OPERATING INSTRUCTIONS
Fire Alarm Panel
815.5-2 GL and 815.5-6 GL

Type approved by Germanischer Lloyd


Certificate No. 35 947 - 85 HH

DESCRIPTION CHAPTER

A. Construction 2

B. Mode of Operation 2-3-4

C. Function Test 4-5

D. Reset of Detectors with Memory 5

E. Data 5

F. Detector List 6

G. Installation Instruction 7

- Firealarmpanel flush mounting 8

- Firealarmpanel wall mounting 9

- Connections diagram 10

- GL Certificate 11

Tel.: +49 (0)4105 / 65 60 0 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 25


E-mail: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de
A. C O N S T R U C T I O N

The Central Cabinet is constructed for desk mounting Page.8


or wall mounting Page. 9.

The central cabinet of one unit, containing:

1. Working lamp
2. Two or Six detector groups - 1 accommodation and 1 engine room
or 2 accommodation of 2 engine rooms with belonging indication
for fire and fault.
3. Internal acoustic sounder
4. Relay for control of fire bell, fire and fault relay
with each a set of potential free change over switches.
5. Function test respectively of fire and for fault in the
two detector groups.

B. M O D E O F O P E R A T I O N

The central cabinet is in normal state:


The central cabinet is connected to primary and secondary
power supply with 24 V DC rated voltage.
All lamps are dark, except for the green working lamp mark
"Mains".
At voltage drop-out from either primary or secondary power
supply the following is indicated:

A. Green pilot lamp labelled "Mains" flashes


B. Internal acoustic signal
C. Faulty relay changes over

You can reset by the push button labelled "Reset". Then:


A. The internal acoustic signal stops
B. Fault relay change back to normal condition
The green pilot lamp does not stop flashing until both
primary and secondary voltage is connected to the central
cabinet and you have reset by the push-button labelled "Reset".
Mode of operation of the detector groups:

The detector groups are working after the one-loop-principle


where the detectors are parallel connected to the line and
the line is finished with an end resistor. The end resistor
determines the current of rest in the loop.

If the fault has stopped the light in the yellow lamp mark
"Fault" of the group in question stops, if the fault is
stationary, nothing happens.

The yellow fault lamp of the group in question will not stop
lighting until the fault has been repaired and the button mark
"Reset" has been pushed.

Fire Alarm:

Fire Alarm occurs when a detector has been released. At release


of a detector a resistance is connected parallel on the line
(parallel with the end resistor) then the current (no-signal current) will increase.

Fire Alarm is indicated by:

A. Internal acoustic signal


B. External acoustic signal
C. Fire relay changes over
D. Light in the red fire lamp of the group in question

You can reset by pushing the button mark "Reset", then:

A. The internal acoustic signal stops


B. The external acoustic signal stops
C. Fire relay changes back to normal condition
D. If the detector is in normal state, light in the red fire
lamp of the group in question stops lighting - if the
Detector is in alarm state, nothing happens.

The red fire lamp of the group in question will stop


lighting until the detector is in normal state and the button
mark "Reset" has been pushed.

If the central cabinet looses it is working voltage, the green


working lamp mark "Mains" goes out.
C. F U N C T I O N T E S T

Test of fire is achieved by pushing the button placed below


the red fire lamp.

Indication as mentioned in the passage about fire alarm.

Test of fault in the detector loop is achieved by pushing


the button placed below the yellow fault lamp.

Normal state.
A fixed current of rest passes through the loop. Both the
fault and fire alarm lamps are dark.

Fault Alarm
If a loop is broken the current of rest ceases and the group in
question will indicate "Fault".

Fault is indicated by
A. Internal acoustic signal
B. Fault relay changes over
C. Light in the yellow lamp mark "Fault" of the group in
question

You can see reset by pushing the button mark "Reset", then:

A. The internal acoustic signal stops


B. Fault relay changes back to normal condition

Indication as mentioned in the passage about fault alarm.

Test to fire alarm bells are achieved at the same time as test of
fire is done.

Test of power supply fault:


Is obtained by switching-off of primary and secondary power
supply of by removing primary of secondary fuse in central
cabinet.

D. RESET OF DETECTOR WITH ELECTRICAL MEMORY

Detectors with electrical memory and which are connected with


the central cabinet can be reseted by pushing the function test
button "Fault" of the group in question, then te detector loop
is broken and the connected detectors are reseted.
E. D A T A

E1. Voltage

The operating voltage is 2x 24 V DC +30% -25 %

E2. Current consumption


Normal state, detectors not incl. app. 100 mA
Alarm state, detector and bells not incl. app. 250 mA
Detector, normal state app. 0,1 mA
Detector, alarm state app. 40 mA

E3. Limits
Max. load of fire bell output 2,0 A
Max. number of detectors per group 25 pcs
Max. number of man call points unlimited
F. D E T E C T O R L I S T

Engine room

Opt. Smoke detector Type 130A + 143 AS


Type SLR-EM+ YBM-R4M+ MBB-1

Heat detector Type 215A + 143 AS


Type DCD-1EM+ YBM-R4M+ MBB-1 60C
Type DCD-1REM+ YBM-R4M+ MBB-1 90C

Manual call point Type NS-CPWP WR 4072

UV-Flame Detector Type 810A + 133 AS


Type 1121+1411+1421 NS DUV

Accommodation

Opt. Smoke detector Type 130A + 143 A Surface


Type 130A + 143 UH Flushm.
Type SLR-EM+ YBM-R4M.

Heat detector Type 215 A + 143 A Surface


Type 215 A + 143 UH Flushm.
DCD-1EM+ YBM-R4M 60C
DCD-1REM+ YBM-R4M 90C

Manual call point Type NS-CP WR 2072


G. I N S T A L L A T I O N I N S T R U C T I O N

Installation instruction for automatic fire alarm and fire


indication system, type 815.5-6 (2) GL.

1. The central is mounted on the navigation bridge as the screw


for the 2 upper holes in the cabinet are screwed in the bulk-
head until approx. 3 mm from the bulkhead surface.

The cabinet is "pulled" down over the screws and kept to the
bulkhead by means of internal mounted plate springs.

Further the cabinet is fastened with a third screw at the


bottom in the middle.

2. The detector group/s is/are connected with the central


cabinet; remember the end resistance at the last detector
in each group; and so are fire bells and voltage supply 24 V.

The central cabinet is put back into normal state.

3. The system is ready for tests, which are to be done according


to the check list, see this.
Type Approval Certificate
This is to certify that the undernoted product(s) has/have been tested in accordance with
the relevant requirements of the GL Type Approval System.

Certificate No. 3594785 HH


Company DECKMA GmbH
Bahnhofstrae 79
D-21224 Rosengarten-Klecken

Product Description Fire Detection System

Type 815.5

Environmental Category C, EMC1


Technical Data / Power supply: 2 x 24 V DC
Range of Application Connection: up to 6 conventional fire detection lines
Loop voltage: 24 V DC
Output: 1 c/o contact each for failure and fire alarm
Contact rating: 2 A 24 V DC
Degree of protection: IP 42

Test Standard Guidelines for the Performance of Type Approvals, Edition 2003

Documents Manual: 815.5


Circuit diagram: 821.5A S529, 8215.5 1S525, 8215.5 2S526, 8215.5 3S527
Drawing: 8015.5 6S530, 8015.5 6S528, Test reports: DASA 478.100.94, EMV Services
01/0221-1-1, EMV Services 03/3202-1-1

Remarks None

Valid until 2007-12-19


Page 1 of 1 Type Approval Symbol
File No. I.A.01

Hamburg, 2003-12-18

J. Wittburg T. Huthoff
This certificate is issued on the basis of "Regulations for the Performance of Type Tests, Part 0, Procedure".

Internet Publication: GL-Approvals