Bulletin 140U

Molded Case Circuit Breakers


Overview
Bulletin 140U Molded Case Circuit Breakers Product Selection
151200 A Molded Case Circuit Breakers 125 A H-Frame .............. 41
Thermal-Magnetic 15800 A 250 A J-Frame ............... 45
Electronic 701200 A 400 A K-Frame .............. 49
-LS Long Time/Short Time 600 A Q-Frame .............. 53
-LSI Long Time/Short Time/High Instantaneous 800 A M-Frame .............. 57
-LSG Long Time/Short Time/Ground Fault 1200 A N-Frame ............ 61
-LSIG Long Time/Short Time/High Instantaneous/Ground Fault Conformity to Standards
Molded Case Switches 1251200 A UL 489
Factory- or field-installed accessories CSA 22.2, No. 5
Flex cable operating mechanisms IEC 60947-2
Rotary variable-depth operating mechanisms
High interrupting ratings in compact dimensions Approvals
Globally rated and approved product line for worldwide application UL Listed
CSA Certified
CE
KEMA-KEUR

Product Line Overview

Frame Reference H-Frame J-Frame K-Frame Q-Frame M-Frame N-Frame


Max. Current In 125 A 250 A 400 A 600 A 800 A 1200 A
Current Range 15125 A 70250 A 100400 A 300600 A 300800 A 6001200 A
Thermal Magnetic
Electronic:
LS
LSI
LSG
LSIG
Interrupting Ratings:
380415V (Icu) 25 40 70 25 40 70 40 65 100 45 70 50 70 50 70 100
480V 25 35 65 25 35 65 35 65 100 35 65 50 65 50 65 100
600V 18 22 25 18 18 25 25 35 50 25 35 25 35 25 35 50
690V (Icu) 3 4 6 6 6 7 10 13 18 20 25 20 25 20 25 30
Molded Case Switches
Flex Cable Operators
Rotary Operators
Internal Control Modules
(Field installed)
Standards Compliance
UL 498
CSA 22.2, No. 5
IEC 60947-2
CE
KEMA-KEUR

38
Bulletin 140U
Molded Case Circuit Breakers
Catalog Number Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce
a valid cat. no. Refer to the tables on the following pages for descriptions of options.

Complete Circuit Breaker Assemblies

140U - H 6 C 3 C50 H

Bulletin No. Voltage Code


Code Description See the following pages for
140U Molded Case Circuit Breaker voltage code descriptions:
H-Frame Page 41
J-Frame Page 45
K-Frame Page 49
Frame/Rating
Code Description Q-Frame Page 53
H 125 A M-Frame Page 57
J 250 A N-Frame Page 61
K 400 A
Q 600 A
M 800 A
N 1200 A Internal Control Modules
Code Description
A 1 Auxiliary contact
B 2 Auxiliary contacts
Interrupting Rating/Breaking Capacity
(based on Ic at 480V) D 1 Alarm contact

Code Description F 1 Auxiliary + 1 Alarm contact

2 2029 kA G Undervoltage release only

3 3039 kA P Shunt trip only

5 5059 kA Control Module Combinations

6 6069 kA Code Description

8 8089 kA H 1 Auxiliary contact + undervoltage release

0 100 kA J 2 Auxiliary contacts + undervoltage release


1 Auxiliary + 1 Alarm contact +
L undervoltage release
N 1 Alarm contact + undervoltage release

Protection Type Q 1 Auxiliary contact + shunt trip

Code Description R 2 Auxiliary contacts + shunt trip

C Fixed Thermal/Fixed Magnetic T 1 Auxiliary + 1 Alarm contact + shunt trip

D Fixed Thermal/Adjust Magnetic V 1 Alarm contact + shunt trip

E Adjust Thermal/Fixed Magnetic


F Adjust Thermal/Adjust Magnetic
G Electronic (LSG) Long, short, ground fault
H Electronic (LSI) Long, short, high instant Current Range
I Electronic (LSIG) Long, short, high instant, ground fault Code Description
L Electronic (LS) Long and Short time C 10 rr. A
S Molded Case Switch (Isolator) D 100 rr0 A
E 1000 rr00 A

Poles
Code Description
3 3 poles

39
Bulletin 140U
Molded Case Circuit Breakers
Catalog Number Explanation
Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce
a valid cat. no. Refer to the tables on the following pages for descriptions of options.

Frames

140U - J 3 X 3

Bulletin No. Poles


Code Description Code Description
140U Molded Case Circuit Breaker 3 3 poles

Frame/Rating Interrupting Rating/Breaking Capacity Protection Type


Code Description (based on Ic at 480V) Code Description
J 250 A Code Description X Frame Only
K 400 A 2 2029 kA
L 600 A 3 3039 kA
M 800 A 5 5059 kA
6 6069 kA
8 8089 kA
0 100 kA

Trip Units

140U - J T F 3 C50

Bulletin No. Current Range

Code Description Code Description

140U Molded Case Circuit Breaker C 10 rr. A


D 100 rr0 A
E 1000 rr00 A

Frame/Rating
Code Description Poles
J 250 A Code Description
K 400 A Interrupting Rating/Breaking Capacity
(based on Ic at 480V) 3 3 poles
Q 600 A
Code Description
M 800 A
T Trip Unit

Protection Type
Code Description
C Fixed Thermal/Fixed Magnetic
D Fixed Thermal/Adjust Magnetic
E Adjust Thermal/Fixed Magnetic
F Adjust Thermal/Adjust Magnetic
G Electronic (LSG) Long, short, ground fault
H Electronic (LSI) Long, short, high instant
I Electronic (LSIG) Long, short, high instant, ground fault
L Electronic (LS) Long and Short time
S Molded Case Switch (isolator)

40
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 125 A, H-Frame

UL 489 Terminal box lugs provided as standard


CSA 22.2, No. 5
IEC 60947-2
CE
KEMA-KEUR

25/25 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic


Rated Thermal Trip Magnetic Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Current [A] Trip [A] Icu /Ics [kA] [kA] Cat. No.
In [A] Ir = In (Fixed) Im = 10 x In 220240V 380415V 500V 690V 240V 480V 600/347V
15 15 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C15
20 20 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C20
25 25 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C25
30 30 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C30
35 35 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C35
40 40 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C40
45 45 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C45
50 50 500 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C50
60 60 600 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C60
70 70 700 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C70
80 80 800 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C80
90 90 900 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-C90
100 100 1000 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D10
110 110 1100 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D11
125 125 1250 35 35 25 25 22 17 3 3 35 25 18 140U-H2C3-D12

40/35 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic


Rated Thermal Trip Magnetic Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Current [A] Trip [A] Icu /Ics [kA] [kA] Cat. No.
In [A] Ir = In (Fixed) Im = 10 x In 220240V 380415V 500V 690V 240V 480V 600/347V
15 15 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C15
20 20 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C20
25 25 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C25
30 30 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C30
35 35 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C35
40 40 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C40
45 45 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C45
50 50 500 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C50
60 60 600 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C60
70 70 700 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C70
80 80 800 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C80
90 90 900 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-C90
100 100 1000 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D10
110 110 1100 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D11
125 125 1250 85 43 40 30 25 18 4 3 85 35 22 140U-H3C3-D12

70/65 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic


l

Rated Thermal Trip Magnetic Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Current [A] Trip [A] Icu /Ics [kA] [kA] Cat. No.
In [A] Ir = In (Fixed) Im = 10 x In 220240V 380415V 500V 690V 240V 480V 600/347V
15 15 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C15
20 20 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C20
25 25 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C25
30 30 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C30
35 35 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C35
40 40 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C40
45 45 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C45
50 50 500 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C50
60 60 600 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C60
70 70 700 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C70
80 80 800 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C80
90 90 900 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-C90
100 100 1000 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D10
110 110 1100 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D11
125 125 1250 100 50 70 35 35 18 6 3 100 65 25 140U-H6C3-D12

Molded Case Switch UL 1087


Rated Magnetic Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Thermal Trip
Current Trip [A] Icu /Ics [kA] [kA] Cat. No.
Ir = In [A]
In [A] Im = 10 x In 220240V 380415V 500V 690V 240V 480V 600/347V
125 None 1250 100 50 70 35 35 18 6 3 100 65 25 140U-H6S3-D12

41
Bulletin 140U
Molded Case Circuit Breakers
Accessories 125 A, H-FrameInternal Control Modules Field Installed

Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-H-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-H-EA2
Right side only

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)- 140U-H-ER1


the breaker is in the 1B (break) AL B M B M B M

TRIPPED state I>


1c 1c 1c

Right side only

OFF ON TRIP
Auxiliary/Alarm Contact (AX/AL) 1b 1a 1b 1a 1b 1a
Combination (1) 1a-1b AX

Combination of auxiliary (1) 1M (make)- AL 1c


B M
1c
B M
1c
B M 140U-H-EA1R1
1B (break) I>
contact and alarm contact 1c 1c 1c

Right side only

1260V, 140U-H-SNJ
Shunt Trip (SNT) 50/60/DC
Provides remote tripping of S1
the circuit breaker 110240V, SNT
140U-H-SND
Undervoltage trip not 50/60/DC
available when shunt trip is I> S2
used 380600V,
Left side only 140U-H-SNB
50/60
24V
140U-H-UJ
50/60/DC
Undervoltage Release (UVT)
Automatically trips breaker 110127V,
140U-H-UD
50/60 U1
when voltage falls between UVT
preset value, 3570% 208240V, U>
140U-H-UA
50/60
Shunt trip is not available I> U2
when undervoltage release is 380500V,
50/60 140U-H-UB
used Left side only
525600V,
50/60 140U-H-UC

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Auxiliary and Shunt Trip Undervoltage Release


Suffix Suffix Suffix
Alarm Contacts Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX + (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1260 110240 380600 Voltage [V] 24 110127 208240 380500 525600
AC, AC,
50/60 Hz J D B J D A B C
50/60 Hz
DC J D DC J

For additional voltages, consult your local Allen-Bradley distributor.

42
Bulletin 140U
Molded Case Circuit Breakers
Accessories 125 A, H-Frame, Continued
External Accessories
Description Cat. No.

0.25 in. (6.4 mm) Diameter Cable Entry 140U-H-TC2

Terminal End Cover Qty: 1


0.41 in. (10.4 mm) Diameter Cable Entry 140U-H-TC4

Terminal Shields IP20 Ingress Protection Qty: 1 140U-H-TS

3 ft. (0.9 m) Cable 140U-H-FCX03

4 ft. (1.3 m) Cable 140U-H-FCX04


Non-Metallic Type 1/3/12/4/4X
Flange-Mount Operating Handle
6 ft. (1.8 m) Cable 140U-H-FCX06

10 ft. (3.0 m) Cable 140U-H-FCX10


Flex-Cable Operating Mechanism
3 ft. (0.9 m) Cable 140U-H-FCS03

4 ft. (1.3 m) Cable 140U-H-FCS04


Stainless Steel Type 4/4X
Flange-Mount Operating Handle
6 ft. (1.8 m) Cable 140U-H-FCS06

10 ft. (3.0 m) Cable 140U-H-FCS10

Black Handle 140U-H-RM12B

Rotary, Variable-Depth Operating Rotary Handle Type 1/12


Mechanism 12 in. (305 mm) operating rod
Red/Yellow Handle 140U-H-RM12R

Black Handle 140U-H-RCB

Rotary, Direct Couple Operating Rotary Handle Type 1


Mechanism Breaker Mounted
Red/Yellow Handle 140U-H-RCR

Provides 3-phase connections for


End Cap Kit terminal or bolt-on connections Qty: 1 140U-H-ECM
Metric Hardware provided

Provides additional phase clearance


Phase Barriers Qty: 2 140U-H-PB
when special connections are required

Padlocking Hasp
Padlock Kit Qty: 1 140U-H-PL
Lock-OFF only

Allows H-frame MCCB to mount to


DIN Rail Adapter Qty: 1 140U-H-DRA
35 mm DIN Rail

43
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 125 A, H-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Line End 4 .17 (4.32) x .19 (4.83) Dia. .78


Slot for #6 Mounting Screws (19.81)
.09
.45 .50 .50 (2.29)
(11.43) (12.70) (12.70) 6 .35 (8.90) Dia.

.56 .58
(14.22) (14.73)

.22
(5.59)

Attachment
Leads Side
Exit Point

5.50
Push to (139.70)
Trip Button
3.81
(96.78) 3.03
(76.96)

1.73 Handle
(43.94) R2.13 C
L

.15
(3.81)
.17
(4.32)
2.18
1.38 E (55.37)
(35.05) .22
.17 D (5.59)
(4.32) A
1.08 B
.72 (27.43)
(18.29) .55 .57
(13.97) (14.48)

.09
(2.29) .03
.20 (5.08) Dia. .77
(19.56) (0.76)
Thru Conductors 1.00 1.00
(25.40) (25.40) 1.42
(36.07)
1.21 2.77
(30.73) (70.36)
2.93
2.99 (74.42)
(75.95)
C

3.00
(76.20)
1.50
(38.10)
.94
(23.88) Breaker Status Dimension
.44
(11.18) A B C D E
.47
(11.94)
Attachment On 2.71 2.53 3.46 2.83 2.75
Leads Rear
Exit Point (68.83) (64.26) (87.88) (71.88) (69.85)
Off 1.54 1.62 3.46 1.66 1.84
(39.12) (41.15) (87.88) (42.16) (46.74)
Tripped 2.33 2.23 3.54 2.46 2.45
(59.18) (56.64) (89.92) (67.48) (62.23)
Reset 1.39 1.49 3.42 1.52 1.70
(35.31) (37.85) (86.87) (38.61) (43.18)

1.44
(36.58)

.67
(17.02)

44
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 250 A, J-Frame

UL 489 Terminal box lugs must be ordered


CSA 22.2, No. 5 separately. See page 47
IEC 60947-2
CE
KEMA-KEUR (Pending)

Breaker Frames
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current
Icu /Ics [kA] [kA] Cat. No.
In [A]
220240V 380415V 500V 690V 240V 480V 600V
65 65 25 25 20 12 6 3 65 25 18 140U-J2X3
250 85 85 40 40 35 20 6 3 85 35 18 140U-J3X3
100 100 70 70 42 20 7 3 100 65 25 140U-J6X3

Trip Units
Thermal-Magnetic Electronic
Rated Adjustment Range [A] Rated Adjustment Range [A]
Protection
Current Thermal Trip [A] Magnetic Trip Cat. No. Current Thermal Trip Magnetic Trip Cat. No.
Type
In [A] Ir = In (Fixed) Im = 510 x In In [A] Ir = 0.41.0 x In Im = 214 x In
90 90 450900 140U-JTD3-C90 50 2050 40700 LS 140U-JTL3-C50
100 100 5001000 140U-JTD3-D10 50 2050 40700 LSI 140U-JTH3-C50
125 125 6001250 140U-JTD3-D12 100 40100 801400 LS 140U-JTL3-D10
150 150 7501500 140U-JTD3-D15 100 40100 801400 LSI 140U-JTH3-D10
175 175 8751750 140U-JTD3-D17 160 63160 1262240 LS 140U-JTL3-D16
200 200 10002000 140U-JTD3-D20 160 63160 1262240 LSI 140U-JTH3-D16
225 225 11252250 140U-JTD3-D22 250 100250 2003500 LS 140U-JTL3-D25
250 250 12502500 140U-JTD3-D25 250 100250 2003500 LSI 140U-JTH3-D25

Assembled Circuit Breakers, Thermal-Magnetic Trip Units


400/480V 400/480V 400/480V
Rated Current In [A] Cat. No. Cat. No. Cat. No.
[kA] [kA] [kA]
90 25/25 140U-J2D3-C90 40/35 140U-J3D3-C90 70/65 140U-J6D3-C90
100 25/25 140U-J2D3-D10 40/35 140U-J3D3-D10 70/65 140U-J6D3-D10
125 25/25 140U-J2D3-D12 40/35 140U-J3D3-D12 70/65 140U-J6D3-D12
150 25/25 140U-J2D3-D15 40/35 140U-J3D3-D15 70/65 140U-J6D3-D15
175 25/25 140U-J2D3-D17 40/35 140U-J3D3-D17 70/65 140U-J6D3-D17
200 25/25 140U-J2D3-D20 40/35 140U-J3D3-D20 70/65 140U-J6D3-D20
225 25/25 140U-J2D3-D22 40/35 140U-J3D3-D22 70/65 140U-J6D3-D22
250 25/25 140U-J2D3-D25 40/35 140U-J3D3-D25 70/65 140U-J6D3-D25

Assembled Circuit Breakers, Electronic Trip Units


Rated Current 400/480V 400/480V 400/480V
Protection Type Cat. No. Cat. No. Cat. No.
In [A] [kA] [kA] [kA]
50 LS 25/25 140U-J2L3-C50 40/35 140U-J3L3-C50 70/65 140U-J6L3-C50
50 LSI 25/25 140U-J2H3-C50 40/35 140U-J3H3-C50 70/65 140U-J6H3-C50
100 LS 25/25 140U-J2L3-D10 40/35 140U-J3L3-D10 70/65 140U-J6L3-D10
100 LSI 25/25 140U-J2H3-D10 40/35 140U-J3H3-D10 70/65 140U-J6H3-D10
160 LS 25/25 140U-J2L3-D16 40/35 140U-J3L3-D16 70/65 140U-J6L3-D16
160 LSI 25/25 140U-J2H3-D16 40/35 140U-J3H3-D16 70/65 140U-J6H3-D16
250 LS 25/25 140U-J2L3-D25 40/35 140U-J3L3-D25 70/65 140U-J6L3-D25
250 LSI 25/25 140U-J2H3-D25 40/35 140U-J3H3-D25 70/65 140U-J6H3-D25

Molded Case Switch UL 1087

Rated Magnetic Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Thermal Trip
Current Trip [A] Icu /Ics [kA] [kA] Cat. No.
Ir = In [A]
In [A] Im = 10 x In 220240V 380415V 500V 690V 240V 480V 600V
250 None 2500 100 100 70 70 42 20 7 3 100 65 25 140U-J6S3-D25

45
Bulletin 140U
Molded Case Circuit Breakers
Accessories 250 A, J-Frame

Internal Control Modules Field Installed


Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-H-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-H-EA2
Left AND Right side

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)-


the breaker is in the 1B (break) AL B M B M B M 140U-J-ER1
TRIPPED state I>
1c 1c 1c

Right side only

OFF ON TRIP
Auxiliary/Alarm Contact (AX/AL) 1b 1a 1b 1a 1b 1a
Combination (1) 1a-1b AX

Combination of auxiliary (1) 1M (make)- AL 1c


B M
1c
B M
1c
B M 140U-J-EA1R1
1B (break) I>
contact and alarm contact 1c 1c 1c

Right side only

1260V,
Shunt Trip (SNT) 140U-H-SNJ
50/60/DC
Provides remote tripping of S1
the circuit breaker 110240V, 50/ SNT
140U-H-SND
Undervoltage trip not 60/DC
available when shunt trip is I> S2
used 380600V, 50/
Left side only 140U-H-SNB
60
24V
140U-H-UJ
50/60/DC
Undervoltage Release (UVT) 110127V, 50/
Automatically trips breaker 140U-H-UD
60
when voltage falls between U1
208240V, 50/ UVT
preset value, 3570% 60 U>
140U-H-UA
Shunt trip is not available
380500V, 50/ U2 140U-H-UB
when undervoltage release is 60
I>
used Left side only
525600V, 50/
60 140U-H-UC

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Shunt Trip Undervoltage Release


Auxiliary and Alarm Contacts Suffix Suffix Suffix
Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX + (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1260 110240 380600 Voltage [V] 24 110127 208240 380500 525600
AC, J D B AC, J D A B C
50/60 Hz 50/60 Hz
DC J D DC J

For additional voltages, consult your local Allen-Bradley distributor.

46
Bulletin 140U
Molded Case Circuit Breakers
Accessories 250 A, J-Frame, Continued
External Accessories
Description Cat. No.

Terminal Shields IP20 Ingress Protection Qty 2 140U-J-TS

3 ft. (0.9 m) Cable 140U-J-FCX03

4 ft. (1.3 m) Cable 140U-J-FCX04


Non-Metallic Type 1/3/12/4/4X
Flange-Mount Operating Handle
6 ft. (1.8 m) Cable 140U-J-FCX06

10 ft. (3.0 m) Cable 140U-J-FCX10


Flex-Cable Operating Mechanism
3 ft. (0.9 m) Cable 140U-J-FCS03

4 ft. (1.3 m) Cable 140U-J-FCS04


Stainless Steel Type 4/4X
Flange-Mount Operating Handle
6 ft. (1.8 m) Cable 140U-J-FCS06

10 ft. (3.0 m) Cable 140U-J-FCS10

Black Handle 140U-J-RM12B

Rotary, Variable-Depth Operating Rotary Handle Type 1/12


Mechanism 12 in. (305 mm) operating rod

Red/Yellow Handle 140U-J-RM12R

Black Handle 140U-J-RCB

Rotary, Direct Couple Operating Mechanism Rotary Handle Type 1


Breaker Mounted

Red/Yellow Handle 140U-J-RCR

Provides additional phase clearance


Phase Barriers when special connections are required Qty: 2 140U-J-PB

Padlocking Hasp
Padlock Kit Lock-OFF only Qty: 1 140U-J-PL

Stainless Steel Box Lugs


Copper wire only Qty: 1 140U-J-TLS1
(1) 4/0350MCM
Terminal Lugs
Aluminum Lugs
Aluminum or copper wire
(1) 4/0350MCM Qty: 1 140U-J-TLA1
(1) 25185 mm2

Provides 3-phase connections for


End Cap Kit terminal or bolt-on connections Qty:1 140U-J-ECM
Metric Hardware

47
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 250 A, J-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

5.048 .170 4.125


6.000
2.062 #8-32 TAP
4.453
4 HOLES
5.642
1.541
THERMAL ADJUSTMENT
.281 5.500
.256 3.922

.110 X .310 DEEP


.145 R 7.000 5.500
TYP(4) 4 HOLES
BREAKER H
HANDLE

.688
2.750
4.125 1.375
.664

2.062 .688
.203
1.375

FRONT CONNECTED DRILL PLAN


PUSH TO TRIP GNETIC ADJUST
.650 .897 2.906 4.125
TYP(6)
3.978 .500 2.062 .625
6 HOLES
1.188
TRIP .594
R2.656 4.0
.500

7.000
6.000 BREAKER HANDLE

4.427
3.570
3.440 3.344
1.375
3.344
3.194 .187 2.750
1.906 .188
REF 1.771 REAR CONNECTED STUDS
.624
2.062
.125 .198
.625
.625
1.000 .125
7.000
R.188 1.875

3.922
4.938
.173
BREAKER
K HANDLE

.949 .859

1.062
.949 .500

.281
2.000
4.000

.260

48
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 400 A, K-Frame

UL 489 Terminal box lugs must be ordered


CSA 22.2, No. 5 separately. See page 51
IEC 157-1
KEMA-KEUR

Breaker Frames
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current
Icu /Ics [kA] [kA] Cat. No.
In [A]
220240V 380415V 500V 690V 240V 480V 600V
65 65 40 40 30 30 10 5 65 35 25 140U-K3X3
400 100 100 65 65 50 38 13 6 100 65 35 140U-K6X3
200 200 100 100 65 49 18 9 200 100 50 140U-K0X3

