Sei sulla pagina 1di 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO.

1, FEBRUARY 2017 453

Fault Models of Inverter-Interfaced Distributed


Generators Within a Low-Voltage Microgrid
Wen-Ming Guo, Long-Hua Mu, and Xin Zhang

AbstractThe traditional overcurrent protection is not suitable S Complex power output of PQ-IIDG.
for the microgrid. One of the main reasons is that the fault response Z Equivalent impedance measured by V/f-IIDG.
of the inverter-interfaced distributed generator (IIDG) is very Fundamental angular frequency.
different from that of the rotational generator. This paper develops
fault models of IIDGs within a low-voltage microgrid, including ac- Phase angle of voltage quantity.
tive/reactive power (PQ)-controlled IIDGs and voltage-controlled Phase angle of current quantity.
IIDGs. Considering that the control strategy of the PQ-controlled g1 , g2 , g3 , g4 Transfer factors.
IIDG varies, this paper introduces adjustable parameters into the IPQlim Limitation of PQ-IIDGs output peak current.
model to reflect its fault characteristics as comprehensive as possi- IVFlim Limitation of V/f -IIDGs output current.
ble. Voltage-controlled IIDG is of great significance on maintaining
a stable microgrid. The model of voltage-controlled IIDG proposed kP The set ratio of positive sequence active power
in this paper keeps its voltage-source nature while accomplishing to total active power for PQ-IIDG.
current limiting. The performance of the proposed IIDG fault mod- kQ The set ratio of positive sequence reactive power
els has been tested by Matlab simulations. The achievements of this to total reactive power for PQ-IIDG.
paper are expected to have a positive impact on the development Iset The set peak value of PQ-IIDGs output positive
of microgrid fault analysis and protection.
sequence currents.
Index TermsCurrent limitation, fault model, inverter- set The set value of PQ-IIDGs positive sequence
interfaced distributed generator, microgrid. power factor.

NOMENCLATURE LIST OF SUPERSCRIPTS


LIST OF ABBREVIATIONS + Variable related to positive sequence component.
IIDG Inverter-interfaced distributed generator. Variable related to negative sequence component.
PQ-IIDG PQ controlled IIDG. * Reference of variable.
V/f-IIDG Voltage controlled IIDG.
FRT Fault ride through. LIST OF SUBSCRIPTS
PC Point of connection. ini Initial value of variable.
DER Distributed energy resource. mod Modified value of variable.
P Variable related to active power component.
LIST OF SYMBOLS Q Variable related to reactive power component.
u Three-phase PC voltages vector of IIDG. A, B, C Variable related to phase A, B, C.
i Three-phase output currents vector of IIDG. max Maximum value of variable.
U PC voltage of IIDG. lim Upper limit of variable.
I Output current of IIDG. nom Nominal value of variable.
L AC-side filtering inductor of IIDG. Orthogonal vector.
C AC-side filtering capacitor of IIDG.
P Active power output of PQ-IIDG. I. INTRODUCTION
Q Reactive power output of PQ-IIDG.
ICROGRID, which provides a new and effective way of

Manuscript received July 31, 2015; revised January 3, 2016; accepted Febru-
M making full use of distributed energy, still faces numer-
ous technical challenges [1][3]. Microgrid protection [4], [5]
ary 28, 2016. Date of publication March 14, 2016; date of current version
January 20, 2017. This work was supported in part by the National Natural is one of them. A reliable protection system is indispensable
Science Foundation of China (51407128). Paper no. TPWRD-01016-2015. to ensure the safe operation of microgrid. Unfortunately, the
W.-M. Guo and X. Zhang are with the College of Electronics and Information traditional overcurrent protection is not suitable for microgrid,
Engineering, Tongji University, Shanghai 201804, China (e-mail: gwmsch@
163.com; zxln1979@163.com). especially in islanded mode, for its fault characteristics are very
L.-H. Mu is with the Department of Electrical Engineering, Tongji University, different from those of traditional distribution grid. To under-
Shanghai 201804, China (e-mail: lhmu@tongji.edu.cn). stand the fault features of microgrid, it is necessary to explore
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. the fault models of IIDGs, which take the dominant position of
Digital Object Identifier 10.1109/TPWRD.2016.2541344 micro-sources within a microgrid.
0885-8977 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
454 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

