Operating Instructions & Parts Manual 2TFZ4 thru 2TFZ9

Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product
described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury
and/or property damage! Retain instructions for future reference.

Dayton Fire Dampers

Round
Description Optional Accessories
DYNAMIC FIRE DAMPERS E
Description Item No.
N
Dayton dynamic fire dampers are designed for use in HVAC systems that are
operational in the event of a fire up to 1 hours. Airflow through these dampers 165F Fusible Link: 2TGJ3 G
may be in either direction. May be mounted either horizontally or vertically and Models are intended for installation in accordance
L
close with the aid of a steel spring. They are rated up to 4 wg pressure and with fire damper requirements established by: I
NFPA - National Fire Protection Association S
2,000 fpm velocity.
DFDRHV1 model is classified BOCA - National Building Codes
for fire barrier and smoke ICBO - Uniform Building Codes H
Dimensions and Specifications applications (UL 555). SBCCI - Standard Building Codes
(See Figure 1) File No. R26094 CSFM - California State Fire Marshal

Item Nominal Damper Free Area Retaining Plate Clearance for Expansion
No. Duct Dia. (Sq. Ft.) (Optional) Retaining Plate
Blade Latch
2TFZ4 4" 0.064 Duct Connection 2" Access door to be
Area on same side as
2TFZ5 6 0.160 blade latch

2TFZ6 8 0.301 Airow

2TFZ7 10 0.485 2"


Duct Connection
Area E
2TFZ8 12 0.649 135/8"
S
2TFZ9 14 0.910 Dia. DO NOT PLACE RETAINING
PLATE IN THIS GROOVE
P
NOTE: Actual damper size is undersized 1/8" Figure 1 Dimensions A
6" Max. 6" Max.
TW
Unpacking 2. Installation shall comply with Sleeve Length O
the requirements of NFPA 90A Figure 2 Clearance Requirements L
1. Inspect for any damage that may
Standard for the Installation of Air
have occurred during transit and file
Conditioning and Ventilating Systems.
shipping damage claim with carrier. Wood
Metal
Stud

2. Check all parts of shipment, including Installation Stud

accessories, are accounted for. Installation, Damper


troubleshooting and Frame
1"
3. Dampers must be kept dry and clean. parts replacement is to be performed Min.

Indoor storage and protection from only by a qualified personnel.


dirt, dust and weather is highly 1. Cut wall/floor opening so that it is a
DO NOT PLACE RETAINING F
PLATE IN THIS GROOVE FOR
recommended. Do not store at minimum of 7/8 inch larger than the
METAL OR WOOD INSTALLATIONS R
temperature in excess of 100 F. Figure 3 Wall Opening A
outside diameter of your fire damper
General Safety Information to allow for expansion during periods N
24" o.c. 24" o.c. Ceiling Runner
Improper of intense heat. Refer to Figure 2. Maximum
(metal studs)
Maximum
(metal studs)
installation, 2. Prepare your opening.
12 in.
A
adjustment, alteration, service or
a. Frame wall opening as shown in I
maintenance can cause property
damage, injury or death. Figure 3. S
24". o.c.
Maximum
1. Read and follow all instructions and b. Fasten gypsum wall board 12 inches
cautionary markings. on center to all stud and runner 2"
2 Panhead

NOTE: Specific requirements in these flanges surrounding opening. Refer Screws 2"
16" o.c. 16" o.c.
instructions are mandatory. These to Figure 4. Floor Runner Maximum
(wood studs)
Maximum
(wood studs)

instructions meet the requirements of


Figure 4 Fasten Gypsum Wall Board
UL 555.
Form 5S6146 Printed in U.S.A. 471969
04632 Rev. 1 August 2008
0808/325/VCPVP