Trip Units and Rating Plugs


Thermal-Magnetic Electronic
Adjustment Range [A] Adjustment Range [A]
Rated Current Rated Current
Thermal Trip [A] Magnetic Trip Cat. No. Thermal Trip Magnetic Trip Protection Type Cat. No.
In [A] In [A]
Ir = In (Fixed) Im = 510 x In Ir = 1.0 x In Im = 28 x In
100 100 5001000 140U-KTD3-D10 LS 140U-KTL3-D40
125 125 6251250 140U-KTD3-D12 400 200400 4003200 LSI 140U-KTH3-D40
150 150 7501500 140U-KTD3-D15 LSG 140U-KTG3-D40
175 175 8951750 140U-KTD3-D17
200 200 10002000 140U-KTD3-D20 Rating Plugs
225 225 11252250 140U-KTD3-D22 Thermal Trip Thermal Trip
Cat. No. Cat. No.
250 250 12502500 140U-KTD3-D25 In [A] In [A]
300 300 15003000 140U-KTD3-D30 200 140U-KRP3-D20 300 140U-KRP3-D30
350 350 17503500 140U-KTD3-D35 225 140U-KRP3-D22 350 140U-KRP3-D35
400 400 20004000 140U-KTD3-D40 250 140U-KRP3-D25 400 140U-KRP3-D40

Assembled Circuit Breakers, Thermal-Magnetic Trip Units


Rated Current 400/480V 400/480V 400/480V
Cat. No. Cat. No. Cat. No.
In [A] [kA] [kA] [kA]
100 40/35 140U-K3D3-D10 65/65 140U-K6D3-D10 100/100 140U-K0D3-D10
125 40/35 140U-K3D3-D12 65/65 140U-K6D3-D12 100/100 140U-K0D3-D12
150 40/35 140U-K3D3-D15 65/65 140U-K6D3-D15 100/100 140U-K0D3-D15
175 40/35 140U-K3D3-D17 65/65 140U-K6D3-D17 100/100 140U-K0D3-D17
200 40/35 140U-K3D3-D20 65/65 140U-K6D3-D20 100/100 140U-K0D3-D20
225 40/35 140U-K3D3-D22 65/65 140U-K6D3-D22 100/100 140U-K0D3-D22
250 40/35 140U-K3D3-D25 65/65 140U-K6D3-D25 100/100 140U-K0D3-D25
300 40/35 140U-K3D3-D30 65/65 140U-K6D3-D30 100/100 140U-K0D3-D30
350 40/35 140U-K3D3-D35 65/65 140U-K6D3-D35 100/100 140U-K0D3-D35
400 40/35 140U-K3D3-D40 65/65 140U-K6D3-D40 100/100 140U-K0D3-D40

Assembled Circuit Breakers, Electronic Trip Units


Rated Current Thermal Trip 400/480V 400/480V 400/480V
Protection Type Cat. No. Cat. No. Cat. No.
In [A] Ir = 0.51.0 x In [kA] [kA] [kA]
LS 40/35 140U-K3L3-D40 65/65 140U-K6L3-D40 100/100 140U-K0L3-D40
400 100400 LSI 40/35 140U-K3H3-D40 65/65 140U-K6H3-D40 100/100 140U-K0H3-D40
LSG 40/35 140U-K3G3-D40 65/65 140U-K6G3-D40 100/100 140U-K0G3-D40

Select proper rating plug to cover thermal trip requirement.

Molded Case Switch UL 1087


Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current Magnetic Trip
Icu /Ics [kA] [kA] Cat. No.
In [A] 10 x In
220240V 380415V 500V 690V 240V 480V 600V
400 4000 100 100 65 65 50 38 13 6 100 65 35 140U-K6S3-D40

49
Bulletin 140U
Molded Case Circuit Breakers
Accessories 400 A, K-Frame
Internal Control Modules Field Installed
Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-K-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-K-EA2
Left AND Right side

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)-


the breaker is in the 1B (break) AL B M B M B M 140U-K-ER1
TRIPPED state I>
1c 1c 1c

Right side ONLY


\

OFF ON TRIP
Auxiliary/Alarm Contact (AX/AL) 1b 1a 1b 1a 1b 1a

Combination (1) 1a-1b AX

Combination of auxiliary (1) 1M (make)- AL 1c


B M
1c
B M
1c
B M
140U-K-EA1R1
1B (break) I>

contact and alarm contact 1c 1c 1c

Right side ONLY

1224V, 140U-K-SNJ
50/60/DC
Shunt Trip (SNT) S1
Provides remote tripping of 110240V AC, SNT 140U-K-SND
the circuit breaker 110125V DC
Undervoltage trip not 380440V AC, I> S2
available when shunt trip is 140U-K-SNN
220250V DC
used Left side ONLY
480600V, 50/
140U-K-SNB
60 Hz
24V,
140U-K-UJ
Undervoltage Release (UVT) 50/60
Automatically trips breaker 110127V, 50/ U1
when voltage falls between UVT 140U-K-UD
60 U>
preset value, 3570% 208240V, 50/
Shunt trip is not available I> U2 140U-K-UA
60
when undervoltage release is
used 380500V, 50/ Left side ONLY
60 140U-K-UB

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Shunt Trip Undervoltage Release


Auxiliary and Alarm Contacts Suffix Suffix Suffix
Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX + (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1224 110240 380440 480600 Voltage [V] 24 110127 208240 380480
AC J D N B
AC
J D A B
50/60 Hz 50/60 Hz
Voltage [V] 1224 110125 220250 Voltage [V]
DC J D N DC
For additional voltages, consult your local Allen-Bradley distributor.

50
Bulletin 140U
Molded Case Circuit Breakers
Accessories 400 A, K-Frame, Continued
External Accessories
Description Cat. No.

Terminal Shields IP20 Ingress Protection Qty: 1 140U-K-TS

3 ft. (0.9 m) Cable 140U-K-FCX03

Non-Metallic Type 1/3/12/4/4X 4 ft. (1.3 m) Cable 140U-K-FCX04


Flange-Mount Operating Handle 6 ft. (1.8 m) Cable 140U-K-FCX06
10 ft. (3.0 m) Cable 140U-K-FCX10
Flex-Cable Operating Mechanism
3 ft. (0.9 m) Cable 140U-K-FCS03

Stainless Steel Type 4/4X 4 ft. (1.3 m) Cable 140U-K-FCS04


Flange-Mount Operating Handle 6 ft. (1.8 m) Cable 140U-K-FCS06
10 ft. (3.0 m) Cable 140U-K-FCS10

Black Handle 140U-K-RM12B

Rotary, Variable-Depth Operating Rotary Handle Type 1/12


Mechanism 12 in. (305 mm) operating rod

Red/Yellow Handle 140U-K-RM12R

Black Handle 140U-K-RCB

Rotary, Direct Couple Operating Mechanism Rotary Handle Type 1


Breaker Mounted
Red/Yellow Handle 140U-K-RCR

Operating Handle Extension Provides handle extension for ease Qty: 1


of operation 140U-K-OHE

Provides additional phase


Phase Barriers clearance when special Qty: 2 140U-K-PB
connections are required

Padlock Kit Padlocking Hasp 140U-K-PL


Lock-OFF only

Copper lug
Copper wire only
(1) 250500 MCM Qty: 1 140U-K-TLC1
(1) 120240 mm2
Copper lug
Copper wire only
Terminal Lugs (1) 3/0250 MCM Qty: 3 140U-K-TLC2
(1) 95120 mm2
Aluminum lug
Aluminum or copper wire
(1) 250500 MCM Qty: 1 140U-K-TLA1
(1) 120240 mm2

Provides 3-phase connections for


End Cap Kit terminal or bolt-on connections Qty: 1 140U-K-ECM
Metric Hardware

51
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 400 A, K-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Front View
5.490(139.43)
Side View
4.313
3.438
.110 (2.79) Dia. x .297 (7.54) (109.55)
.625 (15.88) (87.32) Deep, 4 Holes Accept #6
6 Holes (M3) Thread Cutting Screws

