EP-MS-P4/S3-040
Specification for
LV XLPE Cables
Document Control
Department Document Type Document Title
EP-MS-P4/S3-040
Material
EP Specification Specification for
LV XLPE Cables
Standards
Issue Approval
Prepared By Approved By
Signature: Signature:
Issue Record
Issue No. Date Reason for re-issuing Document
When this document is approved for publishing on the intranet, a copy of its Document Control page should be sent to
the QA section who is custodian of KM quality management system.
1.0 SCOPE
2.0 GENERAL
The details given in this specification are based on international standards and
KAHRAMAA requirements in general and for the guideline to the manufacturers. The
parameters given herewith are minimum requirements, however, manufacturer shall
confirm in all aspects to supply of best design, selection of high quality material and
good workmanship in the manufacturing for the safe and accurate installation and
continuous smooth operation through out the life of the material stipulated herein.
KAHRAMAA reserve the right to reject any material if found not as per International
standards mentioned hereto and KAHRAMAA requirements.
Manufacturer may offer any better product up and above the specified one herein,
however, KAHRAMAA reserves the right to accept or not.
All cables covered under this Specification should be designed for continuous operation
life for not less than 30 years under the climatic conditions specified herein.
The cables shall be inconformity with IEC 60502 Part 1, and subsequent amendments,
except as may be otherwise stated in this standard. The general classification of cables is
mentioned below.
6.1.5 Armour:
The armour shall comprise a single layer consisting of both galvanized steel and
tinned copper round wires. The conductivity of the copper wires alone shall be at
least 50% of that of any phase conductor, at their respective normal working
temperatures. The tinned copper wire shall be of substantially the same diameter
as, and not less than the diameter/thickness of the armour wires. They shall
comprise not less than 25% of the total number of armour wires. The whole
combination of steel and copper wires shall be laid in close contact with no
discernable gaps. An open helix consisting of galvanized steel tape of minimum
nominal thickness 0.3 mm shall be provided over round steel wire armour.
Galvanizing of the wires shall be in conformity with BS EN 10257. The copper
wires shall be uniformly dispersed among the steel wires. Two swallowable water
blocking tapes shall be provided one each, over and under the armour layer.
These tapes shall be capable of absorbing water and remain dry by forming into
gel. The purpose of which is to inhibit flow of water in the event of penetration
of the over-sheath, or inflow from a faulty joint. The material shall be chemically
inactive with the components with which it is in contact, both with and without
the presence of water. It shall be solid at the working temperature of the
adjoining components.
6.1.6 Oversheath:
PVC extruded directly over the armour and water inhibitor (water blocking
tape). The material should be fire retardant, UV resistance and comprises of anti
aging components and high resistant to soil. It shall be type ST2 in accordance
with IEC 60502 and IEC 60332-1. Thickness shall be in compliance with the
above standard. The over sheath shall be coloured in BLACK, and shall be
embossed with the legend:
- KAHRAMAA
- 600/1000V LV XLPE
- CABLE SIZE & NUMBER OF CORES
- STANDARD NO.
- YEAR OF MANUFACTURE
- NAME OF MANUFACTURER
- RUNNING SERIAL NUMBER (at interval of 1 meter)
6.2.3 Insulation:
Designation XLPE IEC 60502. Highest rated temperature 90oC IEC 60502.
Insulation thickness appropriate to applied voltage, IEC 60502.
6.2.5 Armour:
This shall serve as an earthed screen to provide protection in the event of
penetration.
To avoid the risk of corrosion resulting from penetration of the oversheath, and
to ensure compatibility with termination glands, this shall be of round copper
wires.
The copper wires shall be laid in close contact with no discernable gaps.
6.2.6 Oversheath:
PVC extruded directly over the armour. The material should be fire retardant,
UV resistance and comprises of anti aging components and high resistant to soil.
It shall be type ST2 in accordance with IEC 60502 and IEC 60332-1. Thickness
shall be in compliance with the above standard. The oversheath shall be coloured
in BLACK, and shall be embossed with the legend:
- KAHRAMAA
- 600/1000V LV XLPE
Issue : 1 19-04-2010 unclassified Page 6 of 10
Specification for LV XLPE Cables EP-MS-P4/S3-040
All cables shall be supplied on cable drums with a maximum diameter of 2.55m and a
maximum width of 1.28m. No drums with cable shall weight more than 7.5 tones. In
addition the lengths of cables on the drums shall be in accordance with the Schedule of
Quantities.
The drums shall be stoutly constructed of wood and supported with steel tie bars and
shall be fully lagged and bonded. On each flange of each drum a steel plate with tubular
steel insert shall be fitted to accept a 100mm diameter spindle to be used during cable
installation. The steel plate shall be a minimum of 400mm x 400mm x 5mm thick,
welded to the tubular insert. The plates shall be fixed with 6 bolts through the flange.
All drums shall be painted and engraved with:
- Manufacturer's name
- Drum number/year & month of manufacture of cable
- Size, number of cores and voltage of cable, including the
designation "Cross Linked Polyethylene (XLPE)".
- Length of cable on the drum with sequential number.
- KAHRAMAA.
- The Contract No.
The nominal lengths to be as stated in the schedule below:-
Cable Size Lengths per Drum
4c x 300 sq.mm. 250 Meters
4c x 240 sq.mm. 250 Meters
4c x 185 sq.mm 300 Meters
4c x 120 sq.mm 500 Meters
4c x 70 sq.mm 500 Meters
4c x 35 sq.mm 700 Meters
4c x 16 sq.mm 1000 Meters
2c x 16 sq.mm 1000 Meters
1c x 300 sq.mm 500 Meters
1c x 400 sq.mm 500 Meters
1c x 630 sq.mm 500 Meters
1c x 800 sq.mm 300 Meters
A tolerance of +5% on the length of cable per drum shall be allowed.
8.0 TESTS:
This relates to type tests and tests to be carried out during or after manufacture of the
specified cables. In addition to the type tests conducted in accordance with the
requirements of IEC 60502-Part 1. Copy of type test reports issued from reputed
independent laboratories need to be submitted.
The following tests shall be carried out on each manufactured length of cable, or sample
length as instructed by KAHRA MAA. The tests shall be as outlined in IEC 60502- Part
1, IEC 60228 and BSI BS EN 60811.
A. Routine Tests:
Routine tests are to be carried out each and every drum manufactured.
One set of routine test reports of each drum shall be fixed with the drum
in a strong water-proof envelope. The following routine tests are to be
carried out.
1. Electrical Resistance of Conductors.
2. Voltage Test.
B. Sample Tests:
Sample tests are to be carried out on 10 % drums of each lot. Samples to
be taken from both sides of the entire length of the drum. One set of
sample test reports of shall be submitted to KAHRAMAA for review and
approval. The following sample tests are to be carried out. One set of
sample test report (wherever applicable) shall be fixed with the drum
along with routine test report.
1. Conductor Examination.
2. Check of Dimensions as per IEC 60811-1-1
3. Hot Set Test.
C. Type Tests:
Manufacturer shall carry out type tests to IEC 60502 on the cable and
issue certificates confirming that the cable has conformed.
In general, following test to be carried out at International Reputed
Independent Laboratory in accordance with IEC 60502- Part -1 and IEC
60228.
Type Test Electrical
1 Insulation Resistance Measurement at ambient temperature.
2 Insulation resistance measurement at maximum temperature in
normal operation
3 Voltage Test for 4 h.
Type Test Non-Electrical
9.2 For every subsequent lot, the manufacturer is obliged to inform Kahramaa, at
least 20 days before dispatch, and obtain clearance for dispatch. KM Engineers
have the option of inspecting & witnessing all factory acceptance tests, including
routine tests, at manufacturers factory premises for each lot.
9.4 Type tests are to be carried out on Samples, essentially of same design and
ratings, as being offered. Manufacturer is obliged to provide details of test
procedures being followed, to the KM inspection team before commencing
factory accepting tests.
9.5 Each Lot needs to be subjected to all routine tests & sample tests at factory
before delivery. Further, each drum may be subjected to inspection on receiving
them at DOHA to verify its healthiness and its conformity with the guaranteed
design data.
9.6 All tests should be performed in accordance with the latest issue of relevant IEC
standards.
9.7 Three sets (copies) of routine tests, sample tests & FAT reports to be prepared.
One set to be attached with the drum, in a strong water-proof envelope. Second
copy to be sent along with delivery note. Third copy to be sent to the end-user
department.
9.8 FAT report shall include copy of quality control report containing list of check
points verified/inspected at factory against each drum. Each delivery note shall
include the details of serial number and month/year of production of each
drum.
9.9 Both the manufacturing date (i.e. month/year) and shipment date should be
marked on each drum, and the time difference between these two dates should
not be more than 6-months.
An illustrated drawing showing the cable cross section design, all components,
dimensions of each layer and data sheets.
A specific compliance (clause by clause up to sub clause level), statement of conformity
with the specification, else details of non-conformity.
Details of the method of protection against water ingress at armour level.
Permissible fault ratings of the conductors and the armour.
Type Test Report from International recognized Independent Laboratory. The report
must be not older than 10 years.
Complete product catalogue with all ratings, characteristics & recommended installation
procedure.
Supply record for GCC and other countries.
11.0 GUARANTEE
The Bidders are required to attach a separate deviation list to their Technical Offer and
include it in the Technical Package if the offered equipments do not meet the requirements
of any clause of the Specification.
Offers without any deviation list attached to the Technical Offer and included in the
Technical Package shall mean that the offer meets the requirements of the Specifications on
all the clauses.
Offers with deviations listed out shall mean that the offer meets the requirements of the
Specification on all the other clauses not included in the deviation list.