FireDampRdRev1_EN_ES_FR.indd 1 9/30/08 2:59:26 PM


Dayton Operating Instructions and Parts Manual 2TFZ4 thru 2TFZ9

Dayton Fire Dampers Round

Installation (Continued) 5. Connect duct to damper sleeve using


Nut
E 3. Insert your damper/sleeve assembly the appropriate connection type.
N into the prepared opening to NOTE: Gauge of factory furnished
G appropriate depth. Refer back to sleeve determines type of duct to sleeve
L Figure 2 for recommended depth. Retaining connection required. See Figure 6.
Plate Assembly
I NOTE: Recommended maximum and Type of Duct to Maximum Sleeve
S minimum insertion depth can be Sleeve Connection Duct Dimension Gauge
Clamping Screw
H exceeded as long as the center line of Rigid or Breakaway 24" 10
Figure 5 Retaining Plate
damper blade remains within the plane 14
b. Slip the retaining plate over the 16
of the wall/floor.
damper with the clamping screw Breakaway 24" 20
Do not insert screws
into the damper facing away from the wall or floor.
Important: Sleeve thickness must not be less than
frame unless used for duct connection Retaining plate is designed to the gauge of the connection duct.
within 2 inches of frame end. mount flush to the wall/floor to UL Standard 555 requires all ducts to terminate at
the re damper sleeves or the damper frames.
NOTE: All dampers are supplied with a hold damper in the opening.
factory mounted sleeve and can be in- Figure 6 Minimum Sleeve Thickness
NOTE: Do not position the retaining
stalled without the need for additional plate in the damper frame groove. a. For duct diameters 22" use (3)
field installed sleeves. Refer back to Figure 2. #8 sheet metal screws. For duct
NOTE: The sleeve may extend a maxi- c. Verify damper position and blade diameters > 22" use (5) #8 sheet
mum of 6 inches beyond both sides of orientation, tighten the retaining metal screws.
the wall/floor. plate clamping screw. Retaining NOTE: All breakaway connections
4. Secure damper/sleeve assembly to the plate must overlap the wall/floor described may have duct sealant,
wall/floor opening using the single opening a minimum of 1 inch. PA2084T duct sealant adhesive
retaining plate supplied. d. Secure retaining plate at all (4) manufactured by Precision DP1010
a. Use hardware provided to assemble corners and within 3/4 inch of water base duct sealant by Design
the (2) halves of the retaining plate center to the wall/floor using Polymetrics, in accordance with
together on the side opposite the appropriate fasteners (minimum #8 SMACNA recommendations.
clamping screw. Refer to Figure 5. sheet metal screws).
LIMITED WARRANTY
DAYTON ONE-YEAR LIMITED WARRANTY. DAYTON FIRE DAMPERS ROUND, MODELS COVERED IN THIS MANUAL, ARE WARRANTED BY DAYTON ELECTRIC MFG. CO. (DAYTON) TO THE ORIGINAL USER

AGAINST DEFECTS IN WORKMANSHIP OR MATERIALS UNDER NORMAL USE FOR ONE YEAR AFTER DATE OF PURCHASE. ANY PART WHICH IS DETERMINED TO BE DEFECTIVE IN MATERIAL OR WORKMANSHIP
AND RETURNED TO AN AUTHORIZED SERVICE LOCATION, AS DAYTON DESIGNATES, SHIPPING COSTS PREPAID, WILL BE, AS THE EXCLUSIVE REMEDY, REPAIRED OR REPLACED AT DAYTONS OPTION. FOR
LIMITED WARRANTY CLAIM PROCEDURES, SEE PROMPT DISPOSITION BELOW. THIS LIMITED WARRANTY GIVES PURCHASERS SPECIFIC LEGAL RIGHTS WHICH VARY FROM JURISDICTION TO JURISDICTION.

LIMITATION OF LIABILITY. TO THE EXTENT ALLOWABLE UNDER APPLICABLE LAW, DAYTONS LIABILITY FOR CONSEQUENTIAL AND INCIDENTAL DAMAGES IS EXPRESSLY DISCLAIMED. DAYTONS LIABILITY IN
ALL EVENTS IS LIMITED TO AND SHALL NOT EXCEED THE PURCHASE PRICE PAID.

WARRANTY DISCLAIMER. A DILIGENT EFFORT HAS BEEN MADE TO PROVIDE PRODUCT INFORMATION AND ILLUSTRATE THE PRODUCTS IN THIS LITERATURE ACCURATELY; HOWEVER, SUCH INFORMATION
AND ILLUSTRATIONS ARE FOR THE SOLE PURPOSE OF IDENTIFICATION, AND DO NOT EXPRESS OR IMPLY A WARRANTY THAT THE PRODUCTS ARE MERCHANTABLE, OR FIT FOR A PARTICULAR PURPOSE, OR
THAT THE PRODUCTS WILL NECESSARILY CONFORM TO THE ILLUSTRATIONS OR DESCRIPTIONS. EXCEPT AS PROVIDED BELOW, NO WARRANTY OR AFFIRMATION OF FACT, EXPRESSED OR IMPLIED, OTHER
THAN AS STATED IN THE LIMITED WARRANTY ABOVE IS MADE OR AUTHORIZED BY DAYTON.

Technical Advice and Recommendations, Disclaimer. Notwithstanding any past practice or dealings or trade custom, sales shall not include the furnishing of technical advice or assistance or system
design. Dayton assumes no obligations or liability on account of any unauthorized recommendations, opinions or advice as to the choice, installation or use of products.

Product Suitability. Many jurisdictions have codes and regulations governing sales, construction, installation, and/or use of products for certain purposes, which may vary from those in neighboring areas.
While attempts are made to assure that Dayton products comply with such codes, Dayton cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase
and use of a product, review the product applications, and all applicable national and local codes and regulations, and be sure that the product, installation, and use will comply with them.

Certain aspects of disclaimers are not applicable to consumer products; e.g., (a) some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you; (b) also, some jurisdictions do not allow a limitation on how long an implied warranty lasts, consequently the above limitation may not apply to you; and (c) by law, during
the period of this Limited Warranty, any implied warranties of implied merchantability or fitness for a particular purpose applicable to consumer products purchased by consumers, may not be excluded or
otherwise disclaimed.

Prompt Disposition. A good faith effort will be made for prompt correction or other adjustment with respect to any product which proves to be defective within limited warranty. For any product
believed to be defective within limited warranty, first write or call dealer from whom the product was purchased. Dealer will give additional directions. If unable to resolve satisfactorily, write to Dayton at
address below, giving dealers name, address, date, and number of dealers invoice, and describing the nature of the defect. Title and risk of loss pass to buyer on delivery to common carrier. If product was
damaged in transit to you, file claim with carrier.

Manufactured for Dayton Electric Mfg. Co., 5959 W. Howard St., Niles, Illinois 60714-4014 U.S.A.

Manufactured for Dayton Electric Mfg. Co.


Niles, Illinois 60714 U.S.A.

FireDampRdRev1_EN_ES_FR.indd 2 9/30/08 2:59:27 PM


Manual de Instrucciones Operacin y Lista de Partes Dayton 2TFZ4 a 2TFZ9

Por favor lea y guarde estas instrucciones. Lalas cuidadosamente antes de tratar de montar, instalar, operar o dar
mantenimiento al producto aqu descrito. Protjase usted mismo y a los dems observando toda la informacin de seguridad. El no cumplir con
las instrucciones puede ocasionar daos, tanto personales como a la propiedad! Guarde estas instrucciones para referencia en el futuro.

Cortafuegos Redondos
Dayton

Descripcin Accesorios Opcionales


CORTAFUEGOS DINMICOS Descripcin Artculo N
Los cortafuegos dinmicos Dayton estn diseados para su uso en sistemas de calefaccin,
ventilacin y aire acondicionado que estn en funcionamiento en caso de incendio hasta 74 C Conexin con fusible: 2TGJ3
por 1 1/2 horas. El flujo de aire a travs de estos cortafuegos puede ir en ambas direcciones. Los modelos estn diseados para su instalacin
Se pueden montar de forma horizontal o vertical, y se cierran gracias a un resorte de acero. de acuerdo con los requisitos para cortafuegos
Estn clasificados hasta una presin de 1 kPa y una velocidad de 10,2 m/s. establecidos por:
La Asociacin Nacional de Proteccin contra Incendios
(NFPA, por sus siglas en ingls)
Dimensiones y Especificaciones El modelo DFDRHV1 est clasificado
Los Cdigos Nacionales de Construccin de BOCA
para aplicaciones de barrera contra
(Consulte la Figura 1) incendios y humo (UL 555). Los Cdigos de Construccin Uniforme de ICBO
Dim. Seccin Libre de Paso N de archivo R26094 Los Cdigos de Construccin Estndar de SBCCI
Artculo Nominal del de Aire del Cortafuegos El Jefe de Bomberos del Estado de California (CSFM,
por sus siglas en ingls)
N Conducto (cm cuad.)
Placa de
2TFZ4 10,2 cm 59,5 retencin Holgura para expandirse
(opcional) Placa de retencin
2TFZ5 15,2 148,6 Sujetador de la paleta
rea de 5,1
La puerta de
2TFZ6 20,3 279,6 conexin cm
acceso debe estar
del conducto en el mismo lado
2TFZ7 25,4 450,6 que el sujetador
de la paleta
2TFZ8 30,5 602,9 34,6 cm Flujo de aire

2TFZ9 35,6 845,4 rea de E


Dim. 5,1 conexin
NOTA: El tamao real del cortafuegos est reducido cm del conducto
S
en 0,32 cm Figura 1 - Dimensiones
NO COLOQUE LA PLACA DE P
RETENCIN EN ESTA RANURA
A
Desembalaje Instalacin 15,2 cm 15,2 cm
mx. TW mx.
1. Revise si existen daos que se puedan Slo personal
haber producido durante el transporte y
PRECAUCIN calificado debe realizar Longitud del manguito
O
presente la queja por daos de transporte la instalacin, la solucin de problemas y el Figura 2 - Requisitos de holgura L
a la empresa de transporte. reemplazo de partes.
Entramado de madera Entramado de metal
2. Revise que se incluyan todas las partes del 1. Corte la abertura en la pared o piso de
envo, incluidos los accesorios. manera que sea de un mnimo de 22,3 mm
3. Los cortafuegos se deben mantener secos ms grande que el dimetro exterior del
y limpios. Se recomienda almacenarlos en cortafuegos, a fin de permitir que ste
interiores y protegerlos de la suciedad, el se expanda durante los perodos de calor Marco
del
polvo y de las inclemencias del tiempo. No intenso. Consulte la Figura 2. cortafuegos 2,5 cm
mn.
los almacene a temperaturas superiores a 2. Prepare la abertura.
38 C. a. Enmarque la abertura en la pared como
se muestra en la Figura 3. NO COLOQUE LA PLACA DE RETENCIN EN ESTA
Informacin de Seguridad RANURA PARA INSTALACIONES EN METAL O MADERA