.500 1.719 .844


(12.70) (43.66) (21.44) Line End

.625 .500
(15.88) (12.70)
Trough for
Attachment .694
Leads (17.63) 1.000
2.563 (25.40)
(12.70) 2.813
1.719
(43.66) (71.45)
.188 (4.77) Dia.
.860 (21.84) C'Bore x .031 (.79)
2.063 (52.39) 3.813 43
.125 DP .147 (12.7) Dia. (96.85)

5.966(151.54)
5.000(127.00)
5.766 (146.46)
4.125 (104.78) (3.18) Hole x .500 DP to
Accept #8 (M4) .062
4.437 Thread Cutting (1.57)
(65.10)
.093 R Screws (8 Places)
(2.36) R
1.063
.188 .125 (3.18) Wide x (27.00)
7.406 (4.77) R .750 (19.05) Slots for
(112.70) 3.75 Attachment Leads
(9.52)
ON 4.000 .500
(101.60) (12.70)
.375 3.563 8.438
(9.52) (90.50) (214.33)
2.438
Contact (61.89) 8.875 3.875 R
Position (225.43) Handle (98.42) R
.750 CL
Indicators (19.05)
Red/1 - On 10.125
(257.18) .500
Green/O - Off OFF (12.70)
White - T rip 1.219
(30.96)
.250 R .209
.188
(6.35) R 1.625 1.625 C A (4.77) (5.31)
(41.28) (41.28) D B
.250 1.734
(6.35) (44.04)
1.250
(31.75) .063 2.391 39
(1.60) (60.73)

4.782(121.46)
.547 .698
.188 R (13.89) (17.73)
(4.77) R
.500
(12.70)
.250 (6.35) R
.937 .063 (1.60) .500
1.160 (12.70)
(29.49) (23.80)
Load End
.281 (7.14) Dia. Mounting Holes
4 Holes for .250-20 (M6) x 1.50
(38) Mounting Screws .500 .062
Dimensions for Extended .875 (12.70) Dia. C'Bore from T op 4.062 (1.57)
(22.25) 2.875 (73.03) Deep Load End (103.17)
Terminals and Barrier Style
Nos. 4212B60G02,
.438 2.625 (66.68) Deep Line End .438 E
(11.13) (11.13) Dia C'Bore .750 (10.05)
4212B61G02 and 1492D24H01
Deep from Bottom F

.750 (19.05)
Wide Conductor
with .391 (9.93) Dimensions Handle
Dia Hole Line Breaker
Force
and Load End Status A B C D E F
1.063
(27.00) On 5.39 5.20 5.69 5.61 4.72 4.77 30 lbs.
(136.9) (132.1) (144.5) (142.5) (119.9) (121.2) (13.61 kgs.)
3.812 Tripped 4.77 4.69 5.08 5.11 4.89 4.89 N/A
(96.82) (121.2) (119.1) (129.0) (129.8) (124.2) (124.2)
.188 Off 4.16 4.21 4.46 4.64 4.95 4.91 25 lbs.
(4.77) 2.375 (105.7) (106.9) (113.3) (117.9) (125.7) (124.7) (11.34 kgs.)
(60.33)
Reset 4.07 4.14 4.57 4.56 4.95 4.90 35 lbs.
(103.4) (105.2) (116.1) (115.8) (125.7) (124.5) (15.87 kgs.)
.766
(19.46) All handle forces measured approximately 0.125 (3.17) from top of handle.

52
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 600 A, Q-Frame

UL 489 Terminal box lugs must be ordered


CSA 22.2, No. 5 separately. See page 55
IEC 60947-2
CE
KEMA-KEUR

Breaker Frames
Breaking Capacity (50 Hz)
Rated Current In Interrupting Rating (60 Hz) [kA]
Icu /Ics [kA] Cat. No.
[A]
220240V 380415V 500V 690V 240V 480V 600V
85 85 45 45 30 30 20 10 65 35 25 140U-Q3X3
600
100 100 70 70 50 38 25 13 100 65 35 140U-Q6X3

Trip Units and Rating Plugs


Thermal-Magnetic Electronic
Adjustment Range [A] Adjustment Range [A]
Rated Current In Rated Current
Thermal Trip Magnetic Trip Cat. No. Thermal Trip Magnetic Trip Protection Type Cat. No.
[A] In [A]
Ir = In (Fixed) Im = 510 x In Ir = 0.51.0 x In Im = 28 x In
300 300 15003000 140U-QTD3-D30 LS 140U-QTL3-D60
350 350 17503500 140U-QTD3-D35 600 400600 8004800 LSI 140U-QTH3-D60
400 400 20004000 140U-QTD3-D40 LSG 140U-QTG3-D60
450 450 22504500 140U-QTD3-D45
500 500 25005000 140U-QTD3-D50 Rating Plugs
600 600 30006000 140U-QTD3-D60 Thermal Trip
Cat. No.
In [A]
400 140U-QRP3-D40
500 140U-QRP3-D50
600 140U-QRP3-D60

Assembled Circuit Breakers, Thermal-Magnetic Trip Units


Thermal Trip 400/480V 400/480V
Rated Current In [A] Cat. No. Cat. No.
Ir = In [kA] [kA]
300 300 45/35 140U-Q3D3-D30 70/65 140U-Q6D3-D30
350 350 45/35 140U-Q3D3-D35 70/65 140U-Q6D3-D35
400 400 45/35 140U-Q3D3-D40 70/65 140U-Q6D3-D40
450 450 45/35 140U-Q3D3-D45 70/65 140U-Q6D3-D45
500 500 45/35 140U-Q3D3-D50 70/65 140U-Q6D3-D50
600 600 45/35 140U-Q3D3-D60 70/65 140U-Q6D3-D60

Assembled Circuit Breakers, Electronic Trip Units


Rated Current Thermal Trip 400/480V 400/480V
Protection Type Cat. No. Cat. No.
In [A] Ir = 0.51.0 x In [kA] [kA]
LS 45/35 140U-Q3L3-D60 70/65 140U-Q6L3-D60
600 200600 LSI 45/35 140U-Q3H3-D60 70/65 140U-Q6H3-D60
LSG 45/35 140U-Q3G3-D60 70/65 140U-Q6G3-D60

Select proper rating plug to cover thermal trip requirement.

Molded Case Switch UL 1087


Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current Magnetic Trip
Icu /Ics [kA] [kA] Cat. No.
In [A] Im = 10 x In
220240V 380415V 500V 690V 240V 480V 600V
600 6000 100 100 70 70 50 38 25 13 100 65 35 140U-Q6S3-D60

53
Bulletin 140U
Molded Case Circuit Breakers
Accessories 600 A, Q-Frame
Internal Control Modules Field Installed
Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-M-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-M-EA2
Left AND Right side

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)-


the breaker is in the 1B (break) AL B M B M B M 140U-M-ER1
TRIPPED state I>
1c 1c 1c

Right side ONLY


\

OFF ON TRIP
1b 1a 1b 1a 1b 1a
AX

AL B M B M B M
1c 1c 1c
Auxiliary/Alarm Contact (AX/AL)
Combination (1) 1a-1b I>
1c 1c 1c

Combination of auxiliary (1) 1M (make)- 140U-M-EA1R1


1B (break) Right side ONLY
contact and alarm contact

1224V,
50/60/DC 140U-M-SNJ
Shunt Trip (SNT) S1
Provides remote tripping of 110240V AC, SNT
110125V DC 140U-M-SND
the circuit breaker
Undervoltage trip not 380440V AC, I> S2
available when shunt trip is 220250V DC 140U-M-SNN
used Left side ONLY
480600V,
140U-M-SNB
50/60 Hz
24V,
140U-M-UJ
50/60 Hz
Undervoltage Release (UVT)
Automatically trips breaker 110127V,
when voltage falls between U1 140U-M-UD
50/60 Hz
preset value, 3570% UVT
U>
Shunt trip is not available 208240V, 140U-M-UA
when undervoltage release is 50/60 Hz I> U2
used
380500V, Left side ONLY
50/60 Hz 140U-M-UB

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Shunt Trip Undervoltage Release


Auxiliary and Alarm Contacts Suffix Suffix Suffix
Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX + (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1224 110240 380440 480600 Voltage [V] 24 110127 208240 380480
AC J D N B
AC
J D A B
50/60 Hz 50/60 Hz
Voltage [V] 1224 110125 220250 Voltage [V]
DC J D N DC
For additional voltages, consult your local Allen-Bradley distributor.