In essence, IIDGs can be classified into PQ controlled IIDGs


(PQ-IIDG) and voltage controlled ones (V/f-IIDG). PQ-IIDG
injects a given power into microgrid and acts as a controlled
current source. V/f-IIDG is responsible for maintaining the volt-
age and frequency of microgrid, so it behaves like a controlled
voltage source. The key point of developing IIDGs fault mod-
els is to understand how they respond to abnormal conditions
when fault occurs in microgrid, in other words, how their volt-
age or current references change. In the drafted standard IEEE
P1547.8 [6], the fault ride through (FRT) is a mandatory func-
tionality for DGs, and some grid codes [7], [8] require that DGs
should provide reactive current preferentially. In contrast, Guo
et al [9] introduce that supplying active power achieves more Fig. 1. Configuration and control block diagram of PQ-IIDG.
effective voltage support in low voltage grid. In [10], Cornelis
et al propose that IIDGs inject a pre-defined positive sequence the active and reactive power references; u, i and i represent
current into grid. References [11][15] present various fault PQ-IIDGs PC voltages, output currents and current references.
control strategies for PQ-IIDGs. And the common feature of It is worth noting that the bold symbols represent three-phase
these strategies is that IIDGs could feed positive and negative vectors throughout this paper.
sequence current into grid simultaneously. Zamani et al [16] Distributed energy resources (DER) usually utilize three-
accomplish the current limiting of V/f-IIDG by compressing phase three-leg inverter to convert energy, so a transformer is
its current references without distortion; however, its hard to needed to work as an interface with the four-wire microgrid.
derive the precise expression of IIDGs fault currents. In [17], a We assume that PQ-IIDG keep the original function under
virtual impedance based method is applied to modify the voltage fault conditions. In other words, PQ-IIDG still attempts to track
references of V/f-IIDG, thus to limit the overcurrent caused by the active and reactive power references by regulating its output
load step; however, the cases of unbalanced faults are not taken currents. As illustrated in Fig. 1, the current references of PQ-
into consideration. IIDG are a function of the power references and PC voltages.
The above mentioned post-fault references of IIDGs are usu- After the PC voltages feed-forward, the output currents of PQ-
ally designed based on the major concerns of researchers, such IIDG are determined by the current references alone. If the
as the simplicity of current limiting method, or achieving spec- current controller is designed properly, it can be assumed that
ified power output. In our opinion, IIDGs reference signals
should meet the following two basic requirements. First, main- i = i
taining the original roles of each IIDG as far as possible under It can be seen that the fault model of PQ-IIDG is a group of
the premise of ensuring devices safety. Second, convenient to controlled current sources. To figure out the general expressions
calculate the fault responses of IIDGs. Based on this standpoint, of PQ-IIDGs current references, it is necessary to understand
this paper derives the fault models of PQ-IIDG and V/f-IIDG by the relationship among its output powers, output currents and
analyzing the influence of fault condition and current-limiting PC voltages.
on IIDGs operation. With regard to PQ-IIDG, firstly a study on
the relationship among the output powers, output currents and B. Power Analysis
the voltages at point of connection (PC) from the perspective
of sequence components is carried out. Then, four transfer fac- Three-phase converter equipment is usually connected in un-
tors are introduced to generate the current references combined grounded star [18], and therefore it would not be affected by
with the power references and PC voltages. As to V/f-IIDG, zero sequence voltages when ground fault occurs in microgrid.
an equivalent impedance based method is employed to generate The PC voltages can be decomposed into positive sequence and
the specific voltage references when different types of faults negative sequence components as
occur in microgrid, thus the fault currents can be limited in a u = u+ + u
negative-feedback fashion.
The outline of the paper is as follows. Section III presents the where
fault model of PQ-IIDG. Section VI presents the fault model of +
U cos (t + + )
V/f-IIDG. Section V provides several selected simulation results  

to evaluate the performance of proposed fault models. Finally, u+ = 2 U + cos t + + 120 (1)
 
conclusions are presented in Section VI. U + cos t + + + 120

U cos (t + )
 
II. FAULT MODEL OF PQ-IIDG u = 2 U cos t + + 120 (2)
 
A. Fault Control of PQ-IIDG U cos t + 120
Fig. 1 shows the typical configuration and control block di- Since three-phase PQ-IIDG cannot output zero sequence cur-
agram of a three-phase PQ-IIDG, where P and Q represent rents, the currents of PQ-IIDG can be decomposed into sequence
GUO et al.: FAULT MODELS OF INVERTER-INTERFACED DISTRIBUTED GENERATORS WITHIN A LOW-VOLTAGE MICROGRID 455

Rotating u by 90 degree in counterclockwise direction, we get


u
as

0 1 1
1 1
u = 0 1 u (10)
3 1 1 0
According to (1)(4), (9) and (10), it can be derived that
+ +

u i = 3U + I + cos (+ + )


u i = 3U I cos ( )
(11)

i = 3U I sin ( )
u+ + + + + +



u i = 3U I sin ( )
Fig. 2. Illustration of current and voltage vectors in plane.
Therefore, PQ-IIDGs output powers, output currents and PC
components as voltages have the following relationship.

i = i+ + i P = u+ i+ + u i

(12)
where Q = u+ i + u i
+

+
I cos (t + + )
 

C. PQ-IIDGs Fault Model
i+ = 2 I + cos t + + 120 (3)
 
In order to facilitate the derivation of general expressions of
I + cos t + + + 120 PQ-IIDGs current references, the sequence components of PQ-
IIDGs output currents can be further decomposed into active
I cos (t + )
 
power component and reactive power component as [13]
i = 2 I cos t + + 120 (4)
 
i+ = i+P + iQ
+
I cos t + 120 (13)
i = i
P + iQ
Without consideration of the power consumed on the filter in-
ductor, the complex power of PQ-IIDG is given by The relations among the components of currents and voltages
are shown in (14), where // means parallel.
S = U A IA + U B IB + U C IC (5)
P // u , iP // u , iQ // u , iQ // u
i+ + + +
(14)
where the and above variables means conjugation and +
phasor respectively. Since i+
P , iP and iQ , iQ are related to PQ-IIDGs active power
By using the transformation relation shown in (6), where F and reactive power respectively, the components of PQ-IIDGs
represents U or I, PQ-IIDGs complex power can be expressed output currents can be expressed as
+
by the sequence components of its output currents and PC volt- iP = P g1 u+


ages, as shown in (7).
i = P g2 u
P

+
F a
(15)
F a 1 a a2
i+
Q = Q g3 u
+

=

F b , with a = ej 120 (6)

1 a a iQ = Q g4 u
Fa 2

F c
where g1 , g2 , g3 and g4 can be called transfer factors.
+ According to (12) (15), it can be derived that
S= 3U A+ IA + 3U A IA (7)  

P = P g1 u+  + g2 u 
2 2
According to (1)(4), and (7), it can be derived that
  (16)
P = 3U + I + cos (+ + ) + 3U I cos ( )
Q = Q g3 u+ 2 + g4 u 2
Q = 3U + I + sin (+ + ) + 3U I sin ( )
where   means the norm of a vector.
(8)
The output powers of PQ-IIDG will equal their references if
In stationary reference frame, u+ and u are located in the
transfer factors follow the constraints shown in (17).
plane, as illustrated in Fig. 2. Rotating u+ by 90 degree in
clockwise direction, we get u+ as g1 u+ 2 + g2 u 2 = 1
(17)
0 1 1 g u+ 2 + g u 2 = 1
3 4
1
u+ = 1 0 1 u+ (9)
Naturally, we can set PQ-IIDGs current references as (18) ac-
3
1 1 0 cording to (15), and then the fault model of PQ-IIDG can be
456 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

The third aspect is fault current limiting. The output current


limitation of PQ-IIDG is usually set as twice of the normal
current [19]. When severe fault occurs in microgrid, the PC
voltages will drop substantially and PQ-IIDGs output currents
might exceed the phase current limitation. So it is necessary to
Fig. 3. Sequence component fault model of PQ-IIDG: (left) positive sequence restrict the magnitude of PQ-IIDGs current references vector,
fault model and (right)negative sequence fault model. which can be denoted as  i . Notice that  i  is usually
a time-dependent variable and its maximum value is shown in
(21), which can be easily derived from (18).
easily derived as illustrated in Fig. 3, where the expressions of 
positive and negative sequence controlled current sources are  i m ax =  u+  (P g1 )2 + (Q g3 )2
shown in (19) and (20) respectively. 

i = P g1 u+ + P g2 u + Q g3 u+ +  u  (P g2 )2 + (Q g4 )2 (21)
+ Q g4 u (18)

I + = (P g1 jQ g3 ) U
+ (19) If we make sure that  i m ax is always less than its limitation
value, as shown in (22), where IPQlim represents the limitation
I = (P g2 jQ g4 ) U
(20) of PQ-IIDGs output peak current, then all the phase currents
will be kept within their safety range.
D. Parameters Determination 
3
The basic form of PQ-IIDGs fault model has already been  i m ax  i lim = IPQlim (22)
2
acquired; the next question is how to determine the parameters of
this model, including the power references and transfer factors. Next we will choose two kinds of fault control scenarios
With regard to this issue, we think that there exist three aspects to illustrate how to modify the initial power references and
should be considered. initial transfer factors, thus to limit the magnitude of  i 
The first aspect is FRT requirement, which stipulates that and reserve the expected power or current characteristics. Here
PQ-IIDG change their power references to provide better volt- we denote the modified variables as Pm o d , Qm o d and g1,m o d ,
age support function. For simplicity, here we assume that the g2,m o d , g3,m o d , g4,m o d respectively.
new active and reactive power references are already known and Scenario 1: Power characteristics regulation. Without loss of
denoted as Pini
and Qini respectively. The subscript ini indi- generality, here it is assumed that the reactive power is of higher
cates those variables are initial quantities and would be further priority. The ratio of positive sequence active power to total
modified in the follow-up steps. active power is controlled to be kP , and the ratio of positive
The second aspect is the detailed fault control strategies. sequence reactive power to total reactive power is controlled
The basic control task of PQ-IIDG is to track the power ref- to be kQ . Then, strategy equations can be derived as shown
erences, thus the values of transfer factors should comply with in (23).
2
the constraints presented in (17). However, there exist four un- g1 u+  = kP
known transfer factors in total, so two extra equations which 2
(23)
can be called strategy equations are still needed besides the two g3 u+  = kQ
basic ones provided in (17). The strategy equations are gen- The initial power references are defined by FRT requirement,
erally determined by the additional control requirements. At and the initial transfer factors can be solved out based on (17) and
present, these requirements are mainly put forward from the (23). In this scenario, since the transfer factors are independent
view of power features regulation. In [11], [12], different posi- of power references, it seems more convenient to achieve current
tive/negative sequence power injection ratio is selected to deal limiting by adjusting power references alone, and the modified
with various types of faults. References [13][14][15] present to transfer factors will be set to equal their initial values. The
suppress the oscillation components of instantaneous active or detailed modification procedures are presented as follows.
reactive power to restrict their negative effects. Besides the per- Step 1 Set g1,m o d = g1,ini , g2,m o d = g2,ini , g3,m o d =
spective of power features, we think that current characteristics g3,ini , g4,m o d = g4,ini .
can also be taken into consideration, such as fixing the positive Step 2 Determine the upper limit of PQ-IIDGs pure reactive
or negative sequence current amplitude to a given value. Ma- power output, which is denoted as Qlim , by calculat-
nipulating PQ-IIDGs fault currents with some distinct features ing (24).
is promised to simplify the protection settings. Anyway, once
i lim
the strategy equations are determined, the four transfer factors Qlim = (24)
can be calculated and we denote them as g1,ini , g2,ini , g3,ini and |g3,m o d | u+  + |g4,m o d | u 
g4,ini in this paper, because they are also initial quantities and Step 3 If Qlim < Qini , set Qm o d = Qlim . In this case,
would be modified later. It is worth noting that the values of there has no surplus capacity for PQ-IIDG to export
g1ini and g3ini are usually positive, for PQ-IIDG injects active active power, so we set Pm o d = 0.
and reactive power to microgrid rather than absorbing powers Step 4 If Qlim Qini , set Qm o d = Qini . In this case, the
within positive sequence in most cases. PQ-IIDG still has the capability to output some active
GUO et al.: FAULT MODELS OF INVERTER-INTERFACED DISTRIBUTED GENERATORS WITHIN A LOW-VOLTAGE MICROGRID 457


power, whose upper limit is denoted as Plim . The

value of Plim can be acquired by solving out (25).
Then, set Pm o d as shown in (26), where min( )
means the minimum element among the variables in
brackets.

i lim = u+  (Plim
g 2
1,m o d ) + (Qm o d g3,m o d )
2


+u  (Plim
g 2
2,m o d ) + (Qm o d g4,m o d )
2
(25)
Pm o d = min (Plim

, Pini ) (26)
Scenario 2: Current characteristics regulation. Here we as-
sume the active power is with higher priority. The peak value
of PQ-IIDGs positive sequence current is controlled to be Iset , Fig. 4. Configuration and control block diagram of V/f-IIDG.
and the power factor of positive sequence power is controlled to
be set . Then, the strategy equations can be written as
 
into (21), thus the upper limits of residual unknown quantities
(P g1 )2 + (Q g3 )2 u+  = 3 Iset
2 can be determined.
 (27)

P g1 = set (P g1 ) + (Q g3 )
2 2 According to the analysis above, as long as the phase-current
limitation value, the detailed FRT requirement, and the addi-
Initial power references are known quantities defined by FRT tional fault control requirements are decided, the detailed fault
requirement, and then the initial transfer factors can be cal- model of PQ-IIDG can be derived step by step, which has simple
culated by substituting Pini
and Qini into (17) and (27). The and explicit expression. A prominent merit of this model is that
transfer factors are related to power references, so adjusting the the current limiting and the desired power or current character-
transfer factor alone is a better choice and the modified power istics can be achieved at the same time. In addition, comparing
references will be set to equal their initial values. The detailed with the existing counterpart that has a fixed form [10], the
modification procedures are presented as follows. proposed model of PQ-IIDG is capable to reflect more PQ-
Step 1 Set Pm o d = Pini
, Qm o d = Qini , g1,m o d = IIDGs fault responses which are potential to appear in different
g1,ini , g3,m o d = g3,ini to ensure that the positive scenarios.
sequence currents meet the given current control
requirement. III. FAULT MODEL OF V/F-IIDG
Step 2 Determine the upper limit of |g2 |, which is denoted
A. Fault Control of V/f-IIDG
as |g2 |lim , by calculating (28).
 The loads are likely to be unbalanced in low-voltage micro-
i lim 32 Iset grid. The V/f-IIDG discussed in this paper utilizes three-phase
|g2 |lim = (28) four-leg inverter [20] to regulate three-phase voltages separately.
Pm o d u 
When fault occurs in microgrid, V/f-IIDG will attempt to main-
Step 3 If |g2 |lim < |g2,ini |, then set g2,m o d as shown in (29), tain the PC voltages within their normal range. However, if the
where sgn( ) means the sign (positive or nega- fault is far too severe, V/f-IIDG should modify its voltage ref-
tive) of the variable in brackets. In this case, we set erences actively to avoid overcurrent. Subsequently, the critical
g4,m o d = 0, thus to ensure current limiting. issue of V/f-IIDGs fault control is to calculate the maximum
allowable voltage references of V/f-IIDG with consideration of
g2,m o d = |g2 |lim sgn (g2,ini ) (29) current limiting.
Step 4 If |g2 |lim |g2,ini |, set g2,m o d = g2,ini . The upper Fig. 4 shows the configuration and control block diagram of
limit of |g4 |, which is denoted as |g4 |lim , can be ac- V/f-IIDG, where u and i represent PC voltages and output cur-
quired by solving out (30). Then, set g4,m o d as shown rents, u and i represent the corresponding references of u and
in (31). i. The control system first calculates the equivalent impedances
 of each phase, which are denoted as Zx (x = A, B, C), based on
i lim = u+  (Pm o d g1,m o d )2 + (Qm o d g3,m o d )2 V/f-IIDGs output currents and PC voltages. Then, V/f-IIDGs
 voltage references can be determined by its phase current limita-
+ u  (Pm o d g2,m o d )2 + (Qm o d |g4 |lim )2 (30) tion and the measured equivalent impedances. If both the current
controller and voltage controller are designed properly, and ap-
g4,m o d = min (|g4,ini | , |g4 |lim ) sgn (g4,ini ) (31) propriate feed-forwards are adopted, then it can be assumed
that
It is worth noting that (24), (25), (28) and (30) are derived
by substituting the known power references and transfer factors u = u
458 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

B. V/f-IIDGs Fault Model


The equivalent impedances of each phase can be calculated
as
Zx = Ux /Ix , with x = A, B, C (32)
where Ux and Ix (x = A, B, C) represent the PC voltage and
output current of each phase respectively. When fault occurs
in microgrid, V/f-IIDGs voltage references will not change
Fig. 5. Fault model of V/f-IIDG.
immediately because of the delay of measurement. With the
equivalent impedance of faulty phase dropped substantially, V/f-
IIDGs output currents of faulty phases will increase in a short
time. If the current of a certain phase reaches the limitation
value, the control system will judge that there exists severe fault
in that phase. Then, the voltage references of V/f-IIDG will be
modified based on the fault type and the equivalent impedances.
The voltage references of healthy phases remain unchanged,
thus to minimize the disturbed area.
When single-phase fault (such as phase A) occurs in micro-
grid, the magnitude of voltage reference of phase A will be
modified as

UA,m o d = min (Unom , ZA IVFlim ) (33) Fig. 6. Low-voltage microgrid.

where Unom represents the nominal phase-voltage, and IVFlim


represents the limitation of V/f-IIDGs output current.
The phase angles of the controlled voltage sources remain the
When two-phase fault (such as short circuit between phase
same as those before the fault, because the unbalanced extent of
A and B) occurs, the equivalent impedance of phase A will be
PC voltages will be minimized with this setting.
influenced significantly by the output current of phase B and
Comparing with the existing methods [16], [17], the fault
vice versa. Therefore, the magnitude of voltage references of
control strategy of V/f-IIDG proposed in this paper can handle
these two phases must be modified in a unified manner and they
various types of faults properly, since the the PC Voltages of
are assumed to have the same magnitude as shown in (34).
healthy phases are exempted from the influence of fault and the

UA,m o d = UB,m o d = min (Unom , ZA IVFlim , ZB IVFlim ) (34) voltage drops of faulty phases can be minimized. In addition, the
fault model of V/f-IIDG preserves the nature of voltage source,
When three-phase fault occurs, the magnitudes of three-phase which is useful to maintain the stability of microgrid under fault
voltage references are set to be the same in a similar way. conditions [17].
UA , m o d = UB , m o d = UC , m o d
IV. SIMULATION RESULTS
= min (Un o m , ZA IV F lim , ZB IV F lim , ZC IV F lim ) (35)
By referencing the inverter control techniques presented in
Using the above-mentioned modification method, it can be documents [2], [21], and [22], we developed the proposed fault
ensured that the steady-state phase-currents of V/f-IIDG would models with Matlab/Simulink. The fault models of PQ-IIDG
not exceed their limitation value. However, it is worth noting and V/f-IIDG were tested in a 0.4 kV microgrid as shown in
that the adjustment process of voltage references will last for Fig. 6.
some time (about 1 2 periods, related to the fault severity and When CB is open, the microgrid shown in Fig. 6 will operate
the speed of PLL) to reach steady state. During the transient in islanded mode. DG1 is a 10 kVA PQ-IIDG, whose peak
period, the current references of V/f-IIDG are very likely to current limitation is 40 A. DG2 is a 20 kVA V/f-IIDG, whose
exceed the limitation, so it is necessary to place a saturation peak current limitation is 80 A. The length of Line1 and Line
module before the current control loop, as shown in Fig. 4. 2 are both 0.2 km with the impedance per unit length being
Based on (33) (35), the fault model of V/f -IIDG can be 0.642 + j0.083 /km. The pre-fault active and reactive power
summarized as a group of controlled voltage sources which references of DG1 are 7 kW and 2 kvar respectively. No matter
are shown in Fig. 5, and the magnitudes of controlled voltage which kinds of faults occur, it is assumed that the initial post-
sources are presented in (36). fault active and reactive power references of DG1 are set as 7 kW
and 6 kvar according to the FRT requirement. In other words,
Unom if Unom Zx IVFlim
Ux = we assume Pini = 7 kW and Qini = 6 kvar constantly.
IVFlim min (ZA , ZB , ZC ) if Unom > Zx IVFlim Case 1: Single Phase Fault
(36) At 0.08 s, phase A ground fault occurs at the midpoint of Line1
where x = A, B, C. and the fault resistance is 1 . The fault control strategy of DG1
GUO et al.: FAULT MODELS OF INVERTER-INTERFACED DISTRIBUTED GENERATORS WITHIN A LOW-VOLTAGE MICROGRID 459

TABLE I
TRANSFER FACTORS OF CASE 2

g1 /105 g2 /105 g3 /105 g4 /105

Initial 1.91 V2 2.58 V2 1.08 V2 5.10 V2


Modified 1.91 V2 2.15 V2 1.08 V2 0.00 V2

Fig. 7. Simulation results of DG1 in case 1: (top) output currents and (bottom)
supplied power of positive and negative sequence.

Fig. 9. Simulation results of DG1 in case 2: (top) output currents, (middle)


positive sequence component of output currents, and (bottom) supplied power
of positive and negative sequence.

Fig. 8. Simulation results of DG2 in case 1: (top) output currents and (bottom)
PC voltages.
From Fig. 7 top, it can be observed that the maximum phase-
current of PQ-IIDG is not appeared in the faulty phase, i.e., phase
A. The reasons are as follows. The three-phase three-leg inverter
is the same as that of Scenario 1 introduced in Section III based PQ-IIDG cant regulate the phase-current directly. In fact,
where kP is set as 0.8, and kQ is set as 0.5. PQ-IIDGs current references are generated based on sequence
The simulation results of DG1 are shown in Fig. 7. The active components. More importantly, only if PQ-IIDG injects currents
powers supplied from positive sequence and negative sequence as shown in Fig. 7 top, can the power characteristics required
are 5.62 kW and 1.4 kW, and the reactive powers supplied from by case 2 be achieved.
positive sequence and negative sequence are both 3 kvar. It can The simulation results of DG2 are shown in Fig. 8. Because
be seen that the actual values of kP and kQ meet the expectation. the peak current of phase A is limited to 80 A, the post-fault
The total supplied active power and reactive power are 7 kW voltage of phase A drops to about 64 V. From Fig. 8 top, it
and 6 kvar, which are in accord with the expected values. can be observed that V/f-IIDGs currents of healthy phases are
460 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

Fig. 10. Simulation results of DG2 in case 2: (top) output currents and
(bottom) PC voltages.

Fig. 11. Simulation results of DG1 in case 3: (top) output currents and
changed. The reason is that the fault response of PQ-IIDG influ- (bottom) supplied active and reactive power.
ences the equivalent impedances of V/f-IIDGs healthy phases,
thus the currents of phase B and C are different with the corre-
sponding pre-fault currents.
Case 2: Two-Phase Fault
At 0.08 s, short circuit fault between phase A and phase B
occurs at the midpoint of Line1 and the fault resistance is 2 .
The fault control strategy of DG1 is the same as that of Scenario
2 introduced in Section III, where Iset is set as 30 A, and set
is set as 0.9.
The simulation results of DG1 are shown in Fig. 9. The peak
value of positive sequence current is 30 A. The active and reac-
tive powers supplied from positive sequence are 8.24 kW and
4 kvar, and the power factor of positive sequence is 0.9. These
results indicate that the expected current and power characteris-
tic required by this case are achieved. The total supplied active
power and reactive power are 7.23 kW and 4 kvar, which are
different with the expected values. Based on the initial and mod-
ified transfer factors shown in Table I, we can conclude that the
absorbed active power and the exported reactive power through
negative sequence are both restricted because of current lim-
iting, thus the total active power output is increased while the
total reactive power output is decreased.
The simulation results of DG2 are shown in Fig. 10. The
post-fault voltages of phase A and phase B drop to about 89 V. Fig. 12. Simulation results of DG2 in case 3: (top) output currents and
(bottom) PC voltages.
Case 3: Three-Phase Fault
At 0.08 s, three-phase short circuit fault occurs at the midpoint
of Line1. The fault resistance is 2 . The fault control strategy
of DG1 is the same as those of Scenario 1 introduced in The simulation results of DG2 are shown in Fig. 12. The
Section III. Both kP and kQ are set to 1, for the negative sequence post-fault three phase voltages drop to 68 V.
voltage in microgrid is very low in this case. The black dashed lines in Figs. 712 represent the peak cur-
The simulation results of DG1 are shown in Fig. 11. The rent boundaries. Obviously, the current limiting is implemented
total supplied active power and reactive power are 3.94 kW and successfully in each case. From the simulation results, we can
6 kvar. The reactive power has a higher priority, so the active conclude that IIDGs fault features meet the corresponding fault
power is reduced to achieve current limiting in this case. control strategies. PQ-IIDG behaves like a controlled current
GUO et al.: FAULT MODELS OF INVERTER-INTERFACED DISTRIBUTED GENERATORS WITHIN A LOW-VOLTAGE MICROGRID 461