General b. Fije los paneles de pared de yeso a


Figura 3 - Abertura en la pared
30,5 cm de centro a centro a todos los
La instalacin, el pasadores y rebordes del conducto que
ajuste, la alteracin rodean la abertura. Consulte la Figura 4.
61,0 cm
de centro
61,0 cm
de centro
a centro
como
a centro
como
Viga de apoyo
o el mantenimiento incorrectos pueden mximo
(entramados
mximo
(entramados
del techo

provocar daos a la propiedad, lesiones 3. Inserte el conjunto de cortafuegos/ 30,5 cm


de metal) de metal)

o la muerte. manguito dentro de la abertura


preparada, a la profundidad apropiada.
1. Lea y siga todas las instrucciones y marcas Consulte la Figura 2 para conocer la
de precaucin. profundidad recomendada. 61,0 cm
NOTA: Los requisitos especficos de estas NOTA: Se puede exceder la profundidad de
de centro a
centro como
instrucciones son obligatorios. Estas insercin mxima y mnima recomendadas,
mximo

instrucciones cumplen los requisitos de la siempre y cuando la lnea central de la paleta 5 cm


norma UL 555. del cortafuegos permanezca dentro del
2 tornillos de
cabeza troncocnica
5 cm
40,6 cm 40,6 cm
Viga de apoyo
2. La instalacin debe cumplir los requisitos plano de la pared o piso. del piso
de centro
a centro como
mximo
de centro
a centro como
mximo
(entramados (entramados
de la norma 90A de la NFPA para de madera) de madera)

la instalacin de sistemas de aire Figura 4 - Fijacin del panel de pared de yeso


acondicionado y ventilacin.

Formulario 5S6146 Impreso en EE.UU. 471969


04632 Rev. 1 de agosto 2008
0808/325/VCPVP

FireDampRdRev1_EN_ES_FR.indd 3 9/30/08 2:59:28 PM


Manual de Instrucciones de Operacin y Lista de Partes Dayton 2TFZ4 a 2TFZ9

Cortafuegos Redondos Dayton

Instalacin (continuacin) Tuerca


NOTA: El calibre del manguito que viene
de fbrica determina el tipo de conexin
No inserte tornillos del conducto al manguito que se necesita.
en el marco del Consulte la Figura 6.
cortafuegos a menos que se usen para la
conexin del conducto dentro de 5,1 cm de Tipo de Conducto Dimensin
distancia del extremo del marco. Conjunto de hacia la Conexin Mxima del Calibre del
placa de con el Manguito Conducto Manguito
retencin
NOTA: Todos los cortafuegos se suministran
con manguitos montados en fbrica y se Rgido o 61,0 cm 10
Desmontable 14
pueden instalar sin necesidad de manguitos Tornillo de apriete
16
adicionales de terreno. Figura 5 - Placa de retencin
Desmontable 61,0 cm 20
NOTA: El manguito puede extenderse un NOTA: No coloque la placa de retencin
mximo de 15,2 cm ms all de ambos lados en la ranura del marco del cortafuegos. Importante: El espesor del manguito no debe ser
de la pared o del piso. inferior al calibre del conducto de conexin.
Consulte la Figura 2. La norma UL 555 exige que todos los conductos terminen
4. Fije el conjunto del manguito/cortafuegos c. Verifique la posicin del cortafuegos, en los manguitos o los marcos de los cortafuegos.
a la abertura de la pared o piso con la placa la orientacin de la paleta y apriete
de retencin nica que se proporciona. el tornillo de apriete de la placa de Figura 6 - Espesor mnimo del manguito
a. Use las piezas metlicas que se retencin. La placa de retencin se debe a. Para los dimetros de conductos
proporcionan para ensamblar las superponer a la abertura de la pared o 55,9 cm use (3) tornillos de plancha N
E mitades (2) de la placa de retencin en el piso en un mnimo de 2,54 cm. 8. Para los dimetros de conductos >
el lado opuesto al tornillo de apriete. d. Fije la placa de retencin en las (4) 55,9 cm use (5) tornillos de plancha N 8.
S Consulte la Figura 5. esquinas y dentro de 19,1 mm del centro NOTA: Todas las conexiones desmontables
P b. Deslice la placa de retencin sobre el a la pared o piso usando los sujetadores que se describen pueden tener sellador de
A cortafuegos con el tornillo de apriete correspondientes (tornillos de plancha conductos, adhesivo de sellador de conductos
apuntando en direccin contraria a la de un mnimo de N 8). PA2084T fabricado por Precision, sellador de
pared o el piso. La placa de retencin 5. Conecte el conducto al manguito del conductos a base de agua DP1010 fabricado
O est diseada para que se monte a ras cortafuegos usando el tipo de conexin por Design Polymetrics, de acuerdo con
L con la pared o el piso a fin de mantener correspondiente. recomendaciones de la SMACNA.
el cortafuegos en la abertura.

GARANTA LIMITADA
GARANTA LIMITADA DE UN AO DAYTON. CORTAFUEGOS REDONDOS DAYTON , LOS MODELOS INCLUIDOS EN ESTE MANUAL, TIENEN GARANTA DE DAYTON ELECTRIC MFG. CO.

(DAYTON) POR DEFECTOS DE FABRICACIN O MATERIALES DURANTE SU USO NORMAL DURANTE UN AO A PARTIR DE LA FECHA DE COMPRA. TODA PIEZA QUE SE DEMUESTRE
QUE TENGA DEFECTOS DE MATERIAL O DE MANO DE OBRA Y SE DEVUELVA A UN LUGAR DE SERVICIO TCNICO AUTORIZADO, DESIGNADO POR DAYTON, COSTOS DE TRANSPORTE
PREPAGADOS, SER COMO RECURSO EXCLUSIVO, REPARADA O REEMPLAZADA SEGN EL CRITERIO DE DAYTON. POR DEMANDA DE GARANTA LIMITADA, VER DISPOSICIN INMEDIATA A
CONTINUACIN. ESTA GARANTA LIMITADA LE DA AL COMPRADOR DERECHOS LEGALES ESPECFICOS QUE VARAN DE UNA JURISDICCIN A OTRA.
RESTRICCIN DE RESPONSABILIDAD. HASTA DONDE LO PERMITA LA LEGISLACIN PERTINENTE, DAYTON NIEGA EXPRESAMENTE SU RESPONSABILIDAD EN DAOS DE INDIRECTOS O
EMERGENTES. LA RESPONSABILIDAD DE DAYTON EN TODOS LOS CASOS SE LIMITA AL PRECIO DE COMPRA Y NO DEBE EXCEDER STE.
DENEGACIN DE GARANTA. SE HA HECHO UN GRAN ESFUERZO POR PROPORCIONAR INFORMACIN SOBRE EL PRODUCTO E ILUSTRAR LOS PRODUCTOS DE MANERA PRECISA EN
ESTE DOCUMENTO; SIN EMBARGO, TAL INFORMACIN E ILUSTRACIONES TIENEN EL NICO PROPSITO DE IDENTIFICACIN, Y NO EXPRESA NI IMPLICA UNA GARANTA DE QUE LOS
PRODUCTOS SEAN DE BUENA CALIDAD, O QUE SE ADAPTEN E UN PROPSITO EN ESPECIAL, NI QUE LOS PRODUCTOS ESTN NECESARIAMENTE DE ACUERDO CON LAS ILUSTRACIONES O
DESCRIPCIONES. CON EXCEPCIN DE LO QUE SE DETALLA A CONTINUACIN, NINGUNA GARANTA NI AFIRMACIN DE HECHO, EXPRESA O IMPLCITA, APARTE DE LO QUE SE INCLUYE EN
LA GARANTA LIMITADA EST HECHA O AUTORIZADA POR DAYTON.
Asesora Tcnica y Recomendaciones, Exencin de Responsabilidad. No obstante las prcticas, tratos o costumbre del oficio anteriores, las ventas no incluirn asesora o asistencia
tcnica, o el diseo del sistema. Dayton no asume obligaciones ni responsabilidades debido a recomendaciones, opiniones o asesoras no autorizadas en cuanto a la eleccin, la instalacin
o el uso de productos.
Aptitud del Producto. Muchas jurisdicciones tienen cdigos y ordenanzas que regulan las ventas, la construccin, la instalacin, y/o el uso de productos para ciertos propsitos, que
pueden variar con respecto a los de las reas vecinas. Si bien se hacen intentos para garantizar que los productos Dayton cumplan tales cdigos, Dayton no garantiza su cumplimiento y
no puede ser responsable por la manera en que se instalen o usen los productos. Antes de la compra y del uso de un producto, revise sus aplicaciones y todos los cdigos, y reglamentos
nacionales y locales pertinentes, y asegrese de que el producto, su instalacin y su uso estn en conformidad con ellos.
Ciertos aspectos de la denegacin no se aplican a productos del consumidor; por ej., (a) algunas jurisdicciones no permiten la exclusin o la limitacin de daos accidentales o resultantes,
por lo que la limitacin o exclusin mencionadas anteriormente, pueden no aplicarse a usted; (b) adems, algunas jurisdicciones no permiten una limitacin sobre la duracin de una
garanta implcita, en consecuencia, la limitacin mencionada anteriormente puede no aplicarse a usted; y (c) por ley, durante el perodo de esta Garanta Limitada, cualquier garanta
implcita de comerciabilidad o aptitud para un propsito en particular que se aplique a productos del consumidor adquiridos por consumidores, no puede ser excluda ni rechazada.
Disposicin Inmediata. Se realizar un esfuerzo de buena fe para corregir o realizar otros ajustes de manera oportuna con respecto a cualquier producto que se demuestra que tenga
defectos dentro de la garanta limitada. En caso de existir un producto con fallas dentro de la garanta limitada, escriba o llame al distribuidor a quien le compr el producto. ste le
indicar qu hacer. Si el problema no se resuelve de manera satisfactoria, escriba a Dayton a la direccin que figura a continuacin, indicando nombre del distribuidor, direccin, fecha y
nmero de la factura del distribuidor, y describa la naturaleza de la falla. Ttulo y riesgo de prdida pasan al comprador en la entrega a la compaa de transporte. Si el producto se da
durante el transporte, presente el reclamo al transporte.
Fabricado por Dayton Electric Mfg. Co., 5959 W. Howard St., Niles, Illinois 60714 U.S.A.

Fabricado para Dayton Electric Mfg. Co.


Niles, Illinois 60714 EE.UU.

FireDampRdRev1_EN_ES_FR.indd 4 9/30/08 2:59:29 PM


Manuel dutilisation et de pices dtaches de Dayton 2TFZ4 2TFZ9

Veuillez lire et conserver ces instructions. Lisez avez attention avant dessayer dassembler, dinstaller, dutiliser ou
dentretenir le produit dcrit. Pour votre protection et celle des autres, respectez toutes les informations de scurit. Toute infraction ces
instructions peut provoquer des blessures corporelles et des dommages matriels ! Conservez ces instructions pour consultation ultrieure.

Registres coupe-feu de
Dayton ronds

Description Accessoires en option


REGISTRES COUPE-FEU DYNAMIQUES
Description Rf. pice
Les registres coupe-feu dynamique Dayton sont conus pour tre utiliss dans les systmes de
chauffage, ventilation et climatisation, qui restent oprationnels en cas dincendie jusqu un lment fusible 74 C : 2TGJ3
maximum de 1,5 heure. Lcoulement dair travers ces registres peut se faire dans les deux Ces modles sont destins tre poss en conformit
sens. Ils se posent horizontalement ou verticalement et se ferment au moyen dun ressort en avec les exigences sur les registres coupe-feu tablies
acier. Ils prsentent une capacit de pression nominale de 1 kPa et une vitesse nominale de par :
10,2 m/s. NFPA - National Fire Protection Association
Le modle DFDRHV1 est class
BOCA - National Building Codes
pour les applications de blocage du
Dimensions et caractristiques feu et de la fume (UL 555). ICBO - Uniform Building Codes
Fichier n R26094 SBCCI - Standard Building Codes
(Voir la Figure 1) CSFM - California State Fire Marshal
Rf. Dia. nominal Section libre
Bride de retenue
pice gaine registre (cm ) 2

(facultative) Dgagement pour dilatation


Bride de retenue
2TFZ4 10,2 cm 59,5 Verrou de clapet
Zone de 5,1
2TFZ5 15,2 148,6 raccordement cm Porte daccs du
mme ct que
de gaine le verrou de clapet
2TFZ6 20,3 279,6
coulement
2TFZ7 25,4 450,6 dair

2TFZ8 30,5 602,9 34,6 cm Zone de


raccordement
5,1
cm de gaine
2TFZ9 35,6 845,4
Dia.
REMARQUE : Taille relle du registre rduite de 3 mm NE PAS PLACER LA
BRIDE DE RETENUE
Figure 1 Dimensions DANS CETTE GORGE

15,2 cm 15,2 cm
maxi. maxi.
Dballage Pose Mur

1. Vrifier labsence de tout dommage La pose, le dpannage Longueur manchon

ventuellement caus par le transport et et le remplacement de Figure 2 Dgagements requis


pices doivent tre effectus exclusivement
adresser toute rclamation ce sujet au par du personnel qualifi. Montant bois Montant mtal
transporteur.
1. Dcouper dans le mur/plancher une
2. Vrifier que toutes les pices commandes, ouverture qui est suprieure dun
y compris les accessoires, sont prsentes. minimum de 22,3 mm au diamtre
3. Les registres doivent tre gards propres extrieur du registre pour permettre sa Bti de
et secs. Il est fortement conseill de les dilatation en cas de chaleur intense. Voir registre
2,5 cm
entreposer lintrieur, labri de la la Figure 2. mini.

salet, de la poussire et des intempries. 2. Prparer louverture.


Ne pas entreposer au-dessus de 38 C. F
a. Encadrer louverture comme sur la NE PAS PLACER LA BRIDE DE RETENUE DANS CETTE
Informations gnrales sur la Figure 3. GORGE POUR LES POSES SUR MTAL OU SUR BOIS
R
scurit b. Fixer les plaques de parement de pltre Figure 3 Ouvertures murales A
Les poses, rglages, tous les 30,5 cm sur tous les montants et
modifications, lisses qui entourent louverture. Voir la N
61,0 cm 61,0 cm
Lisse de
entretiens et rparations incorrects peuvent Figure 4. maximum
(montants
mtal)
maximum
(montants
mtal)
plafond
provoquer des dgts matriels, des blessures
ou la mort.
3. Introduire lensemble registre/manchon 30,5 cm
A
dans louverture jusqu la profondeur
1. Lire et respecter toutes les instructions et qui convient. Voir la profondeur I
marques de mise en garde. recommande la Figure 2. S
61,0 cm
REMARQUE : Certaines exigences de ces REMARQUE : La profondeur dinsertion maximum
instructions ont un caractre obligatoire. Ces maximale ou minimale recommande peut
instructions snt conformes aux exigences de tre dpasse condition que laxe mdian
UL 555. du clapet de registre reste dans le plan du 2 vis tte
bombe
5 cm

5 cm
2. La pose doit tre conforme aux exigences mur/plancher. Lisse de 40,6 cm
maximum
40,6 cm
maximum
plancher
de la norme sur la pose de systmes de (montants
bois)
(montants
bois)

climatisation et de ventilation NFPA 90A.


Figure 4 Fixation du parement

Form 5S6146 Imprim aux tats-Unis 471969


04632 Rv. 1er aot 2008
0808/325/VCPVP

FireDampRdRev1_EN_ES_FR.indd 5 9/30/08 2:59:29 PM


Manuel dutilisation et de pices dtaches de Dayton 2TFZ4 2TFZ9

Registres coupe-feu de Dayton ronds

Pose (suite) crou


REMARQUE : Le type de raccord requis entre
la gaine et la manchon dpend de lpaisseur
Ne pas enfoncer de du manchon fourni. Voir la Figure 6.
vis dans le bti du
registre, sauf pour le raccordement de gaine Type de raccord Dimension de paisseur
moins de 5,1 mm de lextrmit du bti. gaine-manchon gaine maximale manchon
REMARQUE : Tous les registres sont fournis Bride de
Rigide ou 61,0 cm 10
retenue
avec un manchon prassembl et peuvent sparable 14
tre poss sans ncessiter de manchons 16
supplmentaires. Vis de serrage
Sparable 61,0 cm 20
REMARQUE : Le manchon peut dpasser de Figure 5 Bride de retenue
15,2 cm de part et dautre du mur/plancher. Important : Lpaisseur du manchon ne doit pas tre
REMARQUE : Ne pas placer la bride de infrieure lpaisseur de la gaine de raccordement.
4. Fixer lensemble registre/manchon La norme UL 555 prvoit que toutes les gaines se
retenue dans la gorge du bti de registre.
louverture du mur/plancher laide de la nissent sur les manchons ou btis de registres
Voir la Figure 2. coupe-feu.
bride de retenue unique fournie.
c. Vrifier la position du registre et
a. Utiliser la visserie fournie pour Figure 6 paisseur de manchon
lorientation du clapet, puis serrer la
assembler les deux (2) demi-brides minimale
vis de la bride de retenue. La bride de
de retenue lune lautre sur le ct
retenue doit chevaucher louverture
oppos de la vis de serrage. Voir la a. Pour les gaines de diamtre 55,9 cm,
du mur/plancher sur un minimum de
Figure 5. utiliser trois (3) vis tle n8. Pour les
2,5 cm.
b. Enfiler la bride de retenue sur le gaines de diamtre > 55,9 cm, utiliser
d. Fixer la bride de retenue aux quatre (4) cinq (5) vis tle n8.
registre, avec la vis de serrage place
coins et moins de 19 mm du centre sur
vers lextrieur du mur ou du plancher. REMARQUE : Tous les raccords sparables
le mur/plancher avec des vis adaptes
La bride de retenue est destine tre dcrits doivent comporter un mastic
(vis tle n8 minimum).
pose contre le mur/plancher pour dtanchit, ladhsif dtanchit PA2084T
maintenir le registre dans louverture 5. Raccorder la gaine au manchon du registre fabriqu par Precision DP1010 ou le mastic
laide dun raccord qui convient. leau de Design Polymetrics, conformment
aux recommandations SMACNA.

GARANTIE LIMITE
GARANTIE LIMITE DE UN AN DE DAYTON. LES MODLES REGISTRES COUPE-FEU DE DAYTON RONDS DE DAYTON COUVERTS DANS CE MANUEL SONT GARANTIS LUTILISATEUR