54
Bulletin 140U
Molded Case Circuit Breakers
Accessories 600 A, Q-Frame, Continued
External Accessories
Description Cat. No.
4 ft. (1.3 m) Cable 140U-M-FCX04
Non-Metallic Type 1/3/12/4/4X
6 ft. (1.8 m) Cable 140U-M-FCX06
Flange-Mount Operating Handle
10 ft. (3.0 m) Cable 140U-M-FCX10
Flex-Cable Operating Mechanism
4 ft. (1.3 m) Cable 140U-M-FSX04
Stainless Steel Type 4/4X
6 ft. (1.8 m) Cable 140U-M-FSX06
Flange-Mount Operating Handle
10 ft. (3.0 m) Cable 140U-M-FSX10

Black Handle 140U-M-RM12B

Rotary, Variable-Depth Operating Rotary Handle Type 1/12


Mechanism 12 in. (305 mm) operating rod

Red/Yellow Handle 140U-M-RM12R

Provides additional phase clearance


Phase Barriers when special connections are Qty:2 140U-M-PB
required

Padlocking Hasp
Padlock Kit Lock-OFF only 140U-M-PL

Provides handle extension for ease of


Operating Handle Extension operation Qty: 1 140U-M-OHE

Copper lug
Copper wire only
(2) 250350 MCM Qty: 1 140U-Q-TLC2
(2) 120250 mm2
Terminal Lugs
Aluminum lug
Aluminum or Copper wire
(2) 3/0350 MCM Qty:1 140U-Q-TLA2
(2) 95150 mm2

55
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 600 A, Q-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Front View Side View


Terminal Barrier Used .516 (13.11) Hex .406 (10.31) Removable T erminal 4.375 (111.12)
with Extended T erminals .250 (6.35) Deep Dia. Cover Must Be in 4.062 (103.17)
Only (TA603LD) .328 (8.33) Dia. .250-20(6.35) Place While in Service
Tap 3.812 (96.82)
Hole Line End .375 (9.52)
12 Holes .147(3.73) Dia Hole
.500(12.70) Deep To .531 (13.49)
.875 (22.22)
Accept #8 Thread Cutting
.438 (11.12) Screws 8 Places Trough For
Attachment 1.000(25.40) R
Leads x 1.906 (48.41)
Wide
.125(3.17) Wide
x .750 (19.05)
Slots For
6.489 (164.82)

Attachment Leads
5.958 (151.33)

.250(6.35) R 1.126
5.052 (128.32)

11 )
5.083 (129.10)

)
2 ( .65
5.614 (142.59)
(28.60)

.23
1.125
4.864 (123.54)

.44 6 (15
(28.57) .219

4.327 (109.90)
3.622 (92.00)
2.281 (5.56)
11.344 (288.14) CL / CL Extended T erminals

9.594 (243.68) CL / CL Standard T erminals


3.019 (76.68)
12.500 (317.50) Overall Extended Length

.61
(57.94) 1.594 45
9.531 (242.09) CL / CL Mounting Holes

.250(6.35) R (40.49) .297


.156(3.96) R .375 (7.54)

4.000 (101.60)
On/I On/I (9.52) 14.7
3.4 .375

3.094 (78.59)
On

8.213 (208.61)
6.688 (169.87)
96 (9.52)
1.142

10.750 (273.05)
(88 .500
(29.00) .80
)R (12.70)

CL Handle CL Handle
.750 0.2

2.292 (58.22)
(19.05) 19.2 Tripped .420
(10.67)
Off/O Off/O Off
24.2 .482
4.260 (108.20)

Reset (12.24) .500


(12.70) .1.151
1.232
(31.29) 45 (29.23)

.250 (6.35)

5.136 (130.45)
0.062 R

B
A
Trip Unit May Be .188 R (1.57) R
Either Thermal/Magnetic (4.77) R 1.500
Or Electronic (38.10)

.800
(20.32)

.313 R 1.000(25.40) R x
(7.95) R 1.906(48.41) Wide
1.375
(34.92) .110(2.79) Dia Hole Load End .062 (1.57)
Contact Position .016

CLHandle
2.750 .312(7.92) Deep To
Indicators (69.85) (0.41)
Accept #6
.531 (13.49)
Red/I - On 2.062 Thread Cutting Screws .375 (9.52)
Green/O - Off (52.37) 6 Places
White - T rip 1.265 (32.13)
2.750 (69.85) 2.047 (51.99)
4.125 (104.77) .313 (7.95) Dia. Mounting Holes
(4) for .250 (6.35) - 20 x 1.50 (38.10)
5.500 (139.70) Mounting Screws
3.641 (92.48) .531 (13.49) Dia C'Bore from Top
7.281 (184.94) 2.625 (66.67) Deep Line End (2)
4.125 (104.77) 2.875 (73.02) Deep Load End (2)
.531 (13.49) Dia. C'Bore
8.250 (209.55) .875 (22.22) from Bottom
Handle Forces
3.250 (82.55)
1.625 (41.27)
On 45 lbs.
1.875 (47.62) Wide .812 (20.62) Off 50 lbs.
Conductor with .406 1.625
(10.31) Dia. Hole Line and (41.27) Reset 60 lbs.
Load Ends (Current
Carrying Parts Omitted 1.906 1.906 Measurements taken approximately 3/16 in.
(48.41) (48.41)
in Center Pole for 2-Pole from end of handle.
Breaker)

3.218
2.750 (81.74)
(69.85)

56
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 800 A, M-Frame

UL 489 Terminal box lugs must be ordered


CSA 22.2, No. 5 separately. See page 59
IEC 60947-2
CE
KEMA-KEUR

Breaker Frames
Breaking Capacity (50 Hz)
Rated Current Interrupting Rating (60 Hz) [kA]
Icu /Ics [kA] Cat. No.
In [A]
220240V 380415V 500V 690V 240V 480V 600V
65 65 50 50 50 25 20 10 65 50 25 140U-M5X3
800
100 100 70 70 70 50 25 13 100 65 35 140U-M6X3

Trip Units and Rating Plugs


Thermal-Magnetic Electronic
Adjustment Range [A] Adjustment Range [A]
Rated Current Rated Current Protection
Thermal Trip Magnetic Trip Cat. No. Thermal Trip Magnetic Trip Cat. No.
In [A] In [A] Type
Ir = In Im = 510 x In Ir = 1.0 x In Im = 28 x In
300 300 15003000 140U-MTD3-D30 LS 140U-MTL3-D80
350 350 17503500 140U-MTD3-D35 800 400800 8006400 LSI 140U-MTH3-D80
400 400 20004000 140U-MTD3-D40 LSG 140U-MTG3-D80
450 450 22504500 140U-MTD3-D45
500 500 25005000 140U-MTD3-D50 Rating Plugs
600 600 30006000 140U-MTD3-D60 Thermal Trip Thermal Trip
Cat. No. Cat. No.
700 700 35007000 140U-MTD3-D70 In [A] In [A]
800 800 40008000 140U-MTD3-D80 400 140U-MRP3-D40 700 140U-MRP3-D70
500 140U-MRP3-D50 800 140U-MRP3-D80
600 140U-MRP3-D60

Assembled Circuit Breakers, Thermal-Magnetic Trip Units


Rated Current Thermal Trip 400/480V 400/480V
Cat. No. Cat. No.
In [A] Ir = In [kA] [kA]
300 300 50/50 140U-M5D3-D30 70/65 140U-M6D3-D30
350 350 50/50 140U-M5D3-D35 70/65 140U-M6D3-D35
400 400 50/50 140U-M5D3-D40 70/65 140U-M6D3-D40
450 450 50/50 140U-M5D3-D45 70/65 140U-M6D3-D45
500 500 50/50 140U-M5D3-D50 70/65 140U-M6D3-D50
600 600 50/50 140U-M5D3-D60 70/65 140U-M6D3-D60
700 700 50/50 140U-M5D3-D70 70/65 140U-M6D3-D70
800 800 50/50 140U-M5D3-D80 70/65 140U-M6D3-D80

Assembled Circuit Breakers, Electronic Trip Units


Thermal Trip 400/480V 400/480V
Rated Current In [A] Protection Type Cat. No. Cat. No.
Ir = 0.51.0 x In [kA] [kA]
LS 50/50 140U-M5L3-D80 70/65 140U-M6L3-D80
800 200800 LSI 50/50 140U-M5H3-D80 70/65 140U-M6H3-D80
LSG 50/50 140U-M5G3-D80 70/65 140U-M6G3-D80

Select proper rating plug to cover thermal trip requirement.

Molded Case Switch UL 1087


Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current Magnetic Trip
Icu /Ics [kA] [kA] Cat. No.
In [A] Im = 10 x In
220240V 380415V 500V 690V 240V 480V 600V
800 8000 100 100 70 70 70 50 25 13 100 65 35 140U-M6S3-D80

57
Bulletin 140U
Molded Case Circuit Breakers
Accessories 800 A, M-Frame
Internal Control Modules Field Installed
Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-M-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-M-EA2
Left AND Right side

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)-


the breaker is in the 1B (break) AL B M B M B M 140U-M-ER1
TRIPPED state I>
1c 1c 1c

Right side ONLY


\

OFF ON TRIP
Auxiliary/Alarm Contact (AX/AL) 1a 1a 1a
Combination (1) 1a-1b AX
1b 1b 1b

Combination of auxiliary (1) 1M (make)- AL 1c


B M
1c
B M
1c
B M 140U-M-EA1R1
1B (break)
contact and alarm contact I>
1c 1c 1c

Right side ONLY

1224V,
50/60/DC 140U-M-SNJ
Shunt Trip (SNT)
Provides remote tripping of 110240V AC,
110125V DC
S1 140U-M-SND
the circuit breaker SNT
Undervoltage trip not 380440V AC,
available when shunt trip is 220250V DC I> S2 140U-M-SNN
used Left side ONLY
480600V,
140U-M-SNB
50/60 Hz
24V AC,
140U-M-UJ
50/60 Hz
Undervoltage Release (UVT)
Automatically trips breaker 110127V AC,
when voltage falls between U1 140U-M-UD
50/60 Hz UVT
preset value, 3570% U>
Shunt trip is not available 208240V AC, U2 140U-M-UA
I>
when undervoltage release is 50/60 Hz Left side ONLY
used
380500V AC,
50/60 Hz 140U-M-UB

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Shunt Trip Undervoltage Release


Auxiliary and Alarm Contacts Suffix Suffix Suffix
Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX + (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1224 110240 380440 480600 Voltage [V] 24 110127 208240 380480
AC, AC,
50/60 Hz J D N B J D A B
50/60 Hz
Voltage [V] 1224 110125 220250 Voltage [V]
DC J D N DC
For additional voltages, consult your local Allen-Bradley distributor.

58
Bulletin 140U
Molded Case Circuit Breakers
Accessories 800 A, M-Frame, Continued
External Accessories
Description Cat. No.
4 ft. (1.3 m) Cable 140U-M-FCX04
Non-Metallic Type 1/3/12/4/4X
6 ft. (1.8 m) Cable 140U-M-FCX06
Flange-Mount Operating Handle
10 ft. (3.0 m) Cable 140U-M-FCX10
Flex-Cable Operating Mechanism
4 ft. (1.3 m) Cable 140U-M-FSX04
Stainless Steel Type 4/4X
6 ft. (1.8 m) Cable 140U-M-FSX06
Flange-Mount Operating Handle
10 ft. (3.0 m) Cable 140U-M-FSX10

Black Handle 140U-M-RM12B

Rotary, Variable-Depth Operating Rotary Handle Type 1/12


Mechanism 12 in. (305 mm) operating rod

Red/Yellow Handle 140U-M-RM12R

Copper lug
Copper wire only
(3) 3/0300MCM Qty: 1 140U-M-TLC3
(3) 95135 mm2
Terminal Lugs
Aluminum lug
Aluminum or Copper wire
(3) 3/0400MCM Qty: 1 140U-M-TLA3
(3) 95185 mm2

Phase Barriers Provides additional phase clearance Qty: 2 140U-M-PB


when special connections are required

Padlock Kit Padlocking Hasp 140U-M-PL


Lock-OFF only

Operating Handle Extension Provides handle extension for ease of Qty: 1 140U-M-OHE
operation

59
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 800 A, M-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

CL
Handle
Pivot
Line End 2.018 .500
.375 (9.53) Dia. 4-Holes for .312 (7.92) - (51.26) (12.70)
16 (406.40) x 1.75 (44.45) Large Mounting Screws. 1.411 .547
(35.84) (13.89)
Max.

8.302
(210.87) 7.677
(195.00)
6.052
(153.72) .415
(10.54)

Tripped
0.2
11.500
On/I On/I (292.10)
On
14.7

C
L
Handle
Pivot Off/O Off/O Off
14.750 19.2
(374.65) Reset
24.2

16.000
(406.40)

Dim. Dim.
B A

.531
1.375 .500 (12.70) - 13 Tap (13.49)
(34.93) .500
Thru. (12.70)
2.750 2.531
(69.85) (64.29)

2.750 4.062
(69.85) (103.17)
5.500 4.375
(139.70) (111.13)
4.250
(107.95)
8.250
(209.55)
Breaker Status Dimension A Dimension B
Load End
On 8.72 9.17
3.250
(221.49) (232.92)
(82.55)
1.625
Off 6.72 7.14
(41.28) (170.69) (181.36)
1.625
(41.28) Tripped 7.86 8.30
.813
(20.65) (199.64) (210.82)
1.874
(47.60)
Reset 6.44 6.84
(163.58) (173.74)

60
Bulletin 140U
Molded Case Circuit Breakers
Product Selection 1200 A, N-Frame

UL 489 Terminal box lugs must be ordered


CSA 22.2, No. 5 separately. See page 63
IEC 60947-2
CE
KEMA-KEUR

Assembled Circuit Breakers, Electronic Trip Units


Rated Adjustment Range Ir [A] Breaking Capacity (50 Hz) Interrupting Rating
Protection (60 Hz) [kA]
Current Thermal Trip Magnetic Trip Icu /Ics [kA] Cat. No.
Type
In [A] Ir = 0.51.0 x In Im = 28 x In 220240V 380415V 500V 690V 240V 480V 600V
1200 6001200 120010,600 LS 85 85 50 50 40 20 20 10 65 50 25 140U-N5L3-E12
LS 100 100 70 50 50 25 25 13 100 65 35 140U-N6L3-E12
1200 6001200 120010,600 LSI 100 100 70 50 50 25 25 13 100 65 35 140U-N6H3-E12
LSG 100 100 70 50 50 25 25 13 100 65 35 140U-N6G3-E12
LS 200 100 100 50 65 33 35 18 200 100 50 140U-N0L3-E12
1200 6001200 120010,600 LSI 200 100 100 50 65 33 35 18 200 100 50 140U-N0H3-E12
LSG 200 100 100 50 65 33 35 18 200 100 50 140U-N0G3-E12

Select proper rating plug to cover thermal trip requirement.

