Sei sulla pagina 1di 2

SITE TEST REPORT DATE : 1/6/2016

NCC
132KV SALBOUKH 9018 132KV SALBOUKH 9018
CT Secondary Injection Test Report CT Secondary Injection Test Report
CT Details:

PANEL NO BCT Class Adopted Ratio Function


LCP (GT-03) 13 PX 3000/1A 87T1

Current Injected:
IN 1A

Panel LCP (GT 03) 6XGT-02.1405+R1 6XGT-02.1405+R1 6XGT-02.1405+R1 6XGT-02.1405+R1


Phas
Terminals Value(A) Terminals Value(A) Terminals Value(A) Terminals Value(A) Terminals Value(A)
e
IN X9:48 0.994 X1C:1 0.982 TS2:17,18 0.992 87T1:C14 0.992
87T1 DISPLAY 0.991
INE X9:50 0.974 X1C:3 0.990 TS2:19,20 0.990 87T1:C13 0.987

LOOP BURDEN:
PHASE CURRENT(A) VOLTAGE(V) BURDEN (VA)
IN-INE 1 0.723 0.723

Eqpt : Feja 300 Eqpt : Digital Clamp Meter Eqpt : Digital Multi Meter Fluke
Test Inst. Used ID# : 7601706 ID# : 43651 ID# : 30850258
Calibration Due Date :2-03-2017 Calibration Due Date : 18-08-2016 Calibration Due Date : 08-10-2016
Tested By Witnessed By
Company Name: Abdullah Sharif XER/001 Company Name: R.RIYAS
Xervon NG-CSD
Signature: Signature:
SITE TEST REPORT DATE : 1/6/2016

NCC
132KV SALBOUKH 9018 132KV SALBOUKH 9018
CT Secondary Injection Test Report CT Secondary Injection Test Report

LOOP RESISTANCE EXCLUDING CT


PHASE RESISTANCE()
Single point Earthing is checked:
IN-INE 0.9 Star point is verified :
T.B shorting and Isolation Facility is Checked:
Color coding of external wires is checked:

Eqpt : Feja 300 Eqpt : Digital Clamp Meter Eqpt : Digital Multi Meter Fluke
Test Inst. Used ID# : 7601706 ID# : 43651 ID# : 30850258
Calibration Due Date :2-03-2017 Calibration Due Date : 18-08-2016 Calibration Due Date : 08-10-2016
Tested By Witnessed By
Company Name: Abdullah Sharif XER/001 Company Name: R.RIYAS
Xervon NG-CSD
Signature: Signature: