Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
INTRODUCTION:
Common practice of design and construction is to support the slabs by beams and
support the beams by columns. This may be called as beam -slab construction. The
beam reduce the available net clear ceiling height. Hence in warehouses, offices and
public halls sometimes beams are avoided and slabs are directly supported by
columns. A reinforced concrete slab supported directly by concrete columns without
the use of beams is called as flat slab. These types of construction are aesthetically
appealing also. Flat slabs which are directly supported by columns. Construction of
slab involves different varieties. Some of them are:
Flat slab
Flat slab with drop panel
Flat slab with column head
Flat slab with drop panel and column head
Drops: The punching shear which is predominant at the contact of slab and column support
resisted by providing drop. The drop dimension should not be less than one-third of panel length
in that direction.
Column heads: Certain amount of negative moment is transferred from the slab to the
column at the support, to resist this negative moment the area at the support needs to be
increased. This is facilitated by providing column capitals/heads. These are increase shear
strength of slab and reduce the moment in the slab by reducing the clear or effective span.
FIG 2.1
FIG 2.2
BENEFITS:
5. Building score
Allows standardized structural members and prefabricated sections to be integrated into the
design for ease of construction and reduce the number of site workers and increase the
productivity at site. To achieve a higher buildable score.
DESIGN PROCEDURE:
Nowadays flat slabs place a vital role due to its aesthetical application and method of
construction. Column head, one of the component of flat slab is sometimes widened to reduce
the punching shear in the slab. These are provide with an angle of 45o on either side of vertical as
for design consideration. Slab will thickened near column by providing drop to overcome
moments. The portion of flat slab that is bound on its four sides by center lines of adjacent
columns is called a panel with size of LL. Panel may be divided into column strips and middle
strips. Column strips means a design strip having a width of 0.25L. The remaining middle
portion which is bound by the column strips is called middle strip.
If drops are not provided or size of drops do not satisfy the specification, the ratio shall not
exceed 0.9 times the value specified above i.e.,
It is specified that is no case, the thickness of flat slab shall be less than 125mm.
DETERMINATION OF BENDING MOMENT AND SHEAR STRENGTH:
0 =
8
Where,
M-Total moment
Ln - Circular span extending from face to face of columns, capitals, brackets or not less
than 0.65L
In taking the values of L, L1, and L2, the following clauses are to be carefully noted:
a) Circular supports shall be treated as square supports having the same area i.e., squares of
size 0.886D.
b) When the span adjacent and parallel to an edge is being considered, the distance from
the edge to the center line of the panel shall be substituted for L2.
Distribution of Bending Moment in to ve and +ve Moments:
The total design moment M in a panel is to be distributed into ve moment and +ve moment as
specified below:
In an Interior span
In an end span
0.10
Interior negative design moment = [0.75 1 ] 0
1+
0.28
Positive design moment = [0.63 1 ] 0
1+
0.65
Exterior negative design moment = [ 1 ] 0
1+
Where is the ratio of flexural stiffness at the exterior columns to the flexural stiffness of the
slab at a joint taken in the direction moments are being determined and is given by
Where
The +ve and ve moments found are to be distributed across the column strip in a panel. The
moment in the middle strip shall be the difference between panel and the column strip moments.
SHEAR FORCE:
The critical section for shear shall be d/2 from the periphery of the column/capital drop panel.
Hence if drop are provided there are two critical sections near columns. The shape of the critical
section in plan is similar to the support immediately below the slab. The nominal shear stress
may be calculated as
=
0
Where
The permissible shear stress in concrete may be calculated as k, where k = 0.5+ c but not
greater than 1, where c is the ratio of short side to long side of the column/capital.
= 0.25
If shear stress < no shear reinforcement are required. If v < < 1.5c, shear reinforcement
shall be provided. If shear stress exceeds 1.5c flat slab will be redesigned.
SLAB REINFORCEMENT
SPACING:
The spacing of bars in a flat slab, shall not exceed 2 times the slab thickness.
AREA OF REINFORCEMENT:
When the drop panels are used, the thickness of drop panel for determining area of reinforcement
shall be the lesser of the following:
At least 50% of bottom bars should be from support to support. The rest may be bent up. The
minimum length of different reinforcement in flat slabs should be as shown in below fig (from IS
456:2000). If adjacent spans are not equal, the extension of the reinforcement beyond each face
shall be based on the longer span. All slab reinforcement should be anchored property at
discontinuous edges.
TABLE 2.1
1.A flat slab system consists of 6m*6m panels and is without drop and column
head. It has to carry a live load of 3 KN/m2 and a finishing load of 1 kn/m3 .It
is to be designed using M20 grade and Fe415 steel. The size of the columns
supporting the system is 500*500.
Ans. 1.THICKNESS:
For Fe415 =
320.9
6000
d= = 208mm
28.8
2.LOADS:
=1565.5 = 495 KN
WLn
Moment (M0) =
8
4955.5
= =340.31 KN-m
8
The above moments are to be distributed into column strip and middle strip.
Mu=0.138fckbd2
34010^6 =0.138203000d2
d=202.2mm
Hence safe.
=532.24KN
532.24 1000
v = = 0.026 N/mm2
4 710 710
Ks = 1
6. DETAILING OF REINFORCEMENT:
415
167*10^6 = 0.87415Ast210(1 3000210 )
20
Ast =2390mm2
using 16 mm bars
4
16^2
spacing = 3000
2390
=252.3mm
415
7210^6 = 0.87415Ast210(1 )
300021020
Ast = 981.29 mm
Using10mm bars
4
102
spacing = 3000
981
=240.18 mm
415
5610^6 = 0.87415Ast210(1 300021020)
=311.45mm