Rating Plugs
Rated Current Rated Current
Cat. No. Cat. No.
In [A] In [A]
600 140U-NRP3-D60 900 140U-NRP3-D90
700 140U-NRP3-D70 1000 140U-NRP3-E10
800 140U-NRP3-D80 1200 140U-NRP3-E12

Molded Case Switch UL 1087


Breaking Capacity (50 Hz) Interrupting Rating (60 Hz)
Rated Current Magnetic
Icu /Ics [kA] [kA] Cat. No.
In [A] Trip 10 x In
220240V 380415V 500V 690V 240V 480V 600V
1200 12,000 100 100 70 50 50 25 25 13 100 65 35 140U-N6S3-E12

61
Bulletin 140U
Molded Case Circuit Breakers
Accessories 1200 A, N-Frame
Internal Control Modules Field Installed
Description Mounting Location Diagram Cat. No.

(1) 1a-1b OFF ON TRIP 140U-N-EA1


Auxiliary Contact (AX) 1b 1a 1b 1a 1b 1a
AX
Electrically indicates ON/
OFF status of breakers 1c 1c 1c
(2) 1a-1b I>
140U-N-EA2
Left AND Right side

OFF ON
Alarm Contact (AL) TRIP

Electrically indicates when (1) 1M (make)-


the breaker is in the 1B (break) AL B M B M B M 140U-N-ER1
TRIPPED state I>
1c 1c 1c

Right side ONLY

OFF ON TRIP
1b 1a 1b 1a 1b 1a
AX

AL B M B M B M
1c 1c 1c
Auxiliary/Alarm Contact (AX/AL)
Combination (1) 1a-1b I>
1c 1c 1c

Combination of auxiliary (1) 1M (make)- 140U-N-EA1R1


1B (break) Right side ONLY
contact and alarm contact

1224V,
50/60/DC 140U-N-SNJ
Shunt Trip (SNT) S1
Provides remote tripping of 110240V AC, SNT
110125V DC 140U-N-SND
the circuit breaker
Undervoltage trip not 380440V AC, I> S2
available when shunt trip is 220250V DC 140U-N-SNN
used Left side ONLY
480600V,
140U-N-SNB
50/60 Hz
24V AC,
140U-N-UJ
50/60 Hz
Undervoltage Release (UVT)
Automatically trips breaker 110127V AC,
50/60 Hz 140U-N-UD
when voltage falls between U1
preset value, 3570% 208240V AC, UVT
50/60 Hz
U> 140U-N-UA
Shunt trip is not available
when undervoltage release is Left side ONLY I> U2
used 380500V AC,
50/60 Hz 140U-N-UB

Internal Control Modules Factory Installed

Left side only Mounting Location Right side only

(1) Shunt Trip (SNT) (1) Auxiliary contact (AX)


or or
(1) Undervoltage Release (UVT) (2) Auxiliary contacts (AX)
or
(1) Alarm contact (AL)
or
(1) Alarm contact (AL) + Auxiliary contact (AX)

Shunt Trip Undervoltage Release


Auxiliary and Alarm Contacts Suffix Suffix Suffix
Combinations Combinations
(1) AX -A (1) SNT only - P (1) UVT only - G
(2) AX -B (1) AX + (1) SNT - Q (1) AX + (1) UVT - H
(1) AL -D (2) AX + (1) SNT - R (2) AX + (1) UVT - J
(1) AX/ (1) AL -F (1) AX + (1) AL + (1) SNT - T (1) AX + (1) AL + (1) UVT - L
(1) AL + (1) SNT - V (1) AL + (1) UVT - N
Standard Voltage Suffix Codes Standard Voltage Suffix Codes
Voltage [V] 1224 110240 380440 480600 Voltage [V] 24 110127 208240 380480
AC, AC,
50/60 Hz J D N B 50/60 Hz J D A B
Voltage [V] 1224 110125 220250 Voltage [V]
DC J D N DC
For additional voltages, consult your local Allen-Bradley distributor.

62
Bulletin 140U
Molded Case Circuit Breakers
Accessories 1200 A, N-Frame, Continued
External Accessories
Description Cat. No.

4 ft. (1.3 m) Cable 140U-N-FCX04

Flex-Cable Operating Mechanism Non-Metallic Type 1/3/12/4/4X


6 ft. (1.8 m) Cable 140U-N-FCX06
Flange-Mount Operating Handle

10 ft. (3.0 m) Cable 140U-N-FCX10

Rotary, Variable-Depth Operating Rotary Handle Type 1/12 Black Handle


Mechanism 12 in. (305 mm) operating rod 140U-N-RM12B

Phase Barriers Provides additional phase clearance Qty: 2


when special connections are required 140U-N-PB

Padlock Kit Padlocking Hasp Qty: 1


Lock-OFF only 140U-N-PL

Copper lug
Copper wire only
(4) 3/0400MCM Qty: 1 140U-N-TLC4
(4) 95185 mm2
Terminal Lugs
Aluminum lug
Aluminum or Copper wire
(4) 4/0500MCM Qty:1 140U-N-TLA4
(4) 120300 mm2

63
Bulletin 140U
Molded Case Circuit Breakers
Approximate Dimensions 1200 A, N-Frame
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

.344(8.738) Dia. Mounting Holes


.703(17.856) Dia. C'Bore
4.453(113.106) Deep from Top
.594(15.088) Dia C'Bore
Removable T erminal .359(9.119) Deep from Bottom 1.157(29.388)
Cover Must Be in 1.062(26.987) .532(13.513)
Place While in Service .531 (13.481) .500-13 (12 X 1.75) Tap
12-Holes .062(1.575)
Line End

3.236
(82.194)

11.431 Trough for


(290.348) Attachment Lead

.250R .125 X .750


115.00(292.075)
9.250(234.950)
14.750(374.650)
8.625(219.075)

7.000(177.774)

(6.350)R (3.175 X 19.050)


Slots for
.062R Attachment Leads
(1.575)R

.094R 3.850R
(2.388)R
.297
(7.544)
212
ON/I ON .353
02 (6.331)
CL Handle TRIPPED
132OFF
.946 152 .375
16.000(406.401)

(24.022) .750 (19.050) RESET (9.525)


OFF/O .375 (9.525)
2.982
(75.743)
.188R
(4.762)R
1.500
(38.100)
B A
1.034
Handle (33.281)
.147 (3.734) Dia. Hole Pivot
3.808
(96.723) .500 (12.70) Deep to
2.798
Accept a #8Thread
(71.057) Cutting Screw
6-Places

2.511 Contact Position Indicator


(63.786) Red-I/ON Load End .062(1.575)
.312R 1.375
(7.925)R Green-O/OFF .532(13.513)
(34.925) 2.750 White-TRIPPED
(69.850) 1.095(27.813)
3.187 2.344
(80.950) (59.541) Removable Terminal 3.344(84.938)
6.375 Cover Must Be in
(161.925) Place While in Service 5.188(131.769)
4.124
(104.750) 5.248(133.293)
8.250
(209.550) 5.500(139.687)
3.375
Dimensions 6.000(152.400)
(85.725) Breaker Status A B
2.750 Ref. 7.132 (181.146)
1.688 (69.850) Ref. On 7.90 (200.66) 8.30 (210.82)
(42.863)
1.562 2.000 Tripped 6.50 (165.10) 6.90 (175.26)
2.000 (39.687) (50.800)
(50.800)
.781 (19.844) Off 5.70 (144.78) 6.10 (154.94)
.062 .062 1.000 Reset 5.60 (142.24) 6.00 (152.40)
(1.588) (1.588) (25.400)
R R
CL Push To Trip

Handle Forces (At Handle C)L


On 130 lbs. (58.97 kgs.)
Off 105 lbs. (47.63 kgs.)
1.500 Ref
Reset 160 lbs. (72.57 kgs.) (38.100) Ref
3.906
(99.187)
4.875 3.819
(123.799) (96.723)

2.493
(63.792)
.062 For 2-Pole Breaker Omit Current 6.375 Ref
(1.575) Carrying Parts from Center Pole (161.925) Ref

64