DORIGINE PAR DAYTON ELECTRIC MFG. CO. (DAYTON), CONTRE TOUT DFAUT DE FABRICATION OU DE MATRIAUX, LORS DUNE UTILISATION NORMALE, ET CELA PENDANT UN AN APRS LA
DATE DACHAT. TOUTE PICE, DONT LES MATRIAUX OU LA MAIN DOUVRE SERONT JUGS DFECTUEUX, ET QUI SERA RENVOYE PORT PAY, UN CENTRE DE RPARATION AUTORIS PAR
DAYTON, SERA, TITRE DE SOLUTION EXCLUSIVE, SOIT RPARE, SOIT REMPLACE PAR DAYTON. POUR LE PROCD DE RCLAMATION SOUS GARANTIE LIMIT, REPORTEZ-VOUS LA CLAUSE
DE DISPOSITION PROMPTE CI-DESSOUS. CETTE GARANTIE LIMITE DONNE AUX ACHETEURS DES DROITS LGAUX SPCIFIQUES QUI VARIENT DE JURIDICTION JURIDICTION.
LIMITES DE RESPONSABILIT. LA RESPONSABILIT DE DAYTON, DANS LES LIMITES PERMISES PAR LA LOI, POUR LES DOMMAGES INDIRECTS OU FORTUITS EST EXPRESSEMENT DNIE.
DANS TOUS LES CAS LA RESPONSABILIT DE DAYTON EST LIMITE ET NE DPASSERA PAS LA VALEUR DU PRIX DACHAT PAY.
DSISTEMENT DE GARANTIE. DE DILIGENTS EFFORTS SONT FAITS POUR FOURNIR AVEC PRCISION LES INFORMATIONS ET ILLUSTRATIONS DES PRODUITS DCRITS DANS CETTE
F BROCHURE ; CEPENDANT, DE TELLES INFORMATIONS ET ILLUSTRATIONS SONT POUR LA SEULE RAISON DIDENTIFICATION, ET NEXPRIMENT NI NIMPLIQUENT QUE LES PRODUITS SONT
COMMERCIALISABLES, OU ADAPTABLES UN BESOIN PARTICULIER, NI QUE CES PRODUITS SONT NCESSAIREMENT CONFORMES AUX ILLUSTRATIONS OU DESCRIPTIONS. SAUF POUR CE
R QUI SUIT, AUCUNE GARANTIE OU AFFIRMATION DE FAIT, NONCE OU IMPLICITE, AUTRE QUE CE QUI EST NONC DANS LA GARANTIE LIMITE
A CI-DESSUS NEST FAITE OU AUTORISE PAR DAYTON.
Dsistement sur les conseils techniques et les recommandations. Peu importe les pratiques ou ngociations antrieures ou les usages commerciaux, les ventes nincluent pas loffre
N de conseils techniques ou dassistance ou encore de conception de systme. Dayton na aucune obligation ou responsabilit quant aux recommandations non autorises, aux opinions et aux
suggestions relatives au choix, linstallation ou lutilisation des produits.

Conformit du produit. De nombreuses juridictions ont des codes et rglements qui gouvernent les ventes, constructions, installations et/ou utilisations de produits pour certains usages qui
A peuvent varier par rapport ceux dune zone voisine. Bien que Dayton essaie de sassurer que ses produits saccordent avec ces codes, Dayton ne peut garantir cet accord, et ne peut tre juge
responsable pour la faon dont le produit est install ou utilis. Avant lachat et lusage dun produit, revoir les applications de ce produit, ainsi que tous les codes et rglements nationaux et
I locaux applicables, et sassurer que le produit, son installation et son usage sont en accord avec eux.

S Certains aspects de dsistement ne sont pas applicables aux produits pour consommateur ; ex : (a) certaines juridictions ne permettent pas lexclusion ou la limitation des dommages indirects
ou fortuits et donc la limitation ou exclusion ci-dessus peut ne pas sappliquer dans le cas prsent ; (b) galement, certaines juridictions nautorisent pas de limitations de dure de la garantie
implicite, en consquence, la limitation ci-dessus peut ne pas sappliquer dans le cas prsent ; et (c) par force de loi, pendant la priode de cette Garantie Limite, toutes garanties impliques
de commerciabilit ou dadaptabilit un besoin particulier applicables aux produits de consommateurs achets par des consommateurs, peuvent ne pas tre exclues ni autrement dsistes.
Disposition prompte. Un effort de bonne foi sera fait pour corriger ou ajuster rapidement tout produit prouv dfectueux pendant la priode de la garantie limite. Pour tout produit
considr dfectueux pendant la priode de garantie limite, contacter tout dabord le concessionnaire o lappareil a t achet. Le concessionnaire doit donner des instructions
supplmentaires. Sil est impossible de rsoudre le problme de faon satisfaisante, crire Dayton ladresse ci-dessous, en indiquant le nom et ladresse du concessionnaire, la date et le
numro de la facture du concessionnaire, et en dcrivant la nature du dfaut. Le titre et le risque de perte passent lacheteur au moment de la livraison par le transporteur. Si le produit a t
endommag pendant le transport, une rclamation doit tre faite auprs du transporteur.
Fabriqu pour Dayton Electric Mfg. Co., 5959 W. Howard St., Niles, Illinois 60714-4014 tats-Unis

Fabriqu pour Dayton Electric Mfg. Co.


Niles, Illinois 60714 tats-Unis

FireDampRdRev1_EN_ES_FR.indd 6 9/30/08 2:59:31 PM


Dayton Operating Instructions and Parts Manual
Manual de Instrucciones de Operacin y Lista de Partes Dayton
Manuel dutilisation et de pices dtaches de Dayton 2TFZ4 thru 2TFZ9

Notes/Notas/Notes

E
N
G
L
I
S
H

E
S
P
A

O
L

F
R
A
N

A
I
S

FireDampRdRev1_EN_ES_FR.indd 7 9/30/08 2:59:31 PM


Dayton Operating Instructions and Parts Manual
Manual de Instrucciones de Operacin y Lista de Partes Dayton
Manuel dutilisation et de pices dtaches Dayton 2TFZ4 thru 2TFZ9