source and its fault response is closely related to control strat- [15] J. Suul, A. Luna, P. Rodriguez, and T. Undeland, Virtual-flux-based
egy. V/f-IIDG behaves like a controlled voltage source, and the voltage-sensor-less power control for unbalanced grid conditions, IEEE
Trans. Power Electron., vol. 27, no. 9, pp. 40714087, Sep. 2012.
voltages of healthy phases remain unchanged while the voltages [16] M. A. Zamani, A. Yazdani, and T. S. Sidhu, A control strategy for en-
of faulty phases are reduced. hanced operation of inverter-based microgrids under transient disturbances
and network faults, IEEE Trans. Power Del., vol. 27, no. 4, pp. 1737
1747, Oct. 2012.
V. CONCLUSION [17] A. D. Paquette and D. M. Divan, Virtual impedance current limiting for
inverters in microgrids with synchronous generators, IEEE Trans. Ind.
This paper proposes the fault models of the three-phase three- Appl., vol. 51, no. 2, pp. 16301638, Mar./Apr. 2015.
leg inverter based PQ-IIDG and the three-phase four-leg inverter [18] A. Sannino, M. H. J. Bollen, and J. Svensson, Voltage tolerance testing
of three-phase voltage source converters, IEEE Trans. Power Del., vol.
based V/f-IIDG. The fault model of PQ-IIDG, which is a group 20, no. 2 2, pp. 16331639, Apr. 2005.
of controlled current sources, can reflect various fault responses [19] E. Casagrande, W. L. Woon, H. H. Zeineldin, and D. Svetinovic, A
of PQ-IIDG under different control strategies by adjusting pa- differential sequence component protection scheme for microgrids with
inverter-based distributed generators, IEEE Trans. Smart Grid, vol. 5,
rameters of the model. The fault model of V/f-IIDG is a group no. 1, pp. 2937, Jan. 2014.
of controlled voltage sources, which can handle different types [20] J. Liang, T. Green, C. Feng, and G. Weiss, Increasing voltage utilization
of faults flexibly while achieving current limiting. V/f-IIDGs in split-link, four-wire inverters, IEEE Trans. Power Electron., vol. 24,
no. 6, pp. 15621569, Jun. 2009.
model preserves the nature of voltage source, and this property [21] R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh, Proportional reso-
is very helpful to maintain the stability of microgrid. Simulation nant controllers and filters for grid-connected voltage-source converters,
results validate the performance of the fault models proposed in in Proc. Inst. Elect. Eng., Elect. Power Appl., Sep. 2006, vol. 153, no. 5,
pp. 750762.
this paper. [22] P. Rodriguez, A. Luna, R. Munoz-Aguilar, I. Etxeberria-Otadui,
R. Teodorescu, and F. Blaabjerg, A stationary reference frame grid syn-
chronization system for three-phase grid-connected power converters un-
REFERENCES der adverse grid conditions, IEEE Trans. Power Electron., vol. 27, no. 1,
pp. 99112, Jan. 2012.
[1] J. A. P. Lopes, C. L. Moreira, and A. G. Madureira, Defining control
strategies for microgrids islanded operation, IEEE Trans. Power Syst.,
vol. 21, no. 2, pp. 916924, May 2006.
[2] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodrguez, Control of power
converters in AC microgrids, IEEE Trans. Power Electron., vol. 27,
no. 11, pp. 47344749, Nov. 2012.
[3] D. Olivares et al., Trends in microgrid control, IEEE Trans. Smart Grid, Wen-Ming Guo received the B.S. degrees in elec-
vol. 5, no. 4, pp. 19051919, Jul. 2014. trical engineering from Tongji University, Shanghai,
[4] M. Haj-Ahmed and M. Illindala, The influence of inverter-based DGs China, in 2011, where he is currently pursuing the
and their controllers on distribution network protection, IEEE Trans. Ind. Ph.D. degree.
Appl., vol. 50, no. 4, pp. 29282937, Jul./Aug. 2014. His current research interests are microgrid pro-
[5] T. S. Ustun, C. Ozansoy, and A. Ustun, Fault current coefficient and time tection and control.
delay assignment for microgrid protection system with central protection
unit, IEEE Trans. Power Syst., vol. 28, no. 2, pp. 598606, May 2013.
[6] M. H. Coddington, B. D. Kroposki, and T. S. Basso, Evaluating future
standards and codes with a focus on high penetration photovoltaic (HPPV)
system deployment, in Proc. 35th IEEE Photovoltaic Specialists. Conf.,
2010, pp. 544549.
[7] The Grid Code, Issue 4 Revision 2, No. 2366977, Nat. Grid Elect. Transm.
plc, London, U.K., (Mar. 2010). [Online]. Available: http://www2.
nationalgrid.com/uk. Long-Hua Mu received the B.E., M.E., and Ph.D.
[8] Wind Turbines Connected to Grids With Voltages Below 100 kV, Technical degrees in electrical engineering from China Univer-
Regulations TF 3.2.6, No. 177899, Energinet, Fredericia, Denmark, (May. sity of Mining and Technology, Xuzhou, China, in
2004). [Online]. Available: http://www.energinet.dk/EN. 1986, 1988, and 1998, respectively.
[9] X. Guo, X. Zhang, B. Wang, W. Wu, and J. Guerrero, Asymmetrical He has been a Full Professor in the Department
grid fault ride-through strategy of three-phase grid-connected inverter of Electrical Engineering, Tongji University, Shang-
considering network impedance impact in low voltage grid, IEEE Trans. hai, China, since 2004. His current research interests
Power Electron., vol. 29, no. 3, pp. 10641068, Mar. 2014. include the protective relaying of power systems, mi-
[10] C. A. Plet and T. C. Green, Fault response of inverter interfaced distributed crogrids, and power quality.
generators in grid-connected applications, Elect. Power Syst. Res., vol.
106, pp. 2128, Jan. 2014.
[11] A. Camacho, M. Castilla, J. Miret, J. Vasquez, and E. Alarcon-Gallo,
Flexible voltage support control for three-phase distributed generation
inverters under grid fault, IEEE Trans. Ind. Electron., vol. 60, no. 4,
pp. 14291441, Apr. 2013.
[12] A. Camacho, M. Castilla, J. Miret, A. Borrell, and L. de Vicuna, Active
and reactive power strategies with peak current limitation for distributed Xin Zhang received the B.S. and M.S. degrees in
generation inverters during unbalanced grid faults, IEEE Trans. Ind. Elec- electrical engineering from China University of Min-
tron., vol. 62, no. 3, pp. 15151525, Mar. 2015. ing and Technology, Xuzhou, China, in 2002 and
[13] F. Wang, J. Duarte, and M. Hendrix, Design and analysis of active power 2005, respectively, and the Ph.D. degree in electrical
control strategies for distributed generation inverters under unbalanced engineering from Tongji University, Shanghai, China,
grid faults, IET Gen., Transm. Distrib., vol. 4, no. 8, pp. 905916, Aug. in 2012.
2010. Currently, he is a Research Associate at Tongji
[14] P. Rodriguez, A. Timbus, R. Teodorescu, M. Liserre, and F. Blaabjerg, University. His current research interests are power
Flexible active power control of distributed power generation systems system protection and control.
during grid faults, IEEE Trans. Ind. Electron., vol. 54, no. 5, pp. 2583
2592, Oct. 2007.

Potrebbero piacerti anche