mentioned
2 Type to be mentioned
3 Standard IEC 60044-2
4 Type of design Indoor
5 Rated voltage (Ur) kV 24
6 Minimum Rated voltage factor 1,2 Continuous and 1,9 - 30 s
7 Rated Frequency Hz 50
8 Ratio, class, rated output :
a) for metering
- ratio V
- class - 0.2
- burden VA
b) for protection
- ratio V
- class - 3P
- burden VA 25
9 Rated lightning impulse withstand voltage (Up) kV 125
10 Power frequency withstand voltage (Ud) kV 50

C. DISCONNECTOR SWITCH
1 Manufacturer To be mentioned
2 Type To be mentioned
4 Standard IEC 60265
6 Rated voltage kV 24
7 Rated nominal current A
8 Rated lightning impuls withstand voltage kV 125
9 Rated short-time withstand current (Ik) kA 25
10 Making capacity kA 2,5 x Ik
11 Rated frequency Hz 50
12 Interrupting medium SF6 or Vacuum
13 Mechanism type manual
14 Mechanical endurance M2 (5.000 times)

D. PROTECTION RELAY
1 Under Frequncy relay (81U) Yes or No
2 Under Voltage relay (27) Yes or No
3 Port communication comply to IEC 61850 Modem completed with optical wire port or RS485 or RJ45

E. TEST PLUG FOR PROTECTION RELAY AND METERING


1 Manufacturer To be mentioned
2 Type To be mentioned
3 Type of designation Banana plug

F. FUSE

F.1 FUSE-BASE
1 Manufacturer To be mentioned
2 Rated voltage kV 24
3 Rated current A

F.2 FUSE-LINK
1 Manufacturer To be mentioned
2 Type of designation Indoor, limiting current
3 Rated voltage kV 24
4 Rated current A 6

Potrebbero piacerti anche